PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

ELEVATION A ELEVATION B ELEVATION F

ELEVATION G ELEVATION M ELEVATION N

ISSUED FOR CONSTRUCTION 12.07.2023

VERSION 7
SHEET INDEX GENERAL NOTES: ABBREVIATIONS:
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

Express Homes - North Central Texas


SHEET # SHEET NAME SHEET # SHEET NAME 1. CONSTRUCTION SHALL BE IN ACCORDANCE WITH ALL 1R1S 1 ROD 1 SHELF DIM DIMENSION NCF NONCOMBUSTIBLE FLOORING

SSE Architectural Design Services


A00.00 COVER - INDEX, GEN NOTES, ABBRV A60.01 ELEVATION M - FIRST FLOOR PLAN
APPLICABLE CODES, OTHER REGULATIONS AND ORDINANCES, 1R2S 1 ROD 2 SHELVES DL DIVIDED LITE NFA NET FREE AREA
AND ACCEPTED LOCAL PRACTICE, WHICHEVER IS MORE 2R2S 2 RODS 2 SHELVES DV DIRECT VENT NTS NOT TO SCALE
A00.01 REVISION LOG A60.02 ELEVATION M - FIRST FLOOR ELECTRICAL PLAN
RESTRICTIVE, WHETHER OR NOT SPECIFICALLY CALLED OUT IN
A10.00 NOTES & AREAS A60.03 ELEVATION M - EXTERIOR ELEVATIONS & ROOF PLAN 4 SH 4 SHELVES ELEC ELECTRICAL OC ON CENTER
THESE DOCUMENTS.
A10.01 NOTES & AREAS A60.04 ELEVATION M - EXTERIOR ELEVATIONS & ROOF PLAN w/ 5 SH 5 SHELVES ELEV ELEVATION OH OPPOSITE HAND
A10.02 LEAD WALK FIRE RATED SOFFIT @ SIDES 2. CONTRACTOR SHALL ENSURE COMPLIANCE WITH ALL
REQUIREMENTS OF THE LOCAL JURISDICTION, INCLUDING, BUT 7 SH 7 SHELVES EXT EXTERIOR OPQ OPAQUE
A10.03 LEAD WALK A60.05 ELEVATION M - EXTERIOR ELEVATIONS & ROOF PLAN w/

X30B A, B, F, G, M, N
FIRE RATED SOFFIT @ SIDES w/ 5 NFA LOWER NOT LIMITED TO, PERMITS PRIOR TO COMMENCING A/C AIR CONDITIONING EXT'D EXTENDED OPT OPTIONAL
A20.01 ELEVATION A - FIRST FLOOR PLAN
VENTILATION CONSTRUCTION, INSPECTIONS AT VARIOUS STAGES DURING ABV ABOVE FE FINISHED END PL PLATE HEIGHT
A20.02 ELEVATION A - FIRST FLOOR ELECTRICAL PLAN

BLOCK
A70.01 ELEVATION N - FIRST FLOOR PLAN CONSTRUCTION, AND CERTIFICATE OF OCCUPANCY AFTER ADJ ADJUSTABLE FEB FULL EYEBROW PWDR POWDER ROOM
A20.03 ELEVATION A - EXTERIOR ELEVATIONS & ROOF PLAN COMPLETION.
A70.02 ELEVATION N - FIRST FLOOR ELECTRICAL PLAN
A20.04 ELEVATION A - EXTERIOR ELEVATIONS & ROOF PLAN w/ AFF ABOVE FINISH FLOOR FLR FLOOR RAD RADIUS
FIRE RATED SOFFIT @ SIDES A70.03 ELEVATION N - EXTERIOR ELEVATIONS & ROOF PLAN 3. CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONAL,
APPROX APPROXIMATE FLUOR FLUORESCENT REF REFERENCE
A20.05 ELEVATION A - EXTERIOR ELEVATIONS & ROOF PLAN w/ A70.04 ELEVATION N - EXTERIOR ELEVATIONS & ROOF PLAN w/ WATERTIGHT, AND SOUND WORKMANLIKE PROJECT,
FIRE RATED SOFFIT @ SIDES PROVIDING ANY ITEMS OR WORK NEEDED TO ACHIEVE THE B BASE FND FOUNDATION RM ROOM
FIRE RATED SOFFIT @ SIDES w/ 5 NFA LOWER
VENTILATION A70.05 ELEVATION N - EXTERIOR ELEVATIONS & ROOF PLAN w/ ABOVE, WHETHER OR NOT SPECIFICALLY CALLED OUT IN BF BIFOLD FP FIREPLACE RO ROUGH OPENING
A30.01 ELEVATION B - FIRST FLOOR PLAN FIRE RATED SOFFIT @ SIDES w/ 5 NFA LOWER THESE DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR BLK BLACKENED FX FIXED SH SINGLE HUNG
VENTILATION MEANS, METHODS, SEQUENCING, SAFETY PROCEDURES, AND
A30.02 ELEVATION B - FIRST FLOOR ELECTRICAL PLAN BM BEAM GD GARAGE DOOR SL SIDE LITE
A90.01 INTERIOR ELEVATIONS & DETAILS MATERIALS.
A30.03 ELEVATION B - EXTERIOR ELEVATIONS & ROOF PLAN BO BY OTHERS GL GLASS STD STANDARD
A90.02 INTERIOR ELEVATIONS & DETAILS
A30.04 ELEVATION B - EXTERIOR ELEVATIONS & ROOF PLAN w/ 4. THE CONTRACTOR AND ALL SUBCONTRACTORS/TRADES ARE BP BYPASS GYP GYPSUM/DRYWALL T&B TOP AND BOTTOM
FIRE RATED SOFFIT @ SIDES A90.03 INTERIOR ELEVATIONS & DETAILS
RESPONSIBLE FOR REVIEWING ENTIRE SET OF PLANS AND

ADDRESS
A90.04 WALL SECTIONS (2021 IRC) CAB CABINET HB HOSE BIB TBD TO BE DETERMINED

BUILDER
A30.05 ELEVATION B - EXTERIOR ELEVATIONS & ROOF PLAN w/ SPECIFICATIONS, TO INCLUDE DIMENSIONS AND SECTIONS.
FIRE RATED SOFFIT @ SIDES w/ 5 NFA LOWER A100.00 MODERN ELEVATION DETAILS LARGER SCALE DRAWINGS TAKE PRECEDENCE OVER CEB CURVED EYEBROW HDR HEADER TEMP TEMPERED

SUBD.
VENTILATION A100.01 WOOD-LOOK SIDING DETAILS

PLAN
SMALL-SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND NOTIFY CL CENTERLINE HDW HARDWARE TR TRANSOM

CITY
LOT
A40.01 ELEVATION F - FIRST FLOOR PLAN A100.02 1 HR FIRE RATED SOFFIT DETAILS (2021 IRC) BUILDER OF ANY DISCREPANCIES OR VARIANCES PRIOR TO CLG CEILING HS HORIZONTAL SLIDER TV TELEVISION
A40.02 ELEVATION F - FIRST ELECTRICAL PLAN CONSTRUCTION. DO NOT SCALE DRAWINGS.
A40.03 ELEVATION F - EXTERIOR ELEVATIONS & ROOF PLAN
CLO CLOSET HT HEIGHT TYP TYPICAL
5. ALL MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH CLR CLEAR ILO IN LIEU OF VAN VANITY
A40.04 ELEVATION F - EXTERIOR ELEVATION & ROOF PLAN w/ FIRE ALL MANUFACTURER’S INSTALLATION INSTRUCTIONS AND
RATED SOFFIT @ SIDES
RECOMMENDATIONS. CMT CASEMENT INT INTERIOR VEST VESTIBULE DATE 12.07.2023
A40.05 ELEVATION F - EXTERIOR ELEVATION & ROOF PLAN w/ FIRE CMU CONCRETE MASONRY UNIT LF LINEAR FEET VIF VERIFY IN FIELD
6. ALL DIMENSIONS ARE TO FACE OF FRAMING OR FOUNDATION,
A40.06
RATED SOFFIT @ SIDES w/ 5 NFA LOWER VENTILATION
ELEVATION F - OPT BRICK @ FRONT UNLESS NOTED OTHERWISE. ARCHITECTURAL BUILDING AND CO CASED OPENING LVR LOUVER W WIDTH OR WEST SCALE 1" = 10'-0"
A50.01 ELEVATION G - FIRST FLOOR PLAN WALL SECTIONS ARE DIAGRAMMATIC. CONSULT ENGINEER FOR COV'D COVERED MAS MASONRY WB WOOD BURNING
A50.02 ELEVATION G - FIRST FLOOR ELECTRICAL PLAN ACTUAL FRAMING CONFIGURATIONS, SIZES, SPACING, CPT CARPET MAX MAXIMUM WC WATER CLOSET
ANCHORS, SHEATHING TYPE AND THICKNESS, ETC. CRIT CRITICAL MIN MINIMUM WD WOOD
A50.03 ELEVATION G - EXTERIOR ELEVATIONS & ROOF PLAN
12/8/2023 9:52:01 AM

FOUNDATION DESIGN SHALL BE PER ENGINEER.


A50.04 ELEVATION G - EXTERIOR ELEVATIONS & ROOF PLAN w/ DIA DIAMETER MTL METAL WIC WALK IN CLOSET
FIRE RATED SOFFIT @ SIDES 7. CONTRACTOR SHALL ENSURE COMPLIANCE WITH BEST WP WATER PROOF
A50.05 ELEVATION G - EXTERIOR ELEVATIONS & ROOF PLAN w/ PRACTICES FOR RESIDENTIAL CONSTRUCTION AS DEFINED BY

A50.06
FIRE RATED SOFFIT @ SIDES w/ 5 NFA LOWER
VENTILATION
ELEVATION G - OPT BRICK @ FRONT
THE CURRENT AND ADOPTED IRC AND NAHB BUILDING
STANDARDS.
WRF
WS
WATER RESISTANT FLOOR
WAINSCOT A00.00
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET
X30B-REVISION LOG X30B-REVISION LOG

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
Ver. Rev. Date Date Req. Req. By Drawn Ver. Rev. Date Date Req. Req. By Drawn
No. No. Issued Description By No. No. Issued Description By

1 0 01.17.2019 a. New global plan started from X30B - 1359 (DR HORTON) 11.19.2018 DRH FS 6 0 08.29.2023 a. Added Elevation G and Elevation G w/Opt Brick @ Front 08.10.2023 DRH TR 10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204
WO: 2020951R4
2 1 04.30.2019 a. Comprehensive plan & elevation redesign 04.17.2019 DRH CD
b. Revise entire floor plans for new standards & features
c. Revise both elevation A & B for new design standards & 7 0 12.07.2023 a. Added Elevation F and Elevation F w/Opt brick @ Front 11.28.2023 DRH AG
features
WO: 2351667
d. Update construction documents for extensive changes made
to plans & elevations

3 0 11.29.2019 a. Update plan to new Regional standards & features (specifics 11.27.2019 DRH AM
noted below)
b. Update electrical fixtures to new standards (specifics noted
below)
c. Revised to add extra can light @ Bath 1 vanity.
d. Update WH platform & wing wall @ garage to new specs
e. Remove opt. 42x60 tub/shower option.

12.17.2019 a. shift 3050 window 12" to left at dining/kitchen space 12.17.2019 s2e ei
b.remove opening at bedroom 2/3 vest and replace with soffit

X30B - REVISION LOG


Ver. Rev. Date Date Req. Req. By Drawn
No. No. Issued Description By
3 0 12.23.2019 a. Conversion from Express Regional X30B to Express Austin. 12.19.2019 DRH-DL EJ
b. Revised door @ Bath 2 to 2868.
c. Revised door @ Garage to 3068.
d. Revised door @ Utility to 3068.

1 12.27.2019 a. Added lead walks. 12.19.2019 DRH-DL RAG


b. Revised exterior elevations & roof plan sheet to be fire rated.

VERSION 7
c. Updated attic vent calculations (fire rated).
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

d. Added visitability plan sheet.

Express Homes - North Central Texas


e. Added fire rated sheet A100.01 (2015 IRC).

SSE Architectural Design Services


X30B - NORTH CENTRAL TEXAS - REVISION LOG
Ver. Rev. Date Date Req. Req. By Drawn

X30B A, B, F, G, M, N
No. No. Issued Description By

BLOCK
4 0 06.17.2020 a. New Global Conversions from Express Austin X30A (skipped 06.10.2020 DRH-DL GSS
versions 1-3 to match regional version)
b. Added Elevation M w/ optional wood-look siding @ front.
c. Added optional 4010 window @ Bath 1
d. Removed visitability sheets from set.

5 0 05.20.2021 a. Added Elevation N 04.23.2021 DRH-DL MK

ADDRESS
BUILDER
b. Revised outlets @ kitchen per 2020 NEC updates

SUBD.
c. Revised outlets @ garage per 2020 NEC updates

PLAN
CITY
LOT
d. Revised to add tire stop
e. Revised floor plan room tags to Bedroom 1 ilo Master W.O. 2020951R1
Bedroom, Bath 1 ilo Master bath, WIC illo Master WIC DATE 12.07.2023
1 12.06.2021 a. Added new sheet for roof plan w/ 5 NFA ilo 10 NFA lower 11.30.2021 DRH HM SCALE 12" = 1'-0"
attic ventilation for all elevations
b. Added non-fire rated exterior elevation & roof plan sheets for
12/8/2023 9:52:02 AM

all elevations

2 04.28.2022 a. Updated Roof vent notes from 2012/2015 to CURRENT


b. Updated wall section sheet(s)
04.14.2021 DRH-DL KL A00.01
c. Updated 1 HR FIRE RATED SOFFIT DETAILS (2021 IRC) W.0. 2020951R3 STRAND 2351667
sheet
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
FLOOR PLAN NOTES GYPSUM BOARD GYPSUM BOARD GYPSUM BOARD
GYPSUM BOARD GYPSUM BOARD
GYPSUM BOARD GYPSUM BOARD
2x WOOD FRAMED WALL 2x WOOD FRAMED WALL 2x WOOD FRAMED WALL 2x WOOD FRAMED WALL 2x WOOD FRAMED WALL
2x WOOD FRAMED WALL 2x WOOD FRAMED WALL

WALL LEGEND
(REF. STRUCTURAL PLANS (REF. STRUCTURAL PLANS (REF. STRUCTURAL PLANS (REF. STRUCTURAL PLANS (REF. STRUCTURAL PLANS
1. INTERIOR DIMENSIONS ARE TO FACE OF STUD, UNLESS FOR SIZE/SPACING) FOR SIZE/SPACING) FOR SIZE/SPACING) (REF. STRUCTURAL PLANS (REF. STRUCTURAL PLANS FOR SIZE/SPACING) FOR SIZE/SPACING)
GRAPHICALLY INDICATED OTHERWISE. WINDOWS AND DOORS ARE FOR SIZE/SPACING) FOR SIZE/SPACING)
DIMENSIONED TO CENTERLINE OF ROUGH OPENINGS. AIR SPACE AIR SPACE AIR SPACE GYPSUM BOARD GYPSUM BOARD
LAP SIDING STUCCO/STUCCO
2. REFER TO ELEVATIONS AND ROOF PLAN FOR PLATE HEIGHTS. BRICK STONE BRICK w/STONE BOARD/DEF'S 10003 Technology Blvd. West
WAINSCOT
3. CEILING HEIGHT CALL OUTS ARE NOMINAL. SEE ELEVATIONS AND Dallas, TX. 75220
1 EXTERIOR BRICK WALL 2 EXTERIOR STONE WALL 3 EXTERIOR WAINSCOT WALL 4 EXTERIOR SIDING WALL 5 EXTERIOR STUCCO WALL 6 INTERIOR GYPSUM WALL 7 INTERIOR GYPSUM LOW/HALF WALL 972-620-8204
ROOF PLAN FOR PRECISE DIMENSIONS.
4. ALL ANGLES OTHER THAN 90° ANGLES ARE TO BE 45° ANGLES, NOTE:
U.N.O. 1. MATERIAL FINISHES SHOWN ON ELEVATION VIEWS GOVERN OVER FLOOR PLAN. REFERENCE ELEVATION VIEWS FOR ADDITIONAL MATERIAL USES AND DETAILS.
2. REFERENCE FLOOR PLANS FOR SPECIFIC LOW/HALF WALL HEIGHTS AND LOCATIONS.
5. ALL EGRESS HALLWAYS FROM BEDROOMS SHALL NOT BE 3. THE PURPOSE OF THIS LEGEND IS FOR GRAPHICAL REPRESENTATION. ACTUAL WALL ASSEMBLY MATERIALS AND CONSTRUCTION SHALL BE PER BUILDING CODES AND/OR STRUCTURAL ENGINEERING PLANS.
RESTRICTED TO LESS THAN 3'-0” NET CLEAR. 4. GYPSUM BOARD THICKNESS IS 1/2", TYPICAL, AS SHOWN ABOVE. 5/8" THICK AS REQUIRED FOR FIRE/MOISTURE PROTECTION.
6. EXTERIOR BRICK WALLS (BRICK LEDGE) ARE SHOWN AS 5 ½”
WIDTH.
7. ALL PLUMBING WALLS SHALL BE 2x6 MIN.
8. THIS PLAN IS A GRAPHIC REPRESENTATION FOR ESTIMATING
PURPOSES ONLY. ACTUAL FIELD CONDITIONS MAY VARY AND ELECTRICAL LEGEND ADDRESS SPECIFIC OPTIONS FOUNDATION - A FOUNDATION - B
MUST BE VERIFIED BEFORE PROCEEDING WITH CONSTRUCTION.
LOCATION AREA WIDTH DEPTH LOCATION AREA WIDTH DEPTH

WPGFI
9. ALL GLAZING WITHIN 2'-0” HORIZONTAL DISTANCE FROM ANY JAMB
OF EXTERIOR DOORS SHOULD BE TEMPERED GLASS. WATERPROOF OPTIONAL BRICK @ SIDES BASE 1960 SF 29'-11 1/2" 68'-8'' BASE 1960 SF 29'-11 1/2" 68'-8''
GFCI DUPLEX OPT BRICK @ SIDES 52 SF 29'-11 1/2" 68'-8'' OPT BRICK @ SIDES 52 SF 29'-11 1/2" 68'-8''
10. GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND IT'S
OPTIONAL FULL BRICK OPT FULL BRICK 61 SF 29'-11 1/2" 68'-8'' OPT FULL BRICK 61 SF 29'-11 1/2" 68'-8''
ATTIC AREA BY NOT LESS THAN 1/2" GYP. BOARD TO THE GARAGE
SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL BE DUPLEX
SEPARATED BY NOT LESS THAN 5/8" TYPE X GYP BOARD OR OPTIONAL 2468 DOOR @ WIC TOTAL UNDER ROOF - A TOTAL UNDER ROOF - B

GFI
EQUIVALENT. GFCI DUPLEX
OPTIONAL 2468 DOOR @ WC
LOCATION AREA LOCATION AREA
11. ALL OPENINGS TO BE CENTERED ON WALLS UNLESS OTHERWISE FIRST FLOOR LIVING 1396 SF FIRST FLOOR LIVING 1396 SF
NOTED. STANDARD DOOR JAMB TO BE 4”.

220v
GARAGE 397 SF GARAGE 397 SF
12. WATER HEATER TO BE LOCATED IN GARAGE. OPTIONAL SINK @ BATH 1
220 VOLT DUPLEX PORCH 52 SF PORCH 52 SF
13. 6" MIN DROP FROM FINISHED MATERIAL TO FINISHED GRADE; COVERED PATIO 114 SF COVERED PATIO 114 SF
OPTIONAL COVER PLATE, BLOCK & PREWIRE FOR
FINISHED GRADE TO SLOPE AWAY FROM FOUNDATION AT A 1/4"
SPR

CLG FAN W/ SWITCH @ FAMILY ROOM OPT BRICK @ SIDES 52 SF OPT BRICK @ SIDES 52 SF
PER FOOT. GFCI DUPLEX FOR SPRINKLER,
INSTALLED @ 84" AFF OPT FULL BRICK 61 SF OPT FULL BRICK 61 SF
OPTIONAL WOOD-LOOK SIDING @ FRONT ELEVATION
( ONLY APPLICABLE TO AREAS NOTED PER PLAN/ CONDITIONED SPACE (MARKETING) - A CONDITIONED SPACE (MARKETING) - B
CEILING MOUNTED ELEVATION)
CLG
ELEVATION NOTES DUPLEX OPTIONAL 4010 WINDOW @ BATH 1; FOR DRHE
PLANS ONLY
LOCATION AREA LOCATION AREA
TV
TV OUTLET FIRST FLOOR LIVING 1396 SF FIRST FLOOR LIVING 1396 SF
1. PROVIDE ATTIC VENTILATION AS REQUIRED PER CODE. OPT BRICK @ SIDES 44 SF OPT BRICK @ SIDES 44 SF
2. ALL WINDOW ROUGH OPENING SIZES TO BE FRAMED SAME AS TELEPHONE OUTLET OPT FULL BRICK 61 SF OPT FULL BRICK 61 SF
WINDOW CALL-OUT SIZE.
EXHAUST FAN
ROOF VENT LEGEND CONDITIONED SPACE (S/R TO S/R) - A CONDITIONED SPACE (S/R TO S/R) - B
3. WINDOW ROWLOCKS TO HAVE ½” SLOPE MINIMUM.
3
4. NO CORE HOLES TO BE VISIBLE AT ROWLOCKS OR WINDOW SILLS. THREE-WAY SWITCH 28 4x16 CUT IN VENT (28 NFA) LOCATION AREA LOCATION AREA
5. HEIGHT OF CHIMNEY TO BE 2'-0” HIGHER THAN ANY POINT WITHIN 4 INSTALLED IN SOFFIT @ EAVE OR FIRST FLOOR LIVING 1278 SF FIRST FLOOR LIVING 1278 SF
10'-0” HORIZONTALLY AND AT LEAST 4'-0" ABOVE ANY POINT FOUR-WAY SWITCH IN CEILING OF EXTERIOR SPACES
IMMEDIATELY ADJACENT
SINGLE SWITCH 56 8x16 CUT IN VENT (56 NFA)
6. LINEAR FEET OF PERFORATED SOFFIT VENTS T.B.D. BY HOME INSTALLED IN SOFFIT @ EAVE OR
BUILDER.
DB

IN CEILING OF EXTERIOR SPACES


DOOR BELL
SLP VENT (65 NFA)
65 INSTALLED WITHIN 3'-0" OF
G GARAGE DOOR OPENER HIGHEST RIDGE IN ATTIC

ELECTRICAL PLAN NOTES SECURITY LIGHT FIXTURE SLP VENT (150 NFA) ELEVATION A ELEVATION B

VERSION 7
150 INSTALLED WITHIN 3'-0" OF MASONRY CALCULATIONS MASONRY CALCULATIONS
HIGHEST RIDGE IN ATTIC
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

1. 200V/GAS PER SPECS @ W.H., A/C, RANGE AND DRYER. CEILING MOUNTED
LIGHT FIXTURE SIDING: 987 SQ FT SIDING: 987 SQ FT
2. GAS STUBS TO BE LOCATED PER SUBDIVISION SPECIFICATIONS.

Express Homes - North Central Texas


3. HOSE BIBS TO BE LOCATED PER SUBDIVISION SPECIFICATIONS. AREA NOT ALLOWED TO BRICK: 243 SQ FT BRICK: 212 SQ FT
RECESSED CAN

SSE Architectural Design Services


LIGHT FIXTURE HAVE PERFORATED SOFFIT STONE: 0 SQ FT STONE: 101 SQ FT
4. EXTERIOR ELECTRICAL OUTLETS TO BE WEATHER PROOF
5. PROVIDE 110V WIRED "IN SERIES" SMOKE DETECTORS OR PER RECESSED CAN LIGHT STUCCO: 0 SQ FT STUCCO: 0 SQ FT
LOCAL CODES REQUIREMENTS. EYEBALL FIXTURE
TOTAL AREA: 1230 SQ FT TOTAL AREA: 1300 SQ FT
6. WATER HEATERS TO BE LOCATED IN GARAGE. HANGING LIGHT PERCENT MASONRY: 20 % PERCENT MASONRY: 24 %
7. EXTERIOR COLUMN AND PORCH LIGHTS TO BE MOUNTED PER FIXTURE

X30B A, B, F, G, M, N
ELEVATIONS.
PENDANT LIGHT
8. LIGHT FIXTURE IN BEDROOMS TO BE PRE-WIRED AND BLOCKED FIXTURE
FOR CEILING FAN.

