Combine VAC-7
Combine VAC-7
4875
EACH AND EVERY BRANCH DUCT WHETHER VCD IS SHOWN IN
DRAWING OR NOT.
M-AIT_EAL/04 13.FUSIBLE LINK SHALL BE ARRANGED IN AN EXPOSED POSITION AND
A-20 A-12 AT UPSTREAM OF THE DAMPER AND SHALL BE SET AT 74°C.
A-24 14.FLEXIBLE CONNECTION SHALL BE PROVIDED FOR EVERY DUCT
A-23 CONNECTION TO EQUIPMENT. CONNECTION SHALL BE OF
SUFFICIENT LENGTH TO ELIMINATE VIBRATION TRANSMISSION.
150x150 TED BOD:2935 M-MEQ_IDU/CA/23 15.FIRE DAMPERS SHALL BE INSTALLED IN ALL DUCTS PASSING
2 M-DAC_VCD/26
THROUGH FIRE-RATED WALLS AND CEILINGS
M-DAC_VCD/23 16.ALL HANGERS SHALL BE SECURELY ANCHORED TO THE BUILDING
STRUCTURE USING CADMIUM PLATED HARDWARE. HANGERS AND
M-MEQ_IDU/CA/22 M-DAC_VCD/22 LOWER ATTACHMENTS SHALL BE OF ADEQUATE SIZES AND SPACING
A-21 TO CARRY THE WEIGHT OF THE DUCTWORK AND INSULATION
100x100 FAD BOD:3180 M-MEQ_IDU/CA/19 WITHOUT SAGGING.
M-DAC_VCD/19 17.KINDLY REFER TECHNICAL SPECIFICATIONS FOR MATERIAL
M-DAC_VCD/20 M-MEQ_IDU/CA/18 DETAILS : HVAC - L1CEP2-SYTA-2-STN-SPN-20033
5230
M-MEQ_IDU/CA/20 M-MEQ_IDU/CA/17 18.THE EQUIPMENT TO BE INSTALLED ON SITE WILL HAVE TO COMPLY
WITH POWER REQUIREMENTS I.E. 400V, 3P/240V, 1P/60 HZ.
2
M-MEQ_IDU/CA/21
21136 M-DAC_VCD/17
M-DAC_VCD/21 M-DAC_VCD/18 LEGENDS AND SYMBOLS:
A-06
A-18 200x125 FAD BOD:3145
M-MEQ_IDU/CA/13 TED : Toilet Exhaust Duct VSD : Ventilation Supply Duct
3 DTG
FAL : Fresh Air Louver EAL : Exhaust Air Louver
A-22 BOD : Bottom Of Duct EAF : Exhaust Air Fan
A-19
M-MEQ_IDU/VRV/01 BOP : Bottom Of Pipe EAG : Exhaust Air Grille
M-DAC_VCD/15
200x150 FAD BOD:3155 DTG : Door Transfer Grille SAG : Supply Air Grille
M-MEQ_IDU/CA/16 ATG : Air Transfer Grille EAD : Exhaust Air Diffuser
A-17
4695
M-DAC_VCD/13 VRF : Variable Refrigerant Flow
M-DAC_VCD/16 FAF : Fresh Air Fan
M-DAC_VCD/12
IDU : Indoor Unit VRV : Variable Refrigerant Volume
A-13 M-AIT_FAL/02 ODU : Outdoor Unit F/A : Fresh Air
A-16 DCT : Duct MEQ : Mechanical Equipment
M-MEQ_IDU/VRV/02 A-14 M-MEQ_FAF/02
AIT : Air Terminal VCD : Volume Control Damper
REFR : Refrigerant Piping L/S : Liter Per Second
A-15
4 M-MEQ_IDU/CA/15 DAC : Duct Accessories FLFD/FD : Fusible Link Fire Damper/
Fire Damper
200x150 FAD BOD:3155
M-MEQ_IDU/CA/12 : Supply/Exhaust : Y- Joint
M-DAC_VCD/14
Air Grille & Diffuser
M-MEQ_IDU/CA/14 : Toilet Exhaust
: Inline Line Fan Duct (TED)
: Cassette Type : Ventilation Exhaust
Unit (IDU) Duct (VED)
: VRV/VRF Indoor : Ventilation Supply
Unit (IDU) Duct (VSD)
VAC SYSTEM-AIR DISTRIBUTION AND VENTILATION-FIRST FLOOR PLAN : VRV/VRF Outdoor : Supply Air Duct (SAD)
1 SCALE 1 : 100
Unit (ODU)
: Propeller Fan
: Refrigerant Pipe (S)
: Refrigerant Pipe (R)
: Condensate Pipe
: Volume Control Damper
: Fire Damper/
Fusible Link Fire Damper
A B C D E
4830 3690 4190 3890
M-MEQ_IDU/CA/20
1 x300 mm REFR. PIPE TRAY M-MEQ_IDU/CA/18
M-MEQ_IDU/CA/19
C 15OCT2020 UPDATED AS PER COMMENTS BY BYTP/MDC/LRMC/IC/ALSTOM MKR RCH BCO
M-MEQ_IDU/CA/21 3-R
200x125 FAD B 24JUL2020 UPDATED AS PER COMMENTS BY BYTP/MDC/LRMC/IC/ALSTOM MKR RCH BCO
±13
A 20NOV2019 FIRST ISSUE YBA RCH BCO
3168
3125
3125
2970
2970
2970
2970
Transportation Authority
2-S
±8.9
2 M-SECTION B
SCALE 1 : 100
0 1 2 3 5 7m
Scale1: 100