3vt3 MCCB 400 To 600a
3vt3 MCCB 400 To 600a
■ Overview
Connecting sets
4
5
6
7
8
9
10
Switching unit
3
11
12 3
19 20 21
14
15
17 18 22 23 24 25
Accessories
16
26 NSO0_00211a
27 28 29 30
1 Molded case circuit breaker 11 Rotary operating mechanism 22 Auxiliary switch NC/NO
2 Plug-in device 12 Lateral rotary operating mechanism 23 Auxiliary switch NC/NO
3 Withdrawable device 13 Mechanical parallel switching 24 Auxiliary switch, change-over contact
4 Box terminals 14 Mechanical interlocking 25 Auxiliary switch, early
5 Circular conductor terminal 15 Mechanical interlocking by Bowden wire 26 Lockingtype lever
6 Multiple feed-in terminal 16 Motor operating mechanism 27 Sealing inset
7 Multiple feed-in terminal 17 Shunt trip unit 28 Additional cover for
8 Rear connection 18 Undervoltage trip unit overcurrent releases
9 Front connection 19 Connecting cable 29 Terminal cover
10 Auxiliary conductor terminal 20 Position signalling 30 Insulating barriers
21 Keying pins
■ Overview
Switching unit For recommended cross-sections of cables, busbars and flexi-
bars for fixed-mounted, plug-in and withdrawable versions, see
The switching unit includes: page 3/11.
• Two 3VT9 300-4TA30 connecting sets – for connecting
busbars or cable lugs Circuit breaker
• 3VT9 300-8CE30 insulating barriers
• A set of 4 installation bolts (M5 x 25) The circuit breakers consist of a 3- or 4-pole switching unit and
a trip unit which is available with a choice of different character-
The switching unit must be fitted with a trip unit (circuit breaker) istics.
or a 3VT9 363-6DT00 switch disconnector unit
(switch disconnector) Switch disconnector
For maximum circuit breaker/switch disconnector loads in The switch disconnector consists of a switching unit and a
accordance with the ambient temperature, see page 3/11. switch disconnector unit.
1)
Use only with switching unit 3VT3763-.AA36-0AA0 or
3VT3763-.AA46-0AA0.
2)
Use only with switching unit 3VT3763-.AA56-0AA0
■ Overview
The circuit breakers can be equipped with Shunt trip units can trip the circuit breaker from a remote loca-
• auxiliary switches, tion. A control supply voltage is required.
• alarm switches, An undervoltage trip unit trips the circuit breaker automatically
• shunt trip units, when the circuit voltage drops below 70 % Ue. The undervoltage
• undervoltage trip units. trip unit protects motors and other equipment in case of under-
voltage. A control supply voltage is required.
Single NC contacts
AC/DC 60 ... 500 V B 3VT9 300-2AD10 1 unit 0.130
AC/DC 5 ... 60 V B 3VT9 300-2AD20 1 unit 0.130
Leading contacts
AC/DC 60 ... 250 V B 3VT9 300-2AJ00 1 unit 0.040
■ Overview
Rotary operating mechanisms - 3VT9 300-3HG/HH.. coupling driver for door-coupling
operating mechanism
The rotary operating mechanism must be combined from: - 3VT9 300-3HE/HF.. knob
• For rotary operation of the circuit breaker:
- 3VT9 300-3HA.0 or 3VT9 300-3HB.0 for frontside operation Mechanical interlocks and interlock for parallel switching
- 3VT9 300-3HE10 or 3VT9 300-3HE20 black knob or • Mechanical interlocks for fixed-mounted version must be
- 3VT9 300-3HF20 red knob combined from the following parts:
• For operation through the switchgear cabinet door: - 2 x 3VT9 300-3HA/HB.. rotary operating mechanism
- 3VT9 300-3HA.0 or 3VT9 300-3HB.0 for frontside operation - 2 x 3VT9 300-3HE/HF.. knob
- 3VT9 300-3HJ.. extension shaft • Mechanical interlocking by Bowden wire is intended for
- 3VT9 300-3HG/HH.. coupling driver fixed-mounted, plug-in and withdrawable versions
- 3VT9 300-3HE/HF.. knob.
• For operation through side wall of cabinet: • Mechanical interlocks must be combined from the following
- 3VT9 300-3HC10 for right side operation OR parts:
- 3VT9 300-3HD10 for left side operation - 2 x 3VT9 300-3HA/HB.. rotary operating mechanism
- 3VT9 300-3HJ..extension shaft - 1 x 3VT9 300-3HE/HF.. knob
• not lockable
• not lockable
3
• for one 3VT2 and one 3VT3 circuit breaker B 3VT9 300-8LC20 1 unit 0.393
Extension cable for motorized operating mechanism, B 3VT9 300-3MF00 1 unit 0.060
12 wires, length 60 cm
■ Overview
Plug-in version Withdrawable version
• The plug-in base includes: • The withdrawable version base includes complete accesso-
- complete accessories for assembling circuit breakers/ ries for assembling circuit breakers/switch disconnectors in
switch disconnectors in plug-in design withdrawable version.
- a set of four installation bolts (M5 x 30) for fixing the switching • The circuit breaker inside the withdrawable version base can
unit to the plug-in base be moved between an operating position and a checking po-
• The plug-in base must be outfitted with: sition (withdrawn).
- 3-pole version: 3VT3 763-.AA36-0AA0 switching unit • The withdrawable version base must be fitted with:
- 4-pole version: 3VT3 763-.AA46-0AA0 or - 3-pole version: 3VT3 763-.AA36-0AA0 switching unit or
3VT3 763-.AA56-0AA0 switching unit - 4-pole version: 3VT3 763-.AA46-0AA0 or
For mounting the plug-in version on busbars or cable lugs, 3VT3 763-.AA56-0AA0 switching unit
3VT9 300-4TA30 connecting sets are available. These are in-
cluded in the scope of supply of the 3VT3 763-.AA36-0AA0 3-
pole version ; 3VT3 763-.AA46/56-0AA0... 4-pole version switch-
ing unit. For other types of connection, other connecting sets are
3 available.
Terminals for circular 25 ... 150 Cu/Al cables B 3VT9 315-4TD30 1 unit 0.302
conductors
150 ... 240 Cu/Al cables B 3VT9 324-4TD30 1 unit 0.279
For enhancing termination 2 x 25 ... 150 Cu/Al cables B 3VT9 315-4TF30 1 unit 0.800
point protection to degree of 2 x 150 ... 240 Cu/Al cables B 3VT9 324-4TF30 1 unit 0.721
protection IP20, use the 3VT9
300-8CB30 terminal cover
Terminals for circular con- 25 ... 150 Cu/Al cables B 3VT9 315-4TD00 1 unit 0.400
ductors
1 set = 1 unit
150 ... 240 Cu/Al cables B 3VT9 324-4TD00 1 unit 0.370
2 x 25 ... 150 Cu/Al cables B 3VT9 315-4TF00 1 unit 0.500
2 x 150 ... 240 Cu/Al cables B 3VT9 324-4TF00 1 unit 0.960
Terminal for rear connection Cu/Al busbars B 3VT9 300-4RC00 1 unit 0.500
1 set = 1 unit cable lugs
3
when using 3VT9 224-4TD30, 3VT9 215-4TF30,
3VT9 224-4TF30 or 3VT9 203-4TF30 block type terminals,
intended for fixed-mounted, plug-in and withdrawable versions.
