Z VKR Operating Instructions
Z VKR Operating Instructions
Air Conditioner
Model No.
Indoor Unit Outdoor Unit
CS-Z20VKR CU-Z20VKR
CS-Z25VKR CU-Z25VKR
CS-Z35VKR CU-Z35VKR
CS-Z42VKR CU-Z42VKR
CS-Z50VKR CU-Z50VKR
CS-Z60VKR CU-Z60VKR
CS-Z71VKR CU-Z71VKR
CS-Z80VKR CU-Z80VKR
Operating Instructions
Air Conditioner
Before operating the unit, please read these operating English
instructions thoroughly and keep them for future reference.
The included Installation Instructions should be kept and read
by the installer before installation.
Remote control is packaged in the indoor unit and removed
by the installer before installation.
ACXF55-22380
Provides maximum comfort and clean air
with optimal energy saving methods.
Use remote
control within 8 m
from the remote
control receiver of
the indoor unit.
Quick Guide
B Inserting the batteries A Clock setting
1
MODE
2
3
TEMP
FAN SPEED
1 Pull out the back cover time .
A of remote control.
ON SET • Press and hold
2 Insert AAA or R03 for approximately
OFF CANCEL batteries. 5 seconds to show
3 Close the cover. time in 12-hour
(am/pm) or 24 hour
indication.
2 Confirm .
2
Thank you for purchasing
Panasonic Air Conditioner.
Table of contents
Safety precautions……… 4-11
How to use ……………………12-13
To learn more ………………… 14
Cleaning instructions ……… 15
Troubleshooting ………… 16-18
Information………………… 19
Accessories
• Remote control
• AAA or R03 batteries × 2
• Remote control holder
• Screws for remote control
holder × 2
The illustrations in this manual are for
explanation purposes only and may differ
from the actual unit. They are subject
to change without notice for future
improvement.
English
B Basic operation
Power supply
Do not use a modified cord,
joint cord, extension cord or
unspecified cord to prevent
overheating and fire.
To prevent overheating, fire or electric shock:
• Do not share the same power outlet with other
equipment.
• Do not operate with wet hands.
• Do not over bend the power supply cord.
• Do not operate or stop the unit by inserting or
pulling out the power plug.
4
If the supply cord is damaged, it must be
replaced by the manufacturer, service agent CAUTION
or similarly qualified persons in order to avoid
a hazard.
It is strongly recommended to be installed Indoor unit and outdoor unit
with Earth Leakage Circuit Breaker (ELCB)
or Residual Current Device (RCD) to prevent Do not wash the indoor unit with water,
electric shock or fire. benzine, thinner or scouring powder to avoid
damage or corrosion at the unit.
To prevent overheating, fire or electric shock:
• Insert the power plug properly. Do not use for preservation of precise
• Dust on the power plug should be periodically equipment, food, animals, plants, artwork
or other objects. This may cause quality
wiped with a dry cloth. deterioration, etc.
Stop using the product if any abnormality/ Do not use any combustible equipment in front
failure occurs and disconnect the power plug or of the airflow outlet to avoid fire propagation.
turn off the power switch and breaker.
(Risk of smoke/fire/electric shock) Do not expose plants or pet directly to airflow to
avoid injury, etc.
Examples of abnormality/failure
• The ELCB trips frequently. Do not touch the sharp aluminium fin,
• Burning smell is observed. sharp parts may cause injury.
• Abnormal noise or vibration of the unit is
observed. Do not switch ON the indoor unit when waxing
• Water leaks from the indoor unit. the floor. After waxing, aerate the room properly
• Power cord or plug becomes abnormally hot. before operating the unit.
• Fan speed cannot be controlled. Do not install the unit in oily and smoky areas
• The unit stops running immediately even if it to prevent damage to the unit.
is switched on for operation.
Do not dismantle the unit for cleaning purpose
• The fan does not stop even if the operation
to avoid injury.
is stopped.
Contact your local dealer immediately for Do not step onto an unstable bench when
maintenance/repair. cleaning the unit to avoid injury.
Do not place a vase or water container on the
This equipment must be earthed to prevent unit. Water may enter the unit and degrade the
Safety precautions
electrical shock or fire. insulation. This may cause an electric shock.
Do not open window or door for long time during
Prevent electric shock by switching off the operation, it may lead to inefficient power usage
power supply and unplug: and uncomfortable temperature changes.
