Distribution Transformer Voltage Control Using a Single-
Phase Matrix Converter
Citation for published version (APA):
Wang, R., Huisman, H., & Wijnands, C. G. E. (2022). Distribution Transformer Voltage Control Using a Single-
Phase Matrix Converter. In 2022 24th European Conference on Power Electronics and Applications (EPE'22
ECCE Europe) Article 9907157 Institute of Electrical and Electronics Engineers.
https://ieeexplore.ieee.org/document/9907157
Document license:
Unspecified
Document status and date:
Published: 17/10/2022
Document Version:
Accepted manuscript including changes made at the peer-review stage
Please check the document version of this publication:
• A submitted manuscript is the version of the article upon submission and before peer-review. There can be
important differences between the submitted version and the official published version of record. People
interested in the research are advised to contact the author for the final version of the publication, or visit the
DOI to the publisher's website.
• The final author version and the galley proof are versions of the publication after peer review.
• The final published version features the final layout of the paper including the volume, issue and page
numbers.
Link to publication
General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners
and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.
• Users may download and print one copy of any publication from the public portal for the purpose of private study or research.
• You may not further distribute the material or use it for any profit-making activity or commercial gain
• You may freely distribute the URL identifying the publication in the public portal.
If the publication is distributed under the terms of Article 25fa of the Dutch Copyright Act, indicated by the “Taverne” license above, please
follow below link for the End User Agreement:
www.tue.nl/taverne
Take down policy
If you believe that this document breaches copyright please contact us at:
[email protected]providing details and we will investigate your claim.
Download date: 17. Oct. 2024
Distribution transformer voltage control using a single-phase matrix
converter
Rui Wang, dr. ir. Henk Huisman, prof. Korneel Wijnands
Eindhoven University of Technology
P.O. Box 513, 5600 MB Eindhoven, The Netherlands Eindhoven, the Netherlands
Email:
[email protected]Keywords
On-load tap changer(OLTC), Hybrid transformer,AC-AC converter, Single-phase ma-
trix converter.
Abstract
A new topology is proposed for fully-electronic tap changers in distribution transformers. In every single
phase, the voltage is regulated by a 2 × 1 matrix converter, which can be extended using the concept of
multilevel converters. The topology allows reaching the desired functionality with one single tap, which
reduces the cost of the transformer.
Introduction
Medium-voltage (MV) to low-voltage (LV) distribution transformers are used to step down MV grid
voltage to a suitable level for residential consumers. LV side end-users shall receive a stable voltage.
However, due to voltage drop on transmission lines, users can receive different voltage levels due to cor-
responding line impedance and currents. As a trend, residential loads are increasing due to the growing
penetration of electrical vehicles, heat pumps and solar panels. Apart from these, the loads become bidi-
rectional, which roughly doubles the voltage swing at consumer side. As a result, voltage fluctuations
become larger and happen more frequently.
To maintain a relatively stable LV side voltage, tap changers are used to vary the effective transformer
turns ratio. In principle, tap changers can be placed at either MV or LV side of the transformer; the
most common is at the MV side. Fig. 1 shows a simplified circuit of a distribution transformer with
tap changers. The transformer is in Delta-Wye connection; it has (n1a + n1b ) turns at the MV side and
n2 turns at the LV side. The tap winding is located at the MV side, in this example, it has n1b turns in
total and five equivalent tap positions. By switching to different positions, different voltage levels can be
obtained at the LV side.
Fig. 1: Distribution transformer with mechani- Fig. 2: Proposed voltage regulators for a distri-
cal tap changers at the MV side. bution transformer.
Conventional tap changers use mechanical switches, which limit the speed of the tap-changing process.
The resolution of the voltage regulation depends on the number of tap positions. Lifetime of mechan-
ical switches is significantly impacted by arcs during switching. To prolong the lifetime and reduce
maintenance cost, electronically-assisted tap changers use both mechanical and semiconductor switches.
Semiconductor switches are used in the process of switching between different tap position, which helps
to reduce arcs and to extend the lifetime of the mechanical switches. However, the time of the tap-
changing process (between two taps) is still 100 ∼200 ms [1, 2, 3]; and jumping taps is not allowed as
this would lead to large circulating current. Fully-electronic tap changers replace mechanical switches
with semiconductor switches, which bring many advantages compared to mechanical switches [2]:
• Low maintenance cost: The arcs caused by mechanical switches disappear.
• Fast tap-changing process because of the high switching speed of semiconductor devices.
• Better controllability: The LV side voltage can be controlled continuously, which suggests that
these tap changers can be potentially used in power quality management.