BLOCK
ELEVATION A ELEVATION B
9. BUILDER TO INSTALL ALL LIFE SAFETY DEVICES PER CODE. WALL MOUNTED w/ OPT BRICK @ SIDES w/ OPT BRICK @ SIDES
LIGHT FIXTURE
10. BUILDER/SUB-CONTRACTOR IS RESPONSIBLE FOR ENSURING ALL MASONRY CALCULATIONS MASONRY CALCULATIONS
ELECTRICAL CODES AND REQUIRMENTS ARE MET. ELECTRICAL SIDING: 273 SQ FT SIDING: 273 SQ FT
PLANS CONTAINED WITHIN THIS SET ARE FOR SCHEMATIC
CEILING FAN WITH LIGHT BRICK: 964 SQ FT BRICK: 933 SQ FT
PURPOSES ONLY.
STONE: 0 SQ FT STONE: 101 SQ FT
STUCCO: 0 SQ FT STUCCO: 0 SQ FT

CEILING FAN WITHOUT TOTAL AREA: 1237 SQ FT TOTAL AREA: 1307 SQ FT


LIGHT
INTERIOR ELEVATION NOTES PERCENT MASONRY: 78 % PERCENT MASONRY: 79 %

ADDRESS
BUILDER
1x4 FLUORESCENT

SUBD.
1x4 FLUOR

PLAN
1. PROVIDE CABINET BLOCKING FOR VANITY @ 26” TO 32”, RANGE @ LIGHT FIXTURE

CITY
LOT
WALL 54" AND 80”; BASE AT 32” ELEVATION A ELEVATION B
2. PROVIDE CABINET BLOCKING ON KITCHEN WALLS @ 37 ½”, 57 ½”, COVE LIGHT FIXTURE w/ OPT FULL BRICK w/ OPT FULL BRICK
AND 98 ½” A.F.F. MASONRY CALCULATIONS MASONRY CALCULATIONS
UNDER-CABINET
3. SUBSTRATE FOR TILES SHALL BE TILE OR CEMENT BACKER BOARD. LIGHT FIXTURE SIDING: 0 SQ FT SIDING: 0 SQ FT
4. CONTRACTOR TO FIELD VERIFY ALL CABINET DIMENSIONS PRIOR BRICK: 1223 SQ FT BRICK: 1250 SQ FT
DATE 12.07.2023
EP ELECTRICAL PANEL
TO FABRICATION.
5. ALL SHOWER HEADS TO BE AT 6'-10” A.F.F.
STONE: 0 SQ FT STONE: 101 SQ FT SCALE As indicated
STUCCO: 0 SQ FT STUCCO: 0 SQ FT
6. MANTLE BLOCKING AT EACH SIDE OF FIREPLACE EVERY 24” O.C. AP AUTOMATION PANEL
A.F.F. TOTAL AREA: 1223 SQ FT TOTAL AREA: 1351 SQ FT
12/8/2023 9:52:06 AM

7. SECONDARY BATH TUB BLOCKING 26” TO 32” FROM WALL BOTTOM SMOKE DETECTOR PERCENT MASONRY: 100 % PERCENT MASONRY: 100 %
PLATE TO TOP PLATE. SD
8. BATH 1 SHOWER BLOCKING 40” TO 46” FROM WALL BOTTOM PLATE SMOKE & CARBON
SD/CO
A10.00
TO TOP OF PLATE. MONOXIDE DETECTOR

9. VANITY LIGHT FIXTURE 2X4 BLOCKING TO BE IN ALL BATHS AT 94” DENOTES WATERPROOF
WP
A.F.F. TO TOP OF BLOCKING WITH 36" CABINETS, 88" WITH 30" LIGHT FIXTURE
CABINETS.
P
DENOTES PHOTOVOLTAIC
LIGHT FIXTURE
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
FOUNDATION - F FOUNDATION - G FOUNDATION - N FOUNDATION - M

LOCATION AREA WIDTH DEPTH LOCATION AREA WIDTH DEPTH LOCATION AREA WIDTH DEPTH LOCATION AREA WIDTH DEPTH 10003 Technology Blvd. West
BASE 1999 SF 29'-6" 70'-2 1/2" BASE 1970 SF 29'-6" 68'-2 1/2" BASE 1947 SF 29'-11 1/2" 68'-8'' BASE 1951 SF 29'-11 1/2" 68'-8'' Dallas, TX. 75220
BASE w/ OPT BRICK @ 2022 SF 29'-11 1/2" 70'-2 1/2" OPT BRICK @ SIDES 52 SF 29'-11 1/2" 68'-2 1/2" OPT BRICK @ SIDES 52 SF 29'-11 1/2" 68'-8'' OPT BRICK @ SIDES 52 SF 29'-11 1/2" 68'-8'' 972-620-8204
FRONT OPT FULL BRICK 61 SF 29'-11 1/2" 68'-8'' OPT FULL BRICK 61 SF 29'-11 1/2" 68'-8'' OPT FULL BRICK 61 SF 29'-11 1/2" 68'-8''
OPT BRICK @ SIDES 52 SF 29'-11 1/2" 70'-2 1/2" BASE w/ OPT BRICK @ 1981 SF 29'-6" 68'-2 1/2"
OPT FULL BRICK 61 SF 29'-11 1/2" 70'-2 1/2" FRONT TOTAL UNDER ROOF - N TOTAL UNDER ROOF - M

TOTAL UNDER ROOF - F TOTAL UNDER ROOF - G LOCATION AREA LOCATION AREA
FIRST FLOOR LIVING 1396 SF FIRST FLOOR LIVING 1391 SF
LOCATION AREA LOCATION AREA GARAGE 397 SF GARAGE 398 SF
FIRST FLOOR LIVING 1390 SF FIRST FLOOR LIVING 1390 SF PORCH 40 SF PORCH 48 SF
GARAGE 384 SF GARAGE 384 SF COVERED PATIO 114 SF COVERED PATIO 114 SF
PORCH 111 SF PORCH 82 SF OPT BRICK @ SIDES 52 SF OPT BRICK @ SIDES 52 SF
COVERED PATIO 114 SF COVERED PATIO 114 SF OPT FULL BRICK 61 SF OPT FULL BRICK 61 SF
FIRST FLOOR LIVING w/ OPT BRICK @ FRONT 1399 SF FIRST FLOOR LIVING w/ OPT BRICK @ FRONT 1396 SF
GARAGE w/ OPT BRICK @ FRONT 398 SF GARAGE w/ OPT BRICK @ FRONT 397 SF CONDITIONED SPACE (MARKETING) - N CONDITIONED SPACE (MARKETING) - M
PORCH w/ OPT BRICK @ FRONT 111 SF PORCH w/ OPT BRICK @ FRONT 74 SF
OPT BRICK @ SIDES 52 SF OPT BRICK @ SIDES 52 SF LOCATION AREA LOCATION AREA
OPT FULL BRICK 61 SF OPT FULL BRICK 61 SF FIRST FLOOR LIVING 1396 SF FIRST FLOOR LIVING 1391 SF
OPT BRICK @ SIDES 44 SF OPT BRICK @ SIDES 44 SF
CONDITIONED SPACE (MARKETING) - F CONDITIONED SPACE (MARKETING) - G OPT FULL BRICK 61 SF OPT FULL BRICK 61 SF

LOCATION AREA LOCATION AREA CONDITIONED SPACE (S/R TO S/R) - N CONDITIONED SPACE (S/R TO S/R) - M
FIRST FLOOR LIVING 1390 SF FIRST FLOOR LIVING 1390 SF
FIRST FLOOR LIVING w/ OPT BRICK @ FRONT 1399 SF FIRST FLOOR LIVING w/ OPT BRICK @ FRONT 1396 SF LOCATION AREA LOCATION AREA
OPT BRICK @ SIDES 44 SF OPT BRICK @ SIDES 44 SF FIRST FLOOR LIVING 1278 SF FIRST FLOOR LIVING 1278 SF
OPT FULL BRICK 61 SF OPT FULL BRICK 61 SF

CONDITIONED SPACE (S/R TO S/R) - F CONDITIONED SPACE (S/R TO S/R) - G

LOCATION AREA LOCATION AREA


FIRST FLOOR LIVING 1278 SF FIRST FLOOR LIVING 1278 SF

ELEVATION F ELEVATION G ELEVATION N ELEVATION M


ELEVATION F ELEVATION G
w/ OPT BRICK @ FRONT w/ OPT BRICK @ SIDES MASONRY CALCULATIONS MASONRY CALCULATIONS
MASONRY CALCULATIONS MASONRY CALCULATIONS
MASONRY CALCULATIONS MASONRY CALCULATIONS
SIDING: 1498 SQ FT SIDING: 1155 SQ FT SIDING: 1253 SQ FT SIDING: 546 SQ FT SIDING: 1057 SQ FT SIDING: 1064 SQ FT

BRICK: 0 SQ FT BRICK: 669 SQ FT BRICK: 0 SQ FT BRICK: 721 SQ FT BRICK: 167 SQ FT BRICK: 464 SQ FT

STONE: 0 SQ FT STONE: 0 SQ FT STONE: 0 SQ FT STONE: 0 SQ FT STONE: 0 SQ FT STONE: 0 SQ FT

STUCCO: 0 SQ FT STUCCO: 0 SQ FT STUCCO: 0 SQ FT STUCCO: 0 SQ FT STUCCO: 195 SQ FT STUCCO: 0 SQ FT

TOTAL AREA: 1498 SQ FT TOTAL AREA: 1824 SQ FT TOTAL AREA: 1253 SQ FT TOTAL AREA: 1267 SQ FT TOTAL AREA: 1419 SQ FT TOTAL AREA: 1528 SQ FT
PERCENT MASONRY: 0% PERCENT MASONRY: 37 % PERCENT MASONRY: 0% PERCENT MASONRY: 57 % PERCENT MASONRY: 26 % PERCENT MASONRY: 30 %

VERSION 7
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

ELEVATION G
ELEVATION F ELEVATION N ELEVATION M
w/ OPT FULL BRICK

Express Homes - North Central Texas


w/ OPT BRICK @ SIDES w/ OPT BRICK @ SIDES w/ OPT BRICK @ SIDES
MASONRY CALCULATIONS
MASONRY CALCULATIONS MASONRY CALCULATIONS MASONRY CALCULATIONS

SSE Architectural Design Services


SIDING: 140 SQ FT
SIDING: 1225 SQ FT SIDING: 273 SQ FT SIDING: 294 SQ FT
BRICK: 1184 SQ FT
BRICK: 610 SQ FT BRICK: 961 SQ FT BRICK: 1241 SQ FT
STONE: 0 SQ FT
STONE: 0 SQ FT STONE: 0 SQ FT STONE: 0 SQ FT
STUCCO: 0 SQ FT
STUCCO: 0 SQ FT STUCCO: 195 SQ FT STUCCO: 0 SQ FT

X30B A, B, F, G, M, N
TOTAL AREA: 1324 SQ FT
TOTAL AREA: 1835 SQ FT TOTAL AREA: 1429 SQ FT TOTAL AREA: 1535 SQ FT
PERCENT MASONRY: 89 %
PERCENT MASONRY: 33 % PERCENT MASONRY: 81 % PERCENT MASONRY: 81 %

BLOCK
ELEVATION G
ELEVATION F w/ OPT FULL BRICK ELEVATION N ELEVATION M
w/ OPT FULL BRICK MASONRY CALCULATIONS w/ OPT FULL BRICK w/ OPT FULL BRICK
MASONRY CALCULATIONS SIDING:
MASONRY CALCULATIONS MASONRY CALCULATIONS
1113 SQ FT
SIDING: 112 SQ FT BRICK: 144 SQ FT SIDING: 0 SQ FT SIDING: 119 SQ FT

BRICK: 1765 SQ FT STONE: 0 SQ FT BRICK: 1283 SQ FT BRICK: 1465 SQ FT

STONE: 0 SQ FT STUCCO: 0 SQ FT STONE: 0 SQ FT STONE: 0 SQ FT

ADDRESS
BUILDER
STUCCO: 0 SQ FT STUCCO: 195 SQ FT STUCCO: 0 SQ FT
TOTAL AREA: 1257 SQ FT

SUBD.

PLAN
TOTAL AREA: 1877 SQ FT PERCENT MASONRY: 11 % TOTAL AREA: 1478 SQ FT TOTAL AREA: 1584 SQ FT

CITY
LOT
PERCENT MASONRY: 94 % PERCENT MASONRY: 100 % PERCENT MASONRY: 92 %

(INCLUDES OPT BRICK @ FRONT)


DATE 12.07.2023
SCALE
12/8/2023 9:52:09 AM

A10.01
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
A - LEAD WALK B - LEAD WALK
LOCATION AREA LOCATION AREA 10003 Technology Blvd. West
LEAD WALK AREA (16'-0" DRIVEWAY) 57 SF LEAD WALK AREA (16'-0" DRIVEWAY) 57 SF Dallas, TX. 75220
LEAD WALK AREA (17'-0" DRIVEWAY) 55 SF LEAD WALK AREA (17'-0" DRIVEWAY) 55 SF 972-620-8204

FOYER FOYER

COAT COAT

GARAGE GARAGE

4'-0"
4'-0"
7'-7 1/2"

7'-7 1/2"
4'-0"

4'-0"
DRIVEWAY DRIVEWAY

9'-11 1/2" 9'-11 1/2"


10'-5 1/2" 16'-0" WIDTH 10'-5 1/2" 16'-0" WIDTH

17'-0" WIDTH 17'-0" WIDTH

1 ELEVATION A - LEAD WALK 2 ELEVATION B - LEAD WALK


1/8" = 1'-0" 1/8" = 1'-0"

VERSION 7
F - LEAD WALK G - LEAD WALK
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

LOCATION AREA LOCATION AREA

Express Homes - North Central Texas


LEAD WALK AREA (16'-0" DRIVEWAY) 42 SF LEAD WALK AREA (16'-0" DRIVEWAY) 46 SF

SSE Architectural Design Services


LEAD WALK AREA (17'-0" DRIVEWAY) 39 SF LEAD WALK AREA (17'-0" DRIVEWAY) 44 SF

X30B A, B, F, G, M, N
FOYER FOYER

BLOCK
COAT COAT

GARAGE GARAGE

ADDRESS
BUILDER
SUBD.

PLAN
CITY
LOT
5'-0 1/2"
DATE 12.07.2023

4'-0"
DRIVEWAY DRIVEWAY
SCALE 1/8" = 1'-0"
4'-0"

9'-11 1/2"
16'-0" WIDTH 16'-0" WIDTH
12/8/2023 9:52:11 AM

9'-2 1/4" 10'-5 1/2"


17'-0" WIDTH 17'-0" WIDTH
9'-8 1/4"

3 ELEVATION F - LEAD WALK 4 ELEVATION G - LEAD WALK A10.02


1/8" = 1'-0" 1/8" = 1'-0"
STRAND 2351667
12/8/2023 9:52:12 AM C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

7'-0"
LOCATION

1/8" = 1'-0"
FOYER

4'-0"
M - LEAD WALK

LEAD WALK AREA (17'-0" DRIVEWAY)


LEAD WALK AREA (16'-0" DRIVEWAY)

9'-7 1/4"
10'-1 1/4"
55 SF
57 SF

4'-0"
AREA

COAT

3 ELEVATION M - LEAD WALK


17'-0" WIDTH
DRIVEWAY

16'-0" WIDTH
GARAGE

7'-5"
1
4'-0"
FOYER

1/8" = 1'-0"
LOCATION

9'-11 5/8"
10'-5 5/8"

4'-0"
N - LEAD WALK

LEAD WALK AREA (16'-0" DRIVEWAY)


LEAD WALK AREA (17'-0" DRIVEWAY)

COAT
56 SF
54 SF
AREA

ELEVATION N - LEAD WALK


17'-0" WIDTH
DRIVEWAY

16'-0" WIDTH
GARAGE

PLAN CONVERTED FROM X30B V4 REGIONAL SET

BUILDER Express Homes - North Central Texas


SUBD. SSE Architectural Design Services
STRAND
972-620-8204

LOT BLOCK
Dallas, TX. 75220

ADDRESS
CITY
DATE 12.07.2023
SCALE 1/8" = 1'-0"

A10.03
10003 Technology Blvd. West

PLAN
2351667

X30B A, B, F, G, M, N VERSION 7
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

68'-8"
5 1/2"
5 1/2" 67'-9"

9'-6" 11'-4 1/2" 10'-1" 9" 5'-3 1/2" 10'-4 1/2" 20'-4 1/2"
OPT FULL
BRICK
3'-9" 3'-7" 4'-0 1/2" 2'-2 1/2" 7'-10 1/2" 7'-8 1/2" 2'-8"
*FOR DRHE PLANS ONLY
30"x30"x18" WATER HEATER
BATH 1 2'-0"
5 1/2"

OPT BRICK PLATFORM w/ 2x4 WING WALL

5 1/2"
WRF 3050 SH 3050 SH 3050 SH 3050 SH (NOT REQUIRED w/ TANKLESS
@ SIDES

HB
8'-0'' CLG 7'-0" HDR 7'-0" HDR 7'-0" HDR 7'-0" HDR WH)

2'-10 1/2"
2'-9 1/2"

WH
60" x 30"

3'-2"
2668

1'-4 1/2"
OPT 4010 FX

SHOWER
TUB
5'-3 1/2"

36" x 60"
7'-0" HDR OPT SINK 2x4 WALL w/ WH
SLOPE TO 9'-0" BEDROOM 3 BATH 2
2'-6"

2'-6 1/2"
CLG @ 6:12 PITCH

9'-0"
CARPET

9'-6"
WRF
BEDROOM 2

2'-4" x 6'-10" HDR


8'-0" CLG 8'-0" CLG SLOPE
CARPET

2X6
8'-0" CLG
CONCRETE 2"

7'-0"

8'-9 1/2"
OPT 2468 DOOR A90.01 5 A90.01
4

16070 GARAGE DOOR


TIRE STOP
BEDROOM 1 CLOSET
6'-4 1/2"

CARPET CARPET
WC CLOSET

ACCESS
17'-8"

2868

16'-3" R.O.
9'-0'' CLG 8'-0" CLG

ATTIC

19'-0"
WRF CARPET
8'-0'' CLG 2'-4" x 6'-10" HDR WIC 8'-0" CLG GARAGE

5SH
3 1/2" CONCRETE
CARPET
8'-0" CLG

3'-10 1/2"
8'-0'' CLG

20
68
VEST

68
20
2X6 PANTRY

2'-4 1/2"
26

68
2'-8 1/2"
CARPET

2668
8'-4 1/2"

3'-8"

68

26
WRF 8'-0" CLG 1 1/2"
8'-0" CLG 1R1S 1R1S
29'-11 1/2"

29'-11 1/2"
8'-0" CLG
1R1S

9'-6"
1R1S
6'-0"

5SH 7'-10 1/2" 3'-11 1/2" 8'-10"


3'-8" 5'-6 1/2" 9'-0" CLG

1'-4 1/2"
8'-0'' CLG

4'-8"
REF
1R1S UTILITY COAT

20

1'-10 1/2"
9'-0'' CLG KITCHEN

68
HB WRF WRF
WRF CPT

8 1/4"
TEMP WRF 1'-10 1/2"
2'-1 1/2"

8'-0" CLG 8'-0" CLG


9'-0" CLG 4 1/2"
2868 4'-4" 2'-11" 6'-4" 4'-0 1/2" 3'-6" 4'-0 1/2" 6'-4"

2'-1 1/2"
30
1 1R1S
1 1/2"

68
4'-1 1/2"

D
PORCH

2050 FX DL TEMP
DINING

5'-8"
DW

2X6
1SH
A90.01 3
COVERED
5'-1 1/2"

A90.01 6

2'-1"
FAMILY ROOM CONCRETE
SLAB EDGE

WRF

2068

6'-8" HDR
10'-11"

PATIO 9'-0" CLG CARPET 8'-0" CLG

W
2

8'-10 3/4"
SLAB EDGE
CONCRETE 9'-0" CLG

68
7'-0" HDR
3050 SH

TO ISLAND WALL
8'-0" CLG

30
2x6 LOW WALL

3'-3"
14'-11 1/2" 6'-7"
@ 34'-1/2" AFF
TO ISLAND WALL

9'-0" CLG
8'-0" CLG

VERSION 7
SLOPE
6'-2"
1 1/2"
CONCRETE 2" FOYER

4'-8"
3'-8"
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

SLOPE

5 1/2"
WRF
3068
5 1/2"

2'-0"
TYP

2'-7"
SLOPE TO 9'-0" 8'-0" CLG CONCRETE

Express Homes - North Central Texas


CLG @ 6:12 PITCH CPT WRF

SSE Architectural Design Services


3050 SH OPT BRICK 3050 SH 3050 SH SLAB EDGE
5 1/2"

SLAB EDGE

5 1/2"
7'-0" HDR 7'-0" HDR 7'-0" HDR 2'-0"
@ SIDES
6X6 POST (WRAP w/ MASONRY COLUMN
OPT FULL BRICK) 12'-5 1/2" 11'-7" 11'-9 1/2" 13'-10 1/2"
5 1/2"
8'-9" 49'-8 1/2" 4'-9" 3'-7 1/2"

X30B A, B, F, G, M, N
5 1/2" 5 1/2" 5 1/2"
68'-8"

BLOCK
1 ELEVATION A - FIRST FLOOR PLAN
1/8" = 1'-0"

ADDRESS
BUILDER
SUBD.

PLAN
CITY
LOT
DATE 12.07.2023
SCALE 1/8" = 1'-0"
12/8/2023 9:52:14 AM

A20.01
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ELECTRICAL LEGEND 10003 Technology Blvd. West
Dallas, TX. 75220

WPGFI
972-620-8204
WATERPROOF
GFCI DUPLEX

DUPLEX

GFI
GFCI DUPLEX

220v
220 VOLT DUPLEX

SPR
GFCI DUPLEX FOR SPRINKLER,
INSTALLED @ 84" AFF
PRE-WIRE FOR

HB
EXT WALL LIGHT
CEILING MOUNTED
CLG DUPLEX
WP

WH
EP

GFI
TV
TV OUTLET
SPRINKLER OUTLET
84" AFF
WP TELEPHONE OUTLET
ELECTERICAL PANEL
BLOCK & PRE WIRE EXHAUST FAN
GFI
FOR CLG FAN 3
THREE-WAY SWITCH

GFI

LIGHT & SWITCH


4

TV
PRE-WIRE FOR FOUR-WAY SWITCH

GFI

ACCESS

IN ATTIC
ADDITIONAL FAN & GARAGE DOOR

ATTIC
SWITCH REQ'D W/ OPENER
SINGLE SWITCH
OPT. 2468 DOOR
GFI

DB
SD SD/CO SD CLG DOOR BELL

SD
G GARAGE DOOR OPENER

4'-5"
SD/CO SECURITY LIGHT FIXTURE
3'-2"

GFI

GFI

GFI
GFI-REF

GFI-MICRO/VENT
GFI-RANGE

GFI
HB CEILING MOUNTED
LIGHT FIXTURE

GFI-DISP
RECESSED CAN

GFI-DW
LIGHT FIXTURE
GFI

WPGFI
OPT. COVER PLATE, RECESSED CAN LIGHT
DISP
BLOCK & PRE-WIRE GFI EYEBALL FIXTURE

6'-0"
WPGFI FOR CLG FAN
GFI GFI 220v HANGING LIGHT
6'-0" 6'-1 1/2" 6'-0" 4'-6"
FIXTURE

GFI
DB
PENDANT LIGHT
6'-1"

7'-3 1/2"

VERSION 7
3'-6" FIXTURE
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

WALL MOUNTED
LIGHT FIXTURE

Express Homes - North Central Texas


TV
AP

SSE Architectural Design Services


CEILING FAN WITH LIGHT

CEILING FAN WITHOUT

X30B A, B, F, G, M, N
LIGHT

BLOCK
1 ELEVATION A - FIRST FLOOR ELECTRICAL PLAN 1x4 FLUOR 1x4 FLUORESCENT
LIGHT FIXTURE

1/8" = 1'-0" COVE LIGHT FIXTURE

UNDER-CABINET
LIGHT FIXTURE
EP ELECTRICAL PANEL

AP AUTOMATION PANEL

ADDRESS
BUILDER
SMOKE DETECTOR

SUBD.
SD

PLAN
CITY
LOT
SMOKE & CARBON
SD/CO MONOXIDE DETECTOR

DENOTES WATERPROOF
WP
LIGHT FIXTURE
DATE 12.07.2023
DENOTES PHOTOVOLTAIC
P
LIGHT FIXTURE SCALE 1/8" = 1'-0"
12/8/2023 9:52:15 AM

A20.02
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 198 LF (10 NFA) = 1980 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2200 1056 423 528 0 NFA + 450 NFA = 450 NFA 606 1980 NFA + 0 NFA + 0 NFA = 1980 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

SOLDIER COURSE, TYP 1 2"


6" / 8"-1 1/8" PL
6" / 1X6 FASCIA, TYP
" 6:12 12"
EXT WALL LIGHT 6" / 12 COMPOSITION 1'-4 1/4" , TYP
SHINGLE ROOF, TYP 1X4 FRIEZE TRIM, TYP @ 6:12 PITCH

6" / 12"
8'-1 1/8" PL

1X4 TRIM, TYP

8"-1 1/8" PL
LAP SIDING, TYP 6" / 12"
(OPT. BRICK @ SIDES)
5'-0"

3'-3"

150 150

8"-1 1/8" PL
6" / 12"

6" / 12"
2'-0"
BRICK, TYP BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES
150 6" / 12"

ROOF VENT TYP. 8"-1 1/8" PL

6" / 12"
4 ELEVATION A - RIGHT

8"-1 1/8" PL
1/16" = 1'-0"

8"-1 1/8" PL

1X6 FASCIA, TYP

6" / 6:12 1X4 FRIEZE TRIM, TYP


12"

VERSION 7
12" 6" /
6" / 6:12 12" SOLDIER COURSE, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION
SHINGLE ROOF, TYP

Express Homes - North Central Texas


BRICK, TYP
5 ELEVATION A - ROOF PLAN

SSE Architectural Design Services


8'-1 1/8" PL
5'-0" 1/16" = 1'-0"
3'-3"

X30B A, B, F, G, M, N
6X6 POST, TYP. EXT WALL LIGHT
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 2'-0"
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
3 ELEVATION A - LEFT 6" /
12"

1/16" = 1'-0" 2"


1

T. O. FOUNDATION TO ROOF PEAK HEIGHT


6" / 1X6 FASCIA TRIM, TYP
6:12 2" 6" /
1 12"
COMPOSITION 6" / 1X4 FRIEZE TRIM, TYP
SHINGLE ROOF, TYP
6:12
SOLDIER COURSE, TYP

ADDRESS
15'-9" PL

BUILDER
2" 6" /
1X6 FASCIA TRIM, TYP 1 12"
6" / EXT WALL LIGHT

SUBD.
6:12

PLAN
CITY
1X4 FRIEZE TRIM, TYP COMPOSITION SOLDIER COURSE, TYP

LOT
BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


DATE 12.07.2023

5'-0"
LAP SIDING, TYP

3'-3"
(OPT FULL BRICK)
SCALE As indicated
6X6 POST, TYP. MASONRY COLUMN BRICK SILL, TYP BOX OUT HDR w/
(WRAP w/ OPT FULL BRICK) SOFFIT BOARD, TYP
12/8/2023 9:52:17 AM

2 ELEVATION A - REAR
1/16" = 1'-0"
1 ELEVATION A - FRONT
1/8" = 1'-0"
A20.03
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 61 LF (10 NFA) = 610 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2200 1056 423 528 0 NFA + 450 NFA = 450 NFA 606 610 NFA + 0 NFA + 0 NFA = 610 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
A100.02 A100.02
SOLDIER COURSE, TYP 12"
6" / 8"-1 1/8" PL
6" / 1X6 FASCIA, TYP
2" 6:12 12"
1
EXT WALL LIGHT 6" / COMPOSITION 1'-4 1/4" , TYP
SHINGLE ROOF, TYP 1X4 FRIEZE TRIM, TYP @ 6:12 PITCH

