Unit 5 Reactances
Unit 5 Reactances
Machines
Basic formulations
Magnetic circuit is analogical with Electric circuit
F I G V
: Permeance (磁導) G: Conductance
For a rectangular object:
a a
G
l l
where a: area; l: length; µ: permeability (導磁率)
:flux leakage
L n 2
Inductance: i where n: number of conductors.
(Because: = n = n F = n (nI) = n2I)
Reactance: X L X = 1/(w.C)
1
5.1 Leakage reactance
The leakage flux in an a.c. machine consists of the following:
slot leakage
overhang leakage
zigzag leakage
differential leakage (also called harmonic leakage)
2
Slot leakage copy the electrical representation
1. Open slots
does
not link
all
winding
s
Fig. 1a Leakage flux paths for an open slot
3
Basic method: assume I F H B
L n 2
/(n I )
2
(because i )
/(n2 I ) 1 /(n2 I ) 2 /(n2 I ) 3 /(n2 I )
1 2 3
Since the core is ferromagnetic, the permeability of the core is much
B
H
larger, the magnetic field intensity , H is very small, hence the
H in the slot is very small,
mmf drop Hl in the iron core can be neglected. because of this
Fig. 1b
4
Consider path (1), the flux path doesn’t link all the slot conductors.
For an elemental path within the winding of width dx (see Fig. 1b),
x
F nI
Hbs, mff in d1
where n is the total number of conductors in the slot
the slot x x 0 x
Hbs F nI H nI B 0 H nI
H*air gap lenght = F d1 , d1bs , d1bs
The flux of the strip dx is
x
d B( Lcdx) 0 nILcdx
d1bs where Lc = net core length
The number of turns linking the strip is (x/d1)n,
2
x x 0 xLc x 0 Lc
d n d n nIdx n I dx
d1 d1 d1bs d1 bs
The total flux linkage across depth of winding d1 is
5
2
x 0 Lc dx
d1
d1
n I 0 Lc n I
2
0 1
d bs 3bs (2)
For path (2) (above the winding but within the slot), the flux path links all
the slot conductors.
b area
Method: similar to calculating conductance: G L h distance
( Lc d 2 ) area
2 0 0
Therefore bs distance (4)
6
Fig. 1b
(c)
For path (3), assume the leakage flux takes the path as shown in Fig. 1c.
The permeance of the elementary path of width dx is
7
( Lcdx) ( Lc dx)
d3 0 0 area
x x x bs
0
bs distance (5)
2 2
and the strip links all the slot conductors. Thus the permeance for path (3)
1
bt
2
0 Lc dx 0 Lc bt
is
3 0
x bs
ln
2bs
1
(6)
3
s i
The total permeance for open slots is i 1
(7)
lambda ,s
2. Semi-closed slot
8
semi-close slot
There are five leakage flux paths as shown in Fig. 2a. We have, from
derivations for open slots,
( Lc d1 ) area same for open
1 0 0 slot
3bs 3(distance) (8)
2 0 c 2 0
(L d ) area
(9)
bs distance
9
For path (3), we may take the average width as
(b0 + bs)/2. Thus,
( Lc d3 )
3 0 area
b0 bs 0
distance
2
2d3
0 Lc
b0 bs (10)
For path (4),
( Lc d 4 ) area
4 0 0
b0 distance (11)
where b0 is width of the slot opening.
10
For path (5), let us assume that the flux lines are circular (Fig. 2b).
Permeance of the elementary path of radius r and width dr is
( Lc dr ) area
d5 0 0
r distance (12)
Fig. 2 (b)
Therefore,
s
2
dr 1
5 0 Lc 0 Lc ln s
b0 r b0 (13)
2
11
5 may be neglected in induction motors in which the air gap length is
small.