- Before cleaning or servicing, Prevent water leakage by ensuring drainage pipe is:
- When extended non-use, or - Connected properly,
- During abnormally strong lightning activity. - Kept clear of gutters and containers, or
- Not immersed in water
After a long period of use or use with any
combustible equipment, aerate the room regularly.
After a long period of use, make sure the
installation rack does not deteriorate to prevent
the unit from falling down. English
Remote control
Do not use rechargeable (Ni-Cd) batteries. It
may damage the remote control.
Power supply
Do not disconnect the plug by pulling the cord
to prevent electric shock.
nanoe-G generator
Do not touch the sharp pin which may cause
injury.
5
Safety precautions
Must always ensure that foreign matter (oil,
WARNING water, etc.) does not enter the piping. Also,
when storing the piping, securely seal the
opening by pinching, taping, etc. (Handling of
This appliance is filled with R32 R32 is similar to R410A.)
(mild flammable refrigerant). • Operation, maintenance, repairing and
If the refrigerant is leaked and exposed to refrigerant recovery should be carried
an external ignition source, there is a risk out by trained and certified personnel in
of fire. the use of flammable refrigerants and as
recommended by the manufacturer. Any
personnel conducting an operation, servicing
Indoor unit and outdoor unit or maintenance on a system or associated
parts of the equipment should be trained and
The appliance shall be installed, and/or
certified.
operated in a room with floor area larger
• Any part of refrigerating circuit (evaporators,
than Amin (m²) and keep away from ignition
air coolers, AHU, condensers or liquid
sources, such as heat/sparks/open flame or
receivers) or piping should not be located in
hazardous areas such as gas appliances, gas
the proximity of heat sources, open flames,
cooking, reticulated gas supply systems or
operating gas appliance or an operating
electric cooking appliances, etc.(Refer to Table
electric heater.
A of Installation instructions table for Amin (m²))
• The user/owner or their authorised
Be aware that refrigerant may not contain an representative shall regularly check the
odour, highly recommended to ensure suitable alarms, mechanical ventilation and detectors,
flammable refrigerant gas detectors are at least once a year, where as required by
present, operating and able to warn of a leak. national regulations, to ensure their correct
Keep any required ventilation openings clear of functioning.
obstruction. • A logbook shall be maintained. The results
of these checks shall be recorded in the
Do not pierce or burn as the appliance is logbook.
pressurized. Do not expose the appliance to • In case of ventilations in occupied spaces
heat, flame, sparks, or other sources of ignition. shall be checked to confirm no obstruction.
Else it may explode and cause injury or death. • Before a new refrigerating system is put
into service, the person responsible for
Precaution for using R32 refrigerant
placing the system in operation should
The basic installation work procedures are the same as ensure that trained and certified operating
conventional refrigerant (R410A, R22) models. personnel are instructed on the basis of the
Since the working pressure is higher than that instruction manual about the construction,
of refrigerant R22 models, some of the piping supervision, operation and maintenance of
and installation and service tools are special. the refrigerating system, as well as the safety
Especially, when replacing a refrigerant R22 measures to be observed, and the properties
model with a new refrigerant R32 model, and handling of the refrigerant used.
always replace the conventional piping and • The general requirement of trained and
flare nuts with the R32 and R410A piping and certified personnel are indicated as below:
flare nuts on the outdoor unit side. a) Knowledge of legislation, regulations
For R32 and R410A, the same flare nut on the and standards relating to flammable
outdoor unit side and pipe can be used. refrigerants; and,
b) Detailed knowledge of and skills in
The mixing of different refrigerants within
handling flammable refrigerants, personal
a system is prohibited. Models that use
protective equipment, refrigerant leakage
refrigerant R32 and R410A have a different
prevention, handling of cylinders, charging,
charging port thread diameter to prevent
leak detection, recovery and disposal; and,
erroneous charging with refrigerant R22 and
c) Able to understand and to apply in practice
for safety.
the requirements in the national legislation,
Therefore, check beforehand. [The charging port
regulations and Standards; and,
thread diameter for R32 and R410A is 1/2 inch.]
d) Continuously undergo regular and further
training to maintain this expertise.
e) Air-conditioner piping in the occupied
space shall be installed in such a way
to protect against accidental damage in
operation and service.
6
f) Precautions shall be taken to avoid 2. Servicing
excessive vibration or pulsation to 2-1. Service personnel
refrigerating piping. • The system is inspected, regularly supervised
g) Ensure protection devices, refrigerating and maintained by a trained and certified
piping and fittings are well protected service personnel who is employed by the
against adverse environmental effects person user or party responsible.
