Control Schemes
Control Schemes
Cascade control
Control in which the output of one controller is the setpoint for another
controller
STEAM
INLET
FLOW
TRANSMITTER
CONDENSATE
OUTLET TEMPERATURE
TRANSMITTER
HEATED
WATER
COOL OUTLET
WATER
INLET
Advantages
1
Temperature – Temperature Cascade Control
Natural periods in the primary and secondary control loops
Manual Operation
2
Tuning
Tune the secondary controller and then tune the primary controller
Applications
3
Maintain the ratio of fuel flow and airflow constant.
Calorie Control
In – line Blending
FLOW
TRANSMITTER STIRRER
PRIMARY
PRIMARY
FLOW
SECONDARY
FLOW
FLOW
TRANSMITTER
PRIMARY
OUTPUT
OUTPUT
FLOW FLOW
CONTROLLER CONTROLLER
PRIMARY SET POINT PRIMARY
4
Ratio Control Systems
Serial
Parallel
5
Remote Ratio Setting (Cascade)
Digital Blending
6
RATIO SET STATION
Analog Type
IO = nIi +α IO = n2Ii
Digital type
Ratio Expressions
Mode A; MV = SVn (PV + P1) + P4 (EB + P2) + P3
Mode B; MV = SVn (PV + P1) = P4 (EB + P2) + P3
MV = Calculated output
PV = Measured Variable
EB = External Bias
SVn = Internally Calculated Ratio (0.000 ~ 8.000)
P1 ~ P4 = Parameters (P3: Internal Bias)
7
Feedforward Control System
STEAM
SET POINT INLET
COMPUTER FLOW FLOW
TRANSMITTER TRANSMITTER
FLOW CURRENT TO
TRANSMITTER AIR
WATER CONVERTER
CONTROL
VALVE
8
COOL HEATED
WATER WATER
INLET OUTPUT
Energy Balance
9
Feedforward loop with Dynamic Response
10
Auctioneering Control (Override Control, Limiting Control)
AUTO SELECTOR
STATION DISCHARGE
PRESSURE
SUNCTION CONTROLLER
PRESSURE
CONTROLLER
AUCTIONEERING CONTROL
- OVERRIDE -
AUTO SELECTOR
STATION PRESSURE
CONTROLLER
FLOW
CONTROLLER
AUCTIONEERING CONTROL
- LIMITING -
11
In auctioneering control, either the highest or the lowest signal from two or
more input signals is automatically selected. Common examples include the
following:
The symbols in the block diagrams represent the transfer functions of the
respective blocks. In general, such functions have a dynamic part and steady –
state part; when they are combined, they specify the output response to changes
in the input. The combination of often referred to as gain. Some useful insights
into the operation of feedback control can be obtained by considering the transfer
function in a more general way. This is done by recognizing that an integral
action of a controller provides the equivalent of a very high (infinite) gain,
although it may require some time to do so. We also noted that derivative
functions provide a prompt large gain in response to a rate of change on the
input.
By use of the block diagram representation, some essential characteristics
of systems with and without feedback can now be examined. The figure below
shows the block diagram of a single system without feedback, subjected to a
single disturbance U. This might represent, for instance, a process on manual
12
control where M is the manipulated variable, C is controlled variable, and U is a
disturbance. From Eq. 2,it can be seen that the effect of the disturbance is only
modified by G2. Furthermore, even if there is no disturbance (U = 0), a change in
G1 or G2 will cause a corresponding change in the controlled variable C. Since C
= G1G2M when U = 0, nonlinearity in the gains G 1 and G2 as they affect C versus
M1 can be made self-canceling to some extent.
Gain Calculations
Note that the steady – state gains have been calculated under the
operating conditions and will change as the operating conditions change.
If the disturbance U can be calculated as
13
Feedback Control Equations
Key Ratios
14
The ratio of the response of the primary feedback B to reference
input R.
In addition to Eqs. 3 to 7, two others (Eq. 8 and 9) are simply derived.
These equations show another interesting property of feedback control systems:
1. The effect of any additive input (such as R, U 1, and U2) to the system is
modified
directly by the elements between the point of entry and the $elected
signal (also
the case without feedback). Its effect is further modified by multiplying by
the
actuating ratio 1/(1 + GR).
2. The relative effect of changes in G on the control ratio C/ R is modified by
multiplying by the actuating ratio 1/(1 + GR). If the actuating ratio is small,
then
the loop ratio GH is large.
3. The control-ratio response C / R depends primarily on the feedback
elements H. In terms of control and measurement devices, this means that
the linearity and drift of a feedback device may be made satisfactory by
using a high value of loop ratio GH and quality feedback elements H. This
is useful, since GI may be a pneumatic pilot relay or electronic amplifier
stage that must supply power and may not have the required linearity and
low-drift characteristics.
4. For unit feedback (H equal to unity) and high forward gain G the output G
will reproduce the input R. If H is then increased above unity, C will be
less than R. This points out, in a general way, the effect of imperfections in
feedback elements, whether they involve dynamic or merely static
deficiencies.
5. If one of the forward elements G2 contains non - linearity, the effect of
feedback may be to shift the resulting distortion from C, the output of G 2,
back toward M+ U1, the input of G2.
15
Control and Regulation
Integrators have a high (ideally infinite) gain and therefore produce the
same two effects. However, they act less promptly than the proportional action.
Derivative response in the controller produces a prompt, but not sustained, high-
gain response to rapidly changing disturbances. If it were not for stability
considerations, many control requirements could be met by a proportional
controller with a very narrow proportional band, as indicated below.
Stability
Note that, if GH = -1, the denominator goes to zero and the expression
blows up. This occurs when the signal goes out of phase as it traverses the loop
and is a result of dynamic elements in the control loop, as discussed later.
Unfortunately, this limits the maximum value of loop gain that can be used.
Split Range
The standard split range control works well on simple control problems,
such as flow control. If you have a more complicated control, either due to
dynamics or constraints, then this controller will show a dramatic increase in
performance. The operators will also appreciate the simplicity of this control, as it
16
looks and operates like a normal split range control. It can be used in any place
that uses a "bulk" input and "fine tuning" input to achieve a desired setpoint. Flow
control is the most typical, but other important applications are where there are
two different sources of (say) heat, where one is cheap but sloppy, while the
other is expensive but results in precise control.
Benefits
Improves product quality by providing better control.
Saves engineers time because it is simple to install and tune.
17