Product data sheet
Specifications
Motor circuit breaker, TeSys Deca,
3P, 6 to 10A, thermal magnetic,
screw clamp terminals, button
control
GV2ME14
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys Deca
Product name TeSys GV2
TeSys Deca
Product or component type Motor circuit breaker
Device short name GV2ME
Device application Motor protection
Trip unit technology Thermal-magnetic
Complementary
Poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
Motor power kW 3 kW at 400/415 V AC 50/60 Hz
4 kW at 400/415 V AC 50/60 Hz
4 kW at 500 V AC 50/60 Hz
5.5 kW at 690 V AC 50/60 Hz
7.5 kW at 690 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type Push-button
[In] rated current 10 A
Thermal protection adjustment 6…10 A conforming to IEC 60947-4-1
range
Magnetic tripping current 138 A
[Ith] conventional free air 10 A conforming to IEC 60947-4-1
thermal current
Feb 4, 2023 1
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand 6 kV conforming to IEC 60947-2
voltage
Phase failure sensitivity Yes conforming to IEC 60947-4-1
Suitability for isolation Yes conforming to IEC 60947-1 § 7-1-6
Power dissipation per pole 2.5 W
Mechanical durability 100000 cycles
Electrical durability 100000 cycles for AC-3 at 415 V In
Rated duty Continuous conforming to IEC 60947-4-1
Tightening torque 1.7 N.m - on screw clamp terminal
Width 45 mm
Height 89 mm
Depth 78.5 mm
Net weight 0.26 kg
Colour Dark grey
Environment
Standards EN/IEC 60947-2
EN/IEC 60947-4-1
Product certifications CCC
UL
CSA
EAC
ATEX
BV
LROS (Lloyds register of shipping)
UKCA
DNV-GL
RINA
IK degree of protection IK04
IP degree of protection IP20 conforming to IEC 60529
Climatic withstand conforming to IACS E10
Ambient air temperature for -40…80 °C
storage
Fire resistance 960 °C conforming to IEC 60695-2-11
Ambient air temperature for -20…60 °C
operation
Mechanical robustness Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz
Operating altitude 2000 m
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 4.500 cm
Package 1 Width 8.500 cm
Package 1 Length 9.000 cm
Package 1 Weight 272.000 g
Unit Type of Package 2 S02
Number of Units in Package 2 24
2
Feb 4, 2023
Package 2 Height 15.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 6.773 kg
Unit Type of Package 3 P06
Number of Units in Package 3 384
Package 3 Height 75.000 cm
Package 3 Width 80.000 cm
Package 3 Length 60.000 cm
Package 3 Weight 116.368 kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information Yes
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov
Contractual warranty
Warranty 18 months
Feb 4, 2023 3
Product data sheet GV2ME14
Performance Curves
Thermal-Magnetic Tripping Curves for GV2ME and GV2P
Average Operating Times at 20 °C Related to Multiples of the Setting Current
1 3 poles from cold state
2 2 poles from cold state
3 3 poles from hot state
Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))
Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
4
Feb 4, 2023
1 Maximum peak current
2 24-32 A
3 20-25 A
4 17-23 A
5 13-18 A
6 9-14 A
7 6-10 A
8 4-6.3 A
9 2.5-4 A
10 1.6-2.5 A
11 1-1.6 A
12 Limit of rated ultimate breaking capacity on short-circuit of GV2ME (14, 18, 23, and 25 A ratings).
Thermal Limit on Short-Circuit for GV2ME
2
Thermal Limit in kA s in the Magnetic Operating Zone
2
Sum of I dt = f (prospective Isc) at 1.05 Ue = 435 V
Feb 4, 2023 5
1 24-32 A
2 20-25 A
3 17-23 A
4 13-18 A
5 9-14 A
6 6-10 A
7 4-6.3 A
8 2.5-4 A
9 1.6-2.5 A
10 1-1.6 A
6
Feb 4, 2023
Product data sheet GV2ME14
Dimensions Drawings
Dimension
GV2ME
(1) Maximum
X1 Electrical clearance = 40 mm for Ue ≤ 690 V
GV2ME●● 89
GV2ME●●3 101
Mounting
GV2ME
On 35 mm rail
c = 78.5 on AM1 DP200 (35 x 7.5)
c = 86 on AM1 DE200, ED200 (35 x 15)
On panel with adapter plate GV2AF02
On pre-slotted plate AM1 PA
On rails DZ5 MB201
GV2AF01
Combination GV2ME + TeSys k contactor
GV2AF3
Feb 4, 2023 7
Combination GV2ME + TeSys d contactor
GV2ME + LC1D09…D18 LC1D25 and D32
b 176.4 186.8
c1 94.1 100.4
c 99.6 105.9
GV2AF4 + LAD311
Combination GV2ME + TeSys d contactor
GV2ME + LC1D09…D18 LC1D25 and D32
b 176.4 186.8
c1 103.1 136.4
c 135.6 141.9
d1 107 107
d 112.5 112.5
GV2ME + GV1L3 (Current Limiter)
X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue ≤ 690 V
8
Feb 4, 2023
Product data sheet GV2ME14
Connections and Schema
GV2ME•• and GV2RT
Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only
Recommended replacement(s)
Feb 4, 2023 9