Considering the switching and conduction losses, efficiencies of fully-electronic tap changers are lower.
For cost concerns, manufacturing costs are higher for fully-electronic tap changers; however, their main-
tenance costs will be significantly lower compared to designs using mechanical switches. Therefore,
fully-electronic tap changers are very promising compared to conventional products. Previous research
proposed fully-electronic tap changers by inserting parallel half-bridge circuits between multiple tap po-
sitions [5, 6, 7]. In this paper, a new topology is proposed for fully-electronic tap changers as shown in
Fig. 2. The tap changer requires only one tap connection. LV side voltages are controlled by voltage
regulators (VR) on the MV side. In principle, VRs can also be installed at the LV side; in this paper, only
the MV side version is considered.
For simplicity, the following discussion will focus on the VR in one single phase of the distribution
transformer as shown in Fig. 3. Also for simplicity, the transformer is assumed ideal; and filters design
will not be covered.
Voltage regulator
Fig. 4 provides an equivalent circuit of the VR. In this circuit, the VR is presented as three voltage sources
ux , uz and uy . According to coupling of the transformer:
n1a + n1b
uy = uz − uUV + uL (1)
n2
uy can be defined as a function of inputs ux and uz :
1
uy = ((ux + uz ) + K(ux − uz )) (2)
2
where K is a control variable to realize different LV side voltages and −1 6 K 6 1. The effective MV
side winding turns n1,e is defined as:
n1,e uUV
= (3)
n2 uL
By combining (1) and (2), n1,e can be obtained:
1
n1,e = n1a + (1 − K) n1b (4)
2
For K = 1, the tap winding n1b is open and only n1a is used; for K = −1, tap winding is fully connected
and (n1a + n1b ) winding is used at the MV side. The effective MV side winding can be controlled to any
value in between n1a and (n1a + n1b ) by setting K.
For a conventional mechanical tap changer, the grid voltage is applied to the main transformer winding
n1a and part of the tap winding 12 (1 − K) n1b ; whereas the rest of the tap winding 21 (1 + K) n1b is open
and there is no current flowing. However, for the electronic VR, a current iz flows through the entire tap
winding n1b .
Fig. 5 and Fig. 6 show two basic topologies for the VR. For the half-bridge topology, the VR is directly
iy iy
uU iL uU iL
+ +
+ +
un1a n1a un1a n1a
+ +
uUV − ix − uUV − ix −
n2 uL ZL n2 uL ZL
−
+
iy u y Voltage
ux + iy uy ux +
uV un1b n1b uV un1b n1b
+
−
Regulator − uz −
iz − iz −
−
+
uz ideal ideal
Voltage
Regulator
Fig. 3: Voltage regulator of one phase. Fig. 4: Simplified single-phase circuit.
switching between the tap winding terminals. Gate signals are often modulated using PWM. Bidirec-
tional voltage-blocking switches are required due to the AC voltage. The advantage of this circuit is its
simplicity. However, these bidirectional switches need to be controlled very accurately in the commuta-
tion process.
Fig. 6 shows a different solution using the matrix topology, it contains three switching legs X,Y, Z and
a DC link capacitor Cdc . Phases X and Z are connected to the tap winding; they control the circulating
current between the VR and the tap winding. The LV side voltage is determined by the duty cycle of
phase Y . Because of the DC link, bidirectional switches are unnecessary; standard IGBTs or MOSFETs
with diodes can be used. As in the case of mechanical switches, the VR does not need to store energy.
Thus, the DC link voltage is constant in the steady state; and as a consequence, the capacitor can be
small in principal. This circuit needs two more switches compared to the AC half bridge. Thus, the
matrix circuit has a higher manufacturing cost. However, the implementation of control is easier because
bidirectional switches are not required.
Considering MV applications, the high voltage is challenging for IGBTs/MOSFETs. For the half bridge
circuit, the possible solution would be using series connected switches to reduce voltage stress on a single
switch. However, this requires a lot of efforts in hardware design. For the matrix converter, there are
more multilevel solutions available, such like modular multilevel converters (MMC). This topic will be
covered in future research.
Matrix converter control
A cascade control strategy is used for the matrix circuit. The inner current loop controls the circulating
current to guarantee energy balance; and the voltage loop keeps the DC link voltage constant.