6" / 12"
8'-1 1/8" PL

1X4 TRIM, TYP

8"-1 1/8" PL
LAP SIDING, TYP 6" / 12"
(OPT. BRICK @ SIDES)
5'-0"

3'-3"

150 150

8"-1 1/8" PL
6" / 12"

6" / 12"
2'-0"
BRICK, TYP BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES
150 6" / 12"

ELEVATION A - RIGHT w/ FIRE RATED SOFFITS @ ROOF VENT TYP. 8"-1 1/8" PL

6" / 12"
5 SIDES

8"-1 1/8" PL
1/16" = 1'-0"

8"-1 1/8" PL 2 1
A100.02 A100.02

1X6 FASCIA, TYP


FIRE RATED SOFFIT/ BLOCKING WHEN
6" / 6:12 1X4 FRIEZE TRIM, TYP
12" EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
LINE (REF PLOT PLAN)

VERSION 7
1 2" 6" /
6" / 6:12 12" SOLDIER COURSE, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION
SHINGLE ROOF, TYP ELEVATION A - ROOF PLAN w/ FIRE RATED SOFFITS @

Express Homes - North Central Texas


BRICK, TYP
3 SIDES

SSE Architectural Design Services


8'-1 1/8" PL
5'-0" 1/16" = 1'-0"
3'-3"

X30B A, B, F, G, M, N
6X6 POST, TYP. EXT WALL LIGHT
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 2'-0"
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
4 ELEVATION A - LEFT w/ FIRE RATED SOFFITS @ SIDES 6" /
12"

1/16" = 1'-0" 2"


1

T. O. FOUNDATION TO ROOF PEAK HEIGHT


6" / 1X6 FASCIA TRIM, TYP
6:12 2" 6" /
1 12"
COMPOSITION 6" / 1X4 FRIEZE TRIM, TYP
SHINGLE ROOF, TYP
6:12
SOLDIER COURSE, TYP

ADDRESS
15'-9" PL

BUILDER
2" 6" /
1X6 FASCIA TRIM, TYP 1 12"
6" / EXT WALL LIGHT

SUBD.
6:12

PLAN
CITY
1X4 FRIEZE TRIM, TYP COMPOSITION SOLDIER COURSE, TYP

LOT
BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


DATE 12.07.2023

5'-0"
LAP SIDING, TYP

3'-3"
(OPT FULL BRICK)
SCALE As indicated
6X6 POST, TYP. MASONRY COLUMN BRICK SILL, TYP BOX OUT HDR w/
(WRAP w/ OPT FULL BRICK) SOFFIT BOARD, TYP
12/8/2023 9:52:19 AM

ELEVATION A - FRONT w/ FIRE RATED SOFFITS @


2 ELEVATION A - REAR w/ FIRE RATED SOFFITS @ SIDES
1/16" = 1'-0"
1 SIDES
1/8" = 1'-0"
A20.04
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (5 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 61 LF (5 NFA) = 305 NFA 6 (56 NFA) = 336 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2200 1056 423 528 0 NFA + 450 NFA = 450 NFA 606 305 NFA + 336 NFA + 0 NFA = 641 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
A100.02 A100.02
SOLDIER COURSE, TYP 12"
6" / 8"-1 1/8" PL
6" / 1X6 FASCIA, TYP
2" 6:12 12"
1
EXT WALL LIGHT 6" / COMPOSITION 1'-4 1/4" , TYP
SHINGLE ROOF, TYP 1X4 FRIEZE TRIM, TYP @ 6:12 PITCH
56

6" / 12"
8'-1 1/8" PL

1X4 TRIM, TYP

8"-1 1/8" PL
LAP SIDING, TYP 6" / 12"
(OPT. BRICK @ SIDES) 56
5'-0"

3'-3"

150 150

8"-1 1/8" PL
6" / 12"

6" / 12"
2'-0" 56
BRICK, TYP BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES
150 6" / 12"
56
ELEVATION A - RIGHT w/ FIRE RATED SOFFITS @ ROOF VENT TYP. 8"-1 1/8" PL

6" / 12"
56
4 SIDES w/ 5 NFA LOWER VENTILATION

8"-1 1/8" PL
56
1/16" = 1'-0"

8"-1 1/8" PL 2 1
A100.02 A100.02

1X6 FASCIA, TYP


FIRE RATED SOFFIT/ BLOCKING WHEN
6" / 6:12 1X4 FRIEZE TRIM, TYP
12" EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
LINE (REF PLOT PLAN)

VERSION 7
1 2" 6" /
6" / 6:12 12" SOLDIER COURSE, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION
SHINGLE ROOF, TYP
ELEVATION A - ROOF PLAN w/ FIRE RATED SOFFITS @

Express Homes - North Central Texas


BRICK, TYP

5 SIDES w/ 5 NFA LOWER VENTILATION

SSE Architectural Design Services


8'-1 1/8" PL
1/16" = 1'-0"
5'-0"
3'-3"

X30B A, B, F, G, M, N
6X6 POST, TYP. EXT WALL LIGHT
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 2'-0"
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
ELEVATION A - LEFT w/ FIRE RATED SOFFITS @ SIDES
3 w/ 5 NFA LOWER VENTILATION 6" /
12"

1/16" = 1'-0" 2"


1

T. O. FOUNDATION TO ROOF PEAK HEIGHT


6" / 1X6 FASCIA TRIM, TYP
6:12 2" 6" /
1 12"
COMPOSITION 6" / 1X4 FRIEZE TRIM, TYP
SHINGLE ROOF, TYP
6:12
SOLDIER COURSE, TYP

ADDRESS
15'-9" PL

BUILDER
2" 6" /
1X6 FASCIA TRIM, TYP 1 12"
6" / EXT WALL LIGHT

SUBD.
6:12

PLAN
CITY
1X4 FRIEZE TRIM, TYP COMPOSITION SOLDIER COURSE, TYP

LOT
BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


DATE 12.07.2023

5'-0"
LAP SIDING, TYP

3'-3"
(OPT FULL BRICK)
SCALE As indicated
6X6 POST, TYP. MASONRY COLUMN BRICK SILL, TYP BOX OUT HDR w/
(WRAP w/ OPT FULL BRICK) SOFFIT BOARD, TYP
12/8/2023 9:52:20 AM

ELEVATION A - REAR w/ FIRE RATED SOFFITS @ SIDES ELEVATION A - FRONT w/ FIRE RATED SOFFITS @
2 w/ 5 NFA LOWER VENTILATION
1/16" = 1'-0"
1 SIDES w/ 5 NFA LOWER VENTILATION
1/8" = 1'-0"
A20.05
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

68'-8"
5 1/2"
5 1/2" 67'-9"

9'-6" 11'-4 1/2" 10'-1" 9" 5'-3 1/2" 10'-4 1/2" 20'-4 1/2"
OPT FULL
BRICK
3'-9" 3'-7" 4'-0 1/2" 2'-2 1/2" 7'-10 1/2" 7'-8 1/2" 2'-8"
*FOR DRHE PLANS ONLY
30"x30"x18" WATER HEATER
BATH 1 2'-0"
5 1/2"

OPT BRICK PLATFORM w/ 2x4 WING WALL

5 1/2"
WRF 3050 SH 3050 SH 3050 SH 3050 SH (NOT REQUIRED w/ TANKLESS
@ SIDES

HB
8'-0'' CLG 7'-0" HDR 7'-0" HDR 7'-0" HDR 7'-0" HDR WH)

2'-10 1/2"
2'-9 1/2"

WH
60" x 30"

3'-2"
2668

1'-4 1/2"
OPT 4010 FX

SHOWER
TUB
5'-3 1/2"

36" x 60"
7'-0" HDR OPT SINK 2x4 WALL w/ WH
SLOPE TO 9'-0" BEDROOM 3 BATH 2
2'-6"

2'-6 1/2"
CLG @ 6:12 PITCH

9'-0"
CARPET

9'-6"
WRF
BEDROOM 2

2'-4" x 6'-10" HDR


8'-0" CLG 8'-0" CLG SLOPE
CARPET

2X6
8'-0" CLG
CONCRETE 2"

7'-0"

8'-9 1/2"
OPT 2468 DOOR A90.01 5 A90.01
4

16070 GARAGE DOOR


TIRE STOP
BEDROOM 1 CLOSET
6'-4 1/2"

CARPET CARPET
WC CLOSET

ACCESS
17'-8"

2868

16'-3" R.O.
9'-0'' CLG 8'-0" CLG

ATTIC

19'-0"
WRF CARPET
8'-0'' CLG 2'-4" x 6'-10" HDR WIC 8'-0" CLG GARAGE

5SH
3 1/2" CONCRETE
CARPET
8'-0" CLG

3'-10 1/2"
8'-0'' CLG

20
68
VEST

68
20
2X6 PANTRY

2'-4 1/2"
26

68
2'-8 1/2"
CARPET

2668
8'-4 1/2"

3'-8"

68

26
WRF 8'-0" CLG 1 1/2"
8'-0" CLG 1R1S 1R1S
29'-11 1/2"

29'-11 1/2"
8'-0" CLG
1R1S

9'-6"
1R1S
6'-0"

5SH 7'-10 1/2" 3'-11 1/2" 8'-10"


3'-8" 5'-6 1/2" 9'-0" CLG

1'-4 1/2"
8'-0'' CLG

4'-8"
REF
1R1S UTILITY COAT

20

1'-10 1/2"
9'-0'' CLG KITCHEN

68
HB WRF WRF
WRF WRF CPT 1'-10 1/2"
TEMP
2'-1 1/2"

8'-0" CLG 8'-0" CLG


9'-0" CLG 4 1/2"
2868 4'-4" 2'-11" 6'-4" 4'-0 1/2" 3'-6" 4'-0 1/2" 6'-4"

11"
2'-1 1/2"
30
1 1R1S
1 1/2"

68
4'-1 1/2"

D
DINING PORCH

5'-8"
DW

2X6

2050 FX DL TEMP
1SH
A90.01 3
COVERED
5'-1 1/2"

A90.01 6

2'-1"
FAMILY ROOM
SLAB EDGE

WRF CONCRETE

2068

6'-8" HDR
10'-11"

PATIO 9'-0" CLG CARPET 8'-0" CLG

W
2

SLAB EDGE
CONCRETE 9'-0" CLG

68
7'-0" HDR

8'-8"
3050 SH

TO ISLAND WALL
8'-0" CLG

30
2x6 LOW WALL

3'-3"
14'-11 1/2" 6'-7"
@ 34'-1/2" AFF
TO ISLAND WALL

9'-0" CLG
8'-0" CLG

VERSION 7
SLOPE
6'-2"
1 1/2"
CONCRETE 2" FOYER

4'-8"
3'-8"
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

SLOPE

5 1/2"
WRF
3068
5 1/2"

2'-0"
TYP

2'-7"
SLOPE TO 9'-0" 8'-0" CLG CONCRETE

Express Homes - North Central Texas


CLG @ 6:12 PITCH CPT WRF

SSE Architectural Design Services


3050 SH OPT BRICK 3050 SH 3050 SH
5 1/2"

SLAB EDGE SLAB EDGE

5 1/2"
7'-0" HDR 7'-0" HDR 7'-0" HDR 2'-0"
@ SIDES
6X6 POST (WRAP w/ MASONRY COLUMN
OPT FULL BRICK) 12'-5 1/2" 11'-7" 11'-9 1/2" 13'-10 1/2"

8'-9" 49'-8 1/2" 4'-9" 3'-7 1/2"

X30B A, B, F, G, M, N
5 1/2" 5 1/2" 5 1/2"
68'-8" 5 1/2"

BLOCK
1 ELEVATION B - FIRST FLOOR PLAN
1/8" = 1'-0"

ADDRESS
BUILDER
SUBD.

PLAN
CITY
LOT
DATE 12.07.2023
SCALE 1/8" = 1'-0"
12/8/2023 9:52:22 AM

A30.01
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ELECTRICAL LEGEND 10003 Technology Blvd. West
Dallas, TX. 75220

WPGFI
972-620-8204
WATERPROOF
GFCI DUPLEX

DUPLEX

GFI
GFCI DUPLEX

220v
220 VOLT DUPLEX

SPR
GFCI DUPLEX FOR SPRINKLER,
INSTALLED @ 84" AFF
PRE-WIRE FOR

HB
EXT WALL LIGHT
CEILING MOUNTED
CLG DUPLEX
WP

WH
EP

GFI
TV
TV OUTLET
SPRINKLER OUTLET
84" AFF
WP TELEPHONE OUTLET
ELECTERICAL PANEL
BLOCK & PRE WIRE EXHAUST FAN
GFI
FOR CLG FAN 3
THREE-WAY SWITCH

GFI
4

LIGHT & SWITCH


FOUR-WAY SWITCH

TV
PRE-WIRE FOR

GFI

ACCESS

IN ATTIC
ADDITIONAL FAN & GARAGE DOOR

ATTIC
SWITCH REQ'D W/ OPENER SINGLE SWITCH
OPT. 2468 DOOR
GFI

DB
SD SD/CO SD CLG DOOR BELL

SD G GARAGE DOOR OPENER

4'-5"
SD/CO SECURITY LIGHT FIXTURE
3'-2"

GFI

GFI

GFI
GFI-REF

GFI-MICRO/VENT
GFI-RANGE

GFI
HB CEILING MOUNTED
LIGHT FIXTURE

GFI-DISP
RECESSED CAN

GFI-DW
LIGHT FIXTURE
GFI

WPGFI
OPT. COVER PLATE, RECESSED CAN LIGHT
DISP
BLOCK & PRE-WIRE GFI EYEBALL FIXTURE

6'-0"
WPGFI FOR CLG FAN
GFI GFI 220v HANGING LIGHT
6'-0" 6'-1 1/2" 6'-0" 4'-6" FIXTURE

GFI
DB PENDANT LIGHT
6'-1"

7'-3 1/2"

VERSION 7
3'-6" FIXTURE
WALL MOUNTED
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

LIGHT FIXTURE

Express Homes - North Central Texas


TV
AP

SSE Architectural Design Services


CEILING FAN WITH LIGHT

CEILING FAN WITHOUT

X30B A, B, F, G, M, N
LIGHT

BLOCK
1x4 FLUORESCENT
1 ELEVATION B - FIRST FLOOR ELECTRICAL PLAN 1x4 FLUOR
LIGHT FIXTURE

1/8" = 1'-0" COVE LIGHT FIXTURE

UNDER-CABINET
LIGHT FIXTURE
EP ELECTRICAL PANEL

AP AUTOMATION PANEL

ADDRESS
BUILDER
SD SMOKE DETECTOR

SUBD.

PLAN
CITY
LOT
SMOKE & CARBON
SD/CO MONOXIDE DETECTOR

DENOTES WATERPROOF
WP
LIGHT FIXTURE

DENOTES PHOTOVOLTAIC
DATE 12.07.2023
P LIGHT FIXTURE
SCALE 1/8" = 1'-0"
12/8/2023 9:52:23 AM

A30.02
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 178 LF (10 NFA) = 1780 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2196 1055 422 527 0 NFA + 450 NFA = 450 NFA 605 1780 NFA + 0 NFA + 0 NFA = 1780 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

SOLDIER COURSE, TYP


1 2"
6" / 6" /
12" 1X6 FASCIA, TYP
8"-1 1/8" PL
EXT WALL LIGHT 6:12
COMPOSITION 1'-4 1/4" , TYP
1X4 FRIEZE TRIM, TYP 8 1/4" TYP
SHINGLE ROOF, TYP @ 6:12 PITCH
@ RAKE

6" / 12"

RAKE
BRICK, TYP
8'-1 1/8" PL

LAP SIDING, TYP 1X4 TRIM, TYP


5'-0"

(OPT. BRICK @ SIDES)


3'-0"

150 150

8"-1 1/8" PL

6" / 12"

RAKE
6" / 12"
2'-0"
STONE, TYP. BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES 6" / 12"
150

6" / 12"
ROOF VENT TYP. 8"-1 1/8" PL

4 ELEVATION B - RIGHT

8"-1 1/8" PL
1/16" = 1'-0"

8"-1 1/8" PL

1X6 FASCIA, TYP

1X4 FRIEZE TRIM, TYP

VERSION 7
6" /
" 12"
6" / 12 6:12 SOLDIER COURSE, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION 6:12
SHINGLE ROOF, TYP

Express Homes - North Central Texas


BRICK, TYP

5 ELEVATION B - ROOF PLAN

SSE Architectural Design Services


8'-1 1/8" PL

8'-1 1/8" PL
5'-0"
1/16" = 1'-0"
3'-0"

2'-0"

X30B A, B, F, G, M, N
6X6 POST, TYP. EXT WALL LIGHT
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES STONE, TYP

BLOCK
3 ELEVATION B - LEFT 6" /
12"
1X6 FASCIA TRIM, TYP
1/16" = 1'-0" 1 2"
6" /

T. O. FOUNDATION TO ROOF PEAK HEIGHT


1X4 FRIEZE TRIM, TYP
6:12 1 2" 6" /
COMPOSITION 6" / 12"
SOLDIER COURSE, TYP
SHINGLE ROOF, TYP

ADDRESS
15'-9" PL

BUILDER
6" /
1X6 FASCIA TRIM, TYP 12" EXT WALL LIGHT
2"

SUBD.
1 6:12
6" /

PLAN
CITY
1X4 FRIEZE TRIM, TYP COMPOSITION

LOT
BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


DATE 12.07.2023

5'-0"
3'-0"
STONE, TYP
SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP.
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) MASONRY SILL, TYP
12/8/2023 9:52:25 AM

2 ELEVATION B - REAR
1/16" = 1'-0"
1 ELEVATION B - FRONT
1/8" = 1'-0"
A30.03
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 42 LF (10 NFA) = 420 NFA 4 (56 NFA) = 224 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2196 1055 422 527 0 NFA + 450 NFA = 450 NFA 605 420 NFA + 224 NFA + 0 NFA = 644 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
SOLDIER COURSE, TYP 2" A100.02 A100.02
1
6" / 6" /
12" 1X6 FASCIA, TYP 8"-1 1/8" PL
EXT WALL LIGHT 6:12
COMPOSITION 1'-4 1/4" , TYP
1X4 FRIEZE TRIM, TYP 8 1/4" TYP
SHINGLE ROOF, TYP @ 6:12 PITCH
@ RAKE

6" / 12"

RAKE
BRICK, TYP
8'-1 1/8" PL

LAP SIDING, TYP 1X4 TRIM, TYP


5'-0"

(OPT. BRICK @ SIDES)


3'-0"

150 150

8"-1 1/8" PL

6" / 12"

RAKE
2'-0" 6" / 12"
STONE, TYP. BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES 6" / 12"
150 56

ELEVATION B - RIGHT w/ FIRE RATED SOFFITS @ 56

6" / 12"
ROOF VENT TYP. 8"-1 1/8" PL
5 SIDES 56

8"-1 1/8" PL
1/16" = 1'-0" 56

8"-1 1/8" PL 2 1
A100.02 A100.02

1X6 FASCIA, TYP

1X4 FRIEZE TRIM, TYP FIRE RATED SOFFIT/ BLOCKING WHEN


6" / EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
" 12" LINE (REF PLOT PLAN)

VERSION 7
6" / 12 6:12 SOLDIER COURSE, TYP
COMPOSITION 6:12
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

SHINGLE ROOF, TYP


BRICK, TYP
ELEVATION B - ROOF PLAN w/ FIRE RATED SOFFITS @

Express Homes - North Central Texas


3 SIDES

SSE Architectural Design Services


8'-1 1/8" PL

8'-1 1/8" PL
1/16" = 1'-0"
5'-0"
3'-0"

6X6 POST, TYP. 2'-0" EXT WALL LIGHT

X30B A, B, F, G, M, N
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES STONE, TYP

BLOCK
4 ELEVATION B - LEFT w/ FIRE RATED SOFFITS @ SIDES 6" /
12"
1/16" = 1'-0" 1X6 FASCIA TRIM, TYP
1 2"
6" /

T. O. FOUNDATION TO ROOF PEAK HEIGHT


1X4 FRIEZE TRIM, TYP
6:12 1 2" 6" /
COMPOSITION 6" / 12"
SOLDIER COURSE, TYP
SHINGLE ROOF, TYP

ADDRESS
15'-9" PL

BUILDER
6" /
1X6 FASCIA TRIM, TYP

SUBD.
12" EXT WALL LIGHT
2"

PLAN
1 6:12

CITY
6" /

LOT
1X4 FRIEZE TRIM, TYP COMPOSITION BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


DATE 12.07.2023

5'-0"
3'-0"
STONE, TYP SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP. MASONRY SILL, TYP
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK)
12/8/2023 9:52:27 AM

ELEVATION B - FRONT w/ FIRE RATED SOFFITS @


2 ELEVATION B - REAR w/ FIRE RATED SOFFITS @ SIDES 1 SIDES A30.04
1/16" = 1'-0" 1/8" = 1'-0"
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (5 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 42 LF (5 NFA) = 210 NFA 8 (56 NFA) = 448 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2196 1055 422 527 0 NFA + 450 NFA = 450 NFA 605 210 NFA + 448 NFA + 0 NFA = 658 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
SOLDIER COURSE, TYP A100.02 A100.02
12"
6" / 6" /
12" 1X6 FASCIA, TYP
8"-1 1/8" PL
EXT WALL LIGHT 6:12
COMPOSITION 1'-4 1/4" , TYP
1X4 FRIEZE TRIM, TYP 8 1/4" TYP
SHINGLE ROOF, TYP @ 6:12 PITCH
@ RAKE

6" / 12"

RAKE
BRICK, TYP
8'-1 1/8" PL

LAP SIDING, TYP 1X4 TRIM, TYP


5'-0"

(OPT. BRICK @ SIDES)


3'-0"

150 150

8"-1 1/8" PL

6" / 12"

RAKE
6" / 12"
2'-0"
STONE, TYP. BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES 6" / 12"
150 56
56 56
ELEVATION B - RIGHT w/ FIRE RATED SOFFITS @

6" / 12"
LOCATE (1) SOFFIT ROOF VENT TYP. 56 8"-1 1/8" PL
56 VENT @ INTERIOR
4 SIDES w/ 5 NFA LOWER VENTILATION OF PATIO

8"-1 1/8" PL
56
56
56
1/16" = 1'-0"

8"-1 1/8" PL 2 1
A100.02 A100.02

1X6 FASCIA, TYP


FIRE RATED SOFFIT/ BLOCKING WHEN
1X4 FRIEZE TRIM, TYP EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
LINE (REF PLOT PLAN)

VERSION 7
6" /
1 2" 12"
6:12
6" / SOLDIER COURSE, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION
SHINGLE ROOF, TYP
6:12
ELEVATION B - ROOF PLAN w/ FIRE RATED SOFFITS @

Express Homes - North Central Texas


BRICK, TYP
5 SIDES w/ 5 NFA LOWER VENTILATION

SSE Architectural Design Services


8'-1 1/8" PL

8'-1 1/8" PL
5'-0" 1/16" = 1'-0"
3'-0"

2'-0"

X30B A, B, F, G, M, N
6X6 POST, TYP. EXT WALL LIGHT
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES STONE, TYP

BLOCK
ELEVATION B - LEFT w/ FIRE RATED SOFFITS @ SIDES
3 w/ 5 NFA LOWER VENTILATION 6" /
12"
1X6 FASCIA TRIM, TYP
1/16" = 1'-0" 1 2"
6" /

T. O. FOUNDATION TO ROOF PEAK HEIGHT


1X4 FRIEZE TRIM, TYP
6:12 1 2" 6" /
COMPOSITION 6" / 12"
SOLDIER COURSE, TYP
SHINGLE ROOF, TYP

ADDRESS
15'-9" PL

BUILDER
6" /
1X6 FASCIA TRIM, TYP 12"
2" EXT WALL LIGHT

SUBD.
1 6:12
6" /

PLAN
CITY
1X4 FRIEZE TRIM, TYP COMPOSITION

LOT
BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


DATE 12.07.2023

5'-0"
3'-0"
STONE, TYP
SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP.
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) MASONRY SILL, TYP
12/8/2023 9:52:29 AM

ELEVATION B - REAR w/ FIRE RATED SOFFITS @ SIDES ELEVATION B - FRONT w/ FIRE RATED SOFFITS @
2 w/ 5 NFA LOWER VENTILATION
1/16" = 1'-0"
1 SIDES w/ 5 NFA LOWER VENTILATION
1/8" = 1'-0"
A30.05
STRAND 2351667
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

70'-2 1/2"

5 1/2" 1'-6 1/2" 5 1/2"


67'-9"

9'-6" 11'-4 1/2" 10'-1" 9" 5'-3 1/2" 10'-4 1/2" 20'-4 1/2"
OPT FULL
BRICK OPT BRICK @ FRONT 1
3'-9" 3'-7" 4'-0 1/2" 2'-2 1/2" 7'-10 1/2" 7'-8 1/2" 2'-8" A40.06
*FOR DRHE PLANS ONLY
30"x30"x18" WATER HEATER
BATH 1
5 1/2"
OPT BRICK PLATFORM w/ 2x4 WING WALL 2'-0"
WRF 3050 SH 3050 SH 3050 SH 3050 SH (NOT REQUIRED w/ TANKLESS
@ SIDES

HB
8'-0'' CLG 7'-0" HDR 7'-0" HDR 7'-0" HDR 7'-0" HDR WH)

2'-10 1/2"
2'-9 1/2"

5 1/2"
WH
60" x 30"

3'-2"
2668

OPT 4010 FX

SHOWER
TUB

1'-1 1/2"
5'-3 1/2"

36" x 60"
7'-0" HDR
OPT SINK 2x4 WALL w/ WH
SLOPE TO 9'-0" BEDROOM 3 BATH 2
2'-6"

2'-6 1/2"
CLG @ 6:12 PITCH

9'-0"

9'-3"
CARPET WRF
BEDROOM 2

2'-4" x 6'-10" HDR


8'-0" CLG 8'-0" CLG SLOPE
CARPET

2X6
8'-0" CLG
CONCRETE 2"

7'-0"

8'-9 1/2"
OPT 2468 DOOR 5 A90.01

16070 GARAGE DOOR


A90.01 4

TIRE STOP
BEDROOM 1 CLOSET
6'-4 1/2"

CARPET CARPET

16'-3" R.O.
WC CLOSET

ACCESS
17'-8"

2868
9'-0'' CLG 8'-0" CLG

18'-3"
ATTIC
WRF CARPET
8'-0'' CLG 2'-4" x 6'-10" HDR WIC 8'-0" CLG GARAGE

5SH
3 1/2" CONCRETE
CARPET
8'-0" CLG

3'-10 1/2"
8'-0'' CLG

20
68
VEST

68
20
2X6 PANTRY

2'-4 1/2"
26
2'-8 1/2"

68
CARPET

2668
8'-4 1/2"

3'-8"

68

26
WRF 8'-0" CLG
8'-0" CLG 1R1S 1R1S

9'-0"
29'-11 1/2"

29'-11 1/2"
1R1S 8'-0" CLG
1R1S
6'-0"

5SH 7'-10 1/2" 3'-11 1/2" 8'-10"


3'-8" 5'-6 1/2" 9'-0" CLG

1'-7 1/2"
8'-0'' CLG

4'-8"
REF
1R1S UTILITY COAT

20

1'-10 1/2"
9'-0'' CLG KITCHEN

68
HB WRF WRF
WRF WRF CPT 1'-10 1/2"
TEMP

9"
2'-1 1/2"

8'-0" CLG 8'-0" CLG


9'-0" CLG 4 1/2"
2868 4'-4" 2'-11" 6'-4" 4'-0 1/2" 3'-6" 4'-0 1/2" 6'-4" 9"

2'-1" 2'-1 1/2"


30
1 1R1S
1 1/2"

68
4'-1 1/2"

1'-10 1/4"
3'-6 1/2"
DINING PORCH

5'-8"
DW

2X6
1SH

6'-11 3/4" x 8'-0" HDR


A90.01 3
COVERED
5'-1 1/2"

A90.01 6

2050 FX TEMP
FAMILY ROOM CONCRETE
SLAB EDGE

WRF

2068

7'-0" HDR

SLAB EDGE
10'-11"

PATIO 9'-0" CLG CARPET 8'-0" CLG

W
2

VERSION 7
7'-1"
CONCRETE 9'-0" CLG

68
7'-0" HDR
3050 SH

TO ISLAND WALL
8'-0" CLG

30
2x6 LOW WALL
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

3'-3"
14'-11 1/2" 6'-7"

3'-6 1/2"
@ 34'-1/2" AFF SLOPE

1'-10 1/4"
TO ISLAND WALL

9'-0" CLG
8'-0" CLG

Express Homes - North Central Texas


SLOPE

6'-2"
CONCRETE
CONCRETE 2" FOYER

4'-8"
3'-8"

WRF
3068
5 1/2"

2'-0"
TYP

2'-7"
SLOPE TO 9'-0" 8'-0" CLG
CPT WRF 6'-11 3/4" x 8'-0" HDR
CLG @ 6:12 PITCH TEMP

3050 SH OPT BRICK 3050 SH 3050 SH SLAB EDGE


5 1/2"

SLAB EDGE

5 1/2"
7'-0" HDR 7'-0" HDR 7'-0" HDR
@ SIDES
6X6 POST (WRAP w/ 1'-6 1/2"

X30B A, B, F, G, M, N
OPT FULL BRICK) 12'-5 1/2" 11'-7" 11'-9 1/2" 13'-10 1/2" 3'-6 1/2" 3'-6 1/2"

8'-9" 49'-8 1/2" 1'-6" 7'-1" 2'-3"

BLOCK
5 1/2" 5 1/2"
70'-2 1/2"

1 ELEVATION F - FIRST FLOOR PLAN


1/8" = 1'-0"

ADDRESS
BUILDER
SUBD.

