Samsung Electronics

This Training Manual is a property of Samsung Electronics Co.,Ltd.


Any unauthorized use of Manual can be punished under applicable International and/or domestic law.
Control system overview
Overview
■ Individual control system

The must-have, Samsung control system!


To maximize usability & efficiency

Integrated
Individual control Centralized
Management BMS Gateway Others
system control system
system

Individual control system


· Controllers to enable individual control
on each indoor unit.

· Main user : General user

4/100 This Document can not be used without Samsung's authorization


Overview
■ Centralized control system

The must-have, Samsung control system!


To maximize usability & efficiency

Integrated
Individual control Centralized
Management BMS Gateway Others
system control system
system

Centralized control system


· Controllers to enable central controls on
multiple indoor units.

· Main user : System administrator, General user

5/100 This Document can not be used without Samsung's authorization


Overview
■ Integrated management system

The must-have, Samsung control system!


To maximize usability & efficiency

Individual control Centralized Integrated


Management BMS Gateway Others
system control system
system

Integrated management system


· Controllers to enable the integrated management to control
multiple indoor units and to handle energy, error, troubleshooting
history, user management, and so forth.

· Main user : System administrator, General user

6/100 This Document can not be used without Samsung's authorization


Overview
■ BMS Gateway

The must-have, Samsung control system!


To maximize usability & efficiency

Individual control Centralized Integrated


Management BMS Gateway Others
system control system
system

BMS Gateway
· BMS gateway to enable a connection between Samsung
system air conditioner and BMS (Building Management System)
which controls all facilities and managements of an entire
building.

7/100 This Document can not be used without Samsung's authorization


Overview
■ Others

The must-have, Samsung control system!


To maximize usability & efficiency

Individual control Centralized Integrated


Management BMS Gateway Others
system control system
system

Others
· Additional devices used for other purposes to enhance
the control and management of Samsung system air conditioners.

· They can provide special solutions for users who have specific
requirements.

8/100 This Document can not be used without Samsung's authorization


System diagram
S-NET3

DMS Bnet DMS Lnet ※ Control layer : Controller can control multiple outdoor units and their indoor units.
Ethernet
Set layer : Controller can control one outdoor unit and its indoor unit.

DMS 2.5 Control layer Set layer


Max.16 outdoor units (Includes DVM Chillers, I/M)
Max.16 controllers Max. 128 indoor units (Includes MCU, ERV, FCU kit)
Max.16 controllers

F1/F2

F3/F4

R1/R2
CH1
Touch On/Off Wi-Fi kit
R1/R2 centralized controller
controller
Wi-Fi kit Local layer

F1/F2

R1/R2
ERV I/M ERV
CH2
F3/F4

F3/F4

※ Nasa outdoor unit Comm. PBA


R1/R2 Module controller
CH5 CH3
DVM Chiller
F3/F4

F1/F2
F3/F4
3rd party FCU

PIM

CH4 R1/R2
Samsung FCU
R1/R2
FCU Kit F1/F2 OF1/OF2
FCU I/M (High level
(IDU) (ODU) controller)

9/100 This Document can not be used without Samsung's authorization


Individual control system
Wireless remote controller
■ Introduction

AR-KH00E MR-EH00 AR-EH03E


(360 cassette) (Wind free)

An easy controller in a room or an office,


wherever you are!

*AR-EH00E (Wind free) will launch at W48, 2017

11/100 This Document can not be used without Samsung's authorization


Wireless remote controller
■ Introduction
 MR-EH00
- Simple schedule control(On timer / Off timer)
- On/off, operation mode, fan speed, Airflow, temperature setting
- Filter replacement alarm reset
- Zone selecting control (Max. 4 zones)
- Buzzer sound mute
- Address and option setting
- Wind free control (AR-EH03E only)

 AR-KH00E
- 360 cassette air flow direction control
- Simple schedule control(On timer / Off timer)
- On/off, operation mode, fan speed, Airflow, temperature setting
- Filter replacement alarm reset
- Zone selecting control (Max. 4 zones)
- Buzzer sound mute
- Address and option setting
12/100 This Document can not be used without Samsung's authorization
Wireless remote controller
■ Main function & feature
 Zone selecting control
- You can select the indoor unit
- Use the Zone function to choose the indoor unit you want to operate individually
- This function prevents indoor unit mix-up. (Up to 4 channels can be set.)

