GENERAL NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE


C SPECIFIED.
2. THE DRAWING MUST BE READ IN CONJUNCTION WITH ALL RELEVANT
ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE FIGHTING AND
ELECTRICAL DRAWINGS.
3. ANY DISCREPANCIES MUST BE BROUGHT TO THE NOTICE OF THE
2 CONSULTANT.
4. ALL INTERCONNECTING PIPING , JOINTS AND U BENDS WITHIN THE
21135 CONDENSING UNITS SHALL BE PAINTED WITH TWO COATS OF
CLEAR TRANSPARENT COATING OF SUITABLE MATERIAL FOR
PROTECTION AGAINST CORROSION FROM AMBIENT AIR POLLUTION.
A B C D E 5. THE JOINTS SHALL BE PROPERLY SEALED WITH SYNTHETIC GLUE
4830 3690 4190 3890 TO ENSURE PROPER BONDING OF THE ENDS.
6. DRAIN PIPES CARRYING CONDENSATE WATER SHALL BE INSULATED
WITH 6MM NITRILE RUBBER.
7. FOR EQUIPMENT SCHEDULE REFER THE DWG. NO -
L1CEP2-SYTA-2S04-STN-2DM-21140.
8. FOR STANDARD INSTALLATION DETAILS REFER THE DWG. NO -
150x150 TED BOD:3615 L1CEP2-SYTA-S-STN-2DM-21513 & 21514.
9. ALL EQUIPMENT SIZES ARE INDICATIVE AND IT WILL BE FINALIZED
M-MEQ_IDU/CA/11 AFTER FINALIZATION OF EQUIPMENT.
10.FRESH AIR DUCT CONNECTING TO THE FRESH AIR PORT OF
CASSETTE UNIT MUST BE COMPLETED / FINISHED WITH FLEXIBLE
1 DUCT UPTO MAXIMUM LENGTH OF 1000 MM.
A-10 M-DAC_VCD/11 11.ALL FRESH AIR LOUVERS SHALL BE COMPLETED WITH SAND TRAP
A-07 AND 100 MM THICK FILTER.
M-DAC_VCD/10 12.CONTRACTOR TO PROVIDE VOLUME CONTROL DAMPER (VCD) IN
EACH AND EVERY BRANCH DUCT WHETHER VCD IS SHOWN IN
300x200 TED BOD:3590 M-MEQ_IDU/CA/10 DRAWING OR NOT.
M-MEQ_EAF/01 13.FUSIBLE LINK SHALL BE ARRANGED IN AN EXPOSED POSITION AND
A-09

4875
AT UPSTREAM OF THE DAMPER AND SHALL BE SET AT 74°C.
M-MEQ_IDU/CA/09 14.FLEXIBLE CONNECTION SHALL BE PROVIDED FOR EVERY DUCT
CONNECTION TO EQUIPMENT. CONNECTION SHALL BE OF
M-AIT_EAL/01
M-DAC_VCD/09 SUFFICIENT LENGTH TO ELIMINATE VIBRATION TRANSMISSION.
DTG 15.FIRE DAMPERS SHALL BE INSTALLED IN ALL DUCTS PASSING
THROUGH FIRE-RATED WALLS AND CEILINGS
DTG 16.ALL HANGERS SHALL BE SECURELY ANCHORED TO THE BUILDING
STRUCTURE USING CADMIUM PLATED HARDWARE. HANGERS AND
2 M-DAC_VCD/06 300x125 FAD BOD:3838 LOWER ATTACHMENTS SHALL BE OF ADEQUATE SIZES AND SPACING
TO CARRY THE WEIGHT OF THE DUCTWORK AND INSULATION
M-MEQ_IDU/CA/06 WITHOUT SAGGING.
100x100 FAD BOD:3850 M-DAC_VCD/07 17.KINDLY REFER TECHNICAL SPECIFICATIONS FOR MATERIAL
DETAILS : HVAC - L1CEP2-SYTA-2-STN-SPN-20033
M-DAC_VCD/08 18.THE EQUIPMENT TO BE INSTALLED ON SITE WILL HAVE TO COMPLY
A-02 WITH POWER REQUIREMENTS I.E. 400V, 3P/240V, 1P/60 HZ.