The current loop is shown in Fig. 8. The circulating current is defined as:
i∆ = ix − iz (5)
ix phase Y phase X phase Z
ux
S1 S1 S3 S5
ux
uy ix
uy Cdc
iy iy
uz
iz
S2 S2 S4 S6
uz
iz
Fig. 5: Half bridge Fig. 6: Matrix converter
The reference of circulating current is derived from the requirement of energy balance of the VR:
Z t0 + 1
f0
(ix ux + iz uz − iy uy ) dt = 0 (6)
t0
where f0 is the fundamental frequency of the grid voltage; and this equation can be simplified as:
Z t0 + 1
f0 K∆
i − iy (ux − uz ) dt = 0 (7)
t0 2
According to (7), the circulating current reference i∆ref should be
K
i∆ref = iy + i∆⊥ (8)
2
where the term i∆⊥ only contributes to reactive power and 90◦ phase difference is required between the
current term i∆⊥ and the voltage (ux − uz ).
A proportional-resonant (PR) controller Ci∆ is used in the current loop due to the sinusoidal current
reference. In practice, an addition integrator (PIR) might be needed to prevent DC offset in the current.
a
i∆ref −1 a mx
K
× b
iy + i∆err uzx,ref b
+ −
Ci∆ +
0.5 × my
ix −
− i∆ a
iz 1 a mz
b
b
Udc
Fig. 7: Current loop control.
The control diagram including the voltage loop is shown in Fig. 8, a PI controller CUdc is used to keep
a constant DC link voltage. The output of the PI controller is multiplied by the normalized modulation
signal mx , in order to obtain a sinusoidal reference i∆ref,2 to be added to the current loop.
+ i∆ref,2
Udc,ref CUdc
Udc
− ×
normalized mx
+ a
i∆ref,1 + i∆ref −1 a mx
K
× b
iy + i∆err uzx,ref b
+ −
Ci∆ +
0.5 × my
ix −
− i∆ a
iz 1 a mz
b
b
Udc
Fig. 8: Control diagram for the matrix baseline.
Scaled-down test
The purpose of this test is to verify the operating principle of the proposed matrix topology. Fig. 9 shows
the lab setup; the schematic is shown in Fig. 10. The input voltage uin is 50Hz and 240 Vrms. The VR
circuit uses an existing 3-phase IGBT inverter with a 2.45 mF capacitor. the IGBTs are switching at
20kHz with 2µs dead time. The high frequency components of the modulated voltages are eliminated by
LC filters. The selected transformer (USTE 1000/2x115) has rated power of 1 kVA and the turns ratio is
n1a : n1b : n2 = 2.02 : 0.48 : 1. The tap winding n1b is arranged at the primary side. A 60Ω resistor RL is
placed at the secondary side as load.
A V
V
A
Fig. 9: Lab setup Fig. 10: Schematic of the test setup
The control is realized using dSPACE MicrolabBox 1202/1302. The DC link voltage Udc should be
higher than the tap winding peak voltage in order to prevent over modulation. Initially, Udc is controlled
at 80V to just satisfy this requirement. In the current loop, the orthogonal term i∆⊥ is set to zero.
Results
Fig. 11 shows an example of the operation when K is 0.5. Waveforms were recorded using dSPACE. The
input voltage uin and regulated transformer secondary voltage u2 are shown in Fig. 11a; and resulting
VR currents are shown in Fig. 11b. Fig. 11c shows the DC link voltage of the VR; udc was controlled at
80V with a very small ripple. In Fig. 11d, the circulating current i∆ was tracking the reference. However,
the actual current was larger than its ideal reference (Kiy ). This difference could be related to the dead
time, which was not considered in the ideal situation. The modulation errors caused by the dead time
are nonlinear functions of currents. In the VR, currents in switching legs X, Z and Y have different
amplitudes, which lead to different errors of ux , uz and uy . As a result, the circulating current reference
needs to be corrected to maintain the energy balance. Besides, the converter loss is also a concern.
Especially the switching loss can be considerable due to the hard switching.
(a) voltage (b) VR currents
(c) DC link voltage ripple (d) circulating current
Fig. 11: Test results at K = 0.5.
The current flow to the input voltage source iy and also the load current i2 were measured using the
oscilloscope Tektronix MSO54 as shown in Fig. 12. Spikes appeared in the unfiltered waveform of iy
due to the hard switching of IGBTs. After filtering, harmonics at the switching frequency were mostly
eliminated. In terms of the load current i2 , the amplitude of the ripple was less than 3%. The ripple and
harmonic distortion can be further reduced by optimizing the filter design if necessary.
(a) One 50Hz cycle (b) ripples at peak currents
Fig. 12: Current iy and i2 , measured by oscilloscope (K = 0.5).