PLAN
CITY
LOT
DATE 12.07.2023
SCALE 1/8" = 1'-0"
DR'N
12/8/2023 9:52:30 AM

A40.01
STRAND 2351667
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204
ELECTRICAL LEGEND

WPGFI
WATERPROOF
GFCI DUPLEX

DUPLEX

GFI
GFCI DUPLEX

220v
220 VOLT DUPLEX

SPR
GFCI DUPLEX FOR SPRINKLER,
INSTALLED @ 84" AFF

CEILING MOUNTED
CLG DUPLEX
TV
TV OUTLET

HB
TELEPHONE OUTLET

EXHAUST FAN
WP

WH
EP 3

GFI
THREE-WAY SWITCH
SPRINKLER OUTLET
84" AFF 4
WP FOUR-WAY SWITCH
ELECTERICAL PANEL
BLOCK & PRE WIRE GFI SINGLE SWITCH
FOR CLG FAN

DB
DOOR BELL
GFI

LIGHT & SWITCH


TV

PRE-WIRE FOR

GFI

ACCESS

IN ATTIC
ADDITIONAL FAN & GARAGE DOOR

ATTIC
SWITCH REQ'D W/ OPENER
G GARAGE DOOR OPENER
OPT. 2468 DOOR
GFI SECURITY LIGHT FIXTURE
SD SD/CO SD CLG
CEILING MOUNTED
SD LIGHT FIXTURE

RECESSED CAN
4'-5" LIGHT FIXTURE
SD/CO
3'-2"

GFI

GFI

GFI
GFI-REF

GFI-RANGE

GFI-MICRO/VENT

G
RECESSED CAN LIGHT

GFI
HB EYEBALL FIXTURE

VERSION 7
GFI-DISP HANGING LIGHT
FIXTURE
GFI-DW
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

WPGFI
GFI PENDANT LIGHT

Express Homes - North Central Texas


OPT. COVER PLATE, FIXTURE
DISP
BLOCK & PRE-WIRE GFI
6'-0"

WPGFI FOR CLG FAN WALL MOUNTED


GFI GFI 220v LIGHT FIXTURE
6'-0" 6'-1 1/2" 6'-0" 4'-6"
GFI

DB
2'-0"
6'-1"

7'-3 1/2" CEILING FAN WITH LIGHT

X30B A, B, F, G, M, N
3'-6"

2'-0"
TV
AP
PRE-WIRE FOR

BLOCK
EXT WALL LIGHT, TYP CEILING FAN WITHOUT
LIGHT

1x4 FLUOR 1x4 FLUORESCENT


LIGHT FIXTURE

COVE LIGHT FIXTURE


1 ELEVATION F - FIRST FLOOR ELECTRICAL PLAN UNDER-CABINET
LIGHT FIXTURE
1/8" = 1'-0"

ADDRESS
EP ELECTRICAL PANEL

BUILDER
SUBD.

PLAN
AP

CITY
AUTOMATION PANEL

LOT
SD SMOKE DETECTOR

SMOKE & CARBON


SD/CO MONOXIDE DETECTOR DATE 12.07.2023
WP
DENOTES WATERPROOF
LIGHT FIXTURE
SCALE 1/8" = 1'-0"
DENOTES PHOTOVOLTAIC DR'N
P LIGHT FIXTURE
12/8/2023 9:52:31 AM

A40.02
STRAND 2351667
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (LOCATION)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA) 10003 Technology Blvd. West
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 160 LF (10 NFA) = 1600 NFA 3 (56 NFA) = 168 NFA 0 (28 NFA) = 0 NFA Dallas, TX. 75220
2242 1077 431 538 0 NFA + 450 NFA = 450 NFA 627 1600 NFA + 168 NFA + 0 NFA = 1768 NFA 972-620-8204

NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

2 OPT BRICK @ FRONT


A40.06 2"
" /1
" 10
3" / 1 2 10
" /1
BOARD & BATTEN SIDING, TYP 2" 6" /
12" 1X6 FASCIA, TYP
6:12
EXT WALL LIGHT 10:12 LAP SIDING, TYP COMPOSITION
SHINGLE ROOF, TYP 1X4 FRIEZE TRIM, TYP 8"-1 1/8" PL
RAKE RAKE
14'-0" PL

5 1/2"
10'-7 1/8"

8'-1 1/8" PL

1X4 TRIM, TYP


5 1/2" LAP SIDING, TYP
RAKE
6'-0"

(OPT BRICK @ SIDES)


10" / 12"

6" / 12"
1'-4 1/4" TYP

8"-1 1/8" PL
@ 6:12 PITCH 3" / 12"
(FUR OUT WALL 1'-6 1/2" BOX OUT HDR, TYP 1x6 TRIM 150 150

8"-1 1/8" PL
5 1/2" w/ OPT BRICK @ w/ OPT BRICK @ SIDES 9 7/8" TYP
SIDES & OPT FULL BRICK) @ 10:12 PITCH
6" / 12" RAKE
10" / 12" 10"-7 1/8" PL
150
4 ELEVATION F - RIGHT

10" / 12"

RAKE
6" / 12"
ROOF VENT,
VENT TYP.
TYP
1/16" = 1'-0"
8 1/4" TYP
@ RAKE

10" / 12"

RAKE
10
(FUR OUT WALL " /1 1X6 FASCIA, TYP
2" 8"-1 1/8" PL RAKE RAKE 10"-7 1/8" PL
5 1/2" w/ OPT BRICK @ 3" / 12
"
SIDES & OPT FULL BRICK) / 12 " 1X4 FRIEZE TRIM, TYP
"
10
1 2" OPT BRICK @ FRONT
6" / 10:12 2
6:12
COMPOSITION SHINGLE LAP SIDING, TYP A40.06 5 ELEVATION F - ROOF PLAN

VERSION 7
ROOF, TYP
1x4 TRIM, TYP 1/16" = 1'-0"
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

10'-7 1/8" PL
5 1/2"

Express Homes - North Central Texas


8'-1 1/8" PL
LAP SIDING, TYP 5 1/2"

6'-0"
(OPT FULL BRICK)

6X6 POST, TYP LAP SIDING, TYP EXT WALL LIGHT


(WRAP w/ OPT (OPT BRICK @ SIDES) 29'-3 1/2"
FULL BRICK) BOARD AND BATTEN SIDING, TYP

X30B A, B, F, G, M, N
BLOCK
3 ELEVATION F - LEFT 3020 FX
13'-0" HDR
3020 FX
13'-0" HDR
OPT BRICK @ FRONT 2
A50.06

1/16" = 1'-0"

2" 10 10:12 3:12


/1 "

T.O. FOUNDATION TO ROOF PEAK HEIGHT


" /1 COMPOSITION
CB-23 BRACKET 10 2"
REF 3 / A90.03 SHINGLE ROOF, TYP

ADDRESS
BUILDER
10:12 1X6 FASCIA TRIM, TYP

SUBD.
BOARD & BATTEN

PLAN
CITY
19'-3"
6" /

LOT
SIDING, TYP
1X6 FASCIA TRIM, TYP 12" 12" 1X4 FRIEZE TRIM, TYP
6" / 6:12
1X4 FRIEZE TRIM, TYP COMPOSITION

14'-0" PL
SHINGLE ROOF, TYP 1x4 TRIM, TYP
DATE 12.07.2023

10'-7 1/8" PL
8'-1 1/8" PL

8'-1 1/8" PL
1X4 TRIM, TYP LAP SIDING, TYP SCALE As indicated
(OPT FULL BRICK)
DR'N
6'-0"
12/8/2023 9:52:33 AM

6X6 POST, TYP


(WRAP w/ OPT FULL BRICK)

2 ELEVATION F - REAR
1/16" = 1'-0"
EXT WALL LIGHT, TYP

1 ELEVATION F - FRONT
BOARD AND BATTEN SIDING, TYP
A40.03
STRAND 2351667
1/8" = 1'-0"
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (LOCATION)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 51 LF (10 NFA) = 510 NFA 3 (56 NFA) = 168 NFA 0 (28 NFA) = 0 NFA
2242 1077 431 538 0 NFA + 450 NFA = 450 NFA 627 510 NFA + 168 NFA + 0 NFA = 678 NFA 10003 Technology Blvd. West
Dallas, TX. 75220
NOTES:
972-620-8204
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

2 OPT BRICK @ FRONT


A40.06 2"
" /1
" 10
3" / 1 2 10
" /1
BOARD & BATTEN SIDING, TYP 2" 6" /
12" 1X6 FASCIA, TYP
6:12
EXT WALL LIGHT 10:12 LAP SIDING, TYP COMPOSITION FIRE RATED SOFFIT/BLOCKING WHEN
1X4 FRIEZE TRIM, TYP EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY
SHINGLE ROOF, TYP
HATCH INDICATES WHERE
LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
14'-0" PL

NOT ALLOWED
5 1/2"

2
10'-7 1/8"

8'-1 1/8" PL

1X4 TRIM, TYP


5 1/2" 8"-1 1/8" PL A100.02
LAP SIDING, TYP RAKE RAKE
6'-0"

(OPT BRICK @ SIDES)

4"
(FUR OUT WALL 1'-6 1/2" BOX OUT HDR, TYP 1x6 TRIM 10" / 12" RAKE
1'-0"
5 1/2" w/ OPT BRICK @ w/ OPT BRICK @ SIDES

6" / 12"
1'-4 1/4" TYP

8"-1 1/8" PL
SIDES & OPT FULL BRICK)
@ 6:12 PITCH 3" / 12"

150 150

8"-1 1/8" PL
9 7/8" TYP
ELEVATION F - RIGHT w/ FIRE RATED SOFFITS @ 6" / 12"
10" / 12"
RAKE
@ 10:12 PITCH

4 SIDES 150
10"-7 1/8" PL

10" / 12" 10" / 12"


56

6" / 12"
1/16" = 1'-0"

RAKE
ROOF VENT,
VENT TYP.
TYP
56 8 1/4" TYP
@ RAKE

RAKE
10
(FUR OUT WALL " /1 1X6 FASCIA, TYP 56
2"
5 1/2" w/ OPT BRICK @ 3" / 12
"
SIDES & OPT FULL BRICK) / 12 " 1X4 FRIEZE TRIM, TYP
" 8"-1 1/8" PL RAKE RAKE 10"-7 1/8" PL
10
1 2" OPT BRICK @ FRONT
6" / 6:12 10:12 2 FIRE RATED SOFFIT/BLOCKING WHEN
COMPOSITION SHINGLE LAP SIDING, TYP A100.02 EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY

VERSION 7
ROOF, TYP 2 LINE (REF PLOT PLAN)
1x4 TRIM, TYP A40.06
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

10'-7 1/8" PL
ELEVATION F - ROOF PLAN w/ FIRE RATED SOFFITS @
5 1/2"

8'-1 1/8" PL

Express Homes - North Central Texas


LAP SIDING, TYP 5 1/2"
5 SIDES

6'-0"
(OPT FULL BRICK)

1/16" = 1'-0"
6X6 POST, TYP LAP SIDING, TYP EXT WALL LIGHT
(WRAP w/ OPT (OPT BRICK @ SIDES) 29'-3 1/2"
FULL BRICK) 3020 FX 3020 FX OPT BRICK @ FRONT 2
BOARD AND BATTEN SIDING, TYP A50.06

X30B A, B, F, G, M, N
13'-0" HDR 13'-0" HDR

BLOCK
3 ELEVATION F - LEFT w/ FIRE RATED SOFFITS @ SIDES
1/16" = 1'-0" 2" 10 10:12 3:12
/1 "

T.O. FOUNDATION TO ROOF PEAK HEIGHT


" /1 COMPOSITION
CB-23 BRACKET 10 2"
REF 3 / A90.03 SHINGLE ROOF, TYP

1X6 FASCIA TRIM, TYP


BOARD & BATTEN

19'-3"
SIDING, TYP

ADDRESS
10:12 1X4 FRIEZE TRIM, TYP

BUILDER
6" /
2"

14'-0" PL

SUBD.
1X6 FASCIA TRIM, TYP 1 12"
6" /

PLAN
1x4 TRIM, TYP

CITY
6:12

LOT
10'-7 1/8" PL
1X4 FRIEZE TRIM, TYP COMPOSITION
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

DATE 12.07.2023
6'-0"

1X4 TRIM, TYP LAP SIDING, TYP


(OPT FULL BRICK)
SCALE As indicated
DR'N
6X6 POST, TYP
(WRAP w/ OPT FULL BRICK) BOARD AND BATTEN SIDING, TYP
12/8/2023 9:52:35 AM

EXT WALL LIGHT, TYP

2 ELEVATION F - REAR w/ FIRE RATED SOFFITS @ SIDES


1/16" = 1'-0"
1 ELEVATION F - FRONT w/ FIRE RATE SOFFITS @ SIDES
1/8" = 1'-0"
A40.04
STRAND 2351667
ATTIC AREA @ (LOCATION)

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (5 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 1 (65 NFA) = 65 NFA 3 (150 NFA) = 450 NFA MINIMUM 51 LF (5 NFA) = 255 NFA 6 (56 NFA) = 336 NFA 0 (28 NFA) = 0 NFA
2242 1077 431 538 65 NFA + 450 NFA = 515 NFA 562 255 NFA + 336 NFA + 0 NFA = 591 NFA
10003 Technology Blvd. West
NOTES: Dallas, TX. 75220
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
972-620-8204
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

2 OPT BRICK @ FRONT


A40.06 2"
" /1
" 10
3" / 1 2 10
" /1
BOARD & BATTEN SIDING, TYP 2" 6" /
12" 1X6 FASCIA, TYP
6:12
10:12 FIRE RATED SOFFIT/BLOCKING WHEN
EXT WALL LIGHT LAP SIDING, TYP COMPOSITION
1X4 FRIEZE TRIM, TYP EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY
SHINGLE ROOF, TYP HATCH INDICATES WHERE
LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
2
14'-0" PL

NOT ALLOWED
5 1/2"

A100.02
10'-7 1/8"

8'-1 1/8" PL

1X4 TRIM, TYP 8"-1 1/8" PL


5 1/2" LAP SIDING, TYP RAKE RAKE
6'-0"

(OPT BRICK @ SIDES)


1'-4 1/4" TYP
@ 6:12 PITCH 56

4"
RAKE 1'-0"
(FUR OUT WALL 1'-6 1/2" BOX OUT HDR, TYP 1x6 TRIM 10" / 12"
5 1/2" w/ OPT BRICK @ w/ OPT BRICK @ SIDES 56

8"-1 1/8" PL
6" / 12"

14'-0" PL
SIDES & OPT FULL BRICK)

150 150

8"-1 1/8" PL
ELEVATION F - RIGHT w/ FIRE RATED SOFFITS @ SIDES w/ 5 NFA 6" / 12"
10" / 12"
RAKE
56 9 7/8" TYP
@ 10:12 PITCH
4 LOWER VENTILATION 150
10"-7 1/8" PL

6" / 12"
56

10" / 12" 10" / 12"


1/16" = 1'-0"

RAKE
ROOF VENT,
VENT TYP.
TYP
8 1/4" TYP
56 @ RAKE

RAKE
10
(FUR OUT WALL " /1 1X6 FASCIA, TYP 56
2"
5 1/2" w/ OPT BRICK @ 3" / 12
"
SIDES & OPT FULL BRICK) / 12 " 1X4 FRIEZE TRIM, TYP
" 8"-1 1/8" PL RAKE RAKE 10"-7 1/8" PL
10
1 2" OPT BRICK @ FRONT 2
6" / 6:12 10:12 2 FIRE RATED SOFFIT/BLOCKING WHEN
A40.06
COMPOSITION SHINGLE LAP SIDING, TYP A100.02 EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY
ROOF, TYP LINE (REF PLOT PLAN)
1x4 TRIM, TYP
ELEVATION F - ROOF PLAN w/ FIRE RATED SOFFITS @ SIDES w/ 5

VERSION 7
10'-7 1/8" PL
5 1/2"

8'-1 1/8" PL
5 NFA LOWER VENTILATION
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

LAP SIDING, TYP 5 1/2"

6'-0"
(OPT FULL BRICK)

Express Homes - North Central Texas


1/16" = 1'-0"

6X6 POST, TYP LAP SIDING, TYP EXT WALL LIGHT


(WRAP w/ OPT (OPT BRICK @ SIDES) 29'-3 1/2"
FULL BRICK) BOARD AND BATTEN SIDING, TYP

OPT BRICK @ FRONT

X30B A, B, F, G, M, N
ELEVATION F - LEFT w/ FIRE RATED SOFFITS @ SIDES w/ 5 NFA 3020 FX
13'-0" HDR
3020 FX
13'-0" HDR A50.06
2

3 LOWER VENTILATION

BLOCK
1/16" = 1'-0"

2" 10 10:12 3:12


/1 "

T.O. FOUNDATION TO ROOF PEAK HEIGHT


" /1 COMPOSITION
CB-23 BRACKET 10 2"
REF 3 / A90.03 SHINGLE ROOF, TYP

10:12 1X6 FASCIA TRIM, TYP


BOARD & BATTEN

ADDRESS
19'-3"
6" / SIDING, TYP

BUILDER
1X6 FASCIA TRIM, TYP 1 2" 12" 1X4 FRIEZE TRIM, TYP
6" / 6:12

SUBD.
1X4 FRIEZE TRIM, TYP

PLAN
COMPOSITION

14'-0" PL

CITY
LOT
SHINGLE ROOF, TYP 1x4 TRIM, TYP

10'-7 1/8" PL
8'-1 1/8" PL

8'-1 1/8" PL
1X4 TRIM, TYP LAP SIDING, TYP
(OPT FULL BRICK) DATE 12.07.2023
6'-0"

SCALE As indicated
6X6 POST, TYP
(WRAP w/ OPT FULL BRICK)
DR'N
12/8/2023 9:52:37 AM

EXT WALL LIGHT, TYP BOARD AND BATTEN SIDING, TYP

2
ELEVATION F - REAR w/ FIRE RATED SOFFIT @ SIDES
w/ 5 NFA LOWER VENTILATION
ELEVATION F - FRONT - w/ FIRE RATED SOFFITS @ SIDES w/ 5 NFA
1 LOWER VENTILATION
A40.05
1/16" = 1'-0" 1/8" = 1'-0" STRAND 2351667
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10
10003 Technology Blvd. West
2" " Dallas, TX. 75220
" /1 /1
2" 12
" 10
"
10 "/ /1
10 2" 972-620-8204
" 3" / 12
BOARD & BATTEN SIDING, TYP 3" / 1 2 "

1X6 FASCIA, TYP


10:12 6:12 6:12 10:12
LAP SIDING, TYP 1X4 FRIEZE TRIM, TYP

BRICK, TYP
14'-0" PL

5 1/2"
EXT WALL LIGHT
10'-7 1/8" PL

10'-7 1/8" PL
8'-1 1/8" PL

8'-1 1/8" PL
LAP SIDING, TYP BRICK, TYP
LAP SIDING, TYP (OPT BRICK @
6'-0"

6'-0"
(OPT BRICK @ SIDES) SIDES)

BRICK ROWLOCK
HEADER, TYP

EXT WALL LIGHT BRICK SOLDER HEADER, TYP


2'-0"
BRICK ROWLOCK CAP, TYP BRICK SILL, TYP
1X4 TRIM, TYP
(FUR OUT WALL 20'-0"
5 1/2" w/ OPT BRICK @
SIDES & OPT FULL BRICK)

ELEVATION F - RIGHT w/ OPT ELEVATION F - LEFT w/ OPT


4 BRICK @ FRONT 3 BRICK @ FRONT 70'-8" OVERALL

1/8" = 1'-0" 1/8" = 1'-0" 1'-6 1/2" 5 1/2"


20'-4 1/2"

30'X3-'X18" WATER HEATER


PLATFORM w/ 2X4 WING WALL
(NOT REQUIRED w/ TANKLESS WH)

HB
WH

5 1/2"
1'-1 1/2"
2X4 WALL w/ WH
SLOPE

9'-3"
CONCRETE 2"
BEDROOM 2

VERSION 7
CARPET

8'-9 1/2"

16070 GARAGE DOOR


TIRE STOP
8'-0" CLG
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

16'-3" R.O.
ACCESS

Express Homes - North Central Texas


18'-8 1/2"
ATTIC
GARAGE
CONCRETE
3 1/2" 8'-0" CLG

20
68
3020 FX 3020 FX

2'-4 1/2"
68
13'-0" HDR 13'-0" HDR 3'-8"

26

9'-5 1/2"
1R1S

29'-11 1/2"
7'-7" 3'-11 1/2" 8'-10"

X30B A, B, F, G, M, N
10:12

1'-7 1/2"
COMPOSITION

4'-8"
UTILITY

BLOCK
SHINGLE ROOF, TYP
2" 10 WRF
" 3:12
/1 /1

T.O. FOUNDATION TO ROOF PEAK HEIGHT


" 2" 8'-0" CLG
CB-23 BRACKET 10
REF 8 / A90.02

2'-1" 2'-1 1/2"


30
1R1S

68

1'-2 1/2"
D
1X6 FASCIA TRIM, TYP
FAMILY ROOM PORCH

5'-8"

1SH
A90.01

2050 FX TEMP
CARPET
6
CONCRETE

2068

7'-0" x 8'-0" HDR


7'-0" HDR
19'-3"
BRICK ROWLOCK HEADER, TYP 9'-0" CLG 8'-0" CLG

W
1X4 FRIEZE TRIM, TYP

SLAB EDGE

7'-11"

10'-4"
68
30

3'-3"
14'-0" PL

ADDRESS
1x4 TRIM, TYP

9'-0" CLG
8'-0" CLG

BUILDER
1'-2 1/2"
10'-7 1/8" PL

EXT WALL LIGHT, TYP FOYER SLOPE

SUBD.
WRF CONCRETE
3068

PLAN
8'-1 1/8" PL

5 1/2"
2'-7"

CITY
8'-0" CLG

LOT
CPT WRF
TEMP
7'-0" x 8'-0" HDR
6'-0"

5'-0"

3050 SH SLAB EDGE


7'-0" HDR 20'-0"
BOARD & BATTEN SIDING, TYP DATE 12.07.2023
13'-8 1/2"

1'-1" 7'-11"
SCALE 1/8" = 1'-0"
5 1/2" DR'N
1'-4 1/2"
12/8/2023 9:52:38 AM

ELEVATION F - FRONT w/ OPT ELEVATION F - FIRST FLOOR


2 BRICK @ FRONT 1 PLAN - OPT BRICK @ FRONT
1/8" = 1'-0" 1/8" = 1'-0" A40.06
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

68'-2 1/2"

5 1/2" 67'-9"

9'-6" 11'-4 1/2" 10'-1" 9" 5'-3 1/2" 10'-4 1/2" 20'-4 1/2"
OPT FULL
BRICK OPT BRICK @ FRONT 1
3'-9" 3'-7" 4'-0 1/2" 2'-2 1/2" 7'-10 1/2" 7'-8 1/2" 2'-8" A50.06
*FOR DRHE PLANS ONLY 1'-6 1/2"
30"x30"x18" WATER HEATER OPT BRICK @ FRONT
BATH 1
5 1/2"
OPT BRICK PLATFORM w/ 2x4 WING WALL