5230
M-DAC_VCD/05 M-MEQ_IDU/CA/08
A-03
M-MEQ_IDU/CA/05 LEGENDS AND SYMBOLS:
450x175 FAD BOD:3813
M-MEQ_IDU/CA/07
TED : Toilet Exhaust Duct VSD : Ventilation Supply Duct
500x200 FAD BOD:3788
FAL : Fresh Air Louver EAL : Exhaust Air Louver
M-MEQ_FAF/01 BOD : Bottom Of Duct EAF : Exhaust Air Fan
3 BOP : Bottom Of Pipe EAG : Exhaust Air Grille
A-08 DTG : Door Transfer Grille SAG : Supply Air Grille
M-AIT_FAL/01 M-MEQ_IDU/CA/03 ATG : Air Transfer Grille EAD : Exhaust Air Diffuser
FAF : Fresh Air Fan VRF : Variable Refrigerant Flow
M-DAC_VCD/03 IDU : Indoor Unit VRV : Variable Refrigerant Volume
4695

ODU : Outdoor Unit F/A : Fresh Air


M-MEQ_IDU/CA/01 A-04
A-11 DCT : Duct MEQ : Mechanical Equipment
M-MEQ_IDU/CA/04 AIT : Air Terminal VCD : Volume Control Damper
A-01 A-25 A-05
M-DAC_VCD/01 L/S : Liter Per Second
REFR : Refrigerant Piping
M-DAC_VCD/02
M-DAC_VCD/04 DAC : Duct Accessories FLFD/FD : Fusible Link Fire Damper/
Fire Damper
M-MEQ_EAF/03 : Supply/Exhaust : Y- Joint
4 C Air Grille & Diffuser
: Toilet Exhaust
M-AIT_EAL/03 : Inline Line Fan Duct (TED)
100x100 FAD BOD:3855
M-AIT_FAL/03 M-MEQ_EAF/02 : Cassette Type : Ventilation Exhaust
Unit (IDU) Duct (VED)
M-MEQ_IDU/CA/02 M-AIT_EAL/02
: VRV/VRF Indoor : Ventilation Supply
150x150 FAD BOD:3830
Unit (IDU) Duct (VSD)
: VRV/VRF Outdoor : Supply Air Duct (SAD)
Unit (ODU) : Refrigerant Pipe (S)
: Propeller Fan : Refrigerant Pipe (R)
: Condensate Pipe
: Volume Control Damper

VAC SYSTEM-AIR DISTRIBUTION AND VENTILATION GROUND FLOOR PLAN


: Fire Damper/
Fusible Link Fire Damper
1 SCALE 1 : 100

1 2 3 4
4875 5230 4695
C 15OCT2020 UPDATED AS PER COMMENTS BY BYTP/MDC/LRMC/IC/ALSTOM MKR RCH BCO

1 x200 mm REFR. PIPE TRAY B 24JUL2020 UPDATED AS PER COMMENTS BY BYTP/MDC/LRMC/IC/ALSTOM MKR RCH BCO
1 x300 mm REFR. PIPE TRAY
300x125 FAD M-MEQ_IDU/CA/03 A 20NOV2019 FIRST ISSUE YBA RCH BCO
25.0 mmø DRAIN PIPE
M-MEQ_IDU/CA/10 M-MEQ_IDU/CA/07 150x150 FAD 2-SE
±8.92

25.0 mmø DRAIN

4050
4037

3838

3830
3830
3725

3725

3725

3730
3570

3570

3570

1-GR
±3.92

0-RO
±3.47

2 M-SECTION A
SCALE 1 : 100

05-Room Schedule 05-Room Schedule 05-Room Schedule


ROOM ROOM ROOM
TAG ROOM NAME TAG ROOM NAME TAG ROOM NAME

A-01 RECEPTION A-11 TOILET A-18 21 UNITS 46" CCTV MONITORS


A-02 WAITING AREA A-12 OFFICE (8 TABLES & CHAIRS) A-19 DOCUMENT CONTROL ROOM
A-03 HALL ROOM A-13 DATA ROOM/ NETWORK OR LRMC LIBRARY
A-04 DOCTOR'S ROOM OPERATION CENTRE A-20 CAFETERIA
A-05 CLINIC (W/SINGLE BEDS) A-14 SECURITY SUPERVISOR 1 A-21 CORRIDOR
A-06 MEETING ROOM A-15 SECURITY SUPERVISOR 2 A-22 CORRIDOR
A-07 PANTRY A-16 SECURITY MANAGER 2 OFFICE A-23 MALE WASHROOM N
A-08 CORRIDOR W/MEETING AREA A-24 FEMALE WASHROOM
A-09 MALE WASHROOM A-17 SECURITY MANAGER 1 OFFICE A-25 ELECTRICAL ROOM
W/MEETING AREA ST-01 STAIRCASE
A-10 FEMALE WASHROOM

0 1 2 3 5 7m

Scale1: 100