By Trane
Bep nho

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 30 / 26 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.50 0.00 0.50 18.94 0.61 32.28 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.21 0.00 0.21 7.95 0.18 9.52 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.05 0.07 0.12 4.55 0.05 2.65 Wall Cond 0.00 0.00 0.00
Partition/Door 0.37 0.37 14.02 0.34 17.99 Partition/Door 0.00 0.00 0.00 Diffuser 258 258
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 258 258
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 258 258
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.07 1.20 45.45 1.18 62.43 Sub Total ==> 0.00 0.00 0.00 Nom Vent 11 11
AHU Vent 11 11
Internal Loads Internal Loads Infil 0 0
Lights 0.09 0.02 0.11 4.17 0.09 4.76 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.16 0 0 6.06 0.10 5.29 People 0.00 0 0.00 Return 258 258
Misc 0.52 0.00 0.52 19.70 0.52 27.51 Misc 0.00 0.00 0.00 Exhaust 11 11
Sub Total ==> 0.77 0.02 0.79 29.92 0.71 37.57 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.00 0.00 0.00 0.00 0.00 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.65 24.62 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.49 21.49
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.54
W/m² 220.06 0.00
Grand Total ==> 1.90 0.09 2.64 100.00 1.89 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.64 2.06 258 22.6 17.6 10.5 16.1 14.7 9.8 Floor 12 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 37 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.64 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 6 4 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 1 of 49
Room Checksums
By Trane
BPSX phan mem

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.7 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.7 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.59 0.00 5.59 19.30 5.51 29.14 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.73 0.00 1.73 5.97 1.69 8.94 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.01 0.73 1.74 6.01 1.01 5.34 Wall Cond 0.00 0.00 0.00
Partition/Door 0.94 0.94 3.24 1.02 5.39 Partition/Door 0.00 0.00 0.00 Diffuser 2,387 2,387
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 2,387 2,387
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,387 2,387
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 9.27 0.73 10.00 34.52 9.23 48.81 Sub Total ==> 0.00 0.00 0.00 Nom Vent 143 143
AHU Vent 143 143
Internal Loads Internal Loads Infil 0 0
Lights 1.15 0.29 1.44 4.97 1.19 6.29 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 2.18 0 2 7.53 1.30 6.87 People 0.00 0 0.00 Return 2,387 2,387
Misc 7.13 0.00 7.13 24.61 7.13 37.70 Misc 0.00 0.00 0.00 Exhaust 143 143
Sub Total ==> 10.46 0.29 10.75 37.11 9.62 50.87 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 0.32 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 8.26 28.51 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -0.14 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 6.0 6.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 14.64 14.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.33
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.62
W/m² 177.72 0.00
Grand Total ==> 19.79 0.92 28.97 100.00 18.91 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 20

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 28.98 21.41 2,387 22.7 17.9 10.8 15.7 14.4 9.7 Floor 163 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 107 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 28.98 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 64 38 60 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 2 of 49
Room Checksums
By Trane
Ho tro

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 17.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.3 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.44 0.00 5.44 48.48 5.44 58.49 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.63 0.00 1.63 14.53 1.63 17.53 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.47 0.60 1.07 9.54 0.47 5.05 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 3.57 0.40 4.30 Partition/Door 0.00 0.00 0.00 Diffuser 1,500 1,500
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,500 1,500
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,500 1,500
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.94 0.60 8.54 76.11 7.94 85.38 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 1.78 0.16 1.72 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 2.76 0.18 1.94 People 0.00 0 0.00 Return 1,500 1,500
Misc 1.01 0.00 1.01 9.00 1.01 10.86 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 13.55 1.35 14.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.11 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 10.43 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.09 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 1.3 1.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 65.20 65.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 133.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 2.05
W/m² 488.14 0.00
Grand Total ==> 9.43 0.62 11.22 100.00 9.30 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.23 10.16 1,500 22.3 17.2 10.1 17.1 15.0 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.23 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 53 37 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 3 of 49
Room Checksums
By Trane
Ho tro DV

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 6.11 0.00 6.11 31.81 6.11 43.74 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.89 0.00 1.89 9.84 1.89 13.53 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.62 0.62 3.23 0.62 4.44 Partition/Door 0.00 0.00 0.00 Diffuser 1,879 1,879
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,879 1,879
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,879 1,879
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 8.62 0.00 8.62 44.87 8.62 61.70 Sub Total ==> 0.00 0.00 0.00 Nom Vent 80 80
AHU Vent 80 80
Internal Loads Internal Loads Infil 0 0
Lights 0.64 0.16 0.80 4.16 0.64 4.58 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.22 0 1 6.35 0.70 5.01 People 0.00 0 0.00 Return 1,879 1,879
Misc 3.98 0.00 3.98 20.72 3.98 28.49 Misc 0.00 0.00 0.00 Exhaust 80 80
Sub Total ==> 5.84 0.16 6.00 31.23 5.32 38.08 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.21 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 4.61 24.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.2 4.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 20.65 20.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.78
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.74
W/m² 211.08 0.00
Grand Total ==> 14.49 0.11 19.21 100.00 13.97 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 11

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 19.22 14.99 1,879 22.6 17.6 10.5 16.1 14.7 9.9 Floor 91 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 71 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 19.22 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 42 42 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 4 of 49
Room Checksums
By Trane
Hoi truong

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.4 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 19.93 0.00 19.93 39.02 19.93 51.66 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 6.15 0.00 6.15 12.04 6.15 15.94 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 1.09 1.09 2.13 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.84 0.84 1.64 0.84 2.18 Partition/Door 0.00 0.00 0.00 Diffuser 5,459 5,459
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 5,459 5,459
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 5,459 5,459
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 26.92 1.09 28.01 54.85 26.92 69.78 Sub Total ==> 0.00 0.00 0.00 Nom Vent 173 173
AHU Vent 173 173
Internal Loads Internal Loads Infil 0 0
Lights 1.40 0.35 1.75 3.43 1.40 3.63 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 2.65 0 3 5.19 1.53 3.97 People 0.00 0 0.00 Return 5,459 5,459
Misc 8.66 0.00 8.66 16.96 8.66 22.45 Misc 0.00 0.00 0.00 Exhaust 173 173
Sub Total ==> 12.71 0.35 13.06 25.57 11.59 30.04 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 0.18 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 10.04 19.66 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.2 3.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 27.57 27.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 106.88
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.88
W/m² 257.78 0.00
Grand Total ==> 39.70 1.33 51.07 100.00 38.58 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 25

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 51.06 41.86 5,459 22.5 17.5 10.4 16.4 14.8 9.8 Floor 198 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 95 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 51.06 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 153 137 90 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 5 of 49
Room Checksums
By Trane
Internet

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 3 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 29 / 25 OADB: 32 OADB: 21 SADB 16.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.4 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 12.43 0.00 12.43 36.15 12.58 47.29 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 3.03 0.00 3.03 8.81 3.27 12.29 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 3.74 1.73 5.47 15.91 3.60 13.53 Wall Cond 0.00 0.00 0.00
Partition/Door 1.09 1.09 3.17 1.25 4.70 Partition/Door 0.00 0.00 0.00 Diffuser 4,176 4,176
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 4,176 4,176
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 4,176 4,176
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 20.29 1.73 22.02 64.05 20.70 77.82 Sub Total ==> 0.00 0.00 0.00 Nom Vent 92 92
AHU Vent 92 92
Internal Loads Internal Loads Infil 0 0
Lights 0.77 0.19 0.96 2.79 0.70 2.63 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.43 0 1 4.16 0.58 2.18 People 0.00 0 0.00 Return 4,176 4,176
Misc 4.59 0.00 4.59 13.35 4.59 17.26 Misc 0.00 0.00 0.00 Exhaust 92 92
Sub Total ==> 6.79 0.19 6.98 20.30 5.87 22.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.03 0.11 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 5.40 15.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.06 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.2 2.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 39.77 39.77
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 121.42
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.05
W/m² 327.34 0.00
Grand Total ==> 27.12 1.86 34.38 100.00 26.60 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 13