• 3-pole version B 3VT9 300-8CB30 1 unit 0.144
• 4-pole version B 3VT9 300-8CB40 1 unit 0.209
Locking device for knob B 3VT9 300-3HL00 1 unit 0.013
Enables locking the circuit breaker in „switched off manually“ position.
For locking the device, you can use up to three padlocks with a
shank diameter of max. 6 mm
■ Design
Installation and connection Recommended cross-sections of cables, busbars and flexibars
for fixed-mounted, plug-in and withdrawable versions
Main circuit
• Is connected using Cu or Al busbars or cables, and possibly Rated current Permissible cross-section Dimensions of busbars
cables with cable lugs In S WxH
• For further connecting options, connecting sets are available Cu AI Cu Al
(see page 3/9) A mm2 mm2 mm mm
• Generally, conductors from the power supply are connected
100 35 50 20 x 2 25 x 2
to input terminals 1, 3, 5, (N) and conductors from the load to
terminals 2, 4, 6, (N). However, it is possible to reverse this 125 50 70 25 x 2 25 x 3
connection (exchanging input and output terminals) without 160 70 95 25 x 3 32 x 3
limiting the rated short-circuit ultimate breaking capacity Icu) 200 95 120 25 x 4 25 x 5
• In case of feed-in from below, the circuit breakers/switch dis-
connectors must be fitted with 3VT9 300-8CE30 insulating 250 120 150 25 x 5 32 x 5
barriers on the bottom side of the circuit breaker/switch dis- 315 150 185 32 x 5 32 x 6
connector 400 185 240 32 x 6 32 x 8
3
• We recommend painting the connecting busbars in different
500 2 x120 2 x185 32 x 8 32 x 12
colors
• Input and output conductors/busbars must be mechanically 630 2 x185 2 x240 32 x 12 32 x 16
reinforced to avoid transmitting electrodynamic force to the
circuit breaker/switch disconnector during short-circuiting
• The power circuit must be connected in such a way that the Maximum circuit breaker/switch disconnector loads
deionizing space of the circuit breaker/switch disconnector is in accordance with the ambient temperature
not obstructed (see page 3/44).
3VT3 circuit breaker/switch disconnector connection to pole
Auxiliary circuits by 1 x 185 mm2 Cu cable
• Auxiliary switches, shunt trip units or undervoltage trip units
50°C 55 °C 60 °C 65 °C 70 °C
are connected to terminals using flexible 0.5 ... 1 mm2 Cu
conductors. 630 A 630 A 600 A 570 A 540 A
• The motorized operating mechanism and auxiliary circuits of
the plug-in base or withdrawable version base are connected
with a connector.
■ Technical specifications
Description Circuit breakers Switch disconnector unit
Order number 3VT3 763-2AA36/46/56-0AA0, 3VT9 363-6DT00
3VT3 763-3AA36/46/56-0AA0
Standards EN 60 947-2, IEC 947-2 EN 60 947-3, IEC 947-3
Approval marks
Number of poles 3, 4
Rated current In A 250, 315, 400, 500, 630 --
Rated uninterrupted current Iu A 630
Rated operational current Ie A -- 630
Rated operational voltage Ue V AC max. 690 AC max. 690
DC max. 440
Rated frequency fn Hz 50/60
Rated impulse withstand voltage Uimp kV 8
Selectivity AC 690 V A --
Switching mode AC 690 V -- AC-23 B
DC 440 V -- DC-23 B
Rated short-time withstand current Ue = AC 690 V Icw/t 8 kA/50 ms, 7 kA/300 ms, 6.5 kA/1 s 7,5 kA/5 s
Series Ue 3VT3 N 3VT3 H Ue --
Rated ultimate short-circuit breaking 60 kA 100 kA AC 230 V --
capacity (rms value)1) Icu 36 kA 65 kA AC 415 V
20 kA 35 kA AC 500 V
15 kA 20 kA AC 690 V
Rated short-circuit breaking 40 kA 75 kA AC 230 V --
capacity (rms value) Ics/Ue 18 kA 36 kA AC 415 V
10 kA 20 kA AC 500 V
8 kA 15 kA AC 690 V
Rated short-ckt making capacity (peak value) Icm/Ue 75 kA 140 kA AC 415 V 14 kA/AC 415 V, 14 kA/AC 440 V
Off-time at Icu ms 10 --
Losses per pole at In = 630 A W 75
Mechanical endurance cycles 20000
Electrical endurance (Ue = AC 415 V ) cycles 5000
Switching frequency cycles/ 120
hr
Operating force N 110
Front-side device protection IP40
Terminal protection IP20
Operating conditions
Reference ambient temperature °C 40
Ambient temperature range °C -40 ... +55
Working environment dry and tropical climate
Degree of pollution 3
Max. elevation m 2000
Seismic resistance m/s2 3 g at 8 ... 50 Hz
Design modifications
Front/rear connection ✓/✓
Plug-in design ✓/+
Withdrawable design ✓/+
Accessories
Switches-auxiliary/relative/signal/leading ✓/✓/✓/✓
Shunt trip unit ✓
Undervoltage trip unit/with leading switch, with alarm switch ✓/✓
Front rotary oper. mechanism/lateral oper. mech. right/left ✓/✓
Mechanical interlocking to the rotary oper. mechanism, ✓
by Bowden wire
Motorized oper. mechanism with operations counter ✓
Locking-type lever ✓
Bolt sealing insert/additional cover for trip unit ✓/✓
✓ available, 1) If the circuit breaker connection is reversed (input terminals 2, 4, 6 ,
-- unavailable output terminals 1, 3, 5), Icu does not change.
