Combine VAC-6
Combine VAC-6
4875
AT UPSTREAM OF THE DAMPER AND SHALL BE SET AT 74°C.
M-MEQ_IDU/CA/09 14.FLEXIBLE CONNECTION SHALL BE PROVIDED FOR EVERY DUCT
CONNECTION TO EQUIPMENT. CONNECTION SHALL BE OF
M-AIT_EAL/01
M-DAC_VCD/09 SUFFICIENT LENGTH TO ELIMINATE VIBRATION TRANSMISSION.
DTG 15.FIRE DAMPERS SHALL BE INSTALLED IN ALL DUCTS PASSING
THROUGH FIRE-RATED WALLS AND CEILINGS
DTG 16.ALL HANGERS SHALL BE SECURELY ANCHORED TO THE BUILDING
STRUCTURE USING CADMIUM PLATED HARDWARE. HANGERS AND
2 M-DAC_VCD/06 300x125 FAD BOD:3838 LOWER ATTACHMENTS SHALL BE OF ADEQUATE SIZES AND SPACING
TO CARRY THE WEIGHT OF THE DUCTWORK AND INSULATION
M-MEQ_IDU/CA/06 WITHOUT SAGGING.
100x100 FAD BOD:3850 M-DAC_VCD/07 17.KINDLY REFER TECHNICAL SPECIFICATIONS FOR MATERIAL
DETAILS : HVAC - L1CEP2-SYTA-2-STN-SPN-20033
M-DAC_VCD/08 18.THE EQUIPMENT TO BE INSTALLED ON SITE WILL HAVE TO COMPLY
A-02 WITH POWER REQUIREMENTS I.E. 400V, 3P/240V, 1P/60 HZ.
5230
M-DAC_VCD/05 M-MEQ_IDU/CA/08
A-03
M-MEQ_IDU/CA/05 LEGENDS AND SYMBOLS:
450x175 FAD BOD:3813
M-MEQ_IDU/CA/07
TED : Toilet Exhaust Duct VSD : Ventilation Supply Duct
500x200 FAD BOD:3788
FAL : Fresh Air Louver EAL : Exhaust Air Louver
M-MEQ_FAF/01 BOD : Bottom Of Duct EAF : Exhaust Air Fan
3 BOP : Bottom Of Pipe EAG : Exhaust Air Grille
A-08 DTG : Door Transfer Grille SAG : Supply Air Grille
M-AIT_FAL/01 M-MEQ_IDU/CA/03 ATG : Air Transfer Grille EAD : Exhaust Air Diffuser
FAF : Fresh Air Fan VRF : Variable Refrigerant Flow
M-DAC_VCD/03 IDU : Indoor Unit VRV : Variable Refrigerant Volume
4695
1 2 3 4
4875 5230 4695
C 15OCT2020 UPDATED AS PER COMMENTS BY BYTP/MDC/LRMC/IC/ALSTOM MKR RCH BCO
1 x200 mm REFR. PIPE TRAY B 24JUL2020 UPDATED AS PER COMMENTS BY BYTP/MDC/LRMC/IC/ALSTOM MKR RCH BCO
1 x300 mm REFR. PIPE TRAY
300x125 FAD M-MEQ_IDU/CA/03 A 20NOV2019 FIRST ISSUE YBA RCH BCO
25.0 mmø DRAIN PIPE
M-MEQ_IDU/CA/10 M-MEQ_IDU/CA/07 150x150 FAD 2-SE
±8.92
4050
4037
3838
3830
3830
3725
3725
3725
3730
3570
3570
3570
1-GR
±3.92
0-RO
±3.47
2 M-SECTION A
SCALE 1 : 100
0 1 2 3 5 7m
Scale1: 100