5 1/2"
WRF 3050 SH 3050 SH 3050 SH 3050 SH (NOT REQUIRED w/ TANKLESS
@ SIDES

HB
8'-0'' CLG 7'-0" HDR 7'-0" HDR 7'-0" HDR 7'-0" HDR WH)

2'-10 1/2"
2'-9 1/2"

WH
60" x 30"

3'-2"
2668

OPT 4010 FX

SHOWER
TUB
5'-3 1/2"

36" x 60"
7'-0" HDR

1'-4 1/2"
OPT SINK 2x4 WALL w/ WH
SLOPE TO 9'-0" BEDROOM 3 BATH 2
2'-6"
2'-6 1/2"

9'-0"
CLG @ 6:12 PITCH CARPET

9'-6"
WRF
BEDROOM 2

2'-4" x 6'-10" HDR


8'-0" CLG 8'-0" CLG SLOPE
CARPET

2X6
8'-0" CLG
CONCRETE 2"

7'-0"

8'-9 1/2"
OPT 2468 DOOR A90.01 5 A90.01
4

16070 GARAGE DOOR


TIRE STOP
BEDROOM 1 CLOSET
6'-4 1/2"

CARPET CARPET
CLOSET

ACCESS
WC
17'-8"

2868

16'-3" R.O.
9'-0'' CLG 8'-0" CLG

ATTIC

19'-0"
WRF CARPET
8'-0'' CLG 2'-4" x 6'-10" HDR WIC 8'-0" CLG GARAGE

5SH
3 1/2" CONCRETE
CARPET
8'-0" CLG

3'-10 1/2"
8'-0'' CLG

20
68
VEST

68
20
2X6 PANTRY

2'-4 1/2"
26
2'-8 1/2"

68
CARPET

2668
8'-4 1/2"
3'-8"

68

26
WRF 8'-0" CLG
8'-0" CLG 1R1S 1R1S
29'-11 1/2"

29'-11 1/2"
8'-0" CLG

1R1S

9'-6"
1R1S
6'-0"

5SH 7'-10 1/2" 3'-11 1/2" 8'-9 5/8"


3'-8" 5'-6 1/2" 9'-0" CLG
8'-0'' CLG

1'-4 1/2"
4'-8"
REF
1R1S UTILITY COAT

20

1'-10 1/2"
9'-0'' CLG KITCHEN

68
HB

6 1/2"
WRF WRF
WRF WRF CPT 1'-10 1/2"
TEMP
2'-1 1/2"

8'-0" CLG 8'-0" CLG


9'-0" CLG 4 1/2"
2868 4'-4" 2'-11" 6'-4" 4'-0 1/2" 3'-6" 4'-0 1/2" 6'-4"

2'-1 1/2"
30
1 1R1S
1 1/2"

68
4'-1 1/2"

7 1/2"
DINING PORCH

5'-8"
DW

2X6
1SH
COVERED A90.01 3
5'-1 1/2"

A90.01 6

2'-1"
FAMILY ROOM CONCRETE
SLAB EDGE

2068
WRF
10'-11"

PATIO 9'-0" CLG CARPET 8'-0" CLG

W
2

SLAB EDGE

10'-0 1/2"
SLAB EDGE
CONCRETE 9'-0" CLG

68
7'-0" HDR
3050 SH

8'-3"
TO ISLAND WALL
8'-0" CLG

30

VERSION 7
2x6 LOW WALL

3'-3"
14'-11 1/2" 6'-7"
@ 34'-1/2" AFF
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

TO ISLAND WALL

9'-0" CLG
8'-0" CLG
SLOPE

6'-2"
CONCRETE 2" FOYER

4'-8"
SLOPE
3'-8"

Express Homes - North Central Texas


7 1/2"
WRF CONCRETE
5 1/2"

3068

2'-0"
TYP

2'-7"
SLOPE TO 9'-0" 8'-0" CLG

SSE Architectural Design Services


CLG @ 6:12 PITCH CPT WRF
TEMP

3050 SH OPT BRICK 3050 SH 3050 SH SLAB EDGE


5 1/2"

SLAB EDGE

5 1/2"
7'-0" HDR 7'-0" HDR 7'-0" HDR
@ SIDES
8x8 BUILT-UP POST, TYP 1
6X6 POST (WRAP w/ 1'-6 1/2"
12'-5 1/2" 11'-7" 11'-9 1/2" 13'-10 1/2" A90.03
OPT FULL BRICK)

X30B A, B, F, G, M, N
8'-9" 49'-8 1/2" 6'-8 1/2" 1'-6"
5 1/2" 5 1/2"

BLOCK
7 1/2"
68'-2 1/2"

1 ELEVATION G - FIRST FLOOR PLAN


1/8" = 1'-0"

ADDRESS
BUILDER
SUBD.

PLAN
CITY
LOT
DATE 12.07.2023
SCALE 1/8" = 1'-0"
12/8/2023 9:52:40 AM

A50.01
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ELECTRICAL LEGEND 10003 Technology Blvd. West
Dallas, TX. 75220

WPGFI
972-620-8204
WATERPROOF
GFCI DUPLEX

DUPLEX

GFI
GFCI DUPLEX

220v
220 VOLT DUPLEX

SPR
GFCI DUPLEX FOR SPRINKLER,
WP INSTALLED @ 84" AFF

WH
EP

GFI
SPRINKLER OUTLET CEILING MOUNTED
84" AFF CLG DUPLEX
WP PRE-WIRE FOR
ELECTERICAL PANEL EXT WALL LIGHT, TYP TV
TV OUTLET
BLOCK & PRE WIRE GFI
FOR CLG FAN
TELEPHONE OUTLET

GFI

LIGHT & SWITCH


EXHAUST FAN

TV
PRE-WIRE FOR

GFI

ACCESS

IN ATTIC
ADDITIONAL FAN & GARAGE DOOR 3

ATTIC
SWITCH REQ'D W/ OPENER THREE-WAY SWITCH
OPT. 2468 DOOR 4
GFI FOUR-WAY SWITCH
SD SD/CO SD CLG
SINGLE SWITCH
SD

DB
DOOR BELL
4'-5"
SD/CO
3'-2"

GFI

GFI

GFI
GFI-REF

GFI-MICRO/VENT
GFI-RANGE

G
G GARAGE DOOR OPENER

GFI
SECURITY LIGHT FIXTURE

GFI-DISP
GFI-DW
CEILING MOUNTED

WPGFI
GFI LIGHT FIXTURE
OPT. COVER PLATE,
DISP
BLOCK & PRE-WIRE GFI RECESSED CAN

6'-0"
WPGFI FOR CLG FAN LIGHT FIXTURE
GFI GFI 220v
6'-0" 6'-1 1/2" 6'-0" 4'-6" RECESSED CAN LIGHT

GFI
DB EYEBALL FIXTURE
6'-1"

7'-3 1/2"
HANGING LIGHT
FIXTURE
3'-6"
TV
AP PENDANT LIGHT

VERSION 7
FIXTURE
WALL MOUNTED
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

LIGHT FIXTURE

Express Homes - North Central Texas


SSE Architectural Design Services
CEILING FAN WITH LIGHT

1 ELEVATION G - FIRST FLOOR ELECTRICAL PLAN


CEILING FAN WITHOUT

X30B A, B, F, G, M, N
1/8" = 1'-0" LIGHT

BLOCK
1x4 FLUOR 1x4 FLUORESCENT
LIGHT FIXTURE

COVE LIGHT FIXTURE

UNDER-CABINET
LIGHT FIXTURE
EP ELECTRICAL PANEL

AP AUTOMATION PANEL

ADDRESS
BUILDER
SD SMOKE DETECTOR

SUBD.

PLAN
CITY
LOT
SMOKE & CARBON
SD/CO MONOXIDE DETECTOR

DENOTES WATERPROOF
WP
LIGHT FIXTURE

DENOTES PHOTOVOLTAIC
DATE 12.07.2023
P LIGHT FIXTURE
SCALE 1/8" = 1'-0"
12/8/2023 9:52:41 AM

A50.02
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 198 LF (10 NFA) = 1980 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2173 1044 418 522 0 NFA + 450 NFA = 450 NFA 594 1980 NFA + 0 NFA + 0 NFA = 1980 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION 8"-1 1/8" PL
ALTERATIONS.

@ 10:12 PITCH
1'-4 1/4" TYP

9 7/8" , TYP
@ 6:12 ROOF

10" / 12"

RAKE
6" / 12"
4 OPT BRICK @ FRONT
" 10
A50.06
/ 12 "
" /1
10 2"

56

8"-1 1/8" PL
6" / 1X6 FASCIA, TYP
6:12
12" 150 150

8"-1 1/8" PL

10" / 12"
56
EXT WALL LIGHT 10:12 COMPOSITION
1X4 FRIEZE TRIM, TYP 10" / 12"

RAKE
SHINGLE ROOF, TYP 6" / 12"

65
10" / 12"

56
150 8"-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


5 1/2" LAP SIDING, TYP

10" / 12"

RAKE
6" / 12"
(OPT BRICK @ SIDES) ROOF VENT,
VENT TYP.
TYP

56

10" / 12"
8 1/4" TYP

RAKE
1'-6 1/2" @ RAKE
(FUR OUT WALL BOX OUT HDR, TYP 1x6 TRIM
5 1/2" w/ OPT BRICK @ w/ OPT BRICK @ SIDES
SIDES & OPT FULL BRICK)
8"-1 1/8" PL

4 ELEVATION G - RIGHT 5 ELEVATION G - ROOF PLAN


1/16" = 1'-0" 1/16" = 1'-0"

(FUR OUT WALL 10 1X6 FASCIA, TYP


2" "
5 1/2" w/ OPT BRICK @ " /1 /1
2"
SIDES & OPT FULL BRICK) 10 1X4 FRIEZE TRIM, TYP

" OPT BRICK @ FRONT 3


6" / 12 6:12 10:12 10:12
A50.06
COMPOSITION SHINGLE
ROOF, TYP

VERSION 7
1x4 TRIM, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

10'-7 1/8" PL
8'-1 1/8" PL

Express Homes - North Central Texas


LAP SIDING, TYP 5 1/2"
(OPT FULL BRICK)

SSE Architectural Design Services


1'-6 1/2"
6X6 POST, TYP.
6X6 POST LAP SIDING, TYP EXT WALL LIGHT
(WRAP w/ OPT (OPT BRICK @ SIDES)
FULL BRICK) 8x8 BUILT-UP POST 1 OPT BRICK @ FRONT 2
A90.03

X30B A, B, F, G, M, N
A50.06

3 ELEVATION G - LEFT

BLOCK
1/16" = 1'-0" 2"
" /1 GABLE DETAIL, TYP
10 10 REF 7 / A90.02
10:12 " /1
2" 2"
/1

T.O. FOUNDATION TO ROOF PEAK HEIGHT


COMPOSITION
SHINGLE ROOF, TYP 1
0" EXT WALL LIGHT, TYP
1X6 FASCIA TRIM, TYP
10 1X4 FRIEZE TRIM, TYP
" /1 1x2 TRIM OVER
10 2"
" BOARD & BATTEN 1x10 TRIM
2" /1

18'-9 3/4"
" /1 2"
10:12
6" /
2" 6:12TYP
SIDING,
10

ADDRESS
1
6" / 12" 12" 6" /

BUILDER
1X6 FASCIA TRIM, TYP 6" / 12"

SUBD.
6:12

PLAN
1X4 FRIEZE TRIM, TYP COMPOSITION 1x4 TRIM, TYP

CITY
LOT
SHINGLE ROOF, TYP

8'-1 1/8" PL
8'-1 1/8" PL

CB-12 BRACKET, TYP

8'-6"
REF 2 / A90.03
1X4 TRIM, TYP LAP SIDING, TYP
(OPT FULL BRICK) 1 8x8 BUILT-UP POST, TYP
DATE 12.07.2023
A90.03
LAP SIDING, TYP
SCALE As indicated
6X6 POST, TYP.
(WRAP w/ OPT FULL BRICK)
12/8/2023 9:52:43 AM

2 ELEVATION G - REAR 1 ELEVATION G - FRONT


1/16" = 1'-0" 1/8" = 1'-0" A50.03
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 1 (65 NFA) = 65 NFA 3 (150 NFA) = 450 NFA MINIMUM 31 LF (10 NFA) = 310 NFA 4 (56 NFA) = 224 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2173 1044 418 522 65 NFA + 450 NFA = 515 NFA 529 310 NFA + 224 NFA + 0 NFA = 534 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/BLOCKING WHEN


HATCH INDICATES WHERE EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY
4 OPT BRICK @ FRONT PERFORATED SOFFITS ARE LINE (REF PLOT PLAN)
A50.06 2" 10 NOT ALLOWED 2
" /1 " /1
10 2" A100.02
8"-1 1/8" PL
6" / 1X6 FASCIA, TYP
12"
6:12

@ 10:12 PITCH
EXT WALL LIGHT 10:12 COMPOSITION 1'-4 1/4" TYP

9 7/8" , TYP
1X4 FRIEZE TRIM, TYP

10" / 12"
SHINGLE ROOF, TYP

RAKE
6" / 12"
@ 6:12 ROOF

56

8"-1 1/8" PL
8'-1 1/8" PL

1X4 TRIM, TYP


5 1/2" LAP SIDING, TYP
(OPT BRICK @ SIDES) 150 150

8"-1 1/8" PL

10" / 12"
56
10" / 12"

RAKE
6" / 12"

65
10" / 12"
1'-6 1/2"
(FUR OUT WALL BOX OUT HDR, TYP 1x6 TRIM

56
5 1/2" w/ OPT BRICK @ w/ OPT BRICK @ SIDES 150 8"-1 1/8" PL
SIDES & OPT FULL BRICK)

10" / 12"

RAKE
6" / 12"
ROOF VENT,
VENT TYP.
TYP

56
ELEVATION G - RIGHT w/ FIRE RATED SOFFITS @

10" / 12"
4 SIDES 8 1/4" TYP

RAKE
@ RAKE
1/16" = 1'-0"
8"-1 1/8" PL
2 FIRE RATED SOFFIT/BLOCKING WHEN
A100.02 EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY
LINE (REF PLOT PLAN)

(FUR OUT WALL 10 1X6 FASCIA, TYP


2" "
5 1/2" w/ OPT BRICK @ " /1 /1
2"
SIDES & OPT FULL BRICK) 10 1X4 FRIEZE TRIM, TYP

/ 12
"
6:12 10:12 10:12 OPT BRICK @ FRONT 3 ELEVATION G - ROOF PLAN w/ FIRE RATED SOFFITS @
6"
COMPOSITION SHINGLE
ROOF, TYP
A50.06
5 SIDES
1x4 TRIM, TYP

VERSION 7
1/16" = 1'-0"

10'-7 1/8" PL
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

8'-1 1/8" PL
LAP SIDING, TYP 5 1/2"

Express Homes - North Central Texas


1
(OPT FULL BRICK)
A90.03

SSE Architectural Design Services


1'-6 1/2"
6X6 POST,
6X6 POST
TYP. LAP SIDING, TYP EXT WALL LIGHT
(WRAP w/ OPT (OPT BRICK @ SIDES)
FULL BRICK) 8x8 BUILT-UP POST

X30B A, B, F, G, M, N
3 ELEVATION G - LEFT w/ FIRE RATED SOFFITS @ SIDES

BLOCK
OPT BRICK @ FRONT 2
A50.06
1/16" = 1'-0"

2"
" /1 GABLE DETAIL, TYP
10 10 REF 7 / A90.02
10:12
" /1
2" 2"
/1

T.O. FOUNDATION TO ROOF PEAK HEIGHT


COMPOSITION
0" EXT WALL LIGHT, TYP
SHINGLE ROOF, TYP 1
1X6 FASCIA TRIM, TYP

ADDRESS
10 1X4 FRIEZE TRIM, TYP

BUILDER
" /1 1x2 TRIM OVER
10 2"

SUBD.
" BOARD & BATTEN 1x10 TRIM
2" /1

18'-9 3/4"

PLAN
/1 10:12 6:12TYP

CITY
2" SIDING,
" 2"

LOT
10 1 6" /
6" / 12" 1 2" 6" /
1X6 FASCIA TRIM, TYP 6" / 12"
6:12
1X4 FRIEZE TRIM, TYP COMPOSITION 1x4 TRIM, TYP
SHINGLE ROOF, TYP
DATE 12.07.2023

8'-1 1/8" PL
SCALE As indicated
8'-1 1/8" PL

CB-12 BRACKET, TYP

8'-6"
REF 2 / A90.03
1X4 TRIM, TYP LAP SIDING, TYP
(OPT FULL BRICK) 1 8x8 BUILT-UP POST, TYP
A90.03
12/8/2023 9:52:44 AM

LAP SIDING, TYP


6X6 POST, TYP.
(WRAP w/ OPT FULL BRICK)

ELEVATION G - FRONT w/ FIRE RATED SOFFITS @ A50.04


2 ELEVATION G - REAR w/ FIRE RATED SOFFITS @ SIDES 1 SIDES
1/16" = 1'-0" 1/8" = 1'-0"
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (5 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 1 (65 NFA) = 65 NFA 3 (150 NFA) = 450 NFA MINIMUM 31 LF (5 NFA) = 155 NFA 7 (56 NFA) = 392 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2173 1044 418 522 65 NFA + 450 NFA = 515 NFA 529 155 NFA + 392 NFA + 0 NFA = 547 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.
FIRE RATED SOFFIT/BLOCKING WHEN
HATCH INDICATES WHERE EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY
PERFORATED SOFFITS ARE LINE (REF PLOT PLAN)
NOT ALLOWED 2
4 OPT BRICK @ FRONT A100.02
A50.06 1 2" 10 8"-1 1/8" PL
"/ " /1
10 2"

@ 10:12 PITCH
6" / 1X6 FASCIA, TYP

56

9 7/8" , TYP
12"

10" / 12"
6:12

RAKE
6" / 12"
EXT WALL LIGHT 10:12 COMPOSITION
SHINGLE ROOF, TYP 1X4 FRIEZE TRIM, TYP

56

8"-1 1/8" PL
1'-4 1/4" TYP
8'-1 1/8" PL

1X4 TRIM, TYP @ 6:12 ROOF 150 150


5 1/2"

8"-1 1/8" PL

10" / 12"
LAP SIDING, TYP

56
(OPT BRICK @ SIDES) 10" / 12"

RAKE
6" / 12"

65
10" / 12"

56
1'-6 1/2" 150 8"-1 1/8" PL
(FUR OUT WALL BOX OUT HDR, TYP 1x6 TRIM
5 1/2" w/ OPT BRICK @ w/ OPT BRICK @ SIDES

10" / 12"

RAKE
6" / 12"
ROOF VENT,
VENT TYP.
TYP

56
SIDES & OPT FULL BRICK)

10" / 12"

RAKE
ELEVATION G - RIGHT w/ FIRE RATED SOFFITS @ SIDES w/ 5 NFA

56
56

4 LOWER VENTILATION 8 1/4" TYP


8"-1 1/8" PL
1/16" = 1'-0" @ RAKE
2 FIRE RATED SOFFIT/BLOCKING WHEN
A100.02 EAVE IS ≥ 2'-0" TO < 5'-0" FROM PROPERTY
LINE (REF PLOT PLAN)

1X6 FASCIA, TYP


ELEVATION G - ROOF PLAN w/ FIRE RATED SOFFITS @ SIDES w/ 5
(FUR OUT WALL 10
5 1/2" w/ OPT BRICK @
10
"/
12
" " /1
2" 5 NFA LOWER VENTILATION
SIDES & OPT FULL BRICK) 1X4 FRIEZE TRIM, TYP
1/16" = 1'-0"
12" 10:12 10:12 OPT BRICK @ FRONT 3
6" / 6:12

VERSION 7
A50.06
COMPOSITION SHINGLE
ROOF, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

1x4 TRIM, TYP

Express Homes - North Central Texas


10'-7 1/8" PL
8'-1 1/8" PL

SSE Architectural Design Services


LAP SIDING, TYP 5 1/2" 1
(OPT FULL BRICK)
A90.03

1'-6 1/2"
6X6 POST,
6X6 POST
TYP. LAP SIDING, TYP EXT WALL LIGHT
(WRAP w/ OPT (OPT BRICK @ SIDES) OPT BRICK @ FRONT 2

X30B A, B, F, G, M, N
FULL BRICK) 8x8 BUILT-UP POST A50.06

BLOCK
ELEVATION G -LEFT w/ FIRE RATED SOFFITS @ SIDES w/ 5 NFA
2"
3 LOWER VENTILATION 10
" /1
10
"
GABLE DETAIL, TYP
REF 7 / A90.02
10:12 /1
1/16" = 1'-0" 2" 2"
/1

T.O. FOUNDATION TO ROOF PEAK HEIGHT


COMPOSITION
0" EXT WALL LIGHT, TYP
SHINGLE ROOF, TYP 1
1X6 FASCIA TRIM, TYP
10 1X4 FRIEZE TRIM, TYP
" /1 1x2 TRIM OVER
2"
BOARD & BATTEN 1x10 TRIM

18'-9 3/4"

ADDRESS
6:12TYP
SIDING,

BUILDER
10 "
" " 6" /
/ 12 10:12
/1
2" 6" / 12 12"
" 2"

SUBD.
10 1 6" /
6" /

PLAN
12"

CITY
1x4 TRIM, TYP

LOT
1X6 FASCIA TRIM, TYP
6:12
1X4 FRIEZE TRIM, TYP COMPOSITION

8'-1 1/8" PL
SHINGLE ROOF, TYP
CB-12 BRACKET, TYP

8'-6"
REF 2 / A90.03 1 DATE 12.07.2023
8'-1 1/8" PL

A90.03
8x8 BUILT-UP POST, TYP
1X4 TRIM, TYP LAP SIDING, TYP SCALE As indicated
(OPT FULL BRICK)
LAP SIDING, TYP
12/8/2023 9:52:46 AM

6X6 POST, TYP.


(WRAP w/ OPT FULL BRICK)

ELEVATION G - REAR w/ FIRE RATED SOFFITS @ SIDES w/ 5 NFA ELEVATION G - FRONT w/ FIRE RATED SOFFITS @ SIDES w/ 5 NFA A50.05
2 LOWER VENTILATION 1 LOWER VENTILATION STRAND 2351667
1/16" = 1'-0" 1/8" = 1'-0"
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

2" 10 2" 10
" /1 " /1 /1 " /1
10 2" 10
" 2"

10:12 10:12
10:12 6:12
10:12SHINGLE
COMPOSITION 6:12
1X6 FASCIA, TYP
ROOF, TYP
1X4 FRIEZE TRIM, TYP 1X6 FASCIA, TYP
EXT WALL LIGHT 68'-8" OVERALL
EXT WALL LIGHT
1X4 FRIEZE TRIM, TYP
20'-4 1/2" 5 1/2"
30"x30"x18" WATER HEATER
PLATFORM w/ 2x4 WING WALL

10'-7 1/8" PL
1x4 TRIM, TYP 1x4 TRIM, TYP
(NOT REQUIRED w/ TANKLESS

5 1/2"
LAP SIDING, TYP WH)
8'-1 1/8" PL

8'-1 1/8" PL
BRICK ROWLOCK 2'-0"

HB
BRICK ROWLOCK 5 1/2" LAP SIDING, TYP LAP SIDING, TYP CAP
CAP, TYP (OPT BRICK @ SIDES) (OPT BRICK @ SIDES)

2'-10 1/2"

WH
BRICK, TYP
3'-0"

3'-0"

1'-4 1/2"
BRICK, TYP

2x4 WALL w/ WH
(FUR OUT WALL

9'-6"
2'-0"
5 1/2" w/ OPT BRICK @ 2'-0" 8x8 BUILT-UP POST 1 SLOPE
SIDES & OPT FULL BRICK) BOX OUT HDR, TYP A90.03 CONCRETE 2"
w/ OPT BRICK @ SIDES

8'-9 1/2"

16070 GARAGE DOOR


TIRE STOP
GARAGE
ELEVATION G - RIGHT w/ OPT ELEVATION G - LEFT w/ OPT

ACCESS

16'-3" R.O.
ATTIC

19'-0"
CONCRETE
8'-0" CLG
4 BRICK@ FRONT 3 BRICK @ FRONT 3REF.
1/2"STRUCTURAL

1/8" = 1'-0" 1/8" = 1'-0"

2'-4 1/2"

29'-11 1/2"
9'-6"
7'-7" 3'-11 1/2" 8'-9 5/8"

1'-4 1/2"
4'-8"
COAT

6 1/2"
WRF
8'-0" CLG

VERSION 7
2'-1 1/2"
30
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

1R1S

68

Express Homes - North Central Texas


7 1/2"
PORCH

5'-8"

2X6
2"

1SH
/1 GABLE DETAIL, TYP A90.01 6

2'-1"

SSE Architectural Design Services


" 10 CONCRETE

2068

7'-0" HDR
10 " REF 7 / A90.02

2050 FX
/1 8'-0" CLG

W
2"

SLAB EDGE

10'-0 1/2"
10:12 "

4'-8"

SLAB EDGE
12

68
T.O. FOUNDATION TO ROOF PEAK HEIGHT
COMPOSITION /

8'-3"
"

30
10 EXT WALL LIGHT, TYP

3'-3"
SHINGLE ROOF, TYP
1X6 FASCIA TRIM, TYP UTILITY FOYER

9'-0" CLG
8'-0" CLG
10 1X4 FRIEZE TRIM, TYP WRF WRF

7 1/2"
" /1 8'-0" CLG 8'-0" CLG SLOPE

X30B A, B, F, G, M, N
2" 1x2 TRIM OVER 3068

3'-0 1/2"
CONCRETE
BOARD & BATTEN 1x10 TRIM

18'-9 3/4"
CPT WRF
6:12TYP
SIDING, TEMP

BLOCK
1 2" 6" /
6" / 12"
SLAB EDGE

5 1/2"
2'-0" SLAB EDGE
1x4 TRIM, TYP
6'-8 1/2" 1'-7 1/2"
BRICK ROWLOCK
8'-1 1/8" PL

CAP, TYP 7 1/2" 4"


CB-12 BRACKET, TYP
8'-6"

REF 2 / A90.03

1 8x8 BUILT-UP POST, TYP BRICK, TYP


ELEVATION G - FIRST FLOOR
3'-0"

A90.03

ADDRESS
1 PLAN - OPT BRICK @ FRONT

BUILDER
SUBD.