+ in preparation
■ Schematics
Circuit breakers with accessories
3-pole version
3VT9 325-6..00 1 3 5
3VT9 300-2AJ00
B1
10.Y1
10.Y1
A1
A1
3VT9 300-1U.00
3VT9 300-1U.10
3VT9 300-1U.10
10.Y3
3VT9 300-1S.00
X3 12 10 9 7 3 4 1 5
I>
A
3
I>
NC NO
NC NO
or or or
V Q
S6 S5 M P U< U U< B
C C
T1
T2
TEST T3
MP
10.Y2
10.Y2
10.Y4
A2
A2
B2
11 8 6 2 2 1 2 4 6
X3 X4 J
acc.comp. no. 10 3VT9 300-4PA.0
NSO0_00249
PE N- YC SO 2 SO 3 3VT9
300-
Ext.oper. 4WA.0
counter
1 4 2 1 4 2 2 4 6
Plug-in device/Withdrawable device
Connecting cable
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
X2
Switches
signal relative auxiliary auxiliary auxiliary auxiliary
1.3
1.1
1.2
1.4
2.3
2.1
2.2
2.4
3.3
3.1
3.2
3.4
4.3
4.1
4.2
4.4
5.3
5.1
5.2
5.4
2.3
3.3
2.1
3.3
2.1
3.1
A
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AH10
B
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AH10
or or
3.4 3VT9 300-2AG10
or or or or or or or or or or or
NSO0_00250
1.4
1.2
1.1
2.4
2.2
2.1
3.4
3.2
3.1
4.4
4.2
4.1
5.4
5.1
2.4
2.2
2.2
acc.c. no. 1 acc.c. no. 2 acc.c. no. 3 acc.c. no. 4 acc.c. no. 5 acc.c. no. 2 + 3
X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Connecting cable
3VT9 325-6..0 1 3 5 7
3VT9 300-2AJ00
B1
10.Y1
10.Y1
A1
A1
3VT9 300-1U.00
3VT9 300-1U.10
10.Y3
3VT9 300-1S.00
A
X3 12 10 9 7 3 4 1 5
I>
I>
NC NO
3 NC NO
or or or
V Q
S6 S5 M P U< U U< B
C C
T1
T2
TEST T3
T4
MP
10.Y2
10.Y2
10.Y4
A2
A2
B2
11 8 6 2 2 1
X3 X4 J 2 4 6 8
acc.comp. no. 10 3VT9 300-4PA.0
NSO0_00251
PE N- YC SO 2 SO 3 3VT9
300-
Ext.oper. 4WA.0
counter 1 4 2 1 4 2 2 4 6 N
Plug-in device/Withdrawable device
Connecting cable
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
X2
Switches
signal relative auxiliary auxiliary auxiliary auxiliary auxiliary auxiliary auxiliary auxiliary
7.3
7.1
7.2
7.4
1.3
1.1
1.2
1.4
9.3
9.1
9.2
9.4
3.3
3.1
3.2
3.4
4.3
4.1
4.2
4.4
5.3
5.1
5.2
5.4
2.3
3.3
2.1
3.3
2.1
3.1
6.3
6.1
6.2
6.4
2.3
2.1
2.2
2.4
8.3
8.1
8.2
8.4
A
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AH10
B or or
2.2 3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AH10
or or
NSO0_00252
or or or or or or or or or or or or or or or or
7.4
7.1
9.4
9.1
1.4
1.2
1.1
3.4
3.1
4.4
4.1
5.4
5.1
2.4
2.2
2.2
6.4
6.1
2.4
2.1
8.4
8.1
acc.c. no. 1 acc.c. no. 2 acc.c. no. 3 acc.c. no. 4 acc.c. no. 5 acc.c. no. 2 + 3 acc.c. no. 6 acc.c. no. 7 acc.c. no. 8 acc.c. no. 9
X1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Connecting cable
■ Functions
States of auxiliary switches located in the switching unit accessory compartment
Circuit breaker state Accessory compartment
1 2 3, 4, 5 10 2 and 3 2 and 3 2 and 3 1 2 3, 4, 5
(6 ... 9)1) (6 ... 9)1)
Lever position of circuit breaker
3VT9 300-2AD10
3VT9 300-2AD10
3VT9 300-2AD10
3VT9 300-2AH10
3VT9 300-2AH10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AC10
3VT9 300-2AC10
3VT9 300-2AE10
3VT9 300-2AG10
3VT9 300-2AF10
3VT9 300-2AJ00
3VT9 300-1U.10
State of the main contacts
Switched no 1 1 0 0 1 1 0 1 0 1 1 0 1 0 0 1 0 0 1 1 0
■ Overview
The electronic trip unit is a separate and interchangeable unit, ETU MP trip units
which has to be ordered in addition to the 3VT3 switching unit.
By exchanging the trip unit, the range of the circuit breaker’s L I
rated current can be easily changed.
Ir
Trip units for 3VT3 switching units are available for current values t
of In = 250, 400 and 630 A. The ETU LP trip units feature rated
currents of 250, 315, 400, 500 and 630A. The trip units (including
regulation of -60%) cover a current range from 100 to 630 A. tr
Tripping characteristics
Several different trip units are available. Some have adjustable
characteristics (in order to match the protected device and to
achieve the required selectivity): Ii
50 ms
ETU LP trip units
NSO0_00354
0 ms
3
L I
t I
Electronic trip units ETU LP have have more characteristics with
adjustable Ir, tr and Irm.
ETU MPS trip units
L S I
Ir
t
tr
NSO0_00502
I
Electronic trip units ETU LP have one type of characteristic and Isd
tsd
fixed In and Irm settings.
ETU DP trip units
NSO0_00214
L I
Ir
t I
Electronic trip units ETU MPS have more characteristics with ad-
justable Ir, tr, Isd and tsd.
ETU LP, DP, MP and MPS trip units are intended for 3-pole 3VT3
763-.AA36-0AA0 switching units and 4-pole
3VT3 763-.AA46-0AA0 switching units with disconnecting of the
N pole.
Ii
ETU DPN trip units
L I
NSO0_00353
Ir
t
I
IN
Electronic trip units ETU DP have one type of characteristic with tr
adjustable Ir and Irm.
Ii
NSO0_00531
I
ETU DPN trip units are intended for 4-pole 3VT3 763-.AA56-
0AA0 switching units with protected N pole. They have more
characteristics with adjustable Ir, tr, Irm and IN.
3 NSO0_00355
3VT9 325-6AB00 250 1000
1.0 3VT9 331-6AB00 315 1260
k [-]
3VT9 340-6AB00 400 1600
3VT9 350-6AB00 500 2000
0.8
3VT9 363-6AB00 630 2520
0.6
Tripping characteristics
T
NSO0_00356
0.4 10000
5000 Ir
t [s]
2000
0.2
1000
500
0.0
50 60 70 80 90 100 200
L
Ir [%] 100
50
Decrease of tripping time with load
20
T - When tripping from the trip unit’s “warm” state, the tripping
time of the characteristic is cut short during the standstill time tu 10
by coefficient k. 5
In = 250 A
Thermal standstill time of the characteristics 2
In = 315 A
For all trip units, the thermal standstill time is tu ≥ 30 min. During 1 In = 400 A
this time, the tripping time tsd is cut short from the cold-state 0.5 In = 500 A I
characteristic by the coefficient k. In = 630 A
0.2
In = 500 A
In = 400 A
In = 630 A
In = 250 A
In = 315 A
Ii
The real tripping time is ts = k . tsd 0.1
Example 0.05
The shortening constant can be read from the diagram. With 0.02
steady current 85% of Ir the real tripping time will be decreased 0.01
to: 0.5 1 2 5 10 20 50
x In
ts = 0.74 . tsd
k [–] time shortening coefficient
Ir [A] adjusted rated current of the trip units
tsd [s] tripping time of the trip unit, derived from the characteristic
ts [s] real tripping time of the trip unit, tripped from warm state
tu [s] standstill period for particular characteristics
Trip units are preset by the manufacturer
Ir = min
Restart = T(t)
Ii = min, 0 ms
tr = TV, t(t), min
Isd = 0 ms, min
IN = 0.5 Ir
Another parameter for adjusting the trip unit consists of the rated 3VT9 325-6AP00 250 172 3 (M 3) T(0) 3,75
current and short-circuit tripping level. The time delay of the 180 3 (M 3) T(t) 3,75
short-circuit trip unit can be set to 0 ms or 50 ms. The operational 190 8 (M 8) T(t) 3,1
state 70% of Ir is signalled by an LED indicator that flashes green
3 in a 1.5 s interval. As the load grows, the blinking frequency of
the diode increases. In case of a load larger than 110% of Ir, this
200
210
15 (M 15)
20 (M 20)
T(t)
T(t)
2.5
2,0 50
LED will turn red and just before tripping will begin to blink red. 220 20 (TV 20) T(t) 1,5
Located on the lower part of the trip unit cover are two photocells 231 10 (TV 10) T(t) 1,0
for communicating with the signalling unit.