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 34.39 29.53 4,176 22.4 17.3 10.2 16.9 15.0 9.8 Floor 105 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 99 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 34.39 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 128 60 47 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 6 of 49
Room Checksums
By Trane
Ke hoach dau tu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 4.97 0.00 4.97 31.00 4.97 42.37 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.53 0.00 1.53 9.54 1.53 13.04 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.81 0.81 5.05 0.81 6.91 Partition/Door 0.00 0.00 0.00 Diffuser 1,584 1,584
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,584 1,584
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,584 1,584
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.31 0.00 7.31 45.60 7.31 62.32 Sub Total ==> 0.00 0.00 0.00 Nom Vent 66 66
AHU Vent 66 66
Internal Loads Internal Loads Infil 0 0
Lights 0.53 0.13 0.66 4.12 0.53 4.52 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.00 0 1 6.24 0.58 4.94 People 0.00 0 0.00 Return 1,584 1,584
Misc 3.28 0.00 3.28 20.46 3.28 27.96 Misc 0.00 0.00 0.00 Exhaust 66 66
Sub Total ==> 4.81 0.13 4.94 30.82 4.39 37.43 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.26 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.80 23.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.12 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.12 21.12
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 98.65
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.67
W/m² 213.91 0.00
Grand Total ==> 12.15 0.08 16.03 100.00 11.73 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 16.05 12.57 1,584 22.6 17.6 10.5 16.1 14.7 9.9 Floor 75 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 92 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 16.05 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 34 34 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 7 of 49
Room Checksums
By Trane
Ke toan hanh chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.11 0.00 3.11 31.90 3.11 43.38 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.96 0.00 0.96 9.85 0.96 13.39 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.44 0.44 4.51 0.44 6.14 Partition/Door 0.00 0.00 0.00 Diffuser 969 969
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 969 969
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 969 969
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.51 0.00 4.51 46.26 4.51 62.90 Sub Total ==> 0.00 0.00 0.00 Nom Vent 39 39
AHU Vent 39 39
Internal Loads Internal Loads Infil 0 0
Lights 0.32 0.08 0.40 4.10 0.32 4.46 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.60 0 1 6.15 0.35 4.88 People 0.00 0 0.00 Return 969 969
Misc 1.97 0.00 1.97 20.21 1.97 27.48 Misc 0.00 0.00 0.00 Exhaust 39 39
Sub Total ==> 2.89 0.08 2.97 30.46 2.64 36.82 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.28 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.28 23.38 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.53 21.53
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 99.40
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.62
W/m² 216.41 0.00
Grand Total ==> 7.42 0.05 9.75 100.00 7.17 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.74 7.65 969 22.6 17.6 10.5 16.1 14.7 9.9 Floor 45 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 50 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.74 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 21 21 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 8 of 49
Room Checksums
By Trane
Kho

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 30 / 26 OADB: 31 OADB: 21 SADB 16.2 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.50 0.00 0.50 19.76 0.61 33.33 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.21 0.00 0.21 8.30 0.18 9.84 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.05 0.07 0.12 4.74 0.05 2.73 Wall Cond 0.00 0.00 0.00
Partition/Door 0.37 0.37 14.62 0.34 18.58 Partition/Door 0.00 0.00 0.00 Diffuser 253 253
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 253 253
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 253 253
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.07 1.20 47.43 1.18 64.48 Sub Total ==> 0.00 0.00 0.00 Nom Vent 10 10
AHU Vent 10 10
Internal Loads Internal Loads Infil 0 0
Lights 0.08 0.02 0.10 3.95 0.08 4.37 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.15 0 0 5.93 0.09 4.92 People 0.00 0 0.00 Return 253 253
Misc 0.48 0.00 0.48 18.97 0.48 26.23 Misc 0.00 0.00 0.00 Exhaust 10 10
Sub Total ==> 0.71 0.02 0.73 28.85 0.65 35.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.00 0.00 0.00 0.00 0.00 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.60 23.72 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.8 3.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 22.97 22.97
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 100.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.36
W/m² 229.14 0.00
Grand Total ==> 1.84 0.09 2.53 100.00 1.83 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.52 1.99 253 22.6 17.6 10.5 16.2 14.8 9.9 Floor 11 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 37 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.52 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 6 4 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 9 of 49
Room Checksums
By Trane
Kiem soat

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 17.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.3 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.44 0.00 5.44 48.48 5.44 58.49 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.63 0.00 1.63 14.53 1.63 17.53 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.47 0.60 1.07 9.54 0.47 5.05 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 3.57 0.40 4.30 Partition/Door 0.00 0.00 0.00 Diffuser 1,500 1,500
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,500 1,500
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,500 1,500
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.94 0.60 8.54 76.11 7.94 85.38 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 1.78 0.16 1.72 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 2.76 0.18 1.94 People 0.00 0 0.00 Return 1,500 1,500
Misc 1.01 0.00 1.01 9.00 1.01 10.86 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 13.55 1.35 14.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.11 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 10.43 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.09 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 1.3 1.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 65.20 65.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 133.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 2.05
W/m² 488.14 0.00
Grand Total ==> 9.43 0.62 11.22 100.00 9.30 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.23 10.16 1,500 22.3 17.2 10.1 17.1 15.0 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.23 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 53 37 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 10 of 49
Room Checksums
By Trane
KV nghien cuu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.7 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.4 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 4.66 0.00 4.66 45.33 4.66 55.61 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.44 0.00 1.44 14.01 1.44 17.18 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.35 0.35 3.40 0.35 4.18 Partition/Door 0.00 0.00 0.00 Diffuser 1,250 1,250
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,250 1,250
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,250 1,250
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.45 0.00 6.45 62.74 6.45 76.97 Sub Total ==> 0.00 0.00 0.00 Nom Vent 29 29
AHU Vent 29 29
Internal Loads Internal Loads Infil 0 0
Lights 0.23 0.06 0.29 2.82 0.23 2.74 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.44 0 0 4.28 0.25 2.98 People 0.00 0 0.00 Return 1,250 1,250
Misc 1.44 0.00 1.44 14.01 1.44 17.18 Misc 0.00 0.00 0.00 Exhaust 29 29
Sub Total ==> 2.11 0.06 2.17 21.11 1.92 22.91 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.12 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.67 16.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.3 2.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 37.88 37.88
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 121.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.21
W/m² 311.77 0.00
Grand Total ==> 8.57 0.04 10.28 100.00 8.38 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 10.29 8.76 1,250 22.4 17.3 10.2 16.7 15.0 9.9 Floor 33 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 40 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.29 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 32 32 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 11 of 49
Room Checksums
By Trane
KV phan cung

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 6.11 0.00 6.11 32.38 6.11 44.28 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.89 0.00 1.89 10.02 1.89 13.70 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.62 0.62 3.29 0.62 4.49 Partition/Door 0.00 0.00 0.00 Diffuser 1,864 1,864
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,864 1,864
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,864 1,864
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 8.62 0.00 8.62 45.68 8.62 62.46 Sub Total ==> 0.00 0.00 0.00 Nom Vent 77 77
AHU Vent 77 77
Internal Loads Internal Loads Infil 0 0
Lights 0.62 0.16 0.78 4.13 0.62 4.49 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.18 0 1 6.25 0.68 4.93 People 0.00 0 0.00 Return 1,864 1,864
Misc 3.85 0.00 3.85 20.40 3.85 27.90 Misc 0.00 0.00 0.00 Exhaust 77 77
Sub Total ==> 5.65 0.16 5.81 30.79 5.15 37.32 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.22 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 4.46 23.64 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.11 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.18 21.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 98.77
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.66
W/m² 214.30 0.00
Grand Total ==> 14.30 0.11 18.87 100.00 13.80 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 11