1 2 1 1

13/100 This Document can not be used without Samsung's authorization


Wireless remote controller
■ Main function & feature
 Individual blade control
- By using wireless remote controller, opening angles of each blades can be set individually
in same or different angle within 32~65° for more efficiency cooling.

Individual blade control

※ AR-KH00E has 360 cassette air flow direction control function.


14/100 This Document can not be used without Samsung's authorization
Wired remote controller
■ Introduction

A built-in type remote controller


to control wired indoor unit only

MWR-WE11N

HOME HOTEL OFFICE STORE

MWR-SH00N

MWR-SH10N

15/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Introduction
 MWR-WE11N, MWR-WE13N
- Individual or group control (Maximum 16 units)
- Control and monitoring AC and ERV together.
- Wireless R/C restriction
- Child lock, different button permission levels
- Temperature range limit
- Automatic operation stop function
- 360 cassette air flow control & display
- Wind free control (MWR-WE13N only)

 MWR-SH10N
- Touch screen
- Intuitive UI/UX
- Built-in room temperature sensor and IR receiver
- Outing operation

*MWR-WE13N (Wind free) will launch at W50, 2017

16/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Models
MWR-WE11N MWR-SH10N MWR-SH00N MWR-VH12N
(Multifunction) (Touch simplified) (Simplified) (ERV controller)
Dimension (WxHxD, mm) 120x124x19.5 94.2x122x19,5 75x122x16.6 75x122x16.6
Indoor unit control ● ● ● -
Connection ERV control ● - - ●
Max. connectable unit number 16 16 16 16
On/Off ● ● ● ●
Operation mode ● ● ● ●
Control & Fan speed ● ● ● ●
monitoring Air swing ● ● ● -
Filter cleaning alarm reset ● ● ● -
Error display ● ● ● ●
Weekly schedule ● - - -
Schedule
Simple timer(On/Off) - ● ● ●
Touch screen - ● - -
Built-in room sensor ● ● - -
LCD backlight ● ● - -
Wireless R.C restriction ● ● ● -
Child lock ● ● ● ●
Partial button lock ● ● ● ●
Quiet mode ● ● ● -
Sleep mode ● ● - -
Outing mode (SAC) - ● - -
Convenient Away mode (ERV) - - - ●
function IR receiver - ● - -
Real-time clock ● - - -
Summer time ● - - -
Individual blade control ● - - -
Virus doctor(Spi) display ● ● - -
Virus doctor(Spi) control ● - - -
CO2 display O(ERV) - - ●
Humidity display O(ERV) - - -
Purification mode O(ERV) - - -
Temperature range limit ● ● ● -
Energy saving Automatic operation stop ● - - -
Energy saving mode with ERV ● - - -

17/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Main function & feature
 Built-in room temperature sensor (MWR-WE11N / MWR-SH10N)

(81℉)

(72℉)

Which room temperature is used for operating indoor unit?


• Default : Indoor unit's room temperature
• Wired R/C option
Room temperature sensor 1) Wired RC's room temperature
2) The average room temperature between
indoor unit and wired R/C
18/100 This Document can not be used without Samsung's authorization
Wired remote controller
■ Main function & feature
 Automatic operation stop function (MWR-WE11N)
- If there is no control by wired R/C during specific time, the indoor unit will stop operating.

Stop
Set time
(0~12 hours)

19/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Main function & feature
 Temperature range limit
- Energy saving function to set the maximum temperature for heating as well as the minimum one for cooling.

20/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Main function & feature
 Wireless R/C restriction
- Default : Both of wireless & wired R/C can control indoor units.
- Set to disable wireless R/C : It's not allowed to control indoor units.