243 3 (TV 3) T(t) 0,6
The trip units have tripping characteristics especially designed 250 1 (TV 1) T(t) 0,32
for practical purposes that provide for optimal exploitation of
transformers up to 1.5 Ir. A total of 8 characteristics can be set 160 1 (TV 1) T(0) 0,5
on the trip unit. Mode “M” provides 4 characteristics suitable for 172 3 (TV 3) T(0) 1,0
protecting motors and in mode “TV” are 4 characteristics for pro- 180 10 (TV 10) T(0) 1,6
tecting transformers and lines. The shape of each characteristic
190 20 (TV 20) T(0) 2,4
can be changed using a selector switch.
200 20 (M 20) T(0) 3,2 0
210 15 (M 15) T(0) 4,0
220 8 (M 8) T(0) 5,0
3VT9 340-6AP00 400 231 3 (M 3) T(0) 6,0
243 3 (M 3) T(t) 6,0
250 8 (M 8) T(t) 5,0
275 15 (M 15) T(t) 4,0
290 20 (M 20) T(t) 3,2
315 20 (TV 20) T(t) 2,4 50
345 10 (TV 10) T(t) 1,6
360 3 (TV 3) T(t) 1
400 1 (TV 1) T(t) 0,5
250 1 (TV 1) T(0) 0,8
260 3 (TV 3) T(0) 1,4
275 10 (TV 10) T(0 2
290 20 (TV 20) T(0)) 3 0
305 20 (M 20) T(0) 4
315 15 (M 15) T(0) 5,1
345 8 (M 8) T(0) 6,3
3VT9 363-6AP00 630 360 3 (M 3) T(0) 7
400 3 (M 3) T(t) 6,3
435 8 (M 8) T(t) 6,3
455 15 (M 15) T(t) 5,1
480 20 (M 20) T(t) 4
500 20 (TV 20) T(t) 3 50
550 10 (TV 10) T(t) 2
575 3 (TV 3) T(t) 1,4
630 1 (TV 1) T(t) 0,8
3
0.5 0.5
I I
0.2 0.2
0.1 0.1
50 50
0.05 0.05
3.1 3.1
In = 250 A 0.32 0.6 1.0 1.5 2.0 2.5 3.75 Ii [kA] In=250 A 0.32 0.6 1.0 1.5 2.0 2.5 3.75 Ii [kA]
0.02 0 0.02 0
0.01 0.01
0.1 0.1
50 50
0.05 5.0
0.05
In = 400 A Ii [kA] In=400 A 5.0 Ii [kA]
0.5 1.0 1.6 2.4 3.2 4.0 6.0 0.5 1.0 1.6 2.4 3.2 4.0 6.0
0.02 0 0.02 0
0.01 0.01
0.1 0.1
50 50
0.05 6.3 0.05 6.3
In = 630 A 0.8 1.4 2.0 3.0 4.0 5.1 7.0 Ii [kA] In=630 A 0.8 1.4 2.0 3.0 4.0 5.1 7.0 Ii [kA]
0.02 0 0.02 0
0.01 0.01
0.1 0.2 0.5 1 2 5 10 20 50 0.1 0.2 0.5 1 2 5 10 20 50
x In x In
val. As the load grows, the blinking frequency of the diode in-
210 20 (M 20) T(t) 9
creases. In case of a load larger than 110% of Ir, this LED will
turn red and just before tripping will begin to blink red. Located 220 20 (TV 20) T(t) 3
on the lower part of the trip unit cover are two photocells for com- 231 10 (TV 10) T(t) 5 300
municating with the signalling unit. 243 3 (TV 3) T(t) 7
The trip units have tripping characteristics especially designed 250 1 (TV 1) T(t) 9
for practical purposes that provide for optimal exploitation of 160 1 (TV 1) T(0) 3
transformers up to 1.5 Ir. A total of 8 characteristics can be set
on the trip unit. Mode “M” provides 4 characteristics suitable for 172 3 (TV 3) T(0) 5 0
protecting motors, and mode “TV” incorporates 4 characteristics 180 10 (TV 10) T(0) 7
for protecting transformers and lines. The shape of each charac- 190 20 (TV 20) T(0) 9
teristic can be changed with a selector switch.
200 20 (M 20) T(0) 3
210 15 (M 15) T(0) 5 100
220 8 (M 8) T(0) 7
7 3VT9 340-6AS00 400 231 3 (M 3) T(0) 9
243 3 (M 3) T(t) 3
250 8 (M 8) T(t) 5 200
275 15 (M 15) T(t) 7
290 20 (M 20) T(t) 9
315 20 (TV 20) T(t) 3
345 10 (TV 10) T(t) 5 300
360 3 (TV 3) T(t) 7
400 1 (TV 1) T(t) 9
250 1 (TV 1) T(0) 3
260 3 (TV 3) T(0) 5 0
275 10 (TV 10) T(0) 7
290 20 (TV 20) T(0) 9
305 20 (M 20) T(0) 3
315 15 (M 15) T(0) 5 100
345 8 (M 8) T(0) 7
3VT9 363-6AS00 630 360 3 (M 3) T(0) 9
400 3 (M 3) T(t) 3
435 8 (M 8) T(t) 5 200
455 15 (M 15) T(t) 7
480 20 (M 20) T(t) 9
500 20 (TV 20) T(t) 3
550 10 (TV 10) T(t) 5 300
575 3 (TV 3) T(t) 7
630 1 (TV 1) T(t) 9
In = 250 A
3 x Ir
5 x Ir
7 x Ir
9 x Ir
0.05 I The current of the fourth pole (N pole) is adjusted using the IN
0.02 0 switch as a multiple of the Ir current. Measuring of current on the
I sd
0.01 fourth pole can be disabled by turning the button to the “OFF”
0.1 0.2 0.5 1 2 5 10 20 50 position.
x In
Ir tr I sd tv In Tripping characteristics
NSO0_00361
10000
1 x Ir
IN = 0.5 x Ir
0.75 x Ir
5000 IN
t [s] IN Ir tr Ii
2000 Ir
min. max.
