CONSTRUCTION OF BUILDING FOR
M/S. ABHAYA WOMEN ENTREPRENEUR
ASSOCIATION, NAGPUR ON PLOT NO T-56,
MIDC INDUSTRIAL AREA, BUTTIBORI,
DISTRICT- NAGPUR
FOUNDATION & COLUMN DETAILS
NOTES:
1. ALL DIMENSIONS ARE IN mm.
2. FOR DIMENSIONS, LEVELS, CENTERLINE AND GENERAL
ARRANGEMENT REFER ARCHITECTURAL DRAWING.
3. BUILDING IS DESIGNED FOR G ONLY.
4. S.B.C. OF THE SOIL IS 240.0 MT/SQM AS PER SOIL REPORT.
5. PRECAST MORTAR BLOCKS OF STRENGTH NOT LESS THAN THAT OF
CONCRETE SHOULD BE USED TO ENSURE REQUISITE CLEAR COVER
TO REINFORCEMENT.
6. MIN. DEPTH OF FOUNDATION SHOULD BE 1.5 M BELOW NATURAL
GROUND LEVEL.
7. MAXIMUM WATER TABLE WILL BELOW FOUNDATION LEVEL IS
ASSUMED.
8. USE M20 GRADE OF CONCRETE & FE500 GRADE STEEL
REINFORCEMENT OF HIGH STRENGTH DEFORMED BARS.
9. DENSITY OF BRICK ASSUME TO BE 19 KN/M³
10. PROVIDE CLEAR COVER OF 50mm FOR FOOTING R/F.
5. PROVIDE CLEAR COVER OF 40mm FOR COLUMN R/F.
5. PROVIDE CLEAR COVER OF 25mm FOR BEAM R/F.
5. PROVIDE CLEAR COVER OF 20mm FOR SLAB R/F.
6. NOT MORE THAN 50% BARS SHOULD BE LAPPED AT ONE SECTION.
7. EXECUTIONS SHALL BE AS PER IS 456:2000 & IS 13920:2016.
8. FOR DIMENSIONS, LEVELS, CENTERLINE AND GENERAL
ARRANGEMENT REFER ARCHITECTURAL DRAWING.
9. ALL BARS SHOULD BE EXTENDED UPTO DEVELOPMENT LENGTH +
10 DIA. OF BAR.
10. LAP SHOULD BE EQUAL TO DEVELOPMENT LENGTH + 10 DIA. OF
BAR.
11. USE OPC/PCC WITH MINIMUM GRADE 43/53 AND USE MAXIMUM
WATER CEMENT RATIO 0.5.
12. NO OVERLAPS ARE ALLOWED IN FOOTING.
13. FOR ISOLATED FOOTING LONG BARS SHALL BE KEPT BELOW SHORT
BARS.
14. FOR COMBINED AND RAFT FOOTING SHORT BARS SHALL BE KEPT
BELOW LONG BARS.
15. GRADE OF CONCRETE FOR P.C.C. IS 1:3:6.
16. PIPES REQUIRED FOR RAIN WATER/ SANITARY OR ANY OTHER
PURPOSE ARE NOT ALLOWED TO BE TAKEN THROUGH COLUMN.
17. SUPERVISION AT OWN RISK.
18. BUILDING IS DESIGN FOR SEISMIC ZONE II AS PER IS 1893:2016.
19. DESIGN IS CARRIED OUT FOR MILD EXPOSURE CONDITION.
20. POSITION OF DRAIN PIPES IN TOILETS MAY VARY AS PER
ARCHITECTURAL REQUIREMENT & SHALL BE 250mm AWAY FROM
SUPPORT.
21. CONCRETE AND STEEL MATERIAL TESTING AT OWNERS RISK.
22. USE CURED MORTOR COVER BLOCKS OF SAME STRENGTH OF
CONCRETE.
23. USE SUPER PLASTICISER TO MAINTAIN WATER / CEMENT RATIO.
24. CURING EXPOSED SURFACE OF CONCRETE SHALL BE KEPT
CONTINUOUSLY IN WET CONDITION FOR MINIMUM 14 DAYS.
25. ALL HOT ROLLED MEMBERS SHALL CONFORM TO BSEN 10025-S275
OR EQUIVALENT.
26. ALL THE BUILT UP MEMBERS SHALL CONFORM TO ASTM A572 OR
BSEN 10025-S355.
27. ALL WELDS ARE AWS STANDARD UNLESS OTHERWISE NOTED.
28. BOLTS FOR MAIN STRUCTURAL CONNECTIONS ARE ASTM A325.
29. BOLTS FOR BRACINGS, PURLINS, GIRTS ETC.. ARE GRADE 4.6
30. PAINTING SYSTEM AND ALL OTHER TERMS AS PER CONTRACTS.
DIA. Ld 10Ø
OF
BAR
8mm 400mm 80mm
10mm 500mm 100mm
12mm 600mm 120mm
16mm 800mm 160mm
20mm 1000mm 200mm
DRG. NO.- 08
SEISMIC ZONE - II
EXPOSURE CONDITION - MILD
BASED ON IS: 456-2000, IS: 13920-2016, IS: 1893-2016, IS:875-1987.
PROJECT - DESIGN FOR PEB STRUCTURE
TITLE - FOUNDATION & COLUMN DETAILS
CLIENT - M/S. ABHAYA WOMEN ENTREPRENEUR ASSOCIATION, NAGPUR
ISO/ABHAYA/PEB /2022/DRG 08 OF 10 DATE - 19/04/2022
DESIGNED BY
VIKRANT R.NAIR
BE (Civil),
M.Tech.(Structures),
M.Tech.(Structural Dynamics
& Earthquake Engg.),
M.Tech.(Geotechnical Engg..),
MIE , PROFESSIONAL ENGINEER,
PE.No: 7006182