21/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Main function & feature
 Child lock, different button permission levels
- Entire button
- Partial button

1 On/Off 2 Temperature setting 3 Operation mode 4 Fan speed 5 Schedule setting

22/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Main function & feature
 Outing operation (MWR-SH10N)
- Outing operation keeps minimum cooling / heating temperature of indoor for 12 hours.
- This solution is useful to make a pleasantly cool room in case of hotel, resort and even home.
- Outing operation is started when indoor unit temperature has 5℃(9℉) difference with desired outing
temperature.

If cooling outing set is 27℃(81℉),

room temp = 32℃(90℉). On

HOME HOTEL room temp = 27℃(81℉). Off

Ex. Outing operation in cooling mode

23/100 This Document can not be used without Samsung's authorization


Wired remote controller
■ Main function & feature
 IR receiver (Built in wireless signal receiver)
- To use either wireless or wired R/C for a ducted type indoor unit

Conventional solution New solution

 Conventional wired remote controller  New wired remote controller (MWR-SH10N)


 Wireless signal receiver (MRK-A10N)  No other device required

24/100 This Document can not be used without Samsung's authorization


Centralized control system
General introduction
■ Introduction

Simple central management for small & mid size building

Wi-Fi Kit On/Off controller Touch centralized controller

26/100 This Document can not be used without Samsung's authorization


General introduction
■ Models

MIM-H03N MCM-A300N MCM-A202DN

Wi-Fi Kit Touch centralized controller On/Off controller


Dimension (WxHxD, mm) 120 x 124 x 29 203 x 161 x 38 110 x 120 x 55
Indoor unit control ● ● ●
Connection ERV control ● ● ●
Max. connectable unit number 16 128 128
On/Off ● ● ●
Operation mode ● ● ●
Control & Fan speed ● ● -
monitoring Air swing ● ● -
Filter cleaning alarm reset ● ● -
Error display ● ● -
Schedule Weekly schedule ● ● -
Mobile control (App) ● - -
Touch screen - ● -
Summer time setting - ● -
Convenient ● ● ●
Zone (Group) control
function (Editable by user) (Editable by user) (Fixed by installation setting)
Remote controller restriction - ● ●
Operation mode limit - ● -
External contact interlock - ● -
Temperature range limit - ● -
Energy saving ●
Power consumption monitoring - -
(DVM S only)

27/100 This Document can not be used without Samsung's authorization


Wi-Fi Kit
■ Main function & feature
Mobile Solution Key Features for APP.

Controlling all indoors remotely Simple Centralized control function


- Up to 16 indoor units
- Support 360CST air flow control & display  User management
- Support Samsung FCU - 1 Wi-Fi kit can be registered with maximum 5 users.
- Multi tenant function (Up to 4 Wi-Fi kit per outdoor module) - 1 mobile phone can be registered with maximum 4 Wi-Fi kits
 Scheduling
MIM-H03 (Old comm.) - based on seven-days
MIM-H03N (Global)  Grouping
MIM-H03CN (China) - for turning on/off instantaneously
MIM-H03UN (USA)  Energy monitoring
- daily, weekly and monthly

• Can download the Samsung Smart Home App


by searching "Samsung Smart Home“ on Play store,
Galaxy Apps and iPhone App Store.

28/100 This Document can not be used without Samsung's authorization


Wi-Fi Kit
■ Main function & feature
 Remote Control & Monitoring

“Turn it off now,


I forgot it when leaving home”

360 CST

1way
In the office
“Turn it on now,
Cool home before I get there” 4way
“No need to look for
the remote controller”
Ducted

Ceiling

EHS

On the way On the bed ※ Max. 16 indoors


FCU
.
.
.
29/100 This Document can not be used without Samsung's authorization
Wi-Fi Kit
■ Main function & feature
 Scheduling

Easy settings
for 7 day weekly schedule

Shop manager
“Easy-to-use timer for cooling”

30/100 This Document can not be used without Samsung's authorization


Wi-Fi Kit
■ Main function & feature
 Grouping

Enable to group indoors


to turn On/Off in the same time

Shop manager
“One click to turn on all indoors of
desired zone at home”

Group 1

31/100 This Document can not be used without Samsung's authorization


Wi-Fi Kit
■ Main function & feature
 Energy monitoring

Enable to check Outdoor unit energy consumption pattern (daily, weekly and monthly)

outdoor unit is

Shop owner
“How much energy is used
compared with last month?