1000 20
500 N 10
200
3
100
50 1
20
L 20
10
10
5
t r [ S]
2 3
1 I
1
0.5
In = 400 A
In = 630 A
I n = 250 A In = 250 A
0.2
I n = 400 A
2 x Ir
4 x Ir
7 x Ir
9 x Ir
0.1 I n = 630 A
0.05
Ii
0.02
0.01
0.1 0.2 0.5 1 2 5 10 20 50
x In
IN Ir tr In Ii
■ Overview
Order number according to contact arrangement
Arrangement Order No. Number of contacts Contact types
of contacts
01 3VT9 300-2AC10 (20) 1 NO
20 3VT9 300-2AE10 (20) 2 NO
01 3VT9 300-2AD10 (20) 1 NC
02 3VT9 300-2AG10 (20) 2 NC
11 3VT9 300-2AF10 (20) 1 + 1 NC + NO
001 3VT9 300-2AH10 (20) 1 NC + NO
■ Function
State of switches located in the switching unit accessory compartment
Switches
early contact signal relative auxiliary auxiliary auxiliary auxiliary auxiliary auxiliary auxiliary auxiliary
3VT9 300-2AJ00
6.3
6.1
6.2
6.4
7.3
7.1
7.2
7.4
1.3
1.1
1.2
1.4
9.3
9.1
9.2
9.4
3.3
3.1
3.2
3.4
4.3
4.1
4.2
4.4
5.3
5.1
5.2
5.4
2.3
3.3
2.1
3.3
2.1
3.1
10.Y1
10.Y3
2.3
2.1
2.2
2.4
8.3
8.1
8.2
8.4
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AH10
or or
10.Y4
NSO0_00362
or or or or or or or or or or or or or or or or
6.4
6.1
7.4
7.1
9.4
9.1
1.4
1.2
1.1
3.4
3.1
4.4
4.1
5.4
5.1
2.4
2.2
2.2
2.4
2.1
8.4
8.1
acc.c. no. 10 acc.c. no. 1 acc.c. no. 2 acc.c. no. 3 acc.c. no. 4 acc.c. no. 5 acc.c. no. 2 + 3 acc.c. no. 6 acc.c. no. 7 acc.c. no. 8 acc.c. no. 9
■ Technical specifications
Order No. 3VT9 300-2A.10 3VT9 300-2A.201) 3VT9 300-2AJ00 3VT9 300-2AH10 3VT9 300-2AH201)
Rated operational voltage Ue V AC 60 ... 500 AC 5 ... 60 AC 250 AC 24 ...250 AC 5 ..60
DC 60 ... 500 DC 5 ... 60 DC 24 ...250 DC 5 ...60
Rated isolation voltage Ui V 500 250
Rated frequency fn Hz 50/60
Rated operational current Ie/Ue
• AC-12 -- 0.004 ... 0.5 A/5V -- -- --
• AC-15 6 A/240 V,4 A/400 V, -- 1 A/AC 250 V 1.5 A/AC 250 V --
2 A/500 V
• DC-12 -- 0.004 ... 0.5 A/5V -- -- 0.01 A/DC 60 V
• DC-13 0.4 A/240 V, 0.3 A/400 V, 0.004 ... 0.01/60 V -- 0.2 A/DC 250 V --
0.2 A/500 V
Thermal current Ith A 10 0.5 -- 6 0.5
Arrangement of contacts 01, 10, 02, 11, 20 02, 11, 20 001
Connector cross-section S mm2 0.5 ... 1
Terminal protection IP20
(connected switch)
1)
3VT9 300-2A.20 is not suitable for controlling electromagnetic loads.
■ Overview
Order number of shunt trip units
according to the rated operating voltage
Ue Order No.
AC/DC 24, 40, 48 V 3VT9 300-1SC00
1AC/DC 10 V 3VT9 300-1SD00
AC 230, 400, 500 V/DC 220 3VT9 300-1SE00
■ Function
Shunt trip units
Circuit breaker switched off by the shunt trip unit Circuit breaker states and lever positions of the circuit breaker
NSO0_00364
5.4 5.3 20
4.4 4.3 1
3…5
20
1
3VT9 300-1S.00
2.4 2.3
B1
2
0
Relative switch
30
1
2.2 2.1
0 U
t [ms]
NSO0_00518
B2
N-
NSO0_00365
Main contacts Circuit breaker state Lever positions of circuit breakers
Switched on
2 1 20
4 3 1
6 5
0
Auxiliary switch Switched off by trip units, or by TEST
button or by the trip pushbutton on
compartment
accessory
5.4 5.3 30 the motorized operating mechanism
1
3…5
4.4 4.3
3.4 3.3 Switched off manually or electrically
0
Auxiliary switch by operating mechanism
compartment
2 2 NC
accessory
30
1 11 1+1 NC + NO
2.4 2.3
2
3
0 20 2 NONO
Relative switch
30 L+ L+
1
2.2 2.1
0
Early switch
compartment
accessory
3VT9 300-1U.00
20
A1
10.Y1
A1
1
3VT9 300-1U.10
10
10.Y2 10.Y1 0
10.Y4 10.Y3
Early switch
U< U<
20
10.Y2 10.Y1 1
10.Y2
NSO0_00519
10.Y4 10.Y3
0
A2
A2
t [ms]
N- N-
■ Technical specifications
Shunt trip units Undervoltage trip units
Order No. 3VT9 300-1S.00 Order No. 3VT9 300-1U.00 3VT9 300-1U.101)
Rated operating voltage Ue AC 24, 40, 48, 110, 230, 400, 500 V Rated operating voltage Ue AC 24, 40, 48, 110, 230, 400, 500 V
DC 24, 40, 48, 110, 220 V DC 24, 40, 48, 110, 220 V
Rated frequency fn Hz 50/60 Rated frequency fn Hz 50/60
Input power at 1.1 Ue AC < 3 VA Input power at 1.1 Ue AC < 3 VA < 3 VA
DC <3W DC <3W <3W
Functional description U ≥ 0,7 Ue the circuit breaker must trip Functional description U 0.85 Ue
(circuit breaker can switch on)
Time to switch-off ms 20 U 0.35 Ue
Continuous load Yes (the circuit breaker must trip)
Connector cross-section S mm2 0.5 ... 1 Time to switched-off ms 20
Terminal protection IP20 Continuous load Yes
(connected trip unit) Connector cross-section S mm2 0.5 ... 11)
Location in accessory com- 10 Terminal protection IP20
partment No. (connected trip)
Location in accessory 10
compartment No.
Earl switch --
Rated operating voltage Ue V -- AC 250
Rated frequency fn Hz -- 50/60
Rated operating current Ie/Ue V -- AC 1 A/AC 250
Arrangement of contacts -- 02, 11, 20
Connector cross-section S mm2 -- 0.5 ... 11)
Terminal protection -- IP20
(connected trip unit)
1)
Cannot be used in combination with motorized operating mechanism
3VT9 300-3M..0.
