ANALIS PERHITUNGAN BEBAN PENDINGINAN MENGGUNAKAN DIAGRAM
PSYCHOMETRIC
I WAYAN YUDINARTA VIVASTA (2215234013)
PROGRAM STUDI D4 TEKNOLOGI REKAYASA UTILITAS
JURUSAN TEKNIK MESIN
POLITEKNIK NEGERI BALI
2024
This Psychrometrics Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Psychrometrics Program.
This Psychrometrics Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Psychrometrics Program.
1. Psychrometric points
OA RA SA MA
Dry bulb temperature 35,0°C Dry bulb temperature 25,0°C Dry bulb temperature 13,0°C Dry bulb temperature 26,0°C
Wet bulb temperature 30,9°C Wet bulb temperature 17,9°C Wet bulb temperature 12,4°C Wet bulb temperature 19,5°C
Dew point 29,8°C Dew point 13,9°C Dew point 12,0°C Dew point 16,2°C
Relative humidity 74,7% Relative humidity 50,1% Relative humidity 93,5% Relative humidity 54,8%
Absolute humidity 0,0269kg/kg Absolute humidity 0,0099kg/kg Absolute humidity 0,0087kg/kg Absolute humidity 0,0115kg/kg
Enthalpy 104,3kJ/kg Enthalpy 50,4kJ/kg Enthalpy 35,1kJ/kg Enthalpy 55,5kJ/kg
Density 1,128kg/m³ Density 1,177kg/m³ Density 1,227kg/m³ Density 1,172kg/m³
Specific volume 0,911m³/kg Specific volume 0,858m³/kg Specific volume 0,822m³/kg Specific volume 0,863m³/kg
Pressure 101325,0Pa Pressure 101325,0Pa Pressure 101325,0Pa Pressure 101325,0Pa
Airflow 100,0l/s Airflow 900,0l/s Airflow 1000,0l/s Airflow 1000,0l/s
PP1 PP2
Dry bulb temperature 21,6°C Dry bulb temperature 25,0°C
Wet bulb temperature 16,3°C Wet bulb temperature 17,5°C
Dew point 13,2°C Dew point 13,2°C
Relative humidity 58,6% Relative humidity 47,7%
Absolute humidity 0,0094kg/kg Absolute humidity 0,0094kg/kg
Enthalpy 45,7kJ/kg Enthalpy 49,2kJ/kg
Density 1,191kg/m³ Density 1,177kg/m³
Specific volume 0,848m³/kg Specific volume 0,857m³/kg
Pressure 101325,0Pa Pressure 101325,0Pa
Airflow 900,0l/s Airflow 900,0l/s
2. Actions
Mix air: OA, RA, MA
Cooling capacity: RA, PP1, PP2 (Capacities: Total = 5,00kW, Sensible = 3,75kW (75%), Latent = 1,25kW)
This Psychrometrics Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Psychrometrics Program.
KESIMPULAN
Dari hasil pengukuran menggunakan diagram pychrometric didapatkan hasil pengukuran yaitu :
1. Mixing Air
MA
Dry bulb temperature 26,0°C
Wet bulb temperature 19,5°C
Dew point 16,2°C
Relative humidity 54,8%
Absolute humidity 0,0115kg/kg
Enthalpy 55,5kJ/kg
Density 1,172kg/m³
Specific volume 0,863m³/kg
Pressure 101325,0Pa
Airflow 1000,0l/s
2. Sensible : 3,75 kW
3. Laten : 1,25 kW
4. SHR : 75%
Sehingga beban pendinginannya adalah 5,0 kW (17060.71 BTU/hr
This Psychrometrics Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Psychrometrics Program.