※ Caution
- Energy monitoring displays power output which is different from power consumption shown on electricity bills
- When it is connected to two or more outdoor units, some functions including energy monitor can be restricted.
- Energy monitoring can be used through the outdoor unit that support energy monitoring.
32/100 This Document can not be used without Samsung's authorization
Wi-Fi Kit
■ Main function & feature
 Multi tenant function
- Controlling and monitoring of indoor units assigned to one group channel address(RMC1)
by identical tenant address of Wi-Fi kit.

※ Maximum number of Wi-Fi kit that can be connected on “set layer” is 4.


※ Maximum number of indoor unit installation that can be connected to Wi-Fi kit is 16.
33/100 This Document can not be used without Samsung's authorization
On/Off controller
■ Main function & feature
 Easy On/Off control over multiple indoor units as a group
 Best for large as well as small buildings

- Maximum 16 group controls (Maximum 128 Indoor units)


- Group / Individual indoor unit control (On/Off)
- Flexible connection
- Wireless / wired R/C restriction
- Cooling / Heating mode control
- Communication error display

34/100 This Document can not be used without Samsung's authorization


Touch centralized controller
■ Introduction
Easy control over multiple indoor units
Best for large as well as small buildings

Large building Medium/


Small building

35/100 This Document can not be used without Samsung's authorization


Touch centralized controller
■ Introduction

Customized the best controlling method


for various building conditions

36/100 This Document can not be used without Samsung's authorization


Touch centralized controller
■ Main function & feature
 Control & monitoring (Max. 128 indoor units)
- Easy to check each device status using color and icon
- Turning over pages with flicking or simple touch (No scroll bar)

37/100 This Document can not be used without Samsung's authorization


Touch centralized controller
■ Main function & feature
 Zone management
- Simply controls all indoors, zone with one button

Office

T/F room

Dining room

Office

Main conference

Conference

38/100 This Document can not be used without Samsung's authorization


Touch centralized controller
■ Main function & feature
 External device interlock
- Simple operation control interlocking with external contact (2 Digital input)
- Indoor unit operation On/Off status output (1 Digital output)

EX Emergency stop

R1/R2 Emergency

F1/F2 F1/F2

F3/F4 Off F3/F4 Off

39/100 This Document can not be used without Samsung's authorization


Touch centralized controller
■ Main function & feature
 Operation mode restriction

Only cooling mode

All indoor units under same refrigerant system


: “Only cooling mode”

40/100 This Document can not be used without Samsung's authorization


Touch centralized controller
■ Main function & feature
 Remote controller restriction
- Wireless/Wired R/Cs, On/Off controller

Remote controller disable

Its restriction can be included


by setting system environment
of touch centralized controller.

41/100 This Document can not be used without Samsung's authorization


Integrated management system
Data Management Server (DMS) 2.5
■ Introduction

A system controller based on web browser


systematic control and effective management
over multi indoor units up to 256

Energy Schedule Control Logic


Management Management

43/100 This Document can not be used without Samsung's authorization


Data Management Server (DMS) 2.5
■ Main function & feature
 Control & monitoring
- Individual / Zone management (Maximum 256 indoor units)
- Remote control via local/internet

B zone

A zone

Cooling only / No R/C /


A zone Minimum setting temperature in cooling is 20℃

B zone Cooling only / R/C use

44/100 This Document can not be used without Samsung's authorization


Data Management Server (DMS) 2.5
■ Main function & feature
 DVM Chiller and FCU Kit control
- DMS 2.5 can control and monitor DVM Chiller and FCU Kit.
- Using “Control logic” function, user can interlock the operation of DVM Chiller and FCU Kit.