■ Overview
Rotary operating mechanism Mechanical interlocks and mechanical interlock for parallel
switching
The following components of the rotary operating mechanisms
are required: • Mechanical interlocks for fixed-mounted versions require the
following components:
• To switch the switching unit: - 2 x 3VT9 300-3HA/HB.. rotary operating mechanism
- 3VT9 300-3HE10 or 3VT9 300-3HE20 black knob - 2 x 3VT9 300-3HE/HF.. knob
- 3VT9 300-3HF20 red knob
• Mechanical interlocking with Bowden wire is intended for
• To switch the switching unit through the switchgear cabinet fixed-mounted, plug-in and withdrawable versions
door:
- 3VT9 300-3HJ..extension shaft • Mechanical interlocking with Bowden wire requires the follow-
- 3VT9 300-3HG/HH.. coupling driver for door-coupling oper- ing components:
ating mechanism - 2 x 3VT9 300-3HA/HB.. rotary operating mechanism
- 3VT9 300-3HE/HF.. knob - 1 x 3VT9 300-3HE/HF.. knob
■ Design
The rotary operating mechanism makes it possible to actuate the
circuit breaker: 3
Operation from the front panel of the circuit breaker (Fig. 1)
3VT9 300-3HA/HB.. rotary operating mechanism
+ 3VT9 300-3HE/HF.. knob
Operation through the switchgear cabinet door (Fig. 2)
3VT9 300-3HA/HB.. rotary operating mechanism
+ 3VT9 300-3HJ.. extension shaft
+ 3VT9 300-3HE/HF.. knob
+ 3VT9 300-3HG/HH.. coupling driver
Fig. 1: Rotary operating mechanism with knob
Operation through side wall of switchgear cabinet
3VT9 300-3HC/HD10.. rotary operating mechanism
+ 3VT9 300-3HJ.. extension shaft
+ 3VT9 300-3HE/HF.. knob
+ 3VT9 300-3HG/HH.. coupling driver
Enhanced safety for operator:
• The rotary operating mechanism and knob allow operators to
lock the circuit breaker in position “switched off manually“. The
unit and knob of the rotary operating mechanism can be
locked by three padlocks with a shank diameter up to 6 mm
• Each coupling driver for door-coupling operating mechanism
Fig. 2: Rotary operating mechanism with extension shaft, coupling driver prevents the cabinet door from being opened when the circuit
and knob breaker is in on-state or after tripping. Types 3VT9300-3HG10
The rotary operating mechanism makes it possible to actuate the and 3VT9300-3HG20 prevent the cabinet door from being
circuit breaker by turning a knob, e.g. in order to switch ma- opened when the circuit breaker is in the state "switched off
chines on and off. The modular concept of the operating mech- manually" and when the rotary operating mechanism knob is
anisms makes allows simple mounting on the switching unit after locked out.
the accessory compartment cover is removed. The operating • Two circuit breakers with rotary operating mechanisms can be
mechanism and its accessories must be ordered separately provided with mechanical interlocking or with parallel me-
(see page 3/6). chanical switching (see page 3/31).
• The rotary operating mechanism is fixed right on the switching
unit of the circuit breaker.
• The rotary operating mechanism coupling driver is fixed onto
the switchgear door and it provides protection IP40 or IP66.
• The rotary operating mechanism knob is placed on the rotary
operated mechanism unit or on the rotary operating mecha-
nism coupling driver
• The extension shaft is available in two versions, standard
(length 365 mm - can be shortened) and telescopic (adjust-
able length 245 ... 410 mm).
3
3VT9 300-3HG20 Coupling driver yellow -- IP40 yes yes --
3VT9 300-3HH10 Coupling driver black -- IP66 yes no --
3VT9 300-3HH20 Coupling driver yellow -- IP66 yes no --
3VT9 300-3HJ10 Extension shaft, can be shortened -- -- -- -- -- 365
3VT9 300-3HJ20 Extension shaft, telescopic -- -- -- -- -- 245 ... 410
■ Function
3VT9 300-8LA00 mechanical interlocking 3VT9 300-8LB00 mechanical parallel switching
Mechanical interlocks make sure that two circuit breakers can- Mechanical interlocks for parallel switching are for simultaneous
not trip simultaneously, but always just individually. Both circuit switching of two circuit breakers. Parallel switching can be used
breakers may be switched off simultaneously. Interlocking can between two 3VT3 circuit breakers or between 3VT3 and 3VT2
be used between two 3VT3 circuit breakers or between one circuit breakers. Each circuit breaker must be furnished with a
3VT3 and one 3VT2 circuit breaker. Both circuit breakers must rotary operating mechanism and at least one of them with a
be furnished with rotary operating mechanisms (at least one of knob.
them with a rotary operating mechanism and knob).
When using a mechanical interlock it is required to comply with
the dimensions shown in the figure and in the table.
When using a mechanical interlock for parallel switching it is re-
quired to comply with the dimensions shown in the figure and in
3
the table.
1 3 5
L
RP-BD-CK10
PS
PS
PS
X X
TEST
TEST
NSO0_00234
NSO0_00233
RP-BD-CK10
RP-BD-CK10
PS
PS
PS
SP
SV
PS
PS
PS
SP
SV
TEST
TEST
NSO0_00235
NSO0_00366
148
0
ON ON
=4
0 ... 700
min
OFF OFF
R
45
TEST TEST
30 min. 80
■ Design
• The motorized operating mechanism can be locked in off po-
sition using as many as three padlocks with shank diameter
max. 4.3 mm.
• A 3VT9 300-3MF20 cover can be attached to the ON-OFF
switch of the motorized operating mechanism, and then
sealed with sealing wire. The cover prevents turning on the cir-
cuit breaker from the drive panel.
• Extension cable 3VT9 300-3MF00 has a connector on one
side that connects to the connector located on the motor
mechanism and conductors on the other side that connect, for
example, to a terminal block.
3
sured by a closing coil. The motor mechanism can trip the circuit
breaker in 900 ms. This method of tripping is suitable for most Rated frequency fn Hz 50/60
technological applications. When faster circuit breaker tripping Control pulse length for storing ms 400 ∞1)
is required (e.g., because an emergency STOP button was Control pulse length
pressed), it is possible to use the mechanism in combination
for switching on ms 20 ... 700 1)
with an undervoltage trip unit or a shunt trip unit.
for switching off ms 400 ...∞1)
• The motorized operating mechanism front panel contains a
selector switch for selecting the drive modes. There is also the Time before switching on ms < 60
possibility to remotely indicate the selector switch state. Time before switching off ms 900
- The first mode is automatic remote control (selector switch in Frequency of cycles ON/OFF 3 contact making/min
position AUTO). This is the standard position in automatic
operation. Frequency of cycles - instant suc- 10 contact making
cessive ON/OFF cycles
- The second mode is manual control (selector switch position
MANUAL). The motorized operating mechanism does not Mechanical endurance 20000 contact making
need any voltage to perform its function. Input power AC VA 100
• Remote switching on and off in position AUTO is carried out DC W 100
with pushbuttons that must be connected to the drive unit con- Protection
nector. Furthermore, this position makes it is possible to con-
• AC 24, 48, 110 V; AC 230 V LSN 4C/1; LSN 2C/1
trol the circuit breaker with the pushbuttons located on the
drive unit front panel. • DC 24, 48, 110 V; DC 220 V LSN-DC 4C/1; LSN-DC 2C/1
• In MANUAL mode it is possible to switch on and off with the Rated operating current V AC 5 A/250
green and red pushbuttons located on the front panel of the AUTO / MANUAL switches Ie/Ue DC 0.5 A/250
motorized operating mechanism cover. The function of the re- Order No. 3VT9 300-3MF00
mote control ON button in MANUAL mode is locked out,
Number of conductors 12
whereas the function of the remote control OFF button remains
active for safety reasons. Conductor cross sections S mm2 0.35
• The motorized operating mechanism, as opposed to the cir- Conductor lengths cm 60
cuit breaker, recognizes only two fixed positions. In the first 1)
position the circuit breaker is ON. When the circuit breaker is For sequence of control pulses, see page 3/34.
tripped in AUTO mode by the trip unit or shunt/undervoltage
trip units, then because of mechanical link between the circuit
breaker and the motor mechanism, a pulse will be generated
to automatically wind up the spring of the storage unit. The
motor mechanism can be wound up automatically by perma-
nent closing switch S. In the second fixed position the circuit
breaker is switched off and the loaded drive is ready to switch
the breaker on after it has received the setting pulse.