(such as the danger of water collecting and • Ensure the actual refrigerant charge is in
freezing in relief pipes or the accumulation accordance with the room size within which
of dirt and debris). the refrigerant containing parts are installed.
h) Expansion and contraction of long runs • Ensure refrigerant charge not to leak.
piping in refrigerating systems shall be • Any qualified person who is involved with
designed and installed securely (mounted working on or breaking into a refrigerant
and guarded) to minimize the likelihood circuit should hold a current valid certificate
hydraulic shock damaging the system. from an industry-accredited assessment
i) Protect the refrigerating system from authority, which authorizes their competence
accidental rupture due to moving furniture to handle refrigerants safely in accordance
or reconstruction activities. with an industry recognised assessment
j) To ensure no leaking, field-made refrigerant specification.
joints indoors shall be tightness tested. • Servicing shall only be performed
The test method shall have a sensitivity of as recommended by the equipment
5 grams per year of refrigerant or better manufacturer. Maintenance and repair
under a pressure of at least 0.25 times the requiring the assistance of other skilled
maximum allowable pressure (>1.04MPa, personnel shall be carried out under the
max 4.15MPa). No leak shall be detected. supervision of the person competent in the
1. Installation (Space) use of flammable refrigerants.
• Product with flammable refrigerants, shall • Servicing shall be performed only as
be installed according to the minimum room recommended by the manufacturer.
area, Amin (m2) mentioned in Table A of the 2-2. Work
Installation Instructions. • Prior to beginning work on systems containing
Safety precautions
• In case of field charge, the effect on flammable refrigerants, safety checks are
refrigerant charge caused by the different pipe necessary to ensure that the risk of ignition
length has to be quantified, measured and is minimised. For repair to the refrigerating
labelled. system, the precautions in #2-2 to #2-8 must be
followed before conducting work on the system.
• Must ensure the installation of pipe-work shall
• Work shall be undertaken under a controlled
be kept to a minimum. Avoid use dented pipe procedure so as to minimize the risk of a
and do not allow acute bending. flammable gas or vapour being present while
• Must ensure that pipe-work shall be protected the work is being performed.
from physical damage. • All maintenance staff and others working in the
• Must comply with national gas regulations, local area shall be instructed and supervised
state municipal rules and legislation. Notify on the nature of work being carried out.
relevant authorities in accordance with all • Avoid working in confined spaces. Always
ensure away from source, at least 2 meter of
applicable regulations.
safety distance, or zoning of free space area
English
• Must ensure mechanical connections be of at least 2 meter in radius.
accessible for maintenance purposes. • Wear appropriate protective equipment, including
• In cases that require mechanical ventilation, respiratory protection, as conditions warrant.
ventilation openings shall be kept clear of • Keep all sources of ignition and hot metal
obstruction. surfaces away.
• When disposal of the product, do follow to the
precautions in #12 and comply with national
regulations.
Always contact to local municipal offices for
proper handling.
7
Safety precautions
2-3. Checking for presence of refrigerant 2-7. Checks to the refrigerating equipment
• The area shall be checked with an • Where electrical components are being
appropriate refrigerant detector prior to and changed, they shall be fit for the purpose and
during work, to ensure the technician is aware
of potentially flammable atmospheres. to the correct specification.
• Ensure that the leak detection equipment • At all times the manufacturer’s maintenance
being used is suitable for use with flammable and service guidelines shall be followed.
refrigerants, i.e. non sparking, adequately • If in doubt consult the manufacturer’s
sealed or intrinsically safe. technical department for assistance.
• In case of leakage/spillage happened, • The following checks shall be applied to
immediately ventilate area and stay upwind installations using flammable refrigerants.
and away from spill/release. - The actual refrigerant charge is in
• In case of leakage/spillage happened, do
accordance with the room size within
notify persons down wind of the leaking/
spill, isolate immediate hazard area and keep which the refrigerant containing parts are
unauthorized personnel out. installed.
- The ventilation machinery and outlets
2-4. Presence of fire extinguisher are operating adequately and are not
• If any hot work is to be conducted on the obstructed.
refrigerating equipment or any associated
parts, appropriate fire extinguishing - If an indirect refrigerating circuit is being
equipment shall be available at hand. used, the secondary circuit shall be
• Have a dry powder or CO2 fire extinguisher checked for the presence of refrigerant.
adjacent to the charging area. - Marking to the equipment continues to be
visible and legible. Markings and signs that
2-5. No ignition sources are illegible shall be corrected.