【DVM Chiller integrated system 】


< Field Scope >

FCU
(Field supply)

Water Pump
(Field supply)

45/100 This Document can not be used without Samsung's authorization


Data Management Server (DMS) 2.5
■ Main function & feature
 Accessible level management
- It is possible to specify the scope of control and monitor each unit separately

Manager
Administrator
ㆍUser can monitor the
Manager entire building’s units
ㆍUser can control the
Administrator entire on/off system
ㆍUser can monitor the
entire building’s units
ㆍUser can control the
entire on/off system
ㆍUser can monitor the
total power used
User
ㆍEach user can control
and monitor the allowed
unit only

46/100 This Document can not be used without Samsung's authorization


Data Management Server (DMS) 2.5
■ Main function & feature
 History management
- Recorded history makes it convenient to analyze air-conditioner operation
and perform unit maintenance.

Save history

ㆍIndoor unit operation history


ㆍSchedule history
ㆍControl logic operation history
ㆍSystem environment setting history
ㆍError history

47/100 This Document can not be used without Samsung's authorization


Data Management Server (DMS) 2.5
■ Main function & feature
 Power distribution
- Power distribution to up to 256 indoor units
- 1-year power distribution data storage
- File save in Microsoft Excel format
- Data query for watt-hour, use time and use ratio
- Current actual power consumption monitoring
- Current-type electricity meter support (CT ratio input)

1 Operation data accumulation


and power distribution

DMS2.5
2 Data extract - Excel format

※ PIM(MIM-B16N) must be connected to use power distribution.


48/100 This Document can not be used without Samsung's authorization
Data Management Server (DMS) 2.5
■ Main function & feature
 User editable control logic
- User can edit control logic with arithmetic / conditional operators and parameters
- Efficient energy saving realization for various operation conditions.

EX Free cooling, operation adjustment depending on outdoor temperature


49/100 This Document can not be used without Samsung's authorization
Data Management Server (DMS) 2.5
■ Main function & feature
 External device interlocking
- Provides digital input/output ports for interlocking 3rd party’s device and indoor unit.
- Provides the dedicated input /output ports for special function.
* Input : Emergency stop operation / Output : Indoor unit state check

EX Emergency stop by alarm signal interlocking

Operation Emergency

Error

50/100 This Document can not be used without Samsung's authorization


Data Management Server (DMS) 2.5
■ Main function & feature
 Vacant room control / occupied room control
- Keeps the room temperature when user goes out for a while.
 Occupied room control
- Detects a user entrance (via key-tag) and operates as pre-heating, pre-cooling condition.

EX Vacant room control

• Air-conditioner keeps operating


and follows DMS vacant room setting.

Ex) Cooling, 26℃(79℉), Auto fan

Out

Manager can set operation via DMS2.5

51/100 This Document can not be used without Samsung's authorization


Pulse Input Module (PIM)
■ Introduction

Local Watt Hour Meter


with pulse initiators

Pulse 485 comm.

PIM DMS2.5

52/100 This Document can not be used without Samsung's authorization


Pulse Input Module (PIM)
■ Main function & feature
 MIM-B16N
- Interface with pulse-type electricity meters for electricity billing system
- Max. 8 watt hour meters per PIM
- Pulse-type gas / water meters compatibility
- Total 8 PIM per DMS 2.5
- Pulse coefficient setting (1Wh/pulse ~ 1000Wh/pulse)
- Pulse width setting (20ms~1,000ms)
- No support of pulse coefficient with decimal points
- Power data storage in non-volatile memory (8 channels)
- Current time setting and display
- Configuration information display on LCD
- Error display (communication, out-of-range pulse width..)

53/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Introduction
 S-NET 3 is a complex management program that controls
and monitors a complete air conditioner network system.
The S-NET series provides flexible and complete control for a variety of applications.

