Product data sheet
Specifications
Circuit breaker, ComPact NSX160F
AC/DC, 18kA/415VAC, TMD trip unit
160A, 2 poles 2d
LV438700
To be discontinued on: 31 December 2022
To be discontinued Important message : This product has been switched to new
ComPacT range and is no longer commercialized. It will continue
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
to be available until Q4 2022 only limited to specific projects.
Main
Range ComPact
Product name ComPact NSX
Range of product ComPact NSX100...250 DC
ComPact NSX100...250
Device short name NSX160F
Product or component type Circuit breaker
Device application Distribution
Number of poles 2P
Protected poles description 2t
[In] rated current 160 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
500 V DC
Network type DC
AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 36 kA Icu at 250 V DC 1P conforming to IEC 60947-2
36 kA Icu at 125 V DC 1P conforming to IEC 60947-2
36 kA Icu at 500 V DC 2P conforming to IEC 60947-2
10 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Performance level F 18 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 750 V AC 50/60 Hz conforming to IEC 60947-2
Dec 7, 2022 1
[Uimp] rated impulse withstand 8 kV conforming to IEC 60947-2
voltage
[Ics] rated service short-circuit 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 36 kA at 250 V DC conforming to IEC 60947-2
36 kA at 125 V DC conforming to IEC 60947-2
36 kA at 500 V DC conforming to IEC 60947-2
10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 40000 cycles
Electrical durability 5000 cycles at 440 V In
10000 cycles at 440 V In/2
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 35 mm
Protection type for overload protection (thermal)
for short-circuit protection (magnetic)
Trip unit rating 160 A at 40 °C
Long-time pick-up adjustment Fixed
type Ir (thermal protection)
[Ir] long-time protection pick-up 1 In
adjustment range
Long-time protection delay Fixed
adjustment type tr
[Im] magnetic protection pick- 1250 A
up range
Earth-leakage protection Without
Width (W) 70 mm
Height (H) 161 mm
Depth (D) 86 mm
Environment
Standards EN/IEC 60947
Product certifications CCC
EAC
Marine
Overvoltage category Class II
Electrical shock protection Class II
class
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for -25…70 °C
operation
Ambient air temperature for -50…85 °C
storage
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating
2000 m...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
2
Dec 7, 2022
Number of Units in Package 1 1
Package 1 Height 8.0 cm
Package 1 Width 13.0 cm
Package 1 Length 17.5 cm
Package 1 Weight 1.288 kg
Unit Type of Package 2 S03
Number of Units in Package 2 12
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 15.943 kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: DINP, which is known to the State of
California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or
other reproductive harm. For more information go to www.P65Warnings.ca.gov
Contractual warranty
Warranty 18 months
Recommended replacement(s)
LV438700 is replaced by:
Circuit breaker, ComPacT NSX160F AC/DC, 18kA/415VAC, 2 poles, TMD trip unit
1x 160A
C16F2TM160