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 18.87 14.78 1,864 22.6 17.6 10.5 16.1 14.7 9.9 Floor 88 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 71 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 18.87 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 42 42 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 12 of 49
Room Checksums
By Trane
Mang phan tai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 30 / 26 OADB: 31 OADB: 21 SADB 15.4 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 23.0 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.23 0.00 3.23 9.24 3.95 18.81 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.42 0.00 1.42 4.06 1.21 5.76 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.19 0.60 1.79 5.12 1.25 5.95 Wall Cond 0.00 0.00 0.00
Partition/Door 1.16 1.16 3.32 1.05 5.00 Partition/Door 0.00 0.00 0.00 Diffuser 2,516 2,516
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 2,516 2,516
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,516 2,516
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.00 0.60 7.60 21.75 7.46 35.52 Sub Total ==> 0.00 0.00 0.00 Nom Vent 200 200
AHU Vent 200 200
Internal Loads Internal Loads Infil 0 0
Lights 1.61 0.40 2.01 5.75 1.66 7.90 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 3.05 0 3 8.73 1.82 8.67 People 0.00 0 0.00 Return 2,516 2,516
Misc 9.97 0.00 9.97 28.53 9.97 47.48 Misc 0.00 0.00 0.00 Exhaust 200 200
Sub Total ==> 14.63 0.40 15.03 43.02 13.45 64.05 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.09 0.43 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 12.36 35.37 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -0.14 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 7.9 7.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 11.03 11.03
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.96
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.52
W/m² 153.23 0.00
Grand Total ==> 21.71 0.87 34.94 100.00 21.00 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 28

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 34.95 23.92 2,516 23.0 18.3 11.1 15.4 14.4 9.8 Floor 228 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 110 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 34.95 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 55 28 50 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 13 of 49
Room Checksums
By Trane
MDF center

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.17 0.00 2.17 29.28 2.17 41.18 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.67 0.00 0.67 9.04 0.67 12.71 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.19 0.24 0.43 5.80 0.19 3.61 Wall Cond 0.00 0.00 0.00
Partition/Door 0.31 0.31 4.18 0.31 5.88 Partition/Door 0.00 0.00 0.00 Diffuser 718 718
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 718 718
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 718 718
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.34 0.24 3.58 48.31 3.34 63.38 Sub Total ==> 0.00 0.00 0.00 Nom Vent 29 29
AHU Vent 29 29
Internal Loads Internal Loads Infil 0 0
Lights 0.23 0.06 0.29 3.91 0.23 4.36 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.44 0 0 5.94 0.25 4.74 People 0.00 0 0.00 Return 718 718
Misc 1.44 0.00 1.44 19.43 1.44 27.32 Misc 0.00 0.00 0.00 Exhaust 29 29
Sub Total ==> 2.11 0.06 2.17 29.28 1.92 36.43 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.19 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.67 22.54 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.0 4.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.76 21.76
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 96.54
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.44
W/m² 225.25 0.00
Grand Total ==> 5.46 0.28 7.41 100.00 5.27 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.44 5.90 718 22.6 17.6 10.5 16.1 14.6 9.8 Floor 33 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 36 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.44 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 21 15 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 14 of 49
Room Checksums
By Trane
P cai dat

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.18 0.00 5.18 31.57 5.18 42.99 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.60 0.00 1.60 9.75 1.60 13.28 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.79 0.79 4.81 0.79 6.56 Partition/Door 0.00 0.00 0.00 Diffuser 1,630 1,630
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,630 1,630
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,630 1,630
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.57 0.00 7.57 46.13 7.57 62.82 Sub Total ==> 0.00 0.00 0.00 Nom Vent 67 67
AHU Vent 67 67
Internal Loads Internal Loads Infil 0 0
Lights 0.54 0.13 0.67 4.08 0.54 4.48 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.02 0 1 6.22 0.59 4.90 People 0.00 0 0.00 Return 1,630 1,630
Misc 3.32 0.00 3.32 20.23 3.32 27.55 Misc 0.00 0.00 0.00 Exhaust 67 67
Sub Total ==> 4.88 0.13 5.01 30.53 4.45 36.93 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.85 23.46 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.12 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.45 21.45
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 99.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.63
W/m² 215.94 0.00
Grand Total ==> 12.48 0.08 16.41 100.00 12.05 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 16.42 12.89 1,630 22.6 17.6 10.5 16.1 14.7 9.9 Floor 76 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 90 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 16.42 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 36 36 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 15 of 49
Room Checksums
By Trane
P cuoc phi

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.2 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.98 0.00 2.98 28.19 2.93 38.45 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.89 0.00 0.89 8.42 0.88 11.55 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.48 0.37 0.85 8.04 0.48 6.30 Wall Cond 0.00 0.00 0.00
Partition/Door 0.60 0.60 5.68 0.65 8.53 Partition/Door 0.00 0.00 0.00 Diffuser 1,051 1,051
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,051 1,051
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,051 1,051
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.95 0.37 5.32 50.33 4.94 64.83 Sub Total ==> 0.00 0.00 0.00 Nom Vent 39 39
AHU Vent 39 39
Internal Loads Internal Loads Infil 0 0
Lights 0.32 0.08 0.40 3.78 0.33 4.33 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.61 0 1 5.77 0.36 4.72 People 0.00 0 0.00 Return 1,051 1,051
Misc 1.97 0.00 1.97 18.64 1.97 25.85 Misc 0.00 0.00 0.00 Exhaust 39 39
Sub Total ==> 2.90 0.08 2.98 28.19 2.66 34.91 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.26 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.28 21.57 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.09 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.7 3.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 23.35 23.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 99.40
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.26
W/m² 234.78 0.00
Grand Total ==> 7.87 0.42 10.57 100.00 7.62 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 10.57 8.48 1,051 22.5 17.5 10.4 16.2 14.7 9.8 Floor 45 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 71 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.57 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 33 20 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 16 of 49
Room Checksums
By Trane
P hop