* Fully integrated PC management software


* For large site. (Ex. University)
DMS-3 192.168.0.4

Up to 16 DMSs connection through DMS-2 192.168.0.3


the Ethernet
DMS-4 192.168.0.5
DMS-1 192.168.0.2

Supports
16 DMSs

54/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Main function & feature
 Control and Monitoring
- Control & Monitoring of up to 4,096 indoor units
- Wireless/wired R/C restriction
- Temperature limit setting
- Multiple / Full indoor unit selection
- Icon-based indoor unit display mode

55/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Main function & feature
 Schedule Control
- Graphical schedule settings
- Weekly / Daily schedule control
- Exception date setting ex) Air-conditioning operation schedule
• Tuesday : Heating (AM 09:00~AM 11:00)
• Thursday : Cooling (AM 09:00~AM 10:00)
Cooling (AM 10:30~AM 11:30)

56/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Main function & feature
 Zone Management
- Management structure customization regardless of installation structure
- Control zone creation / edition / deletion
- Tree structure zone management control

ex) Control zone edit


• Building A,B,C
• Building C
- Class zone
- Admin zone

57/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Main function & feature
 Zone Management
- Management structure customization regardless of installation structure
- Control zone creation / edition / deletion
- Tree structure zone management control

▶ Class zone

58/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Main function & feature
 Power Distribution Management
- Data query for power distribution and operation time
- Power distribution report generation and print
- Time section setting for different electricity rates
- Group setting for power distribution summation

59/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Main function & feature
 Power Distribution Management
- Power distribution time zone setting
: Used for the case that electricity billing rates differ in time section of day

- Print power distribution result bill


4 Floor (one-room)

137 kWh
3 Floor (office)

171 kWh
2 Floor (restaurant )

125 kWh
1 Floor (shop)

240 kWh

60/100 This Document can not be used without Samsung's authorization


S-NET 3
■ Main function & feature
 History Management
- Error / Event history management
- Indoor unit operation history management
- Report generation and print

61/100 This Document can not be used without Samsung's authorization


Building management system
BMS gateway
■ Introduction

Building management system


An integrated control and management system
on different company sub-system in a building

BMS SAC

DMS BACnet Gateway

DMS LonWorks Gateway

Modbus Gateway

KNX Gateway

63/100 This Document can not be used without Samsung's authorization


BMS gateway
■ Introduction

Open protocol gateways for Building Management System (BMS)

DMS BACnet Gateway DMS LonWorks Gateway Modbus Gateway KNX Gateway

(MIM-B17BN) (MIM-B18BN) (SM-ACN-MBS-***) (SM-ACN-KNX-***)

64/100 This Document can not be used without Samsung's authorization


BACnet gateway (MIM-B17BN)
■ Main function & feature
· Interface for BACnet Building Management System
· Included DMS2.5 function
BACnet · Central management of up to 256 indoor units
DMS 2.5 interface · Communication connection
- Lower layer : RS485 (To Air conditioner)
- Upper layer : Ethernet 10/100 Base-T (To Internet)
- BACnet layer : Ethernet 10/100 Base-T (To BMS)

BMS Control Function Monitoring Function


• On/Off control • On/Off
• Temperature setting • Set/Room temperature
• Operation mode • Operation mode
• Fan speed/direction • Fan speed/direction
• Filter alarm reset • Filter alarm
• User control restriction • User control restriction
• Operation mode lock & set temp limit • Operation mode lock & set temp limit
• Emergency stop • Power distribution
• Error information

65/100 This Document can not be used without Samsung's authorization


BACnet gateway (MIM-B17BN)
■ System diagram

3rd party system

BMS (BACnet)

※ One gateway can connect multiple outdoor units.


Samsung

DMS BACnet Touch centralized On/Off


Gateway controller controller
Control Layer(R1/R2)

Set Layer(F1/F2)

ODU
IDU IDU IDU IDU IDU Touch On/Off
centralized controller
controller

66/100 This Document can not be used without Samsung's authorization


LonWorks gateway (MIM-B18BN)
■ Main function & feature

· Interface for LonWorks Building Management System


· Central management of up to 128 indoor units
· Included DMS 2.5 function DMS 2.5 Lonworks
· Communication connection interface
- Lower layer : RS485 (To Air conditioner)
- Upper layer : Ethernet 10/100 Base-T (To Internet)
- LonWorks layer : TP/FT-10A (To BMS)