• No person carrying out work in relation to a - Refrigerating pipe or components are
refrigerating system which involves exposing installed in a position where they are
any pipe work that contains or has contained unlikely to be exposed to any substance
flammable refrigerant shall use any sources which may corrode refrigerant containing
of ignition in such a manner that it may lead to components, unless the components
the risk of fire or explosion. He/She must not are constructed of materials which are
be smoking when carrying out such work. inherently resistant to being corroded or
• All possible ignition sources, including are properly protected against being so
cigarette smoking, should be kept sufficiently corroded.
far away from the site of installation,
repairing, removing and disposal, during 2-8. Checks to electrical devices
which flammable refrigerant can possibly be • Repair and maintenance to electrical
released to the surrounding space. components shall include initial safety checks
• Prior to work taking place, the area around and component inspection procedures.
the equipment is to be surveyed to make • Initial safety checks shall include but not limit
sure that there are no flammable hazards or to:-
ignition risks. - That capacitors are discharged: this
• “No Smoking” signs shall be displayed. shall be done in a safe manner to avoid
possibility of sparking.
2-6. Ventilated area - That there no live electrical components
• Ensure that the area is in the open or that it is and wiring are exposed while charging,
adequately ventilated before breaking into the recovering or purging the system.
system or conducting any hot work. - That there is continuity of earth bonding.
• A degree of ventilation shall continue during • At all times the manufacturer’s maintenance
the period that the work is carried out. and service guidelines shall be followed.
• The ventilation should safely disperse any • If in doubt consult the manufacturer’s
released refrigerant and preferably expel it technical department for assistance.
externally into the atmosphere. • If a fault exists that could compromise safety,
then no electrical supply shall be connected to
the circuit until it is satisfactorily dealt with.
• If the fault cannot be corrected immediately
but it is necessary to continue operation, an
adequate temporary solution shall be used.
• The owner of the equipment must be
informed or reported so all parties are advised
thereinafter.
8
3. Repairs to sealed components 6. Detection of flammable refrigerants
• During repairs to sealed components, all • Under no circumstances shall potential
electrical supplies shall be disconnected from sources of ignition be used in the searching or
the equipment being worked upon prior to any detection of refrigerant leaks.
removal of sealed covers, etc. • A halide torch (or any other detector using a
• If it is absolutely necessary to have an naked flame) shall not be used.
electrical supply to equipment during
servicing, then a permanently operating 7. The following leak detection methods
form of leak detection shall be located at the are deemed acceptable for all refrigerant
most critical point to warn of a potentially systems.
hazardous situation. • No leaks shall be detected when using
• Particular attention shall be paid to the detection equipment with a sensitivity of 5
following to ensure that by working on grams per year of refrigerant or better under a
electrical components, the casing is not pressure of at least 0,25 times the maximum
altered in such a way that the level of allowable pressure (>1.04MPa, max
protection is affected.This shall include 4.15MPa), for example, a universal sniffer.
damage to cables, excessive number of • Electronic leak detectors may be used
connections, terminals not made to original to detect flammable refrigerants, but the
specification, damage to seals, incorrect fitting sensitivity may not be adequate, or may need
of glands, etc. re-calibration.
• Ensure that apparatus is mounted securely. (Detection equipment shall be calibrated in a
• Ensure that seals or sealing materials have refrigerant-free area.)
not degraded such that they no longer serve • Ensure that the detector is not a potential
the purpose of preventing the ingress of source of ignition and is suitable for the
flammable atmospheres. refrigerant used.
• Replacement parts shall be in accordance • Leak detection equipment shall be set at a
with the manufacturer’s specifications. percentage of the LFL of the refrigerant and
NOTE: The use of silicon sealant may inhibit shall be calibrated to the refrigerant employed
the effectiveness of some types of leak and the appropriate percentage of gas (25 %
detection equipment. maximum) is confirmed.