• The motorized operating mechanism makes it possible to con-
trol the circuit breaker after the loss of control voltage. In MAN-
UAL and AUTO modes, it is possible to wind up the storage
unit by repeated rotation of the foldable handle. After charging
the spring mechanism with spring energy, it is possible to
switch the circuit breaker on and off with the control buttons lo-
cated on the front panel of the motor mechanism.
• The front panel incorporates a storage unit status indicator to
indicate what state the 3VT3 motor mechanism unit storage is
in and whether it is possible to switch the circuit breaker on.
The 3VT3 motor mechanism is also able to remotely indicate
the storage status. A corresponding signal is issued to the ter-
minal strip. 3VT2 motor mechanism have optional designs,
alternatively with MANUAL/AUTO indication.
• The motorized operating mechanism can be furnished with an
electromechanical operations counter that may be installed in
the drive cover or outside of the circuit breaker (e.g. in the
switchgear door). A metal holder included in the scope of sup-
ply of the external operations counter. Connecting is facilitated
with connectors.
■ Function
Circuit breaker switched on/off by the motorized operating mechanism
Circuit breaker switched on by the motorized operating Circuit breaker switched off by the motorized operating
mechanism – electrically by pushbutton ON mechanism- electrically by pushbutton OFF
NSO0_00368
NSO0_00369
Main contacts Main contacts
2 1 50 2 1 900
4 3 1 4 3 1
6 5 6 5
0 0
Auxiliary switch Auxiliary switch
compartment
compartment
5.4 5.3 50 900
accessory
accessory
5.4 5.3
4.4 4.3 1 4.4 4.3 1
3…5
3…5
3.4 3.3 3.4 3.3
0 0
Auxiliary switch Auxiliary switch
5.2 5.1 50 5.2 5.1 900
4.2 4.1 1 4.2 4.1 1
3.2 3.1 3.2 3.1
0 0
3
Relative switch Relative switch
compartment
compartment
accessory
accessory
1 1
2.4 2.3 2.4 2.3
0 0
2
2
1 1
2.2 2.1 2.2 2.1
0 0
Early switch Early switch
compartment
compartment
20 900
accessory
accessory
1 1
10
10
20 900
10.Y2 10.Y1 1 10.Y2 10.Y1 1
10.Y4 10.Y3 10.Y4 10.Y3
0 0
t [ms] t [ms]
Motor drive
Wiring diagram description
Symbol Description
X3 12 10 9 7 3 4 1 5
MP Motorized operating mechanism 3VT9 300-3M..0
M Motor
P Energy storage device
X3 Connector to connect control circuits
NC NO NO
S6 NC M P
X4 Connector for external operations counter
C C
S5 S5 Switch indicating AUTO/MANUAL modes
S6 Switching indicating energy storage
(ready to on: NO-C)
YC External operations counter 3VT9 300-3MF10
MP
B recommended wiring of the control circuits
NSO0_00370
NSO0_00527
Main contacts
2 1 20 Control circuit
4 3 1
6 5 Q3
0 L+
Auxiliary switch
compartment
accessory
20 ON
1 S
3.4 3.3 20
3
0 B OFF
Auxiliary switch
30 Motor drive
1
3.2 3.1
0
B1
A1
Relative switch
3VT9 300-1U.00
3VT9 300-1S.00
X3 12 10 9 7 3 4 1 5
compartment
accessory
20 650
1
2.4 2.3
2
0
3
Relative switch NC NO
NC NO
30 650 or
1
2.2 2.1 S6 S5 M P U< U
0 C C
Early switch
compartment
accessory
20 650
1
1.4 1.3
1
0 MP
Early switch
NSO0_00371
A2
30 650 11
B2
8 6 2 2 1
1 X3 X4 J
1.2 1.1 acc.c. no.10
0
PE N- YC N-
t [ms]
Operations
counter
Tripping of the circuit breaker with motorized operating mecha-
nism by a shunt trip unit or undercurrent trip unit (switch S – Circuit breaker switched on by motorized operating mechanism
automatic spring charging) (electrical ON signal) and switched off by undervoltage trip unit
NSO0_00242
20 ON
accessory
1 S
3.4 3.3 20
0
3
B OFF
Auxiliary switch
20
1 Motor drive
3.2 3.1
0
Relative switch
A1
B1
compartment
30 520
accessory
1
2.4 2.3
X3 12 10 9 7 3 4 1 5
0
2
Relative switch
SP-BHD-X...
SV-BHD-X...
30 520 NC NO
1
2.2 2.1
0 NC NO
t [ms] or
S6 S5
M P U< U
C C
MP
NSO0_00372
A2
B2
11 8 6 2 2 1
X3 X4 J
acc.c. 10
PE N- N-
YC
Operations
counter
520 > 880 IMP ON Make pulse for motorized operating mechanism
RS 1 IMP OFF Break pulse for motorized operating mechanism
0 X Random segment of time
NSO0_00246
> 1400
20 … 700
1
IMP ON
0 Circuit breaker states and toggle positions of the circuit breakers
t [ms]
Circuit breaker state lever positions of circuit breakers
R OFF
3
Switched on
Circuit breaker switched off by trip unit or shunt/undervoltage Switched off by trip units, or by TEST
trip units and switched on by the motorized operating mecha- button or by the trip pushbutton on the
nism - switch S permanently closed (automatic spring charging) motorized operating mechanism
Switched off manually or electrically by
50 the operating mechanism
HK 1
0
> 1400
20 … 700
1
IMP ON
0
t [ms]
R OFF
50
HK 1
0
X > 1400
400 … ∞ 20 … 700
1
IMP S IMP ON
0
t [ms]
R OFF
NSO0_00080
Q3
> 1400
L+ 200 … 700
1
IMP ON
0
ON
S 50
B OFF 1
HK
0
X3 12 10 9 7 3 4 1 5 20
200
3
3VT9 300-1U.00
3VT9 300-1S.00
SV 1
0
NC NO
NC NO
SP 1
S6 S5 or 0
M P U< U t [ms]
C C
NSO0_00081
> 100
MP 400 … ∞ 200 … 700
1
NSO0_00079
IMP S IMP ON
0
A2
B2
11 8 6 2 2 1
X3 X4 J 50
X > 1400
acc.c. 10 1
PE N - N- HK
YC 0
Cycle
counter X + 520 > 880
RS 1
0
Symbol Description 20
>200
M Motor SV 1
P Energy storage device 0
■ Overview
Plug-in bases Position signalling
3VT9 300-4WL00 position signalling switch
3
plug-in base inserting the circuit breaker/disconnector
States of 3VT9 300-4WL00 switches in plug-in base
The plug-in version of the circuit breaker/switch disconnector is according to the circuit breaker position
intended for demanding industrial applications where rapid ex-
change of the circuit breaker is needed. Accessory compartment 11, 12, 13, 14 (19, 20)1)
• The plug-in base includes complete accessories for assem- Circuit breaker position 1 1
bling circuit breaker/switch-disconnector in plug-in design
from the original fixed-mounted version 2 4 2 4
• The components of the plug-in base are: Inserted 0 1
- supporting part of the plug-in base
- 2 connection sets (total of 6 terminals) for fitting on to the Removed 1 0
switching unit 0 = contact open, 1 = contact closed
- interlocking connecting rod (ensures automatic switching off 1)
Accessory compartments 19 and 20 are for 4-pole version only.