PLAN
BRICK SILL 1/8" = 1'-0"

CITY
LOT
BRICK ROWLOCK HEADER

ELEVATION G - FRONT w/OPT DATE 12.07.2023


2 BRICK @ FRONT SCALE 1/8" = 1'-0"
1/8" = 1'-0"
12/8/2023 9:52:48 AM

A50.06
STRAND 2351667
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

68'-8"

5 1/2" 5 1/2"
67'-9"

9'-6" 11'-4 1/2" 10'-1" 9" 5'-3 1/2" 10'-4 1/2" 20'-4 1/2"
OPT FULL
BRICK
3'-9" 3'-7" 4'-0 1/2" 2'-2 1/2" 7'-10 1/2" 7'-8 1/2" 2'-8"
*FOR DRHE PLANS ONLY
30"x30"x18" WATER HEATER
BATH 1 2'-0"
5 1/2"

5 1/2"
OPT BRICK PLATFORM w/ 2x4 WING WALL
WRF 3050 SH 3050 SH 3050 SH 3050 SH (NOT REQUIRED w/ TANKLESS
@ SIDES

HB
8'-0'' CLG 7'-0" HDR 7'-0" HDR 7'-0" HDR 7'-0" HDR WH)

2'-10 1/2"
2'-9 1/2"

WH
SLOPE TO 9'-0" 60" x 30"

3'-2"
2668
OPT 4010 FX

SHOWER

1'-4 1/2"
CLG @ 5:12 PITCH TUB
5'-3 1/2"

36" x 60"
7'-0" HDR OPT SINK 2x4 WALL w/ WH
BEDROOM 3 BATH 2
2'-6"

2'-6 1/2"

9'-0"
CARPET

9'-6"
WRF
BEDROOM 2

2'-4" x 6'-10" HDR


8'-0" CLG 8'-0" CLG SLOPE
CARPET

2X6
8'-0" CLG
CONCRETE 2"

7'-0"

8'-9 1/2"
OPT 2468 DOOR A90.01 5 A90.01
4

16070 GARAGE DOOR


TIRE STOP
BEDROOM 1 CLOSET
6'-4 1/2"

CARPET CARPET
WC CLOSET

ACCESS
17'-8"

2868

16'-3" R.O.
9'-0'' CLG 8'-0" CLG

ATTIC

19'-0"
WRF CARPET
8'-0'' CLG 2'-4" x 6'-10" HDR WIC 8'-0" CLG GARAGE

5SH
3 1/2" CONCRETE
CARPET
8'-0" CLG

3'-10 1/2"
8'-0'' CLG

20
68
VEST

68
20
2X6 PANTRY

2'-4 1/2"
26

68
2'-8 1/2"
CARPET

2668
8'-4 1/2"

3'-8"

68

26
WRF 8'-0" CLG 1 1/2"
8'-0" CLG 1R1S 1R1S
29'-11 1/2"

29'-11 1/2"
8'-0" CLG
1R1S

9'-6"
1R1S
6'-0"

5SH 7'-10 1/2" 3'-11 1/2" 8'-10"


3'-8" 5'-6 1/2" 9'-0" CLG

1'-4 1/2"
8'-0'' CLG

4'-8"
REF
1R1S UTILITY COAT

20

1'-10 1/2"

2'-1 1/2"
9'-0'' CLG KITCHEN

68
HB WRF WRF
WRF WRF CPT 1'-10 1/2"
TEMP
2'-1 1/2"

8'-0" CLG 8'-0" CLG


9'-0" CLG 4 1/2"
2868 4'-4" 2'-11" 6'-4" 4'-0 1/2" 3'-6" 4'-0 1/2" 6'-4"

30
1 1R1S
1 1/2" 4'-7" 1'-3"

68
4'-1 1/2"

3'-4"
D
DINING

5'-8"
DW

2X6
1SH
A90.01 3 SLAB EDGE
COVERED
5'-1 1/2"

A90.01 6
FAMILY ROOM
SLAB EDGE

WRF

2068
10'-11"

PATIO 9'-0" CLG CARPET

W
2

9 3/4"
CONCRETE 9'-0" CLG 3'-6" x 8'-0" HDR

1'-2 1/2"
2'-6 1/2"
68
7'-0" HDR

PORCH
3050 SH

4'-2" x 8'-0" HDR

SLAB EDGE
TO ISLAND WALL
8'-0" CLG

30
2x6 LOW WALL
14'-11 1/2" 6'-7" CONCRETE
@ 34'-1/2" AFF 1 1/2" 8'-0" CLG

5'-1"
TO ISLAND WALL

9'-0" CLG
8'-0" CLG

VERSION 7
6'-2"
SLOPE
FOYER SLOPE

2'-6 1/2"
CONCRETE 2"

4'-8"
3'-8"

3068
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

2'-4 3/4"
WRF CONCRETE

9 3/4"
SLOPE TO 9'-0"

TYP
5 1/2"

8'-0" CLG TEMP

Express Homes - North Central Texas


CLG @ 5:12 PITCH CPT WRF 3'-6" x 8'-0" HDR

3050 SH OPT BRICK 3050 SH 3050 SH SLAB EDGE


5 1/2"

SLAB EDGE 2'-2"

5 1/2"
7'-0" HDR 7'-0" HDR 7'-0" HDR
@ SIDES
6X6 POST (WRAP w/
OPT FULL BRICK) 12'-5 1/2" 11'-7" 11'-9 1/2" 14'-0 1/2"
5 1/2"
8'-9" 49'-10 1/2" 4'-5" 1'-3" 3'-0"

X30B A, B, F, G, M, N
5 1/2" 5 1/2"
68'-8"

BLOCK
1 ELEVATION M - FIRST FLOOR PLAN
1/8" = 1'-0"

ADDRESS
BUILDER
SUBD.

PLAN
CITY
LOT
DATE 12.07.2023
SCALE 1/8" = 1'-0"
DR'N
12/8/2023 9:52:49 AM

A60.01
STRAND 2351667
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ELECTRICAL LEGEND 10003 Technology Blvd. West
Dallas, TX. 75220

WPGFI
972-620-8204
WATERPROOF
GFCI DUPLEX

DUPLEX

GFI
GFCI DUPLEX

220v
220 VOLT DUPLEX

SPR
GFCI DUPLEX FOR SPRINKLER,
INSTALLED @ 84" AFF
PRE-WIRE FOR

HB
EXT WALL LIGHT
CEILING MOUNTED
CLG DUPLEX
WP

WH
EP

GFI
TV
TV OUTLET
SPRINKLER OUTLET
84" AFF
WP TELEPHONE OUTLET
ELECTERICAL PANEL
BLOCK & PRE WIRE EXHAUST FAN
GFI
FOR CLG FAN 3
THREE-WAY SWITCH

GFI

LIGHT & SWITCH


4

TV
PRE-WIRE FOR FOUR-WAY SWITCH

GFI

ACCESS

IN ATTIC
ADDITIONAL FAN & GARAGE DOOR

ATTIC
SWITCH REQ'D W/ OPENER
SINGLE SWITCH
OPT. 2468 DOOR
GFI

DB
SD SD/CO SD CLG DOOR BELL

SD
G GARAGE DOOR OPENER

4'-5"
SD/CO SECURITY LIGHT FIXTURE
3'-2"

GFI

GFI

GFI
GFI-REF

GFI-MICRO/VENT
GFI-RANGE

GFI
HB CEILING MOUNTED
LIGHT FIXTURE

GFI-DISP
RECESSED CAN

GFI-DW
LIGHT FIXTURE
GFI
OPT. COVER PLATE, RECESSED CAN LIGHT
DISP
BLOCK & PRE-WIRE GFI EYEBALL FIXTURE

6'-0"
WPGFI FOR CLG FAN
GFI GFI 220v HANGING LIGHT
6'-0" 6'-1 1/2" 6'-0" 4'-6"
DB FIXTURE

GFI
PENDANT LIGHT
6'-1"

7'-3 1/2"

VERSION 7
3'-6" FIXTURE
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

WALL MOUNTED
WPGFI LIGHT FIXTURE

Express Homes - North Central Texas


TV
AP

CEILING FAN WITH LIGHT

CEILING FAN WITHOUT

X30B A, B, F, G, M, N
LIGHT

BLOCK
1x4 FLUOR 1x4 FLUORESCENT
LIGHT FIXTURE

COVE LIGHT FIXTURE

UNDER-CABINET
LIGHT FIXTURE
1 ELEVATION M - FIRST FLOOR ELECTRICAL PLAN EP ELECTRICAL PANEL
1/8" = 1'-0"
AP AUTOMATION PANEL

ADDRESS
BUILDER
SMOKE DETECTOR

SUBD.
SD

PLAN
CITY
LOT
SMOKE & CARBON
SD/CO MONOXIDE DETECTOR

DENOTES WATERPROOF
WP
LIGHT FIXTURE
DATE 12.07.2023
DENOTES PHOTOVOLTAIC
P
LIGHT FIXTURE SCALE 1/8" = 1'-0"
DR'N
12/8/2023 9:52:51 AM

A60.02
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 191 LF (10 NFA) = 1910 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2260 1085 434 542 0 NFA + 450 NFA = 450 NFA 635 1910 NFA + 0 NFA + 0 NFA = 1910 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

@5:12 PITCH
1'-7 1/2" TYP
4:12 5" /
12" 1 2" 5" / 8"-1 1/8" PL
5" / 1 2" 1X6 FASCIA, TYP
12" 5:12
5" / COMPOSITION 1X4 FRIEZE TRIM, TYP
SHINGLE ROOF, TYP
EXT WALL LIGHT
8'-1 1/8" PL

8"-1 1/8" PL
5" / 12"
LAP SIDING, TYP 1X4 TRIM, TYP 5" / 12"
6'-0"

(OPT. BRICK @ SIDES)


150 150

8"-1 1/8" PL
5" / 12"
2'-0"

5" / 12"
BRICK, TYP BOX OUT HDR w/ 1X6 TRIM 5" / 12"
OPT BRICK @ SIDES
150

5" / 12"
10"-1 1/8" PL
5" / 12"
ROOF VENT TYP.
8"-1 1/8" PL

5" / 12"
4 ELEVATION M - RIGHT 8 1/4" TYP

4" / 12"
@ RAKE

RAKE
1/16" = 1'-0"

RAKE
8"-1 1/8" PL RAKE 10"-1 1/8" PL 12"-3 1/8" PL

5" / 5:12
12" 1

VERSION 7
2"
5" /
5:12 " 1X6 FASCIA, TYP
/ 12
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION 5" 5:12


SHINGLE ROOF, TYP 5" / 1X4 FRIEZE TRIM, TYP

Express Homes - North Central Texas


1 2"
5 ELEVATION M - ROOF PLAN

12'-3 1/8" PL

SSE Architectural Design Services


10'-1 1/8" PL
EXT WALL LIGHT

8'-1 1/8" PL
1/16" = 1'-0"
BRICK, TYP

6'-0"

X30B A, B, F, G, M, N
6X6 POST, TYP. SOLDIER COURSE, TYP
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 1x4 TRIM, TYP
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
3 ELEVATION M - LEFT 5" /
12"
5:12
4" / 1 5" /
1/16" = 1'-0" 2" COMPOSITION 1 2"
SHINGLE ROOF, TYP 1X6 FASCIA TRIM, TYP

T. O. FOUNDATION TO ROOF PEAK HEIGHT


12"
SOLDIER COURSE, TYP 5" / 1X4 FRIEZE TRIM, TYP
5:12

ADDRESS
14'-8 5/8" PL

BUILDER
12" 5" / 5" / 2"
1X6 FASCIA TRIM, TYP 5" / 1 2" 1 2" 4" / 1

12'-3 1/8" PL

SUBD.
5:12

PLAN
CITY
1X4 FRIEZE TRIM, TYP EXT WALL LIGHT

10'-1 1/8" PL
COMPOSITION

LOT
BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
12'-3 1/8" PL
10'-1 1/8" PL

1X4 TRIM, TYP


8'-1 1/8" PL

6'-0"
1X4 TRIM, TYP
DATE 12.07.2023
SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP. BOARD & BATTEN SIDING, TYP BOARD & BATTEN SIDING, TYP;
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) OPT. WOOD-LOOK SIDING
12/8/2023 9:52:52 AM

2 ELEVATION M - REAR 1 ELEVATION M - FRONT


1/16" = 1'-0" 1/8" = 1'-0"
A60.03
STRAND 2351667
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 67 LF (10 NFA) = 670 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2260 1085 434 542 0 NFA + 450 NFA = 450 NFA 635 670 NFA + 0 NFA + 0 NFA = 670 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN

@5:12 PITCH
1'-7 1/2" TYP
EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
4:12 5" / A100.02 A100.02
12 " 1 2" 5" /
5" / 1 2" 1X6 FASCIA, TYP
8"-1 1/8" PL

12" 5:12
5" / COMPOSITION 1X4 FRIEZE TRIM, TYP
SHINGLE ROOF, TYP
EXT WALL LIGHT
8'-1 1/8" PL

8"-1 1/8" PL
5" / 12"
LAP SIDING, TYP 1X4 TRIM, TYP 5" / 12"
6'-0"

(OPT. BRICK @ SIDES)


150 150

8"-1 1/8" PL
5" / 12"
BRICK, TYP 2'-0" BOX OUT HDR w/ 1X6 TRIM

5" / 12"
5" / 12"
OPT BRICK @ SIDES
150

5" / 12"
10"-1 1/8" PL
5" / 12"
ROOF VENT TYP.
ELEVATION M - RIGHT w/ FIRE RATED SOFFITS @ 8"-1 1/8" PL

5" / 12"
8 1/4" TYP

4" / 12"
4 SIDES @ RAKE

RAKE
RAKE
1/16" = 1'-0"

8"-1 1/8" PL RAKE 10"-1 1/8" PL 2 12"-3 1/8" PL


A100.02

FIRE RATED SOFFIT/ BLOCKING WHEN


5" / 5:12 EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
12" 1 2"
5" / LINE (REF PLOT PLAN)

VERSION 7
5:12 1X6 FASCIA, TYP
12"
COMPOSITION 5" / 5:12
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

SHINGLE ROOF, TYP 5" / 1X4 FRIEZE TRIM, TYP


1 2"
ELEVATION M - ROOF PLAN w/ FIRE RATED SOFFITS @

Express Homes - North Central Texas


12'-3 1/8" PL
10'-1 1/8" PL
EXT WALL LIGHT
5 SIDES

8'-1 1/8" PL
BRICK, TYP

6'-0"
1/16" = 1'-0"

6X6 POST, TYP. SOLDIER COURSE, TYP

X30B A, B, F, G, M, N
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 1x4 TRIM, TYP
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
12"
3 ELEVATION M - LEFT w/ FIRE RATED SOFFITS @ SIDES 4" / 1
5" / 5:12
5" /
2" COMPOSITION 1 2"
1/16" = 1'-0" SHINGLE ROOF, TYP 1X6 FASCIA TRIM, TYP

T. O. FOUNDATION TO ROOF PEAK HEIGHT


1 2"
SOLDIER COURSE, TYP 5" / 1X4 FRIEZE TRIM, TYP
5:12

ADDRESS
14'-8 5/8" PL

BUILDER
12" 5" / 5" / 2"
5" / 1 2" 4" / 1

12'-3 1/8" PL
1X6 FASCIA TRIM, TYP 1

SUBD.
2"

PLAN
5:12

CITY
EXT WALL LIGHT

10'-1 1/8" PL

LOT
1X4 FRIEZE TRIM, TYP COMPOSITION BRICK, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
12'-3 1/8" PL

1X4 TRIM, TYP


10'-1 1/8" PL
8'-1 1/8" PL

6'-0"
1X4 TRIM, TYP
DATE 12.07.2023
SCALE As indicated
BOARD & BATTEN SIDING, TYP BOARD & BATTEN SIDING, TYP;
DR'N
LAP SIDING, TYP 6X6 POST, TYP.
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) OPT. WOOD-LOOK SIDING
12/8/2023 9:52:54 AM

ELEVATION M - REAR w/ FIRE RATED SOFFITS @ ELEVATION M - FRONT w/ FIRE RATED SOFFITS @
2 SIDES
1/16" = 1'-0"
1 SIDES
1/8" = 1'-0"
A60.04
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (5 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 67 LF (5 NFA) = 335 NFA 6 (56 NFA) = 336 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2260 1085 434 542 0 NFA + 450 NFA = 450 NFA 635 335 NFA + 336 NFA + 0 NFA = 671 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN

@5:12 PITCH
1'-7 1/2" TYP
EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
4:12 5" / A100.02 A100.02
" 1
5" / 12 2" 5" /
1
8"-1 1/8" PL
2" 1X6 FASCIA, TYP
1 2" 5:12
5" / COMPOSITION 1X4 FRIEZE TRIM, TYP
SHINGLE ROOF, TYP
EXT WALL LIGHT 56
8'-1 1/8" PL

8"-1 1/8" PL
5" / 12"
LAP SIDING, TYP 1X4 TRIM, TYP 5" / 12"
6'-0"

(OPT. BRICK @ SIDES) 56


150 150

8"-1 1/8" PL
5" / 12"
2'-0" 56

5" / 12"
BRICK, TYP BOX OUT HDR w/ 1X6 TRIM 5" / 12"
OPT BRICK @ SIDES
150

5" / 12"
10"-1 1/8" PL
5" / 12"
ELEVATION M - RIGHT w/ FIRE RATED SOFFITS @ 56 ROOF VENT TYP.

4 SIDES w/ 5 NFA LOWER VENTILATION 56 8"-1 1/8" PL

5" / 12"
8 1/4" TYP

4" / 12"
56 @ RAKE
1/16" = 1'-0"

RAKE
RAKE
8"-1 1/8" PL RAKE 10"-1 1/8" PL 2 12"-3 1/8" PL
A100.02

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
" 5" / 5:12
12 1 LINE (REF PLOT PLAN)

VERSION 7
2"
5" /
5:12
12" 1X6 FASCIA, TYP
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION 5" / 5:12


SHINGLE ROOF, TYP 5" / 1X4 FRIEZE TRIM, TYP ELEVATION M - ROOF PLAN w/ FIRE RATED SOFFITS @

Express Homes - North Central Texas


1 2"
5 SIDES w/ 5 NFA LOWER VENTILATION

12'-3 1/8" PL

SSE Architectural Design Services


10'-1 1/8" PL
EXT WALL LIGHT

8'-1 1/8" PL
1/16" = 1'-0"
BRICK, TYP

6'-0"

X30B A, B, F, G, M, N
6X6 POST, TYP. SOLDIER COURSE, TYP
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 1x4 TRIM, TYP
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
ELEVATION M - LEFT w/ FIRE RATED SOFFITS @ SIDES
3 w/ 5 NFA LOWER VENTILATION 5" /
12"
5:12
4" / 1 5" /
1/16" = 1'-0" 2" COMPOSITION 1 2"
SHINGLE ROOF, TYP 1X6 FASCIA TRIM, TYP

T. O. FOUNDATION TO ROOF PEAK HEIGHT


12"
SOLDIER COURSE, TYP 5" / 1X4 FRIEZE TRIM, TYP
5:12

ADDRESS
14'-8 5/8" PL

BUILDER
12" 5" / 5" / 2"
1X6 FASCIA TRIM, TYP 5" / 1 2" 1 2" 4" / 1

12'-3 1/8" PL

SUBD.
5:12

PLAN
CITY
1X4 FRIEZE TRIM, TYP EXT WALL LIGHT

10'-1 1/8" PL
COMPOSITION

LOT
SHINGLE ROOF, TYP BRICK, TYP

8'-1 1/8" PL
12'-3 1/8" PL
10'-1 1/8" PL

1X4 TRIM, TYP


8'-1 1/8" PL

1X4 TRIM, TYP

6'-0"
DATE 12.07.2023
SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP. BOARD & BATTEN SIDING, TYP BOARD & BATTEN SIDING, TYP;
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) OPT. WOOD-LOOK SIDING
12/8/2023 9:52:55 AM

ELEVATION M - REAR w/ FIRE RATED SOFFITS @ ELEVATION M - FRONT w/ FIRE RATED SOFFITS @
2 SIDES w/ 5 NFA LOWER VENTILATION
1/16" = 1'-0"
1 SIDES w/ 5 NFA LOWER VENTILATION
1/8" = 1'-0"
A60.05
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

68'-8"

5 1/2" 67'-9" 5 1/2"

9'-6" 11'-4 1/2" 10'-1" 9" 5'-3 1/2" 10'-4 1/2" 20'-4 1/2"
OPT FULL
BRICK
3'-9" 3'-7" 4'-0 1/2" 2'-2 1/2" 7'-10 1/2" 7'-8 1/2" 2'-8"
*FOR DRHE PLANS ONLY
30"x30"x18" WATER HEATER
BATH 1
5 1/2"

OPT BRICK PLATFORM w/ 2x4 WING WALL 2'-0"

5 1/2"
WRF 3050 SH 3050 SH 3050 SH 3050 SH (NOT REQUIRED w/ TANKLESS
@ SIDES

HB
8'-0'' CLG 7'-0" HDR 7'-0" HDR 7'-0" HDR 7'-0" HDR WH)

2'-10 1/2"
2'-9 1/2"

WH
60" x 30"

3'-2"
2668
OPT 4010 FX

1'-1"
SHOWER

TUB
5'-3 1/2"

36" x 60"
7'-0" HDR

OPT SINK 2x4 WALL w/ WH


SLOPE TO 9'-0" BEDROOM 3 BATH 2
2'-6"

2'-6 1/2"
CLG @ 5:12 PITCH
9'-0"
CARPET

9'-6"
WRF
BEDROOM 2
2'-4" x 6'-10" HDR

8'-0" CLG 8'-0" CLG SLOPE


CARPET

2X6
8'-0" CLG
CONCRETE 2"

7'-0"

8'-9 1/2"
OPT 2468 DOOR A90.01 5 A90.01
4

16070 GARAGE DOOR


TIRE STOP
BEDROOM 1 CLOSET
6'-4 1/2"

CARPET CARPET
CLOSET

ACCESS
WC
17'-8"

2868

16'-3" R.O.
9'-0'' CLG 8'-0" CLG

ATTIC

19'-0"
WRF CARPET
8'-0'' CLG 2'-4" x 6'-10" HDR WIC 8'-0" CLG GARAGE
5SH

3 1/2" CONCRETE
CARPET
8'-0" CLG

3'-10 1/2"
8'-0'' CLG

20
68
VEST

68
20
2X6 PANTRY

2'-4 1/2"
26
2'-8 1/2"

68
CARPET
2668
8'-4 1/2"

3'-8"

68

26
WRF 8'-0" CLG 1 1/2"
8'-0" CLG 1R1S 1R1S
29'-11 1/2"

29'-11 1/2"
8'-0" CLG
1R1S

9'-6"
1R1S
6'-0"

5SH 7'-10 1/2" 3'-11 1/2" 8'-10"


3'-8" 5'-6 1/2" 9'-0" CLG
8'-0'' CLG

4'-8"
REF
1R1S UTILITY COAT
20

1'-10 1/2"

1'-1"
9'-0'' CLG KITCHEN
68

HB WRF WRF
WRF WRF CPT 1'-10 1/2"
TEMP

VERSION 7
2'-1 1/2"

8'-0" CLG 8'-0" CLG


9'-0" CLG 4 1/2"
2868
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

4'-4" 2'-11" 6'-4" 4'-0 1/2" 3'-6" 4'-0 1/2" 6'-4"

30
1 1R1S
1 1/2"

68
PORCH

Express Homes - North Central Texas


4'-1 1/2"

3'-4"
D

1'-3 1/2"
CONCRETE
DINING

5'-8"
DW

2X6
SLAB EDGE

1SH
COVERED A90.01 3
5'-1 1/2"

SSE Architectural Design Services


A90.01 6 8'-0" CLG
FAMILY ROOM 4'-5 1/4" x 8'-0" HDR
SLAB EDGE

2068
WRF
10'-11"

PATIO 9'-0" CLG CARPET

W
CONCRETE
2 9'-0" CLG

4'-5 1/4" x 8'-0" HDR


68
7'-0" HDR
3050 SH

TO ISLAND WALL

2'-3 1/2" 2'-3 1/2"


8'-0" CLG

30
2x6 LOW WALL
14'-11 1/2" 6'-7"

SLAB EDGE
@ 34'-1/2" AFF
TO ISLAND WALL 1 1/2"

9'-0" CLG
8'-0" CLG

4'-7"
SLOPE
6'-2"

CONCRETE 2" FOYER

4'-8"
3'-8"

X30B A, B, F, G, M, N
3068 SLOPE
2'-4 3/4"

WRF
TYP
5 1/2"

SLOPE TO 9'-0" 8'-0" CLG CONCRETE


CLG @ 5:12 PITCH CPT WRF TEMP

BLOCK
3050 SH OPT BRICK 3050 SH 3050 SH
5 1/2"

SLAB EDGE 4'-5 1/4" x 8'-0" HDR

1'-3 1/2"
7'-0" HDR 7'-0" HDR 7'-0" HDR 2'-0" SLAB EDGE
@ SIDES
6X6 POST (WRAP w/
12'-5 1/2" 11'-7" 11'-9 1/2" 13'-10 1/2"
6 2'-3 1/2"
OPT FULL BRICK)

8'-9" 49'-8 1/2"


A90.02
2'-3 1/2"
4'-7" 2'-11 1/2"
5 1/2"
5 1/2" 5 1/2" 1'-3 1/2"
68'-8"

ADDRESS
1

BUILDER
ELEVATION N - FIRST FLOOR PLAN

SUBD.