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.7 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.7 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 20.64 1.21 30.79 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.38 0.00 0.38 6.38 0.37 9.41 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 4.19 0.11 2.80 Wall Cond 0.00 0.00 0.00
Partition/Door 0.27 0.27 4.53 0.29 7.38 Partition/Door 0.00 0.00 0.00 Diffuser 502 502
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 502 502
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 502 502
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.99 0.14 2.13 35.74 1.98 50.38 Sub Total ==> 0.00 0.00 0.00 Nom Vent 29 29
AHU Vent 29 29
Internal Loads Internal Loads Infil 0 0
Lights 0.23 0.06 0.29 4.87 0.24 6.11 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.44 0 0 7.38 0.26 6.62 People 0.00 0 0.00 Return 502 502
Misc 1.44 0.00 1.44 24.16 1.44 36.64 Misc 0.00 0.00 0.00 Exhaust 29 29
Sub Total ==> 2.11 0.06 2.17 36.41 1.94 49.36 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.67 28.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.17 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.7 5.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 15.22 15.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 84.05
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.52
W/m² 180.96 0.00
Grand Total ==> 4.11 0.18 5.96 100.00 3.93 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.97 4.44 502 22.7 17.9 10.8 15.7 14.5 9.7 Floor 33 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 31 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.97 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 17 of 49
Room Checksums
By Trane
P hop 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.8 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.7 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 20.95 1.21 31.19 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.38 0.00 0.38 6.47 0.37 9.54 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 4.26 0.11 2.84 Wall Cond 0.00 0.00 0.00
Partition/Door 0.28 0.28 4.77 0.30 7.73 Partition/Door 0.00 0.00 0.00 Diffuser 498 498
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 498 498
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 498 498
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.00 0.14 2.14 36.46 1.99 51.29 Sub Total ==> 0.00 0.00 0.00 Nom Vent 28 28
AHU Vent 28 28
Internal Loads Internal Loads Infil 0 0
Lights 0.23 0.06 0.29 4.94 0.23 5.93 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.43 0 0 7.33 0.25 6.44 People 0.00 0 0.00 Return 498 498
Misc 1.40 0.00 1.40 23.85 1.40 36.08 Misc 0.00 0.00 0.00 Exhaust 28 28
Sub Total ==> 2.06 0.06 2.12 36.12 1.88 48.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.26 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.62 27.60 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.17 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.6 5.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 15.56 15.56
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 84.87
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.45
W/m² 183.27 0.00
Grand Total ==> 4.07 0.18 5.87 100.00 3.88 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.87 4.38 498 22.7 17.8 10.7 15.8 14.5 9.7 Floor 32 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 32 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.87 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 18 of 49
Room Checksums
By Trane
P hop 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 6.11 0.00 6.11 31.89 6.11 43.52 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.89 0.00 1.89 9.86 1.89 13.46 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.80 0.80 4.18 0.80 5.70 Partition/Door 0.00 0.00 0.00 Diffuser 1,898 1,898
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,898 1,898
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,898 1,898
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 8.80 0.00 8.80 45.93 8.80 62.68 Sub Total ==> 0.00 0.00 0.00 Nom Vent 78 78
AHU Vent 78 78
Internal Loads Internal Loads Infil 0 0
Lights 0.63 0.16 0.79 4.12 0.63 4.49 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.19 0 1 6.21 0.69 4.91 People 0.00 0 0.00 Return 1,898 1,898
Misc 3.89 0.00 3.89 20.30 3.89 27.71 Misc 0.00 0.00 0.00 Exhaust 78 78
Sub Total ==> 5.71 0.16 5.87 30.64 5.21 37.11 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.21 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 4.51 23.54 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.32 21.32
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 99.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.65
W/m² 215.17 0.00
Grand Total ==> 14.54 0.11 19.16 100.00 14.04 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 11

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 19.16 15.02 1,898 22.6 17.6 10.5 16.1 14.7 9.9 Floor 89 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 91 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 19.16 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 42 42 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 19 of 49
Room Checksums
By Trane
P hop 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.7 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.7 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 20.64 1.21 30.79 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.38 0.00 0.38 6.38 0.37 9.41 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 4.19 0.11 2.80 Wall Cond 0.00 0.00 0.00
Partition/Door 0.27 0.27 4.53 0.29 7.38 Partition/Door 0.00 0.00 0.00 Diffuser 502 502
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 502 502
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 502 502
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.99 0.14 2.13 35.74 1.98 50.38 Sub Total ==> 0.00 0.00 0.00 Nom Vent 29 29
AHU Vent 29 29
Internal Loads Internal Loads Infil 0 0
Lights 0.23 0.06 0.29 4.87 0.24 6.11 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.44 0 0 7.38 0.26 6.62 People 0.00 0 0.00 Return 502 502
Misc 1.44 0.00 1.44 24.16 1.44 36.64 Misc 0.00 0.00 0.00 Exhaust 29 29
Sub Total ==> 2.11 0.06 2.17 36.41 1.94 49.36 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.67 28.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.17 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.7 5.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 15.22 15.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 84.05
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.52
W/m² 180.96 0.00
Grand Total ==> 4.11 0.18 5.96 100.00 3.93 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.97 4.44 502 22.7 17.9 10.8 15.7 14.5 9.7 Floor 33 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 31 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.97 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 20 of 49
Room Checksums
By Trane
P ky thuat 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.7 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.7 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 20.60 1.21 30.71 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.38 0.00 0.38 6.37 0.37 9.39 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 4.19 0.11 2.79 Wall Cond 0.00 0.00 0.00
Partition/Door 0.28 0.28 4.69 0.30 7.61 Partition/Door 0.00 0.00 0.00 Diffuser 504 504
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 504 504
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 504 504
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.00 0.14 2.14 35.85 1.99 50.51 Sub Total ==> 0.00 0.00 0.00 Nom Vent 29 29
AHU Vent 29 29
Internal Loads Internal Loads Infil 0 0
Lights 0.23 0.06 0.29 4.86 0.24 6.09 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.44 0 0 7.37 0.26 6.60 People 0.00 0 0.00 Return 504 504
Misc 1.44 0.00 1.44 24.12 1.44 36.55 Misc 0.00 0.00 0.00 Exhaust 29 29
Sub Total ==> 2.11 0.06 2.17 36.35 1.94 49.24 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.67 27.97 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.17 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.7 5.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 15.27 15.27
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 84.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.51
W/m² 181.24 0.00
Grand Total ==> 4.12 0.18 5.97 100.00 3.94 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.98 4.45 504 22.7 17.9 10.8 15.7 14.5 9.7 Floor 33 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 32 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.98 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 21 of 49
Room Checksums
By Trane
P ky thuat 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.02 0.00 5.02 31.55 5.02 43.24 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.55 0.00 1.55 9.74 1.55 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.62 0.62 3.90 0.62 5.34 Partition/Door 0.00 0.00 0.00 Diffuser 1,564 1,564
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,564 1,564
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,564 1,564
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.19 0.00 7.19 45.19 7.19 61.93 Sub Total ==> 0.00 0.00 0.00 Nom Vent 66 66
AHU Vent 66 66
Internal Loads Internal Loads Infil 0 0
Lights 0.53 0.13 0.66 4.15 0.53 4.57 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.00 0 1 6.29 0.58 5.00 People 0.00 0 0.00 Return 1,564 1,564
Misc 3.28 0.00 3.28 20.62 3.28 28.25 Misc 0.00 0.00 0.00 Exhaust 66 66
Sub Total ==> 4.81 0.13 4.94 31.05 4.39 37.81 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.26 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.80 23.88 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.2 4.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 20.85 20.85
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 98.16
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.71
W/m² 212.31 0.00
Grand Total ==> 12.03 0.08 15.91 100.00 11.61 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.93 12.45 1,564 22.6 17.6 10.5 16.1 14.7 9.9 Floor 75 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 71 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.93 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 34 34 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 22 of 49
Room Checksums
By Trane
P lam viec

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 24.36 1.21 33.33 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.37 0.00 0.37 7.33 0.37 10.19 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 4.95 0.11 3.03 Wall Cond 0.00 0.00 0.00
Partition/Door 0.52 0.52 10.30 0.57 15.70 Partition/Door 0.00 0.00 0.00 Diffuser 493 493
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 493 493
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 493 493
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.23 0.14 2.37 46.93 2.26 62.26 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 3.96 0.17 4.68 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 6.14 0.18 4.96 People 0.00 0 0.00 Return 493 493
Misc 1.01 0.00 1.01 20.00 1.01 27.82 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 30.10 1.36 37.47 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.28 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 23.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.42 21.42
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.45
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.55
W/m² 219.70 0.00
Grand Total ==> 3.72 0.16 5.05 100.00 3.63 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.06 3.99 493 22.6 17.6 10.5 16.1 14.7 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 62 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.06 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 23 of 49
Room Checksums
By Trane
P lam viec 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 26.45 1.23 38.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.38 0.00 0.38 8.17 0.38 11.91 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 5.38 0.11 3.45 Wall Cond 0.00 0.00 0.00
Partition/Door 0.11 0.11 2.37 0.11 3.45 Partition/Door 0.00 0.00 0.00 Diffuser 417 417
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 417 417
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 417 417
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.83 0.14 1.97 42.37 1.83 57.37 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 4.30 0.16 5.02 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 6.67 0.18 5.64 People 0.00 0 0.00 Return 417 417
Misc 1.01 0.00 1.01 21.72 1.01 31.66 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 32.69 1.35 42.32 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.31 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 25.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.22 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.8 4.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.13 18.13
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.79
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.95
W/m² 201.83 0.00
Grand Total ==> 3.32 0.16 4.65 100.00 3.19 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.64 3.58 417 22.6 17.7 10.6 15.9 14.5 9.7 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 12 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.64 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 24 of 49
Room Checksums
By Trane
P tiep khach