Safety precautions
Intrinsically safe components do not have to be • Leak detection fluids are also suitable for use
isolated prior to working on them. with most refrigerants, for example, bubble
method and fluorescent method agents. The
4. Repair to intrinsically safe components use of detergents containing chlorine shall
• Do not apply any permanent inductive or be avoided as the chlorine may react with the
capacitance loads to the circuit without refrigerant and corrode the copper pipe-work.
ensuring that this will not exceed the • If a leak is suspected, all naked flames shall
permissible voltage and current permitted for be removed/extinguished.
the equipment in use. • If a leakage of refrigerant is found which
• Intrinsically safe components are the only requires brazing, all of the refrigerant shall
types that can be worked on while live in the be recovered from the system, or isolated
presence of a flammable atmosphere. (by means of shut off valves) in a part of the
• The test apparatus shall be at the correct system remote from the leak. The precautions
English
rating. in #8 must be followed to remove the
• Replace components only with parts specified refrigerant.
by the manufacturer. Unspecified parts by
manufacturer may result ignition of refrigerant
in the atmosphere from a leak.
5. Cabling
• Check that cabling will not be subject
to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse
environmental effects.
• The check shall also take into account the
effects of aging or continual vibration from
sources such as compressors or fans.
9
Safety precautions
8. Removal and evacuation 9. Charging procedures
• When breaking into the refrigerant circuit • In addition to conventional charging
to make repairs – or for any other purpose procedures, the following requirements shall
– conventional procedures shall be used. be followed.
However, it is important that best practice is - Ensure that contamination of different
followed since flammability is a consideration. refrigerants does not occur when using
The following procedure shall be adhered to: charging equipment.
remove refrigerant -> purge the circuit with - Hoses or lines shall be as short as possible
inert gas -> evacuate -> purge with inert gas to minimize the amount of refrigerant
-> open the circuit by cutting or brazing contained in them.
• The refrigerant charge shall be recovered into - Cylinders shall be kept in an appropriate
the correct recovery cylinders. position according to the instructions.
• The system shall be purged with OFN to - Ensure that the refrigerating system is
render the appliance safe. earthed prior to charging the system with
• This process may need to be repeated refrigerant.
several times. - Label the system when charging is
• Compressed air or oxygen shall not be used complete (if not already).
for this task. - Extreme care shall be taken not to over fill
• Purging shall be achieved by breaking the refrigerating system.
the vacuum in the system with OFN and • Prior to recharging the system it shall be
continuing to fill until the working pressure is pressure tested with OFN (refer to #7).
achieved, then venting to atmosphere, and • The system shall be leak tested on completion
finally pulling down to a vacuum. of charging but prior to commissioning.
• This process shall be repeated until no • A follow up leak test shall be carried out prior
refrigerant is within the system. to leaving the site.
• When the final OFN charge is used, the • Electrostatic charge may accumulate and
system shall be vented down to atmospheric create a hazardous condition when charging
pressure to enable work to take place. and discharging the refrigerant.To avoid fire
• This operation is absolutely vital if brazing or explosion, dissipate static electricity during
operations on the pipe work are to take place. transfer by grounding and bonding containers
• Ensure that the outlet for the vacuum pump and equipment before charging/discharging.
is not close to potential ignition sources and
there is ventilation available. 10. Decommissioning
• Before carrying out this procedure, it is
OFN = oxygen free nitrogen, type of inert gas. essential that the technician is completely
familiar with the equipment and all its details.
• It is recommended good practice that all
refrigerants are recovered safely.
• Prior to the task being carried out, an oil
and refrigerant sample shall be taken in
case analysis is required prior to re-use of
recovered refrigerant.
• It is essential that electrical power is available
before the task is commenced.
a) Become familiar with the equipment and
its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure
that:
• mechanical handling equipment is
available, if required, for handling
refrigerant cylinders;
• all personal protective equipment is
available and being used correctly;
• the recovery process is supervised at all
times by a competent person;
• recovery equipment and cylinders conform
to the appropriate standards.
d) Pump down refrigerant system, if possible.
10
e) If a vacuum is not possible, make a manifold • The recovery equipment shall be in good
so that refrigerant can be removed from working order with a set of instructions
various parts of the system. concerning the equipment that is at hand and
f) Make sure that cylinder is situated on the shall be suitable for the recovery of flammable
scales before recovery takes place. refrigerants.
g) Start the recovery machine and operate in • In addition, a set of calibrated weighing scales
accordance with instructions. shall be available and in good working order.
h) Do not over fill cylinders. (No more than • Hoses shall be complete with leak-free
80 % volume liquid charge). disconnect couplings and in good condition.