of the circuit breaker for handling – inserting and removal)
- set of mounting bolts for securing circuit breaker into plug-in Technical specifications
base (to secure plug-in base into switchboard, a set of
mounting bolts is used that is included in delivery of the Order No. 3VT9 300-4WL00
3VT3 763-.AA36-0AA0 switching unit Rated operational voltage Ue V AC 400
AC 250
Main circuit
Rated isolation voltage Ui V AC 500
• The 3VT9 300-4TA30 connecting set is used for connecting
Rated frequency fn Hz 50/60
with busbars or cable lugs and is included in the scope of
supply of the 3VT3 of switching unit , 3 pole Rated operational current Ie/Ue
• for connecting in another way, it is necessary to use connect- AC-13 3 A/AC 400 V
ing sets (see page 3/9) DC-15 0.15 A/250 V, 3 A/125 V, 4 A/30 V
• connections must comply with our recommendations (see
page 3/44). Thermal current Ith A 6
Arrangement of contacts 001
Auxiliary circuits
Connector cross-section S mm2 0.5 ... 1
Terminal protection IP20
(connected switch)
The plug-in base and the circuit breaker can be provided with a
coding set, which prevents inserting any other circuit breaker
into the plug-in base.
Circuit breaker in plug-in version with motorized operating mechanism
3
Q3 Circuit breaker for motorized operating mechanism
AC 24V LSN 4C/1
AC 48V LSN 4C/1
AC 110V LSN 4C/1
NC NO NO AC 230V LSN 2C/1
DC 24V LSN-DC 4C/1
S6 NC M P DC 48V LSN-DC 4C/1
C C
S5 DC 110V LSN-DC 4C/1
DC 220V LSN-DC 2C/1
3VT9 300-2AC10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AH10
3VT9 300-2AC10
3VT9 300-2AH10
the circuit breaker
Lever position of
main contacts
State of the
-
4 2 4 2 4 2 4 2 4 2 4 2
3 1 3 1 3 1 3 1 3 1 3 1
Switched on 1 1 0 0 1 1 0 1 0 1 0 0 1
■ Design
Withdrawable version mounting base Position signalling
3VT9 300-4WL00 position signalling switch
Motor drive
X3 12 10 9 7 3 4 1 5
NC NO NO
S6 NC M P
C C
S5
MP
11 8 6 2 2 1
X3 X4
PE N-
YC
NSO0_00350
Operating
counter
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AC10
3VT9 300-2AD10
3VT9 300-2AC10
3VT9 300-2AD10
State of the main contacts
Lever position of circuit
4 2 4 2 4 2 4 2 4 2 4 2
breaker
3 1 3 1 3 1 3 1 3 1 3 1
Switched on 1 1 0 0 1 1 0 1 0 1 0 0 1
3
Manually switched off or by 0 1 0 0 1 0 1 1 0 1 0 0 1
operating mechanism
Switched off by trip units 0 0 1 1 0 0 1 0 1 1 0 0 1
■ Overview
Use of insulating barriers and terminal covers for circuit • Terminals 2, 4, 6
breakers and switch disconnectors - If the circuit breaker/switch disconnector is connected to the
the power supply with terminals 2, 4, 6 and if Ue = AC 415 V,
Fixed-mounted version it is necessary to use 3VT9 300-8CE30 insulating barriers or
Front connection a 3VT9 300-8CB30 terminal cover.
• Terminals 1, 3, 5 - If insulated conductors are not used for connecting the main
- If Ue = AC 415 V, it is necessary to use 3VT9 300-8CE30 circuit to terminals 2, 4, 6, and flexibars or rear connections
insulating barriers or 3VT9 300-8CB30 terminal covers. are not used, then it is necessary to use 3VT9 300-8CE30 in-
- For the connection of the main circuit to terminals 1, 3, 5, in- sulating barriers or 3VT9 300-8CB30 terminal covers.
sulated conductors, flexibars or rear connection terminals Rear connection
are not used. It is necessary to use 3VT9 300-8CE30 insulat- • Neither insulating barriers nor terminal covers have to be
ing barriers or 3VT9 300-8CB30 terminal cover. used.
Plug-in and withdrawable versions
Neither insulating barriers nor terminal covers have to be used.
3 B = 105 C = 80
1 1
D
1 3VT9 300-8CE30
A2
100 … 150
A1
A
B=0 C=0
1 3 5 1 3 5 1 3 5
ON ON ON
275
2 4 6 2 4 6 2 4 6
20
B = 20
140 140 140 B = 20
NSO0_00260
Busbar
max. 3 mm
> 15 mm
max. 3 mm
Cable
Flexibar
3
C < 80 mm A (mm) 50 50 50 50 50 50 50
D ≥ 10 mm A1 (mm) 150 200 100 200 150 150 150
A2 (mm) 250 300 200 300 250 250 250
A (mm) 50 50 50 50 50 50 50
D ≥ 30 mm A1 (mm) 100 150 100 150 150 150 150
A2 (mm) 150 200 150 200 200 200 200
A (mm) 50 50 50 50 50 50 50
C ≥ 80 mm D ≥ 10 mm A1 (mm) 100 150 100 150 150 150 150
A2 (mm) 150 200 150 200 200 200 200
1)
Ik = max. short-circuit current in the protected circuit (rms).
45 45 103
25 6
18
75.5
1 3 5
45
4 x Ø 6.5
60
60
ON
25°
194
17°
154
194
201
234
259
275
65
2°
33
OFF
TEST R 94
134.5
NSO0_00507
2 4 6
45.5
40.5
25 Ø 11 20
33 105 47.5 45 47.5
140 117 5
Drilling pattern
Fixed-mounted version, front connection with 3VT9 324-4TF30, 3VT9 315-4TF30 connecting set
42 28
45 45 25
1 3 5
45
ON
194
234
275
298
344
369
269
319
435
OFF
TEST
2 4 6
NSO0_00261
32
140 Ø 22 Ø 22 3VT9-324-4TF30
Ø 18 Ø 18 3VT9-315-4TF30
105