BMS Control Function Monitoring Function

• On/Off control • On/Off


• Temperature setting • Set/Room temperature
• Operation mode • Operation mode
• Fan speed/direction • Fan speed/direction
• Filter alarm reset • Filter alarm
• User control restriction • User control restriction
• Operation mode lock & set temp limit • Operation mode lock & set temp limit
• Emergency stop • Power distribution
• Error information

67/100 This Document can not be used without Samsung's authorization


LonWorks gateway (MIM-B18BN)
■ System diagram

3rd party system


BMS (Lonworks)

※ One gateway can connect multiple outdoor units.


Samsung

DMS Lonworks Touch centralized On/Off


Gateway controller controller
Control Layer(R1/R2)

Set Layer(F1/F2)

ODU
IDU IDU IDU IDU IDU Touch On/Off
centralized controller
controller

68/100 This Document can not be used without Samsung's authorization


Modbus & KNX gateway (Intesis)
■ Main function & feature

· Interface for Modbus/KNX Building management system


· Central management of up to 32 indoor units (4/8/16/32)
· Communication connection
Modbus (RTU/TCP)
- Lower layer : RS485 (To Air conditioner)
- Modbus layer : RS485, RS232, Ethernet (To BMS)
KNX
- Lower layer : RS485 (To Air conditioner)
- KNX layer : KNX TP1/EIB (To BMS)

Modbus Gateway KNX Gateway


(SM-ACN-MBS-***) (SM-ACN-KNX-***)

• Model supporting up to 4 Samsung indoor units. Ref.: SM-ACN-MBS-4 / SM-ACN-KNX-4


• Model supporting up to 8 Samsung indoor units. Ref.: SM-ACN-MBS-8 / SM-ACN-KNX-8
• Model supporting up to 32 Samsung indoor units. Ref.: SM-ACN-MBS-32 / SM-ACN-KNX-32

※ Email : [email protected](Sales department) / [email protected](Technical support) / [email protected](General information)

69/100 This Document can not be used without Samsung's authorization


Modbus & KNX gateway (Intesis)
■ System diagram

3rd party system


BMS (Modbus)

Intesis gateway
※ One gateway can connect multiple outdoor units.
Control Layer(R1/R2)

Modbus / KNX
Gateway

Samsung Set Layer(F1/F2)


ODU
IDU IDU IDU IDU IDU Touch On/Off
centralized controller
controller

70/100 This Document can not be used without Samsung's authorization


Others
Others

Optional devices to provide various solutions


for a customer's needs

Modbus Interface module


(MIM-B19N)

DVM Chiller control


system
*MIM-B19N will launch at W50, 2017

72/100 This Document can not be used without Samsung's authorization


Others
■ Wireless signal receiver (MRK-A10N)

<Simulation of usage> <Main function & feature>

ㆍOn/Off control
ㆍOperation indication
ㆍError Indication
ㆍFilter replacement sign
ㆍUse with receiver wire

cf A picture for duct installation and usage

73/100 This Document can not be used without Samsung's authorization


Others
■ Operation mode selection switch (MCM-C200)
 Simulation of usage

If you control the indoor unit


in heat mode

Operation mode selection switch:


Set it on as cool

 Main function & feature


- Operation mode restriction (Cooling, Heating or Auto)
- Direct connection to outdoor unit

74/100 This Document can not be used without Samsung's authorization


Others
■ External room temperature sensor (MRW-TA)
 Simulation of usage

(81℉)

(72℉)

 Main function & feature


- Indoor unit is operated by MRW-TA instead of its own sensor.
- Supports all types of indoor unit.
- Wire length: 12m(39ft)

75/100 This Document can not be used without Samsung's authorization


Others
■ Compatible interface module (MIM-N01)
 Simulation of usage
Conventional system New system
(DVM +4) (DVM S)

New system Conventional system


To upper controller (DVM S) To upper controller
connection connection

76/100 This Document can not be used without Samsung's authorization


Others
■ ERV Compatible interface module (MIM-N10)
 Simulation of usage * Blue colored spot: New System
New system New system Conventional system
Up to 16 Up to 16