The dynamic performance was investigated by using step references for K. Results are shown in Fig. 13
and Fig. 14. In both test scenarios, the current loop immediately followed new references. Due to
the disturbance in the current loop, the DC link voltage changed in the beginning and was gradually
controlled back to its references. Especially, in Fig. 14, the step of K happened when the input voltage
was at its peak value. Though oscillations were observed initially, controllers regulated the system to the
steady state in a short period.
(a) voltage (b) circulating current (c) DC link voltage
Fig. 13: Step response: K steps up from -1 to 1.
According to (4), the effective number of turns n1e at the primary side of the transformer can be more
than (n1a + n1b ) if K > 1, or less than n1a if K < 1. However, when K is beyond the normal operation
range of −1 6 K 6 1, the amplitude of the VR output voltage uy will increase. Thus, a higher DC link
(a) voltage (b) circulating current (c) DC link voltage
Fig. 14: Step response: K steps down from 1 to -1.
voltage is required to prevent overmodulation. In Fig. 15, the DC link voltage was increased to 120V. In
the normal operation, the waveform of u2 was limited to the area between u2 |K=−1 and u2 |K=1 . When K
was set to +/-1.2, u2 resulted in slightly larger/smaller amplitudes.
Fig. 15: u2 wrt. K values, Udc = 120V Fig. 16: Voltage regulation range
Fig. 16 summarizes the voltage regulation range as a function of the control variable K. The voltage base
is chosen as the ideal voltage of U2 when K = 0, and the input grid voltage is 240Vrms.
n2
Ubase = 240 × = 106.2 V. (9)
n1a + 21 n1b
The ideal curve is estimated by:
240 V n2
U2 [pu] = × 1
. (10)
Ubase n1a + 2 (1 − K) n1b
During the test, u2 was measured when a different DC link voltage Udc was applied. In normal operation,
U2 did not show a dependency on Udc . However, operations at K < −1 or K > 1 were not allowed when
Udc was 80V. As shown in Fig. 16 , the measured secondary voltages were smaller than their ideal values.
To explain this difference, aside from the dead time distortion as mentioned before, another reason could
be the leakage components of the transformer. This will be investigated in the future.
Conclusion and future work
In this paper, a new power-electronic tap changer (VR) is proposed for distribution transformers. The
voltage regulation is realized by a single-phase matrix type converter. This VR is capable to realize a
wider range of effective turns coupled to the input voltage, which was often limited by the length of tap
winding in previous research. The functionalities of the proposed matrix type circuit are verified in the
scaled-down test. However, there were some mismatches between ideal estimations and measurements.
Further study needs to include more details in modelling: for instance, the three-winding transformer
model including leakage components and also considering the converter loss in the energy balance cal-
culation.
The voltage of the MV grid is normally 10kV or 23kV in Europe. Thus, extending the proposed concept
to multilevel/multi-cell topologies (e.g. modular multilevel converters) is needed. This will be addressed
in future research.
References
[1] G. R. C. Mouli, P. Bauer, T. Wijekoon, A. Panosyan, and E.-M. Bärthlein, “Design of a power-electronic-
assisted oltc for grid voltage regulation,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1086–
1095, 2014.
[2] J. Faiz and B. Siahkolah, Electronic tap-changer for distribution transformers. Springer Science & Business
Media, 2011, vol. 2.
[3] H. Jiang, R. Shuttleworth, B. A. Al Zahawi, X. Tian, and A. Power, “Fast response gto assisted novel tap
changer,” IEEE Transactions on Power Delivery, vol. 16, no. 1, pp. 111–115, 2001.
[4] J. V. López, J. C. Rodrı́guez, S. M. Fernández, S. M. Garcı́a, and M. P. Garcı́a, “Analysis of fast onload
multitap-changing clamped-hard-switching ac stabilizers,” IEEE transactions on Power Delivery, vol. 21,
no. 2, pp. 852–861, 2006.
[5] P. Bauer, S. De Haan, and G. Paap, “Electronic tap changer for 10 kV distribution transformer,” in European
Conference on Power Electronics and Applications, vol. 3. Proceedings published by various publishers,
1997, pp. 3–1010.
[6] J. de Oliveira Quevedo, F. E. Cazakevicius, R. C. Beltrame, T. B. Marchesan, L. Michels, C. Rech, and
L. Schuch, “Analysis and design of an electronic on-load tap changer distribution transformer for automatic
voltage regulation,” IEEE Transactions on Industrial Electronics, vol. 64, no. 1, pp. 883–894, 2016.
[7] S. P. Engel, “Thyristor-based high-power on-load tap changers: control under harsh load conditions,” Ph.D.
dissertation, RWTH Aachen University, 2017.