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.34 0.00 1.34 26.33 1.32 36.16 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.40 0.00 0.40 7.86 0.40 10.96 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.12 0.15 0.27 5.30 0.12 3.29 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 7.86 0.44 12.05 Partition/Door 0.00 0.00 0.00 Diffuser 496 496
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 496 496
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 496 496
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.15 2.41 47.35 2.28 62.47 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 3.93 0.17 4.66 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 6.09 0.18 4.93 People 0.00 0 0.00 Return 496 496
Misc 1.01 0.00 1.01 19.84 1.01 27.67 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 29.86 1.36 37.26 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 22.99 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.55 21.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.51
W/m² 221.56 0.00
Grand Total ==> 3.75 0.17 5.09 100.00 3.65 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.10 4.03 496 22.6 17.6 10.5 16.1 14.7 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.10 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 9 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 25 of 49
Room Checksums
By Trane
P tinh cuoc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.0 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.00 0.00 2.00 21.30 1.97 30.40 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.60 0.00 0.60 6.39 0.60 9.26 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.53 0.29 0.82 8.73 0.53 8.18 Wall Cond 0.00 0.00 0.00
Partition/Door 0.60 0.60 6.39 0.65 10.03 Partition/Door 0.00 0.00 0.00 Diffuser 858 858
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 858 858
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 858 858
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.73 0.29 4.02 42.81 3.75 57.87 Sub Total ==> 0.00 0.00 0.00 Nom Vent 40 40
AHU Vent 40 40
Internal Loads Internal Loads Infil 0 0
Lights 0.33 0.08 0.41 4.37 0.34 5.25 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.63 0 1 6.71 0.36 5.56 People 0.00 0 0.00 Return 858 858
Misc 2.01 0.00 2.01 21.41 2.01 31.02 Misc 0.00 0.00 0.00 Exhaust 40 40
Sub Total ==> 2.97 0.08 3.05 32.48 2.71 41.82 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.31 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.33 24.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.11 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.7 4.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.65 18.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.90
W/m² 204.14 0.00
Grand Total ==> 6.72 0.34 9.39 100.00 6.48 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.39 7.26 858 22.6 17.7 10.6 16.0 14.6 9.8 Floor 46 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 71 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.39 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 26 14 53 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 26 of 49
Room Checksums
By Trane
P truc dai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.2 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.36 0.00 3.36 33.63 3.36 45.04 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.04 0.00 1.04 10.41 1.04 13.94 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.47 0.47 4.70 0.47 6.30 Partition/Door 0.00 0.00 0.00 Diffuser 1,025 1,025
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,025 1,025
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,025 1,025
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.87 0.00 4.87 48.75 4.87 65.28 Sub Total ==> 0.00 0.00 0.00 Nom Vent 39 39
AHU Vent 39 39
Internal Loads Internal Loads Infil 0 0
Lights 0.31 0.08 0.39 3.90 0.31 4.16 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.59 0 1 5.91 0.34 4.56 People 0.00 0 0.00 Return 1,025 1,025
Misc 1.92 0.00 1.92 19.22 1.92 25.74 Misc 0.00 0.00 0.00 Exhaust 39 39
Sub Total ==> 2.82 0.08 2.90 29.03 2.57 34.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.23 22.32 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.8 3.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 23.29 23.29
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 102.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.40
W/m² 227.09 0.00
Grand Total ==> 7.71 0.05 9.99 100.00 7.46 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 10.00 7.95 1,025 22.5 17.5 10.5 16.2 14.8 9.9 Floor 44 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 53 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.00 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 23 23 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 27 of 49
Room Checksums
By Trane
PGD

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.34 0.00 1.34 26.33 1.32 36.16 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.40 0.00 0.40 7.86 0.40 10.96 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.12 0.15 0.27 5.30 0.12 3.29 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 7.86 0.44 12.05 Partition/Door 0.00 0.00 0.00 Diffuser 496 496
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 496 496
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 496 496
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.15 2.41 47.35 2.28 62.47 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 3.93 0.17 4.66 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 6.09 0.18 4.93 People 0.00 0 0.00 Return 496 496
Misc 1.01 0.00 1.01 19.84 1.01 27.67 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 29.86 1.36 37.26 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 22.99 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.55 21.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.51
W/m² 221.56 0.00
Grand Total ==> 3.75 0.17 5.09 100.00 3.65 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.10 4.03 496 22.6 17.6 10.5 16.1 14.7 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.10 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 9 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 28 of 49
Room Checksums
By Trane
PGD hanh chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 24.95 1.21 34.57 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.37 0.00 0.37 7.51 0.37 10.57 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 5.07 0.11 3.14 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 8.11 0.44 12.57 Partition/Door 0.00 0.00 0.00 Diffuser 471 471
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 471 471
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 471 471
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.11 0.14 2.25 45.64 2.13 60.86 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 4.06 0.17 4.86 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 6.29 0.18 5.14 People 0.00 0 0.00 Return 471 471
Misc 1.01 0.00 1.01 20.49 1.01 28.86 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 30.83 1.36 38.86 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 23.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.3 4.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 20.49 20.49
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 95.46
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.66
W/m² 214.49 0.00
Grand Total ==> 3.60 0.16 4.93 100.00 3.50 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.94 3.87 471 22.6 17.6 10.5 16.1 14.6 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.94 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 29 of 49
Room Checksums
By Trane
PGD kinh te

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.34 0.00 1.34 26.33 1.32 36.16 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.40 0.00 0.40 7.86 0.40 10.96 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.12 0.15 0.27 5.30 0.12 3.29 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 7.86 0.44 12.05 Partition/Door 0.00 0.00 0.00 Diffuser 496 496
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 496 496
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 496 496
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.15 2.41 47.35 2.28 62.47 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 3.93 0.17 4.66 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 6.09 0.18 4.93 People 0.00 0 0.00 Return 496 496
Misc 1.01 0.00 1.01 19.84 1.01 27.67 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 29.86 1.36 37.26 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 22.99 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.55 21.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.51
W/m² 221.56 0.00
Grand Total ==> 3.75 0.17 5.09 100.00 3.65 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.10 4.03 496 22.6 17.6 10.5 16.1 14.7 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.10 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 9 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 30 of 49
Room Checksums
By Trane
PGD ky thuat

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.23 0.00 1.23 24.95 1.21 34.57 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.37 0.00 0.37 7.51 0.37 10.57 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.11 0.14 0.25 5.07 0.11 3.14 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 8.11 0.44 12.57 Partition/Door 0.00 0.00 0.00 Diffuser 471 471
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 471 471
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 471 471
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.11 0.14 2.25 45.64 2.13 60.86 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 4.06 0.17 4.86 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 6.29 0.18 5.14 People 0.00 0 0.00 Return 471 471
Misc 1.01 0.00 1.01 20.49 1.01 28.86 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 30.83 1.36 38.86 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 23.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.3 4.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 20.49 20.49
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 95.46
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.66
W/m² 214.49 0.00
Grand Total ==> 3.60 0.16 4.93 100.00 3.50 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.94 3.87 471 22.6 17.6 10.5 16.1 14.6 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.94 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 8 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 31 of 49
Room Checksums
By Trane
Phong bao tri