PLAN
1/8" = 1'-0"

CITY
LOT
DATE 12.07.2023
SCALE 1/8" = 1'-0"
12/8/2023 9:52:57 AM

A70.01
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ELECTRICAL LEGEND 10003 Technology Blvd. West
Dallas, TX. 75220

WPGFI
972-620-8204
WATERPROOF
GFCI DUPLEX

DUPLEX

GFI
GFCI DUPLEX

220v
220 VOLT DUPLEX

SPR
GFCI DUPLEX FOR SPRINKLER,
INSTALLED @ 84" AFF

CEILING MOUNTED
CLG DUPLEX
TV
TV OUTLET

TELEPHONE OUTLET

PRE-WIRE FOR EXHAUST FAN

HB
EXT WALL LIGHT 3
THREE-WAY SWITCH
WP 4

WH
EP FOUR-WAY SWITCH

GFI
SPRINKLER OUTLET
84" AFF
SINGLE SWITCH
WP
ELECTERICAL PANEL

DB
BLOCK & PRE WIRE GFI DOOR BELL
FOR CLG FAN

G GARAGE DOOR OPENER


GFI

LIGHT & SWITCH


TV

PRE-WIRE FOR

GFI

ACCESS

IN ATTIC
ADDITIONAL FAN & GARAGE DOOR

ATTIC
SECURITY LIGHT FIXTURE
SWITCH REQ'D W/ OPENER
OPT. 2468 DOOR
GFI CEILING MOUNTED
SD SD/CO SD CLG LIGHT FIXTURE

RECESSED CAN
SD LIGHT FIXTURE

RECESSED CAN LIGHT


4'-5"
SD/CO EYEBALL FIXTURE
3'-2"

GFI

GFI

GFI
GFI-REF

GFI-RANGE

GFI-MICRO/VENT

G
HANGING LIGHT

GFI
HB FIXTURE

PENDANT LIGHT

GFI-DISP

VERSION 7
GFI-DW
FIXTURE
GFI WALL MOUNTED
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

OPT. COVER PLATE, LIGHT FIXTURE


DISP
BLOCK & PRE-WIRE

Express Homes - North Central Texas


GFI
6'-0"

WPGFI FOR CLG FAN


GFI GFI 220v

SSE Architectural Design Services


6'-0" 6'-1 1/2" 6'-0" 4'-6" CEILING FAN WITH LIGHT
DB
GFI
6'-1"

7'-3 1/2"
3'-6"

WPGFI CEILING FAN WITHOUT

X30B A, B, F, G, M, N
TV
AP LIGHT

BLOCK
1x4 FLUOR 1x4 FLUORESCENT
LIGHT FIXTURE

COVE LIGHT FIXTURE

UNDER-CABINET
LIGHT FIXTURE
EP ELECTRICAL PANEL

1 ELEVATION N - FIRST FLOOR ELECTRICAL PLAN


AP AUTOMATION PANEL

ADDRESS
1/8" = 1'-0"

BUILDER
SD SMOKE DETECTOR

SUBD.

PLAN
CITY
LOT
SMOKE & CARBON
SD/CO MONOXIDE DETECTOR

DENOTES WATERPROOF
WP
LIGHT FIXTURE

DENOTES PHOTOVOLTAIC
DATE 12.07.2023
P LIGHT FIXTURE
SCALE 1/8" = 1'-0"
12/8/2023 9:52:58 AM

A70.02
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 199 LF (10 NFA) = 1990 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2260 1085 434 542 0 NFA + 450 NFA = 450 NFA 635 1990 NFA + 0 NFA + 0 NFA = 1990 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

5" /
1 2"
12" 8"-1 1/8" PL
5" / 5" /
1 2" 1X6 FASCIA, TYP
2"
5 "/1 5:12
5:12 COMPOSITION 1X4 FRIEZE TRIM, TYP
12" SHINGLE ROOF, TYP
5" /
1'-7 1/2" TYP
@ 5:12 PITCH
8'-1 1/8" PL

1X4 TRIM, TYP

8"-1 1/8" PL
EXT WALL LIGHT LAP SIDING, TYP 5" / 12"
6'-0"

(OPT. BRICK @ SIDES)

5" / 12"
150 150
BRICK, TYP

8"-1 1/8" PL
5" / 12"

5" / 12"
2'-0" BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES 5" / 12"
150

5" / 12"
10"-1 1/8" PL
ROOF VENT TYP. 5" / 12"

5" / 12"
5" / 12"
8"-1 1/8" PL
4 ELEVATION N - RIGHT

10'-1 1/8" PL
5" / 12"

1/16" = 1'-0"

8"-1 1/8" PL RAKE 10"-1 1/8" PL 10'-1 1/8" PL

5" / 5:12

VERSION 7
12" 12" 1 2"
5" / 5:12 5" / 5" /
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION 5:12 1 2"


SHINGLE ROOF, TYP

Express Homes - North Central Texas


5:12
5 ELEVATION N - ROOF PLAN

SSE Architectural Design Services


10'-1 1/8" PL
1X6 FASCIA, TYP

8'-1 1/8" PL
1X4 FRIEZE TRIM, TYP
1/16" = 1'-0"

6'-0"
EXT WALL LIGHT
5'-0"

BRICK, TYP

X30B A, B, F, G, M, N
6X6 POST, TYP. STUCCO, TYP
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 1x4 TRIM, TYP
2'-0" BRICK ROWLOCK CAP, TYP
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
3 ELEVATION N - LEFT 12"
5" /
1/16" = 1'-0" 5:12
COMPOSITION 12"

T. O. FOUNDATION TO ROOF PEAK HEIGHT


5" / 1X6 FASCIA TRIM, TYP
5" / SHINGLE ROOF, TYP 5" / 1 2"
1 2"
5:12 1X4 FRIEZE TRIM, TYP

ADDRESS
14'-9 3/4" PL

BUILDER
1X6 FASCIA TRIM, TYP 12" 5" /
5" / 12" 5" /
1 EXT WALL LIGHT

SUBD.
5:12 2"

PLAN
CITY
1X4 FRIEZE TRIM, TYP

10'-1 1/8" PL
COMPOSITION

LOT
STUCCO, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
10'-1 1/8"
8'-1 1/8" PL

6'-0"
1X4 TRIM, TYP
BRICK, TYP
DATE 12.07.2023

5'-0"
SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP BRICK ROWLOCK CAP, TYP STUCCO, TYP (OPT
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) WOOD-LOOK SIDING)
12/8/2023 9:53:00 AM

2 ELEVATION N - REAR
1/16" = 1'-0"
1 ELEVATION N - FRONT
1/8" = 1'-0"
A70.03
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (10 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 67 LF (10 NFA) = 670 NFA 0 (56 NFA) = 0 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2260 1085 434 542 0 NFA + 450 NFA = 450 NFA 635 670 NFA + 0 NFA + 0 NFA = 670 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
A100.02 A100.02
8"-1 1/8" PL

5" /
1 2"
12"
5" / 5" /
1 2" 1X6 FASCIA, TYP
"
5" / 12 5:12 1'-7 1/2" TYP
5:12 COMPOSITION 1X4 FRIEZE TRIM, TYP @ 5:12 PITCH
12 "

8"-1 1/8" PL
SHINGLE ROOF, TYP
5" / 5" / 12"

5" / 12"
150 150
8'-1 1/8" PL

1X4 TRIM, TYP

8"-1 1/8" PL
EXT WALL LIGHT LAP SIDING, TYP 5" / 12"
6'-0"

(OPT. BRICK @ SIDES)

5" / 12"
BRICK, TYP 5" / 12"
150

5" / 12"
10"-1 1/8" PL
2'-0" BOX OUT HDR w/ 1X6 TRIM ROOF VENT TYP. 5" / 12"
OPT BRICK @ SIDES

5" / 12"
5" / 12"
8"-1 1/8" PL

10'-1 1/8" PL
5" / 12"
ELEVATION N - RIGHT w/ FIRE RATED SOFFITS @
4 SIDES
1/16" = 1'-0" 8"-1 1/8" PL RAKE 10"-1 1/8" PL 2 3 10'-1 1/8" PL
A100.02 A100.02

5" / 5:12 FIRE RATED SOFFIT/ BLOCKING WHEN


12" 12" 1 2" EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
5" / 5:12 5" / LINE (REF PLOT PLAN)
5" /
COMPOSITION 5:12 1 2"

VERSION 7
SHINGLE ROOF, TYP
ELEVATION N - ROOF PLAN w/ FIRE RATED SOFFITS @
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

5:12
5 SIDES

10'-1 1/8" PL
1X6 FASCIA, TYP

Express Homes - North Central Texas


8'-1 1/8" PL
1X4 FRIEZE TRIM, TYP

SSE Architectural Design Services


1/16" = 1'-0"

6'-0"
EXT WALL LIGHT
5'-0"

BRICK, TYP

6X6 POST, TYP. STUCCO, TYP


(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 1x4 TRIM, TYP
2'-0" BRICK ROWLOCK CAP, TYP
(OPT. BRICK @ SIDES) OPT BRICK @ SIDES

X30B A, B, F, G, M, N
FULL BRICK)

BLOCK
ELEVATION N - LEFT w/ FIRE RATED SOFFITS @ SIDES
1/16" = 1'-0"
12"
5" /
5:12
COMPOSITION 12"

T. O. FOUNDATION TO ROOF PEAK HEIGHT


5" / 1X6 FASCIA TRIM, TYP
5" / SHINGLE ROOF, TYP 5" / 1 2"
1 2"
5:12 1X4 FRIEZE TRIM, TYP

ADDRESS
14'-9 3/4" PL

BUILDER
1X6 FASCIA TRIM, TYP 12" 5" /
5" / 5" /

SUBD.
12" 1 EXT WALL LIGHT
2"

PLAN
5:12

CITY
10'-1 1/8" PL

LOT
1X4 FRIEZE TRIM, TYP COMPOSITION STUCCO, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
10'-1 1/8"
8'-1 1/8" PL

6'-0"
1X4 TRIM, TYP BRICK, TYP
DATE 12.07.2023

5'-0"
SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP BRICK ROWLOCK CAP, TYP STUCCO, TYP (OPT
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) WOOD-LOOK SIDING)
12/8/2023 9:53:01 AM

ELEVATION N - FRONT w/ FIRE RATED SOFFITS @


2 ELEVATION N - REAR w/ FIRE RATED SOFFITS @ SIDES 1 SIDES A70.04
1/16" = 1'-0" 1/8" = 1'-0"
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
ATTIC AREA @ (MAIN ROOF)
REQUIRED VENTILATION (IN²) REQUIRED UPPER ATTIC VENTILATION (IN²) PROVIDED UPPER ATTIC VENTILATION (IN²) REQUIRED SOFFIT PROVIDED SOFFIT VENTILATION (IN²)
ATTIC AREA (FT²) 1/300 EXCEPTION 40%-50% OF REQUIRED #SLP Slant Back (65 NFA) #SLP 150 Slant Back (150 NFA) VENTILATION (IN²) LINEAR FEET OF PERFORATED SOFFIT VENT (5 NFA) #8x16 Cut-In Vents (56 NFA) #4x16 Cut-In Vents (28 NFA)
MINIMUM MINIMUM MAXIMUM 0 (65 NFA) = 0 NFA 3 (150 NFA) = 450 NFA MINIMUM 67 LF (5 NFA) = 335 NFA 6 (56 NFA) = 336 NFA 0 (28 NFA) = 0 NFA 10003 Technology Blvd. West
2260 1085 434 542 0 NFA + 450 NFA = 450 NFA 635 335 NFA + 336 NFA + 0 NFA = 671 NFA Dallas, TX. 75220
972-620-8204
NOTES:
1. BAFFLES REQUIRED IN ALL BAYS BETWEEN SOFFIT VENTS WHERE INSULATION IS INSTALLED
2. PROVIDE VENTILATION AS REQUIRED BY CURRENT ADOPTED INTERNATIONAL RESIDENTIAL CODE;
PERFORATED SOFFITS ARE NOT ALLOWED IN SIDE YARDS WITH LESS THAN FIVE FEET FROM SOFFIT TO BUILD LINE
3. PROVIDED CALCULATIONS ARE BASED ON CURRENT INTERNATIONAL RESIDENTIAL CODE; ATTIC VENTILATION
REQUIREMENTS MUST BE MET BY ONE OF THE TWO LISTED OPTIONS: 1/150 STANDARD OR 1/300 EXCEPTION.
4. FIRE RATED SOFFITS REQUIRED WHERE BUILDING IS WITHIN 5 FEET OF PROPERTY LINE.
5. RIDGE VENTS TO BE INSTALLED WITHIN 3'-0" VERTICALLY OF HIGHEST RIDGE IN ATTIC PER CODE.
6. PROVIDED CALCULATIONS ARE FOR STANDARD PLAN OPTIONS: CONTACT ARCHITECT FOR EXTERIOR OPTION
ALTERATIONS.

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
HATCH INDICATES WHERE LINE (REF PLOT PLAN)
PERFORATED SOFFITS ARE
NOT ALLOWED 2 1
5" / A100.02 A100.02
1 2"
12" 8"-1 1/8" PL
5" / 5" /
1 2" 1X6 FASCIA, TYP
12" 5:12
5" /
5:12 COMPOSITION 1X4 FRIEZE TRIM, TYP
12" SHINGLE ROOF, TYP
5" / 56
1'-7 1/2" TYP
@ 5:12 PITCH
8'-1 1/8" PL

1X4 TRIM, TYP

8"-1 1/8" PL
EXT WALL LIGHT LAP SIDING, TYP 5" / 12"
6'-0"

(OPT. BRICK @ SIDES) 56

5" / 12"
150 150
BRICK, TYP

8"-1 1/8" PL
5" / 12"
56

5" / 12"
2'-0" BOX OUT HDR w/ 1X6 TRIM
OPT BRICK @ SIDES 5" / 12"
150

5" / 12"
10"-1 1/8" PL
ELEVATION N - RIGHT w/ FIRE RATED SOFFITS @ 56 ROOF VENT TYP. 5" / 12"

5" / 12"
5" / 12"
56 8"-1 1/8" PL
4 SIDES w/ 5 NFA LOWER VENTILATION

10'-1 1/8" PL
5" / 12"
56
1/16" = 1'-0"

8"-1 1/8" PL RAKE 10"-1 1/8" PL 2 3 10'-1 1/8" PL


A100.02 A100.02

FIRE RATED SOFFIT/ BLOCKING WHEN


EAVE IS 2'-0" to < 5'-0" FROM PROPERTY
5" / 5:12 LINE (REF PLOT PLAN)

VERSION 7
12" 12" 1 2"
5" / 5:12 5" / 5" /
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

COMPOSITION 5:12 1 2"


SHINGLE ROOF, TYP ELEVATION N - ROOF PLAN w/ FIRE RATED SOFFITS @

Express Homes - North Central Texas


5:12
5 SIDES w/ 5 NFA LOWER VENTILATION

SSE Architectural Design Services


10'-1 1/8" PL
1X6 FASCIA, TYP

8'-1 1/8" PL
1X4 FRIEZE TRIM, TYP 1/16" = 1'-0"

6'-0"
EXT WALL LIGHT
5'-0"

BRICK, TYP

X30B A, B, F, G, M, N
6X6 POST, TYP. STUCCO, TYP
(WRAP w/ OPT LAP SIDING, TYP BOX OUT HDR w/ 1x4 TRIM, TYP
2'-0" BRICK ROWLOCK CAP, TYP
FULL BRICK) (OPT. BRICK @ SIDES) OPT BRICK @ SIDES

BLOCK
ELEVATION N - LEFT w/ FIRE RATED SOFFITS @ SIDES
3 w/ 5 NFA LOWER VENTILATION 12"
5" /
1/16" = 1'-0" 5:12
COMPOSITION 12"

T. O. FOUNDATION TO ROOF PEAK HEIGHT


5" / 1X6 FASCIA TRIM, TYP
5" / SHINGLE ROOF, TYP 5" / 1 2"
1 2"
5:12 1X4 FRIEZE TRIM, TYP

ADDRESS
14'-9 3/4" PL

BUILDER
1X6 FASCIA TRIM, TYP 12" 5" /
5" / 12" 5" /
1 EXT WALL LIGHT

SUBD.
5:12 2"

PLAN
CITY
1X4 FRIEZE TRIM, TYP

10'-1 1/8" PL
COMPOSITION

LOT
STUCCO, TYP
SHINGLE ROOF, TYP

8'-1 1/8" PL
10'-1 1/8"
8'-1 1/8" PL

6'-0"
1X4 TRIM, TYP
BRICK, TYP
DATE 12.07.2023

5'-0"
SCALE As indicated
LAP SIDING, TYP 6X6 POST, TYP BRICK ROWLOCK CAP, TYP STUCCO, TYP (OPT
(OPT FULL BRICK) (WRAP w/ OPT FULL BRICK) WOOD-LOOK SIDING)
12/8/2023 9:53:03 AM

ELEVATION N - REAR w/ FIRE RATED SOFFITS @ SIDES ELEVATION N - FRONT w/ FIRE RATED SOFFITS @
2 w/ 5 NFA LOWER VENTILATION
1/16" = 1'-0"
1 SIDES w/ 5 NFA LOWER VENTILATION
1/8" = 1'-0"
A70.05
STRAND 2351667
12/8/2023 9:53:04 AM C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

3
6
3'-0"

2'-10 1/2"

1 1/2" COUNTER TOP


THICKNESS

1/4" = 1'-0"
1/4" = 1'-0"

OVERHANG
W

UTILITY

1 1/2" COUNTER TOP


2'-0"
1SH

5'-3 1/2"

3'-8"

6 1/2"
COUNTER TOP
D

KITCHEN ISLAND
6'-0" 2'-1 1/8"

8'-1 1/8"

OVERHANG
@ 34'-12'' AFF
2X6 HALF WALL

1'-0" COUNTER TOP


8'-1 1/8"

3'-0" 4" 4" 3'-6" 11 1/8"


3'-0"

2'-10 1/2"
1 1/2" COUNTER TOP
1'-6"

OVERHANG
THICKNESS

1 1/2" COUNTER TOP


3'-0"

1/4" = 1'-0"
1/4" = 1'-0"
21"(D)

2 1/2"
42'' MIRROR

1'-6"

5 BATH 2

1'-0"
24"(D)
2'-8 1/2"
1'-11 3/4"

3'-0"
24"(D)
6'-8"
6'-11"

2 KITCHEN ISLAND
LOW WALL
COUNTER TOP
1'-11 3/4"

3'-11 1/2"

DW

2'-0"

3" END PANEL


4 1/2"
TUB

2'-6"

2 1/2"
OVERHANG
1 1/2" COUNTER TOP

1
4

2'-6"
2'-6"

12"(D)

24"(D)

1/4" = 1'-0"
1/4" = 1'-0"
BATH 1

KITCHEN
3'-3"
3'-3"
1'-3"

REF
2'-6"
21"(D)
2'-6"

OPT SINK
42'' MIRROR

2'-6"
2'-6"

24"(D)
12"(D)
2'-6"
21"(D)
1'-3"

VENT

3'-0" 4" 4" 3'-6" 11 1/8"


MICRO/

2'-6"
2'-6"

12"(D)

RANGE

8'-1 1/8"

1'-6" 1'-0"
2'-6"
2'-6"

24"(D)
12"(D)

3'-0" 1'-6" 2'-6" 2'-1 1/8"

9'-1 1/8"

PLAN CONVERTED FROM X30B V4 REGIONAL SET

BUILDER Express Homes - North Central Texas


SUBD. SSE Architectural Design Services
STRAND
972-620-8204

LOT BLOCK
Dallas, TX. 75220

ADDRESS
CITY
DATE 12.07.2023
SCALE 1/4" = 1'-0"

A90.01
10003 Technology Blvd. West

PLAN
2351667

X30B A, B, F, G, M, N VERSION 7
The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

°
.81
129
39.8

2'-6 3/4"
° 1
39.8

3 1/2"
6'-1 1/2"

7 GABLE DETAIL
1/4" = 1'-0"

REFERENCE ELEVATION FOR 1x TRIM


1x12 DOUBLE CLEAT AT RE: PLAN CALL OUT.
TRANSITION
EXTERIOR FINISH AS SPEC, REF
EXTERIOR ELEVATIONS FOR MATERIAL

INSULATION PER CODE


12" DEPTH

1'-0" 1'-0" 1'-0" 1'-0"


1x4 CLEAT TYP. 16" DEPTH

1x4 CLEAT TYP. 2'-0"


7'-0"

(NAILED TO STUD, INSTALL INTERMEDIATE SHEATHING PER ENGINEERING


TYP.
6'-0"

EVERY 32", MIN.)


TO HAVE 1x2 2x HORIZONTAL BLOCKING 2x FRAMING, REF STRUCTURAL
CLEAT PER ENGINEERING
3'-6"

45° CUT ON
2'-5"

BOTTOM-FRONT

2'-0"

VERSION 7
CORNERS
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

MASONRY AS SPEC, REF EXTERIOR ELEVATIONS FOR MATERIAL


NOTE: ALL SHELVES TO BE CUT OFF FLOOR AND

Express Homes - North Central Texas


CUT 45° ON FRONT CORNER. NOTE: SUPPORT ALL INTERIOR CORNERS ICC AND/OR CITY APPROVED
AT WALK-IN LINEN/ PANTRY WITH 1x2 EXTERIOR SHEATHING

SSE Architectural Design Services


CLEAT VERTICALLY AT CORNER.

4 TYPICAL ROD & SHELF DETAIL 5 TYPICAL LINEN/ PANTRY 6 TYPICAL FURRED WALL DETAIL
3/16" = 1'-0" 3/16" = 1'-0" 3/8" = 1'-0"

X30B A, B, F, G, M, N
BLOCK
1x12

DOUBLE CLEAT AT
2'-0" TRANSITION
TYP.
1x4 CLEAT
1'-0" 1'-0" 1'-0" 1'-0" 1'-0"

12" DEPTH 1x4 CLEAT


TYP.

ADDRESS
NOTE: ATTIC STAIR PULL-DOWN TO BE

BUILDER
TRIMMED ON INSIDE OF DOOR AND

7'-0"
OUTSIDE OF DOOR FRAME.

SUBD.
6'-0"

PLAN
CITY
LOT
CASING ON DOOR
7'-0"

3'-6"

1x4 CLEAT
45° CUT ON
BOTTOM-FRONT
CORNERS
DATE 12.07.2023
2'-0"

SCALE As indicated
1'-2"

NOTES: 1.) 1x4 CLEAT ONLY ALONG REAR WALL & SIDES AT ROD/SHELF
2.) CLEAT SUPPORT FOR SHELF BRACKET TO BE 9" FROM BOTTOM OF
REAR WALL CLEAT CASING OUTSIDE OF FRAME
NOTE: SHELVES TO BE CUT 3.) DOUBLE CLEAT AT ENDS OF ALL INTERIOR SHELVING
OFF FLOOR AND CUT
12/8/2023 9:53:04 AM

45° ON FRONT CORNER.

TYPICAL ATTIC PULL-DOWN


3 TYPICAL 5 SHELF DETAIL
3/16" = 1'-0"
2 TYPICAL ROD & SHELF DETAIL
3/16" = 1'-0"
1 STAIR TRIM DETAIL
3/16" = 1'-0"
A90.02
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

REF ELEV FOR ROOF


PITCH & OVERHANG
TOP OF PLATE
BEAM PER
STRUCTURAL
GALVANIZED FLASHING, TYP
SOFFIT BOARD
PAINTABLE CAULK
AS SPECIFIED @
CLG OF PORCH

2x FRAMING

SHEET SIDING OVER WEATHER


BARRIER OVER 7/16" OSB EXTERIOR
SHEATHING,TYP

INTERNAL COLUMN PER


STRUCTURAL

REF ELEV

VERSION 7
COLUMN PER STRUCTURAL
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

Express Homes - North Central Texas


7 1/4"

SSE Architectural Design Services


PT 2X PLATE

HOLD SHEATHING 3/4"


ABOVE CONCRETE

11" BRICK/STONE 2'-1 71/256" SLOPE CONCRETE

X30B A, B, F, G, M, N
1/4" PER FOOT

1'-10 71/256"

BLOCK
8" THIN STONE CONCRETE PEDESTAL
FORMED WITH PORCH
1'-7 199/256"
5 1/2" SIDING/STUCCO

1'-0" 7 199/256"

1'-0"
1'-7 199/256"
2'-0"

51
/2"

ADDRESS
BUILDER
7 199/256"

SUBD.
2X FRAMING

PLAN
7 1/4"

CITY
LOT
COLUMN PER STRUCTURAL

EXTEND TO EXTEND TO 2 1/2"


FRAME FRAME SHEET SIDING OVER WEATHER
BARRIER OVER 7/16" OSB EXTERIOR 7 1/4"
8" 5 1/2"
SHEATHING,TYP DATE 12.07.2023
11" SCALE 1/2" = 1'-0"

CB-23 CB/DFB-12
12/8/2023 9:53:04 AM

3 CB-23 BRACKET DETAIL 2 CB-12 BRACKET DETAIL 1 8X8 BUILT-UP POST DETAIL
1/2" = 1'-0" 1/2" = 1'-0" 1/2" = 1'-0"
A90.03
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

ADD INTAKE AIR AS REQUIRED WHERE ADD INTAKE AIR AS REQUIRED WHERE ADD INTAKE AIR AS REQUIRED WHERE ADD INTAKE AIR AS REQUIRED WHERE
NON-PERFORATED, FIRE-RESISTANCE NON-PERFORATED, FIRE-RESISTANCE NON-PERFORATED, FIRE-RESISTANCE NON-PERFORATED, FIRE-RESISTANCE
RATED SOFFIT IS REQUIRED RATED SOFFIT IS REQUIRED RATED SOFFIT IS REQUIRED RATED SOFFIT IS REQUIRED
COMPOSITION SHINGLES AS SPEC COMPOSITION SHINGLES AS SPEC COMPOSITION SHINGLES AS SPEC COMPOSITION SHINGLES AS SPEC
ROOF DECKING AS SPEC ROOF DECKING AS SPEC ROOF DECKING AS SPEC ROOF DECKING AS SPEC
ROOF FRAMING, REF. STRUCTURAL ROOF FRAMING, REF. STRUCTURAL ROOF FRAMING, REF. STRUCTURAL ROOF FRAMING, REF. STRUCTURAL
INSTALL BAFFLES AS REQUIRED TO INSTALL BAFFLES AS REQUIRED TO INSTALL BAFFLES AS REQUIRED TO INSTALL BAFFLES AS REQUIRED TO
MAINTAIN 2" AIR SPACE MAINTAIN 2" AIR SPACE MAINTAIN 2" AIR SPACE MAINTAIN 2" AIR SPACE
DOUBLE 2x CONTINUOUS DOUBLE 2x CONTINUOUS DOUBLE 2x CONTINUOUS DOUBLE 2x CONTINUOUS
TOP PLATE TOP PLATE TOP PLATE TOP PLATE