3. Round slot
There are three flux paths as shown in Fig. 3. For path (1), assume that
the flux crosses the slot in straight lines, it can be shown that the
permeance is independent of the slot diameter and is given by
1 0.623 0 Lc (14)
12
Lc h4
4 0 lambda,4
b0 (15)
1 s
5 0 Lc ln lambda, 5
b0 (16)
The permeances for other slot shapes may be deduced in a similar manner.
Xs =w*Ls
reactance
13
Overhang leakage (the leakage of end windings)
1 turn of
the coil
14
L0
0 0 0.336 ln 0.11
lambda already accounts for both sides, so no need to times 2
b (17)
Eqn. (17) accounts for leakage flux on both sides of the coil.
Total permeance
The total permeance per coil is (one coil has two sides)
2s 0 (18)
where s: slot leakage permeance (one slot);
0: overhang leakage permeance (both sides of the coil).
or n = conductors per slot
For a coil of n turns, the leakage inductance per coil is
(each slot has n conductors)
L n 2 (19)
If N = number of coils per phase, then the leakage inductance per phase is
15
or N = slots per phase
Lp Nn2 (20)
16
Zigzag leakage
18
An empirical expression for the differential leakage
reactance is
X h X m (kh1 kh 2 ) (23)
where kh1 and kh2 are obtained from Fig. 7 (due to Alger).
Fig. 8 Fig. 7
20
Total leakage reactance
21
5.2 Magnetizing reactance
Only for the three-phase windings having balanced iA, iB, iC.
22
For a three-phase machine, the peak value of the armature fundamental
m.m.f. per pole is
3 2 k wT ph
Fa I
p (25)
B
F Hg g
According to 0 , the peak value of flux density in air gap
due to Fa is
g': effective air gap
0 Fa
Ba length
g (26)
Ks: slotting effect Carter's coefficient
where g K s g = effective air gap. Kd: ventilation effect Carter's coefficient
Because of sinusoidal m.m.f. along the air gap, we assume sinusoidal flux
density distribution, the average Bav: average RMS(u can see root and
square, different than average)
2
Bav Ba
The flux per pole is
average value: total/average 23
RMS: root of (mean of square value)
so RMS and average is different
Bav area of airgap per pole
(Dg Lc ) 2 Dg Lc Ba Dg Lc 0 Fa Dg Lc 0 Fa
Bav Ba Ba
2p 2p p p g
(as g )
(27)
where Dg = mean diameter of air gap.
sqr(2)*pi = 4.44
The e.m.f. due to armature reaction is
Ea 2K wTphf
Substituting (27) into above equation gives
0 Fa Dg Lc
Ea 2K wTph f
p.g (28)
3 2 k wT ph
Fa I
Substituting (25) p into (28) gives
24
2
K wTph Dg Lc
Ea 60 f I
p g (29)
The magnetizing reactance per phase is:
2
Ea K wTph Dg Lc
Xm 60 f
I p g (30)
The magnetizing inductance per phase is:
2
Xm X m 3 K wTph Dg Lc
Lm 0
2f p g (31)
(For one phase equivalent circuit, only for balanced three-phase currents.)
For the induction motor, if g
Xm smaller magnetizing current reduces the reactive power
magnetizing current component (I2Z=Q), smaller reactive power, so larger
power factor
power factor
This explains why induction motors usually have very small air gaps.
For a given air gap, if with (DgLc) and p
25
Xm
bigger and high-speed machines operate at higher power factor.
26
Self inductance and mutual inductance in three-phase windings
27
The negative sign arises in (34) because the flux linkage between two
phases is negative.
A simple check:
If the three-phase winding has symmetric balanced current:
28
(Xm = Lm is for balanced three-phase equivalent circuit. Laa,m and Lab,m can
also be used for unbalanced three-phase currents.)
References:
[1] ‘Alternating Current Machines’ by M.G. Say, 5th Ed., ELBS, 1983.
[2] ‘Induction Machines’ by P.L. Alger.
[3] http://ecmweb.com/
[4] http://www.nitrofreeze.com/
29