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.5 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.4 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 4.29 0.00 4.29 34.68 4.29 45.64 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.29 0.00 1.29 10.43 1.29 13.72 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.76 0.56 1.32 10.67 0.76 8.09 Wall Cond 0.00 0.00 0.00
Partition/Door 0.57 0.57 4.61 0.57 6.06 Partition/Door 0.00 0.00 0.00 Diffuser 1,368 1,368
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,368 1,368
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,368 1,368
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.91 0.56 7.47 60.39 6.91 73.51 Sub Total ==> 0.00 0.00 0.00 Nom Vent 37 37
AHU Vent 37 37
Internal Loads Internal Loads Infil 0 0
Lights 0.30 0.07 0.37 2.99 0.30 3.19 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.57 0 1 4.61 0.33 3.51 People 0.00 0 0.00 Return 1,368 1,368
Misc 1.84 0.00 1.84 14.87 1.84 19.57 Misc 0.00 0.00 0.00 Exhaust 37 37
Sub Total ==> 2.71 0.07 2.78 22.47 2.47 26.28 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.21 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.13 17.22 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.7 2.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 32.56 32.56
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 110.55
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.40
W/m² 294.30 0.00
Grand Total ==> 9.64 0.60 12.37 100.00 9.40 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.37 10.41 1,368 22.4 17.4 10.3 16.5 14.8 9.8 Floor 42 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 67 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.37 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 49 29 60 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 32 of 49
Room Checksums
By Trane
Phong hop

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.57 0.00 1.57 23.90 1.57 34.81 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.49 0.00 0.49 7.46 0.49 10.86 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.35 0.22 0.57 8.68 0.35 7.76 Wall Cond 0.00 0.00 0.00
Partition/Door 0.21 0.21 3.20 0.21 4.66 Partition/Door 0.00 0.00 0.00 Diffuser 594 594
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 594 594
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 594 594
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.62 0.22 2.84 43.23 2.62 58.09 Sub Total ==> 0.00 0.00 0.00 Nom Vent 28 28
AHU Vent 28 28
Internal Loads Internal Loads Infil 0 0
Lights 0.23 0.06 0.29 4.41 0.23 5.10 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.43 0 0 6.54 0.25 5.54 People 0.00 0 0.00 Return 594 594
Misc 1.40 0.00 1.40 21.31 1.40 31.04 Misc 0.00 0.00 0.00 Exhaust 28 28
Sub Total ==> 2.06 0.06 2.12 32.27 1.88 41.69 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.22 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.62 24.66 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.15 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.7 4.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.55 18.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 90.30
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.87
W/m² 205.24 0.00
Grand Total ==> 4.69 0.26 6.57 100.00 4.51 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 6.57 5.08 594 22.6 17.7 10.6 15.9 14.5 9.7 Floor 32 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 24 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 6.57 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 11 56 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 33 of 49
Room Checksums
By Trane
Phong khach

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.5 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.94 0.00 1.94 30.46 1.91 39.96 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.58 0.00 0.58 9.11 0.58 12.13 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.50 0.28 0.78 12.24 0.50 10.46 Wall Cond 0.00 0.00 0.00
Partition/Door 0.39 0.39 6.12 0.42 8.79 Partition/Door 0.00 0.00 0.00 Diffuser 687 687
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 687 687
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 687 687
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.41 0.28 3.69 57.93 3.41 71.34 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 3.14 0.17 3.56 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 4.87 0.18 3.77 People 0.00 0 0.00 Return 687 687
Misc 1.01 0.00 1.01 15.86 1.01 21.13 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 23.86 1.36 28.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.21 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 18.37 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.16 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.9 2.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 29.89 29.89
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 107.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.61
W/m² 277.02 0.00
Grand Total ==> 4.90 0.30 6.37 100.00 4.78 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 6.37 5.31 687 22.5 17.4 10.3 16.5 14.8 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 46 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 6.37 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 13 53 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 34 of 49
Room Checksums
By Trane
Phong lab