4 3/4"

4 3/4"
4 3/4"

4 3/4"
2x BLOCKING 2x BLOCKING 2x BLOCKING 2x BLOCKING
GALVANIZED DRIP EDGE GALVANIZED DRIP EDGE GALVANIZED DRIP EDGE GALVANIZED DRIP EDGE
1x FASCIA TRIM 1x FASCIA TRIM 1x FASCIA TRIM 1x FASCIA TRIM
SEALANT SEALANT SEALANT SEALANT
5/16" CEMENTITIOUS SOFFIT 5/16" CEMENTITIOUS SOFFIT
(EXTERIOR), ADD 5/8" TYPE 'X' (EXTERIOR), ADD 5/8" TYPE 'X' 5/16" CEMENTITIOUS SOFFIT 5/16" CEMENTITIOUS SOFFIT
GYPSUM BOARD (INTERIOR) AS GYPSUM BOARD (INTERIOR) AS (EXTERIOR), ADD 5/8" TYPE 'X' (EXTERIOR), ADD 5/8" TYPE 'X'
GYPSUM BOARD (INTERIOR) AS GYPSUM BOARD (INTERIOR) AS

VERSION 7
NEEDED TO MEET REQUIRED FIRE NEEDED TO MEET REQUIRED FIRE
RESISTANCE RATING. DO NOT RESISTANCE RATING. DO NOT NEEDED TO MEET REQUIRED FIRE NEEDED TO MEET REQUIRED FIRE
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

PENETRATE. PENETRATE. RESISTANCE RATING. DO NOT RESISTANCE RATING. DO NOT


PENETRATE. PENETRATE.
SEALANT

Express Homes - North Central Texas


SEALANT
SEALANT
1x FRIEZE TRIM SEALANT

PLATE & CEILING HEIGHT VARY, REF. PLAN

PLATE & CEILING HEIGHT VARY, REF. PLAN


PLATE & CEILING HEIGHT VARY, REF. PLAN

PLATE & CEILING HEIGHT VARY, REF. PLAN

1x FRIEZE TRIM 1x FRIEZE TRIM

SSE Architectural Design Services


SOLDIER 1x FRIEZE TRIM
SOLDIER COURSE

WINDOW HEIGHT VARIES, REF. PLAN


WINDOW HEIGHT VARIES, REF. PLAN

COURSE 1x WINDOW TRIM AS SPEC


WINDOW HEADER BRICK DETAIL AS SPEC INSULATION PER CODE
INSULATION PER CODE
WINDOW HEADER, REF. STRUCTURAL WINDOW HEADER, REF. STRUCTURAL

WINDOW HEADER HEIGHT VARIES, REF. PLAN


WINDOW HEADER HEIGHT VARIES, REF. PLAN

CEILING FINISH AS SPEC


CEILING FINISH AS SPEC INSULATION PER CODE INSULATION PER CODE
CEILING FINISH AS SPEC INTERIOR WALL FINISH AS SPEC
INTERIOR WALL FINISH AS SPEC CEILING FINISH AS SPEC

X30B A, B, F, G, M, N
INTERIOR WALL FINISH AS SPEC
2x STUDS AS SPEC 2x STUDS AS SPEC INTERIOR WALL FINISH AS SPEC

BLOCK
C.I. CONTINUOUS INSULATION PER CODE WINDOW AS SPEC
WINDOW AS SPEC
C.I. CONTINUOUS INSULATION PER CODE
INSULATION PER CODE
WINDOW SILL, REF. STRUCTURAL INSULATION PER CODE
ICC AND/OR CITY APPROVED
WINDOW SILL BRICK DETAIL AS SPEC ICC AND/OR CITY WINDOW SILL, REF. STRUCTURAL
EXTERIOR SHEATHING
(SLOPE TO DRAIN) APPROVED EXTERIOR 1x WINDOW TRIM AS SPEC
MASONRY AS SPEC C.I. CONTINUOUS INSULATION PER CODE SHEATHING
2x STUDS AS SPEC
INSULATION PER CODE SIDING AS SPEC
C.I. CONTINUOUS INSULATION PER CODE

VARIES, REF. PLAN


VARIES, REF. PLAN

MASONRY TIES PER CODE ICC AND/OR CITY APPROVED


EXTERIOR SHEATHING INSULATION PER CODE
FLOOR FINISH AS SPEC

ADDRESS
FLOOR FINISH AS SPEC 2x STUDS AS SPEC FLOOR FINISH AS SPEC

BUILDER
MASONRY TIES PER CODE
BASE AS SPEC ICC AND/OR CITY APPROVED

SUBD.
BASE AS SPEC FLOOR FINISH AS SPEC

PLAN
EXTERIOR SHEATHING

CITY
2x BASE PLATE P.T.

LOT
2x BASE PLATE P.T.
SIDING AS SPEC
MASONRY AS SPEC
ANCHOR PER CODE
WEEP HOLES PER CODE 2x BASE PLATE P.T.
WEEP HOLES PER CODE
ANCHOR PER CODE 2x BASE PLATE P.T.
SEE FOUNDATION DETAILS BASE AS SPEC SEE FOUNDATION DETAILS
BASE AS SPEC DATE 12.07.2023
ANCHOR PER CODE
ANCHOR PER CODE
SEE FOUNDATION DETAILS
SCALE 3/8" = 1'-0"
SEE FOUNDATION DETAILS

TYPICAL WALL SECTION - 1 TYPICAL WALL SECTION - 1


12/8/2023 9:53:05 AM

TYPICAL WALL SECTION - 1 STORY - MASONRY - WINDOW TYPICAL WALL SECTION - 1 STORY - SIDING - WINDOW
STORY - MASONRY (2021 IRC)
3/8" = 1'-0"
(2021 IRC)
3/8" = 1'-0"
STORY - SIDING (2021 IRC)
3/8" = 1'-0"
(2021 IRC)
3/8" = 1'-0"
A90.04
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

BLOCK AS REQUIRED
SLOPE TO BACK
SLOPE TO BACK
SNAP ON METAL COPING,
SNAP ON METAL COPING,
INSTALL PER MANUFACTURER
INSTALL PER MANUFACTURER
RECOMMENDATIONS
RECOMMENDATIONS
DOUBLE 2x CONTINUOUS
DOUBLE 2x CONTINUOUS
TOP PLATE
TOP PLATE
WEATHER BARRIER
WEATHER BARRIER

WEATHER BARRIER TAPE


WEATHER BARRIER TAPE

SIDING AND/OR ONE-COAT


SIDING AND/OR ONE-COAT
STUCCO SYSTEM AS SPEC,
STUCCO SYSTEM AS SPEC,
REF ELEVATION
REF ELEVATION

ICC AND/OR CITY APPROVED


ICC AND/OR CITY APPROVED
WATER REPELLANT SHEATHING,
WATER REPELLANT SHEATHING,
REF STRUCTURAL
REF STRUCTURAL
MASONRY AS SPEC, REF
ELEVATION

TYPICAL PARAPET CAP DETAIL


4 - MASONRY 3 TYPICAL PARAPET CAP DETAIL
1 1/2" = 1'-0" 1 1/2" = 1'-0"

VERSION 7
SIDING AND/OR ONE-COAT STUCCO SIDING AND/OR ONE-COAT STUCCO
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

SYSTEM AS SPEC, REF ELEVATION SYSTEM AS SPEC, REF ELEVATION


ICC AND/OR CITY APPROVED
WEATHER BARRIER TAPE ICC AND/OR CITY APPROVED

Express Homes - North Central Texas


WATER REPELLANT WEATHER BARRIER TAPE
WATER REPELLANT
SHEATHING, REF STRUCTURAL 24 GA GALVANIZED PAINT GRIP SHEATHING, REF STRUCTURAL

SSE Architectural Design Services


24 GA GALVANIZED PAINT GRIP
METAL FLASHING, PAINT TO
METAL FLASHING, PAINT TO
MATCH WOOD LOOK SIDING
MATCH FINISH ABOVE
6" MIN

6" MIN
INSULATION PER CODE CORNER FLASHING TAPE INSULATION PER CODE INSTALL FLASHING IN
FULL BED OF SEALANT
SLOPED MASONRY WAINSCOT
2x STUDS, REF STRUCTURAL

X30B A, B, F, G, M, N
TRANSITION, REF ELEVATION
INTERIOR WALL
FINISH AS SPEC

BLOCK
INTERIOR WALL
FINISH AS SPEC

1/2" MIN
DOUBLE 2x CONTINUOUS
TOP PLATE
SEALANT MATCHING WOOD-LOOK
SIDING

2x STUDS, REF STRUCTURAL


WOOD-LOOK SIDING, TYP MASONRY AS SPEC, REF
ELEVATION

ADDRESS
BUILDER
SUBD.

PLAN
CITY
LOT
WOOD LOOK SIDING WALL CAP MASONRY WAINSCOT CAP
2 DETAIL 1 DETAIL
1 1/2" = 1'-0" 1 1/2" = 1'-0"
DATE 12.07.2023
SCALE 1 1/2" = 1'-0"
12/8/2023 9:53:05 AM

A100.00
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
10003 Technology Blvd. West
Dallas, TX. 75220
972-620-8204

INSULATION PER CODE


WOOD-LOOK SIDING, ABUT TO TRIM INSULATION PER CODE
w/ MANUFACTURER RECOMMENDED CORNER FLASHING TAPE
CORNER FLASHING TAPE
GAP; DO NOT OVERLAY TRIM ON
SIDING 2x STUDS, REF STRUCTURAL WEATHER BARRIER
2x STUDS, REF STRUCTURAL

1x3 WOOD-LOOK TRIM SIDING AS SPEC, REF ELEVATION;


ABUT TO TRIM w/ MANUFACTURER ONE-COAT STUCCO SYSTEM
SURROUND, MITER @ CORNERS
WINDOW STYLE RECOMMENDED GAP; DO NOT INTERIOR WALL FINISH AS SPEC
VARIES, REF PLAN INTERIOR WALL FINISH AS SPEC OVERLAY TRIM ON SIDING BACKER ROD & SEALANT MATCHING
COLOR OF WOOD-LOOK SIDING
PAINTABLE SEALANT, PAINT TO
APPLY SEALANT MATCHING
MATCH ADJACENT SIDING ICC AND/OR CITY APPROVED 1x3 WOOD-LOOK TRIM
WOOD-LOOK SIDING @
ICC AND/OR CITY APPROVED WATER REPELLANT
JAMB & SILL EXPANSION 1X2 TRIM, PAINT TO MATCH
WATER REPELLANT SHEATHING, SHEATHING, REF APPLY SEALANT MATCHING WOOD-
GAPS; DO NOT SEAL @ ADJACENT SIDING
REF STRUCTURAL STRUCTURAL LOOK SIDING @ EXPANSION GAP
HEAD
APPLY SEALANT MATCHING WOOD- WOOD-LOOK SIDING, ABUT TO TRIM
LOOK SIDING @ EXPANSION GAP w/ MANUFACTURER RECOMMENDED
WOOD-LOOK SIDING, ABUT TO TRIM GAP; DO NOT OVERLAY TRIM ON
w/ MANUFACTURER RECOMMENDED SIDING
GAP; DO NOT OVERLAY TRIM ON
SIDING
PLAN VIEW PLAN VIEW

WOOD LOOK SIDING TO


WOOD LOOK SIDING - WINDOW PAINTED SIDING - INSIDE WOOD LOOK SIDING TO
6 5 CORNER 4 STUCCO - INSIDE CORNER
TRIM
1 1/2" = 1'-0" 1 1/2" = 1'-0"
3/8" = 1'-0"

DOUBLE 2x CONTINUOUS

VERSION 7
TOP PLATE
ROOF DECKING, REF
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

STRUCTURAL

Express Homes - North Central Texas


ROOF FRAMING, REF

SSE Architectural Design Services


STRUCTURAL
COMPOSITION
SHINGLES AS SPEC

INSULATION PER CODE


2x SUBFASCIA

X30B A, B, F, G, M, N
CORNER FLASHING TAPE

2x STUDS, REF STRUCTURAL ICC AND/OR CITY APPROVED INTERIOR WALL FINISH AS SPEC

BLOCK
FASCIA, TYP WATER REPELLANT SHEATHING,
REF STRUCTURAL INSULATION PER CODE
SOFFIT BOARD, TYP; BRICK TIES PER CODE
PAINT TO MATCH FASCIA INTERIOR WALL FINISH AS SPEC
2x NAILER MASONRY AS SPEC, WOOD-LOOK SIDING
REF ELEVATION
1X4 FRIEZE TRIM, PAINT TO MATCH FASCIA
ICC AND/OR CITY APPROVED BACKER ROD & SEALANT MATCHING
WOOD-LOOK SIDING, TYP; OVERLAY OF FRIEZE TRIM ON
WATER REPELLANT SHEATHING, COLOR OF WOOD-LOOK SIDING CORNER FLASHING TAPE
SIDING IS ACCEPTABLE
REF STRUCTURAL
INSULATION PER CODE 1x3 WOOD-LOOK TRIM
CLEAR ANODIZED
ICC AND/OR CITY APPROVED WATER APPLY SEALANT MATCHING WOOD-

ADDRESS
ALUMINUM LOW-PROFILE

BUILDER
REPELLANT SHEATHING, REF STRUCTURAL LOOK SIDING @ EXPANSION GAP OUTSIDE CORNER TRIM
2x STUDS, REF STRUCTURAL

SUBD.
INTERIOR WALL FINISH AS SPEC WOOD-LOOK SIDING, ABUT TO TRIM

PLAN
CITY
w/ MANUFACTURER RECOMMENDED

LOT
GAP; DO NOT OVERLAY TRIM ON
PLAN VIEW SIDING PLAN VIEW

DATE 12.07.2023
SCALE As indicated
WOOD-LOOK SIDING - WALL & WOOD LOOK SIDING TO WOOD LOOK SIDING - OUTSIDE
3 SOFFIT INTERSECTION 2 MASONRY - INSIDE CORNER 1 CORNER
12/8/2023 9:53:06 AM

1 1/2" = 1'-0" 1 1/2" = 1'-0" 1 1/2" = 1'-0"

A100.01
STRAND 2351667
PLAN CONVERTED FROM X30B V4 REGIONAL SET

The use of these plans and specifications shall be restricted to the site for which they were prepared. Any reproduction or distribution is expressly limited to such use. Any other reproduction, reuse or disclosure by any method, in whole or in part, is prohibited. These drawings and specifications contain proprietary information and title remains in STRAND SYSTEMS ENGINEERING INC.
IN ACCORDANCE WITH THE 2021
IRC R302.1 EXTERIOR WALLS. EXTERIOR WALLS
DWELLING - GARAGE SEPARATION CONSTRUCTION, PROJECTIONS, OPENINGS
AND PENETRATIONS OF EXTERIOR WALLS OF
DWELLINGS AND ACCESSORY BUILDINGS SHALL MINIMUM FIRE
EXTERIOR WALL ELEMENT MINIMUM FIRE-RESISTANCE RATING
COMPLY WITH TABLE R302.1; OR DWELLINGS SEPARATION DISTANCE 10003 Technology Blvd. West
SEPARATION MATERIAL EQUIPPED THROUGHOUT WITH AN AUTOMATIC
SPRINKLER SYSTEM INSTALLED IN ACCORDANCE 1 HOUR -TESTED IN ACCORDANCE WITH ASTM E119, Dallas, TX. 75220
NOT LESS THAN 1/2-INCH GYPSUM BOARD OR EQUIVALENT APPLIED TO THE WITH SECTION P2904 SHALL COMPLY WITH FIRE-RESISTANCE RATED UL 263 OR SECTION 703.3 OF THE INTERNATIONAL 0 FEET 972-620-8204
FROM RESIDENCE AND ATTICS
TABLE R302.1 BUILDING CODE WITH EXPOSURE FROM BOTH SIDES
GARAGE SIDE WALLS
FROM HABITABLE ROOMS ABOVE GARAGE NOT LESS THAN 5/8-INCH TYPE X GYPSUM BOARD OR EQUIVALENT NOT FIRE-RESISTANCE RATED 0 HOURS >_ 5 FEET

EXCEPTIONS
1. WALLS, PROJECTIONS, OPENINGS OR PENETRATIONS IN WALLS PERPENDICULAR NOT ALLOWED N/A < 2 FEET
STRUCTURE(S) SUPPORTING FLOOR/CEILING ASSEMBLIES USED FOR SEPARATION NOT LESS THAN 1/2-INCH GYPSUM BOARD OR EQUIVALENT TO THE LINE USED TO DETERMINE THE FIRE SEPARATION DISTANCE.
REQUIRED BY THIS SECTION
2. WALLS OF DWELLINGS AND ACCESSORY STRUCTURES LOCATED ON THE SAME 1 HOUR ON THE UNDERSIDE, OR HEAVY TIMBER, OR
PROJECTIONS FIRE-RESISTANCE RATED _> 2 FEET TO < 5 FEET
LOT. FIRE-RETARDANT-TREATED WOOD a,b
GARAGES LOCATED LESS THAN 3 FEET FROM DWELLING UNIT ON THE SAME LOT NOT LESS THAN 1/2-INCH GYPSUM BOARD OR EQUIVALENT APPLIED TO THE
INTERIOR SIDE OF EXTERIOR WALLS THAT ARE WITHIN THIS AREA 3. DETACHED TOOL SHEDS AND STORAGE SHEDS, PLAYHOUSES NOT FIRE-RESISTANCE RATED 0 HOURS >_ 5 FEET
AND SIMILAR STRUCTURES EXEMPTED FROM PERMITS ARE NOT REQUIRED TO
PROVIDE WALL PROTECTION BASED ON LOCATION ON THE LOT. PROJECTIONS
BEYOND THE EXTERIOR WALL SHALL NOT EXTEND OVER THE LOT LINE. NOT ALLOWED N/A < 3 FEET
FOR SI: 1 INCH = 25.4 MM, 1 FOOT = 304.8 MM
4. DETACHED GARAGES ACCESORY TO A DWELLING LOCATED WITHIN 2 FEET (610 OPENINGS IN WALLS 25% MAXIMUMUM WALL AREA 0 HOURS 3 FEET
MM) OF A LOT LINE ARE PERMITTED TO HAVE ROOF EAVE PROJECTION NOT
R302.6 DWELLING - GARAGE FIRE SEPARATION EXCEEDING 4 INCHES (102 MM).
UNLIMITED 0 HOURS 5 FEET
THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE R302.6. OPENINGS IN 5. FOUNDATION VENTS INSTALLED IN COMPLIANCE WITH THIS CODE ARE PERMITTED.
GARAGE WALLS SHALL COMPLY WITH SECTION R302.5. ATTACHMENT OF GYPSUM
COMPLY WITH SECTION R302.4 < 3 FEET
BOARD SHALL COMPLY WITH TABLE R702.3.5. THE WALL SEPARATION PROVISIONS OF
TABLE R302.6 SHALL NOT APPLY TO GARAGE WALLS THAT ARE PERPENDICULAR TO PENETRATIONS ALL
THE ADJACENT DWELLING UNIT WALL. NONE REQUIRED 3 FEET

FOR SI: 1 FOOT = 304.8 MM N/A = NOT APPLICABLE

a. THE ROOF EAVE FIRE-RESISTANCE RATING SHALL BE PERMITTED TO BE REDUCED TO 0 HOURS ON THE UNDERSIDE OF THE EAVE IF FIRE BLOCKING IS PROVIDED
FROM THE WALL TOP PLATE TO UNDERSIDE OF THE ROOF SHEATHING
b. THE ROOF EAVE FIRE-RESISTANCE RATING SHALL BE PERMITTED TO BE REDUCED TO 0 HOURS ON THE UNDERSIDE OF THE EAVE PROVIDED THAT GABLE VENT
OPENINGS ARE NOT INSTALLED.

5 TABLE R302.6 (2021 IRC)1 4 TABLE R302.1(1) (2021 IRC)1


12" = 1'-0" 12" = 1'-0" NOTE:
CONTRACTOR SHALL ENSURE COMPLIANCE WITH LOCAL JURISDICTION REQUIREMENTS AND ADOPTED CODES, REGULATIONS, AND STANDARDS. THE
ABOVE REFERENCE TABLES ARE FROM 2021 IRC - CONTRACTOR TO VERIFY REQUIREMENTS OF DIFFERENT CODE VERSIONS AS APPLICABLE.

COMPOSITION SHINGLES AS SPEC COMPOSITION SHINGLES AS SPEC COMPOSITION SHINGLES AS SPEC

ROOF DECKING AS SPEC ROOF DECKING AS SPEC ROOF DECKING AS SPEC

ROOF FRAMING, REF STRUCTURAL ROOF FRAMING, REF STRUCTURAL ROOF FRAMING, REF STRUCTURAL

VERSION 7
INSULATION PER CODE INSULATION PER CODE INSULATION PER CODE
C:\Users\dgarcia\Desktop\New folder (2)\07-20\nct\New folder (5)\X30B_2023-12-07_v7.rvt

OPT1 - PROVIDE CONTINUOUS 2x FIRE OPT1 - PROVIDE CONTINUOUS 2x FIRE OPT1 - PROVIDE CONTINUOUS 2x FIRE

Express Homes - North Central Texas


BLOCKING FROM WALL TOP PLATE TO BLOCKING FROM WALL TOP PLATE TO BLOCKING FROM WALL TOP PLATE TO
UNDERSIDE OF ROOF SHEATHING UNDERSIDE OF ROOF SHEATHING UNDERSIDE OF ROOF SHEATHING

SSE Architectural Design Services


DOUBLE 2x CONTINUOUS DOUBLE 2x CONTINUOUS DOUBLE 2x CONTINUOUS
TOP PLATE TOP PLATE TOP PLATE
CONTINUOUS 2x BLOCKING CONTINUOUS 2x BLOCKING CONTINUOUS 2x BLOCKING
4 3/4"

4 3/4"

4 3/4"
PROVIDE INTERMEDIATE BLOCKING PROVIDE INTERMEDIATE BLOCKING PROVIDE INTERMEDIATE BLOCKING
@ 12" OC FOR GYP BOARD @ 12" OC FOR GYP BOARD @ 12" OC FOR GYP BOARD
ATTACHMENT ATTACHMENT ATTACHMENT

X30B A, B, F, G, M, N
PLUMB CUT RAFTER TAILW/LEVEL PLUMB CUT RAFTER TAILW/LEVEL PLUMB CUT RAFTER TAILW/LEVEL
HORIZONTAL CUT HORIZONTAL CUT HORIZONTAL CUT

BLOCK
GALVANIZED DRIP EDGE GALVANIZED DRIP EDGE GALVANIZED DRIP EDGE

2x4 SUB-FASCIA 2x4 SUB-FASCIA 2x4 SUB-FASCIA


FASCIA TRIM AS SPEC FASCIA TRIM AS SPEC FASCIA TRIM AS SPEC
OPT2 - (2) LAYERS 5/8" TYPE 'X' OPT2 - (2) LAYERS 5/8" TYPE 'X' OPT2 - (2) LAYERS 5/8" TYPE 'X'
GYPSUM BOARD; ATTACH AND FINISH VARIES - REFER TO ROOF PLAN GYPSUM BOARD; ATTACH AND FINISH GYPSUM BOARD; ATTACH AND FINISH
PER GA RC 2602 FOR REQUIRED 1 PER GA RC 2602 FOR REQUIRED 1 PER GA RC 2602 FOR REQUIRED 1
HOUR FIRE-RESISTANCE RATING. DO HOUR FIRE-RESISTANCE RATING. DO HOUR FIRE-RESISTANCE RATING. DO
NOT PENETRATE. NOT PENETRATE. NOT PENETRATE.
SOFFIT BOARD AS SPEC, DO NOT SOFFIT BOARD AS SPEC, DO NOT SOFFIT BOARD AS SPEC, DO NOT

ADDRESS
PENETRATE. PENETRATE. PENETRATE.

BUILDER
2 x 2 BLOCKING FRIEZE TRIM AS SPEC VARIES - REFER TO ROOF PLAN FRIEZE TRIM AS SPEC

SUBD.

PLAN
SIDING AS SPEC MASONRY AS SPEC

CITY
1/2" REVEAL

LOT
CEILING FINISH AS SPEC CEILING FINISH AS SPEC
VARIES - REFER TO ROOF PLAN STUCCO AS SPEC

CEILING FINISH AS SPEC


DATE 12.07.2023
1 HR FIRE RATED SOFFIT 1 HR FIRE RATED SOFFIT 1 HR FIRE RATED SOFFIT SCALE As indicated
3 DETAIL - STUCCO 2 DETAIL - SIDING 1 DETAIL - BRICK
1" = 1'-0" 1" = 1'-0" 1" = 1'-0"
12/8/2023 9:53:06 AM

NOTE: NOTE: NOTE:


1 HR FIRE RESISTANCE RATED SOFFIT DETAIL ONLY REQUIRED AND APPLICABLE WHERE FIRE SEPARATION DISTANCE IS 1 HR FIRE RESISTANCE RATED SOFFIT DETAIL ONLY REQUIRED AND APPLICABLE WHERE FIRE SEPARATION DISTANCE IS 1 HR FIRE RESISTANCE RATED SOFFIT DETAIL ONLY REQUIRED AND APPLICABLE WHERE FIRE SEPARATION DISTANCE IS
GREATER THAN 2'-0" OR LESS THAN 5'-0" TO PROPERTY LINE PER 2021 IRC TABLE R302.1(1) GREATER THAN 2'-0" OR LESS THAN 5'-0" TO PROPERTY LINE PER 2021 IRC TABLE R302.1(1) GREATER THAN 2'-0" OR LESS THAN 5'-0" TO PROPERTY LINE PER 2021 IRC TABLE R302.1(1)

PROJECTIONS ARE NOT ALLOWED IF SEPARATION DISTANCE IS LESS THAN 2'-0" PER 2021 IRC TABLE R302.1(1)

PENETRATIONS ALLOWED PER R302.4


PROJECTIONS ARE NOT ALLOWED IF SEPARATION DISTANCE IS LESS THAN 2'-0" PER 2021 IRC TABLE R302.1(1) PROJECTIONS ARE NOT ALLOWED IF SEPARATION DISTANCE IS LESS THAN 2'-0" PER 2021 IRC TABLE R302.1(1) A100.02
PENETRATIONS ALLOWED PER R302.4 PENETRATIONS ALLOWED PER R302.4
STRAND 2351667