8.3.5. Vessel Pressure

0,54,5VDC input, to measure the VESSEL PRESSURE (pv_pv) through a 3-wire sensor
(Supply – GND – Signal).

Measure update ≤ 25ms.


Measure tolerance ≤ ±1%.
Input impedance 69kΩ.

A 3-wire ratiometric sensor is used, supplied by 5VDC coming from the controller.
The tolerance of the controller‟s 5VDC supply is nor critical if the measured signal VDC is
compensated as following:
real signal VDC = 5VDC / measured supply VDC * measured signal VDC
In case the 5VDC supply is shortcircuited, the real signal VDC is set to 0.

It is advised to foresee a maximum power usage of 20mA per connected sensor.

There will be one +5VDC supply for all sensors.


One common GND for all analog voltage inputs is allowed.

No extrapolation of the Vessel Pressure value is done if the real signal VDC goes below
0,5VDC.
Extrapolation of the Vessel Pressure value is done if the real signal VDC goes above
4,5VDC.
In case of a sensor failure alarm, the displayed value will be „---„.
Values going from -0,2bar up to +0,3bar will be displayed as 0bar.

Configuration of the Vessel Pressure Sensor is done through following parameters:

VESSEL PRESSURE SENSOR 3080


VALUE @ 0.5VDC: -2.0bar → 55.0bar (0.1bar steps)  default = 0bar
VALUE @ 4.5VDC: -2.0bar → 55.0bar (0.1bar steps)  default = 17bar
INPUT SIGNAL SELECTION: AI0  AI9
Access Level: Master (fixed)

The Vessel Pressure Sensor wiring is monitored for shortcircuit and wirebreak.

If the sensor‟s real signal VDC ≤ 0,25VDC for 0,5s., a VESSEL PRESSURE SENSOR
CIRCUIT controlled stop will appear.
If the sensor‟s real signal VDC ≥ 4,75VDC for 0,5s., a VESSEL PRESSURE SENSOR
CIRCUIT controlled stop will appear.

When a sensor failure is occuring (also when the sensor circuit monitoring delay has not
expired, and the alarm is not active yet), „---„ will be shown in the display as value, but
for modbus broadcasting, alarm logging, calculations, ... the (limited) scaled value will
still be used.