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.4 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.66 0.00 1.66 35.93 1.63 45.40 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.50 0.00 0.50 10.82 0.49 13.65 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.36 0.36 7.79 0.40 11.14 Partition/Door 0.00 0.00 0.00 Diffuser 513 513
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 513 513
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 513 513
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.52 0.00 2.52 54.55 2.52 70.19 Sub Total ==> 0.00 0.00 0.00 Nom Vent 16 16
AHU Vent 16 16
Internal Loads Internal Loads Infil 0 0
Lights 0.13 0.03 0.16 3.46 0.13 3.62 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.24 0 0 5.19 0.14 3.90 People 0.00 0 0.00 Return 513 513
Misc 0.79 0.00 0.79 17.10 0.79 22.01 Misc 0.00 0.00 0.00 Exhaust 16 16
Sub Total ==> 1.16 0.03 1.19 25.76 1.06 29.53 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.28 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.91 19.70 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.1 3.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 28.48 28.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 111.00
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.90
W/m² 256.44 0.00
Grand Total ==> 3.69 0.02 4.62 100.00 3.59 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.62 3.78 513 22.5 17.4 10.3 16.4 14.9 9.9 Floor 18 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 43 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.62 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 11 11 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 35 of 49
Room Checksums
By Trane
Phong nghiep vu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.4 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.20 0.00 1.20 25.59 1.18 34.01 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.36 0.00 0.36 7.68 0.36 10.37 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.60 0.23 0.83 17.70 0.60 17.29 Wall Cond 0.00 0.00 0.00
Partition/Door 0.27 0.27 5.76 0.29 8.36 Partition/Door 0.00 0.00 0.00 Diffuser 496 496
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 496 496
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 496 496
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.43 0.23 2.66 56.72 2.43 70.03 Sub Total ==> 0.00 0.00 0.00 Nom Vent 15 15
AHU Vent 15 15
Internal Loads Internal Loads Infil 0 0
Lights 0.12 0.03 0.15 3.20 0.13 3.75 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.24 0 0 5.12 0.14 4.03 People 0.00 0 0.00 Return 496 496
Misc 0.76 0.00 0.76 16.20 0.76 21.90 Misc 0.00 0.00 0.00 Exhaust 15 15
Sub Total ==> 1.12 0.03 1.15 24.52 1.03 29.68 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.88 18.76 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.1 3.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 28.48 28.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 105.50
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.71
W/m² 269.75 0.00
Grand Total ==> 3.56 0.25 4.69 100.00 3.47 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.70 3.89 496 22.5 17.4 10.3 16.4 14.7 9.7 Floor 17 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 32 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.70 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 21 8 40 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 36 of 49
Room Checksums
By Trane
Phong tiep thi ban hang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 12 Mo/Hr: 6 / 12 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 24 OADB: 30 OADB: 21 SADB 16.2 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 4.39 0.00 4.39 28.84 4.80 44.16 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.94 0.00 0.94 6.18 0.77 7.08 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.72 0.50 1.22 8.02 0.70 6.44 Wall Cond 0.00 0.00 0.00
Partition/Door 0.50 0.50 3.29 0.37 3.40 Partition/Door 0.00 0.00 0.00 Diffuser 1,494 1,494
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,494 1,494
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,494 1,494
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.55 0.50 7.05 46.32 6.64 61.09 Sub Total ==> 0.00 0.00 0.00 Nom Vent 63 63
AHU Vent 63 63
Internal Loads Internal Loads Infil 0 0
Lights 0.53 0.13 0.66 4.34 0.53 4.88 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.85 0 1 5.58 0.53 4.88 People 0.00 0 0.00 Return 1,494 1,494
Misc 3.15 0.00 3.15 20.70 3.15 28.98 Misc 0.00 0.00 0.00 Exhaust 63 63
Sub Total ==> 4.53 0.13 4.66 30.62 4.21 38.73 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.18 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.52 23.13 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.07 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.2 4.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 20.74 20.74
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 98.16
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.73
W/m² 211.18 0.00
Grand Total ==> 11.10 0.60 15.22 100.00 10.87 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.21 12.08 1,494 22.5 17.6 10.5 16.2 14.7 9.8 Floor 72 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 82 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.21 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 43 25 59 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 37 of 49
Room Checksums
By Trane
PNVu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 3 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 29 / 25 OADB: 32 OADB: 21 SADB 17.3 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.3 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 10.66 0.00 10.66 48.65 10.48 57.30 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 2.69 0.00 2.69 12.28 2.91 15.91 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.63 1.33 2.96 13.51 1.86 10.17 Wall Cond 0.00 0.00 0.00
Partition/Door 0.54 0.54 2.46 0.62 3.39 Partition/Door 0.00 0.00 0.00 Diffuser 3,082 3,082
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 3,082 3,082
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,082 3,082
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 15.52 1.33 16.85 76.91 15.87 86.77 Sub Total ==> 0.00 0.00 0.00 Nom Vent 38 38
AHU Vent 38 38
Internal Loads Internal Loads Infil 0 0
Lights 0.32 0.08 0.40 1.83 0.29 1.59 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.58 0 1 2.65 0.24 1.31 People 0.00 0 0.00 Return 3,082 3,082
Misc 1.88 0.00 1.88 8.58 1.88 10.28 Misc 0.00 0.00 0.00 Exhaust 38 38
Sub Total ==> 2.78 0.08 2.86 13.05 2.41 13.18 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.01 0.05 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.21 10.09 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.05 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 1.2 1.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 71.66 71.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 140.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 1.96
W/m² 509.44 0.00
Grand Total ==> 18.32 1.38 21.91 100.00 18.29 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 21.92 19.93 3,082 22.3 17.2 10.1 17.3 15.1 9.8 Floor 43 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 50 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 21.92 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 85 53 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 38 of 49
Room Checksums
By Trane
Quan tri HT mang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 4.97 0.00 4.97 31.00 4.97 42.37 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.53 0.00 1.53 9.54 1.53 13.04 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.81 0.81 5.05 0.81 6.91 Partition/Door 0.00 0.00 0.00 Diffuser 1,584 1,584
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,584 1,584
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,584 1,584
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.31 0.00 7.31 45.60 7.31 62.32 Sub Total ==> 0.00 0.00 0.00 Nom Vent 66 66
AHU Vent 66 66
Internal Loads Internal Loads Infil 0 0
Lights 0.53 0.13 0.66 4.12 0.53 4.52 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.00 0 1 6.24 0.58 4.94 People 0.00 0 0.00 Return 1,584 1,584
Misc 3.28 0.00 3.28 20.46 3.28 27.96 Misc 0.00 0.00 0.00 Exhaust 66 66
Sub Total ==> 4.81 0.13 4.94 30.82 4.39 37.43 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.26 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.80 23.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.12 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 4.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 21.12 21.12
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 98.65
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.67
W/m² 213.91 0.00
Grand Total ==> 12.15 0.08 16.03 100.00 11.73 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 16.05 12.57 1,584 22.6 17.6 10.5 16.1 14.7 9.9 Floor 75 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 92 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 16.05 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 34 34 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 39 of 49
Room Checksums
By Trane
Sanh 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.62 0.00 3.62 30.27 3.62 43.15 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 9.36 1.12 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,095 1,095
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,095 1,095
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,095 1,095
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.74 0.00 4.74 39.63 4.74 56.50 Sub Total ==> 0.00 0.00 0.00 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 0 0
Lights 0.44 0.11 0.55 4.60 0.44 5.24 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.83 0 1 6.94 0.48 5.72 People 0.00 0 0.00 Return 1,095 1,095
Misc 2.71 0.00 2.71 22.66 2.71 32.30 Misc 0.00 0.00 0.00 Exhaust 54 54
Sub Total ==> 3.98 0.11 4.09 34.20 3.63 43.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.14 26.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.0 5.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.66 17.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.53
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.18
W/m² 192.86 0.00
Grand Total ==> 8.74 0.08 11.96 100.00 8.39 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.96 9.08 1,095 22.6 17.7 10.6 15.9 14.6 9.8 Floor 62 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 25 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 40 of 49
Room Checksums
By Trane
Sanh 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.62 0.00 3.62 30.27 3.62 43.15 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 9.36 1.12 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,095 1,095
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,095 1,095
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,095 1,095
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.74 0.00 4.74 39.63 4.74 56.50 Sub Total ==> 0.00 0.00 0.00 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 0 0
Lights 0.44 0.11 0.55 4.60 0.44 5.24 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.83 0 1 6.94 0.48 5.72 People 0.00 0 0.00 Return 1,095 1,095
Misc 2.71 0.00 2.71 22.66 2.71 32.30 Misc 0.00 0.00 0.00 Exhaust 54 54
Sub Total ==> 3.98 0.11 4.09 34.20 3.63 43.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.14 26.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.0 5.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.66 17.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.53
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.18
W/m² 192.86 0.00
Grand Total ==> 8.74 0.08 11.96 100.00 8.39 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.96 9.08 1,095 22.6 17.7 10.6 15.9 14.6 9.8 Floor 62 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 25 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 41 of 49
Room Checksums
By Trane
Sanh 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.62 0.00 3.62 30.27 3.62 43.15 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 9.36 1.12 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,095 1,095
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,095 1,095
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,095 1,095
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.74 0.00 4.74 39.63 4.74 56.50 Sub Total ==> 0.00 0.00 0.00 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 0 0
Lights 0.44 0.11 0.55 4.60 0.44 5.24 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.83 0 1 6.94 0.48 5.72 People 0.00 0 0.00 Return 1,095 1,095
Misc 2.71 0.00 2.71 22.66 2.71 32.30 Misc 0.00 0.00 0.00 Exhaust 54 54
Sub Total ==> 3.98 0.11 4.09 34.20 3.63 43.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.14 26.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.0 5.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.66 17.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.53
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.18
W/m² 192.86 0.00
Grand Total ==> 8.74 0.08 11.96 100.00 8.39 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.96 9.08 1,095 22.6 17.7 10.6 15.9 14.6 9.8 Floor 62 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 25 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 42 of 49
Room Checksums
By Trane
Sanh 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.62 0.00 3.62 30.27 3.62 43.15 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 9.36 1.12 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,095 1,095
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,095 1,095
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,095 1,095
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.74 0.00 4.74 39.63 4.74 56.50 Sub Total ==> 0.00 0.00 0.00 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 0 0
Lights 0.44 0.11 0.55 4.60 0.44 5.24 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.83 0 1 6.94 0.48 5.72 People 0.00 0 0.00 Return 1,095 1,095
Misc 2.71 0.00 2.71 22.66 2.71 32.30 Misc 0.00 0.00 0.00 Exhaust 54 54
Sub Total ==> 3.98 0.11 4.09 34.20 3.63 43.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.14 26.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.0 5.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.66 17.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.53
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.18
W/m² 192.86 0.00
Grand Total ==> 8.74 0.08 11.96 100.00 8.39 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.96 9.08 1,095 22.6 17.7 10.6 15.9 14.6 9.8 Floor 62 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 25 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 43 of 49
Room Checksums
By Trane
Sanh 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.62 0.00 3.62 30.27 3.62 43.15 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 9.36 1.12 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,095 1,095
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,095 1,095
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,095 1,095
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.74 0.00 4.74 39.63 4.74 56.50 Sub Total ==> 0.00 0.00 0.00 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 0 0
Lights 0.44 0.11 0.55 4.60 0.44 5.24 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.83 0 1 6.94 0.48 5.72 People 0.00 0 0.00 Return 1,095 1,095
Misc 2.71 0.00 2.71 22.66 2.71 32.30 Misc 0.00 0.00 0.00 Exhaust 54 54
Sub Total ==> 3.98 0.11 4.09 34.20 3.63 43.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.14 26.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.0 5.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.66 17.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.53
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.18
W/m² 192.86 0.00
Grand Total ==> 8.74 0.08 11.96 100.00 8.39 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.96 9.08 1,095 22.6 17.7 10.6 15.9 14.6 9.8 Floor 62 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 25 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 44 of 49
Room Checksums
By Trane
Sanh 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.62 0.00 3.62 30.27 3.62 43.15 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 9.36 1.12 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,095 1,095
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,095 1,095
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,095 1,095
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.74 0.00 4.74 39.63 4.74 56.50 Sub Total ==> 0.00 0.00 0.00 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 0 0
Lights 0.44 0.11 0.55 4.60 0.44 5.24 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.83 0 1 6.94 0.48 5.72 People 0.00 0 0.00 Return 1,095 1,095
Misc 2.71 0.00 2.71 22.66 2.71 32.30 Misc 0.00 0.00 0.00 Exhaust 54 54
Sub Total ==> 3.98 0.11 4.09 34.20 3.63 43.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.14 26.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.0 5.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.66 17.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.53
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.18
W/m² 192.86 0.00
Grand Total ==> 8.74 0.08 11.96 100.00 8.39 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.96 9.08 1,095 22.6 17.7 10.6 15.9 14.6 9.8 Floor 62 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 25 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 45 of 49
Room Checksums
By Trane
Sanh 7