R1/R2 R1/R2 R1/R2

New system Conventional system New system

 Main function & feature


- Interface module that supports up to 16 ERV units
- Communication transmitter between upper level controllers and the ERV units
* High level controller : DMS 2.5, Touch centralized controller, On/Off controller
77/100 This Document can not be used without Samsung's authorization
Others
■ External contact interface module (MIM-B14)
 Simulation of usage

On/Off On/Off Error On/Off

Key-Tag Window Open Sensor Malfunction Alam Extemal Device Control

 Main function & feature


- Direct indoor unit control by external contact signal
- Window-synchronized indoor unit control
- Indoor unit operation/error state output through relay contacts
- Emergency control with simple contact input

78/100 This Document can not be used without Samsung's authorization


Others
■ External contact interface module (MIM-B14)
 Direct indoor unit control by external contact signal

1) On-Off Control 2) Off-Only Control

Card-key removed(Contact open) Card-key removed(Contact open)


IDU Off IDU Off & Controller disable

Card-key inserted(Contact close) Card-key inserted(Contact close)


IDU On IDU stand-by & Controller enable

79/100 This Document can not be used without Samsung's authorization


Others
■ External contact interface module (MIM-B14)
 Window-synchronized indoor unit control

3) Window Control

Window opened(Contact open)


IDU Off & Controller disable

Window closed(Contact close)


IDU returns to the previous mode
(Running or stand-by mode)
& Controller enable

80/100 This Document can not be used without Samsung's authorization


Others
■ External contact interface module (MIM-B14)
 Indoor unit operation / error state output through relay contacts

Operation status Error status

No error Contact closed Lamp on


* Form A Contact : Normally open
* Form B Contact : Normally Closed

Indoor on Relay on Contact closed


Electric louver open Error Relay on Contact open Lamp off

81/100 This Document can not be used without Samsung's authorization


Others
■ MTFC (Multi Tenant Function Controller, MCM-C210N)
 Main function & feature
- If any indoor is cut off the power, the entire system makes a communication error and stop working.
- MTFC is an auxiliary power supply device which allows indoor unit to turn off (close EEV) normally
and maintain communication when main power supply is cut.

No
MTFC
OFF

ELCB ELCB ELCB ELCB ELCB


AC380V AC220V AC220V AC220V AC220V

Comm.

Indoor unit #1 Indoor unit #2 Indoor unit #3 Indoor unit #N


Error Error Error Error Error

82/100 This Document can not be used without Samsung's authorization


Others
■ MTFC (Multi Tenant Function Controller, MCM-C210N)
 Simulation of usage

Case1 )
- Each tenant uses individual power breaker.
Even one tenant cuts power,
other tenants can use air-conditioner.

Case2 )
- Each card key tag is connected to power line.
Even a card key is removed,
other room can use air-conditioner.

83/100 This Document can not be used without Samsung's authorization


Others
■ DVM Chiller control system
 Control system diagram

【DVM Chiller integrated system 】


< Field Scope >

FCU
(Field supply)

Water Pump
(Field supply)

84/100 This Document can not be used without Samsung's authorization


Others
■ DVM Chiller control system
 Module controller (MCM-A00N) - For DVM Chiller
- DVM Chiller On/Off control (Module /Group)
- Operation mode, water outlet temperature setting
- Optional operation setting, module / group setting
- Weekly operation schedule setting.

 FCU Kit (MIM-F00N) - For 3rd party FCU


- Communication and control interfacing kit between 3rd party FCU
and Samsung control system
- Possible to use wired R/C
- Possible to use DMS 2.5, touch centralized controller
- Provides external contact input
- Outputs control signal for FCU fan / water valve

 FCU interface module (MIM-F10N)


- Communication interface module between FCU Kit or FCU and high level controller
- Supports Samsung FCU, FCU kit
- Max. 16 FCU Kits connection
85/100 This Document can not be used without Samsung's authorization