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 15.9 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.62 0.00 3.62 30.27 3.62 43.15 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 9.36 1.12 13.35 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,095 1,095
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,095 1,095
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,095 1,095
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.74 0.00 4.74 39.63 4.74 56.50 Sub Total ==> 0.00 0.00 0.00 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 0 0
Lights 0.44 0.11 0.55 4.60 0.44 5.24 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.83 0 1 6.94 0.48 5.72 People 0.00 0 0.00 Return 1,095 1,095
Misc 2.71 0.00 2.71 22.66 2.71 32.30 Misc 0.00 0.00 0.00 Exhaust 54 54
Sub Total ==> 3.98 0.11 4.09 34.20 3.63 43.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.14 26.25 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.0 5.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.66 17.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.53
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.18
W/m² 192.86 0.00
Grand Total ==> 8.74 0.08 11.96 100.00 8.39 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.96 9.08 1,095 22.6 17.7 10.6 15.9 14.6 9.8 Floor 62 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 25 25 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 46 of 49
Room Checksums
By Trane
Sanh+ SR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 3 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 29 / 25 OADB: 32 OADB: 21 SADB 16.8 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 14.71 0.00 14.71 37.50 14.36 48.33 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 3.46 0.00 3.46 8.82 3.70 12.45 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.05 1.75 3.80 9.69 2.36 7.94 Wall Cond 0.00 0.00 0.00
Partition/Door 1.48 1.48 3.77 1.69 5.69 Partition/Door 0.00 0.00 0.00 Diffuser 4,559 4,559
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 4,559 4,559
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 4,559 4,559
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 21.70 1.75 23.45 59.78 22.11 74.42 Sub Total ==> 0.00 0.00 0.00 Nom Vent 117 117
AHU Vent 117 117
Internal Loads Internal Loads Infil 0 0
Lights 0.98 0.24 1.22 3.11 0.90 3.03 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 1.83 0 2 4.66 0.80 2.69 People 0.00 0 0.00 Return 4,559 4,559
Misc 5.86 0.00 5.86 14.94 5.86 19.72 Misc 0.00 0.00 0.00 Exhaust 117 117
Sub Total ==> 8.67 0.24 8.91 22.71 7.56 25.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 0.13 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 6.90 17.59 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.6 2.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 34.02 34.02
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 116.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.42
W/m² 292.58 0.00
Grand Total ==> 30.42 1.91 39.23 100.00 29.71 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 17

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 39.22 33.03 4,559 22.5 17.4 10.3 16.8 14.9 9.8 Floor 134 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 131 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 39.22 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 107 67 63 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 47 of 49
Room Checksums
By Trane
To chuc hanh chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 16.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.11 0.00 3.11 33.16 3.11 45.40 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.96 0.00 0.96 10.23 0.96 14.01 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 2.03 0.19 2.77 Partition/Door 0.00 0.00 0.00 Diffuser 923 923
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 923 923
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 923 923
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.26 0.00 4.26 45.42 4.26 62.19 Sub Total ==> 0.00 0.00 0.00 Nom Vent 39 39
AHU Vent 39 39
Internal Loads Internal Loads Infil 0 0
Lights 0.31 0.08 0.39 4.16 0.31 4.53 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.59 0 1 6.29 0.34 4.96 People 0.00 0 0.00 Return 923 923
Misc 1.92 0.00 1.92 20.47 1.92 28.03 Misc 0.00 0.00 0.00 Exhaust 39 39
Sub Total ==> 2.82 0.08 2.90 30.92 2.57 37.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.23 23.77 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.11 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.2 4.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 20.97 20.97
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 98.37
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.69
W/m² 213.00 0.00
Grand Total ==> 7.10 0.05 9.38 100.00 6.85 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.38 7.33 923 22.6 17.6 10.5 16.1 14.7 9.9 Floor 44 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 21 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.38 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 21 21 100 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 48 of 49
Room Checksums
By Trane
TTT+PTT

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 29 / 25 OADB: 31 OADB: 21 SADB 17.1 21.1
Ra Plenum 22.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.2 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.3 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.44 0.00 5.44 48.48 5.44 58.49 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.63 0.00 1.63 14.53 1.63 17.53 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.47 0.60 1.07 9.54 0.47 5.05 Wall Cond 0.00 0.00 0.00
Partition/Door 0.40 0.40 3.57 0.40 4.30 Partition/Door 0.00 0.00 0.00 Diffuser 1,500 1,500
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,500 1,500
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,500 1,500
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.94 0.60 8.54 76.11 7.94 85.38 Sub Total ==> 0.00 0.00 0.00 Nom Vent 20 20
AHU Vent 20 20
Internal Loads Internal Loads Infil 0 0
Lights 0.16 0.04 0.20 1.78 0.16 1.72 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.31 0 0 2.76 0.18 1.94 People 0.00 0 0.00 Return 1,500 1,500
Misc 1.01 0.00 1.01 9.00 1.01 10.86 Misc 0.00 0.00 0.00 Exhaust 20 20
Sub Total ==> 1.48 0.04 1.52 13.55 1.35 14.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.11 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.17 10.43 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.09 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 1.3 1.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 65.20 65.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 133.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 2.05
W/m² 488.14 0.00
Grand Total ==> 9.43 0.62 11.22 100.00 9.30 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.23 10.16 1,500 22.3 17.2 10.1 17.1 15.0 9.8 Floor 23 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.23 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 53 37 70 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: Du an HCM TRACE® 700 v6.2.5 calculated at 03:43 PM on 05/06/2023


Dataset Name: VPCT.trc Alternative - 1 System Checksums Report Page 49 of 49