i) Do not exceed the maximum working • Before using the recovery machine, check
pressure of the cylinder, even temporarily. that it is in satisfactory working order, has
j) When the cylinders have been filled been properly maintained and that any
correctly and the process completed, make associated electrical components are sealed
sure that the cylinders and the equipment to prevent ignition in the event of a refrigerant
are removed from site promptly and all release. Consult manufacturer if in doubt.
isolation valves on the equipment are • The recovered refrigerant shall be returned to
closed off. the refrigerant supplier in the correct recovery
k) Recovered refrigerant shall not be charged cylinder, and the relevant Waste Transfer
into another refrigerating system unless it Note arranged.
has been cleaned and checked. • Do not mix refrigerants in recovery units and
• Electrostatic charge may accumulate and especially not in cylinders.
create a hazardous condition when charging • If compressors or compressor oils are to
or discharging the refrigerant.To avoid fire or be removed, ensure that they have been
explosion, dissipate static electricity during evacuated to an acceptable level to make
transfer by grounding and bonding containers certain that flammable refrigerant does not
and equipment before charging/discharging. remain within the lubricant.
• The evacuation process shall be carried
11. Labelling out prior to returning the compressor to the
• Equipment shall be labelled stating that it suppliers.
has been de-commissioned and emptied of • Only electric heating to the compressor body
Safety precautions
refrigerant. shall be employed to accelerate this process.
• The label shall be dated and signed. • When oil is drained from a system, it shall be
• Ensure that there are labels on the equipment carried out safely.
stating the equipment contains flammable
refrigerant.
12. Recovery
• When removing refrigerant from a system,
either for servicing or decommissioning,
it is recommended good practice that all
refrigerants are removed safely.
• When transferring refrigerant into cylinders,
ensure that only appropriate refrigerant
recovery cylinders are employed.
English
• Ensure that the correct number of cylinders
for holding the total system charge are
available.
• All cylinders to be used are designated for
the recovered refrigerant and labelled for
that refrigerant (i.e. special cylinders for the
recovery of refrigerant).
• Cylinders shall be complete with pressure
relief valve and associated shut-off valves in
good working order.
• Recovery cylinders are evacuated and, if
possible, cooled before recovery occurs.
11
How to use
To adjust airflow direction
Upper direction
AIR SWING
Indicator
Lateral direction
POWER
TIMER
i AUTO-X • Do not adjust the flap by hand.
nanoe X
ECO
To adjust fan speed
AUTO
FAN SPEED FAN
POWERFUL:
MODE To reach temperature quickly
TEMP
• This operation stops automatically after 4 hours.
AIR SWING QUIET:
FAN SPEED To enjoy quiet operation
• This operation reduces airflow noise.
ON SET
MILD DRY
12
See "To learn more..." for details.
Max = 4 hours
• The unit controls set temperature according to room temperature to accelerate room cooling.
• After max 4 hours, the set temperature is shifted according to activity detection.
• Fan speed is fixed at AUTO, fan speed selection is prohibited.
• During unit is off, press will turn on the unit with i AUTO-X mode.
• i AUTO-X mode can be cancelled by pressing the respective button again.
• This operation provides clean air, moisturises your skin and hair, deodorizes odours in the
room.
• This operation can be activated when the unit is turn on or off by pressing the nanoe™X
button. During nanoe™X individual operation, the fan speed will be based on remote control
setting.
• If nanoe™X is activated before the unit is turn off, nanoe™X operation will resume once the
unit is turn on, this includes to ON Timer.
To set the timer
2 sets of ON and OFF timers are available to turn ON or OFF the unit at different preset times.
• To cancel ON or OFF timer, press
How to use
1 2 3 or to select respective or then
press .
ON SET
• If timer is cancelled manually or due to
TIMER
power failure, you can restore the timer
OFF CANCEL
again by pressing or to select
respective or then press .
1 Select ON or OFF Example: • The nearest timer setting will be displayed
timer OFF at 22:00 and will activate in sequence.
English
• Each time pressed: • Timer operation is based on the clock set
Cancel in the remote control and repeats daily
once set. For clock setting, please refer to
Quick Guide.
2 Set the time
3 Confirm
Note
, , , ,
• Can be activated in HEAT, COOL and DRY • Cannot be selected at the same time.
mode and can be cancelled by pressing the • Cannot be activated during MILD DRY.
respective button again.
13
To learn more...
Operation mode
AUTO : During operation mode selection the POWER indicator blinks.
• Unit selects operation mode every 10 minutes according to setting temperature
and room temperature.
HEAT : Unit takes a while to warm up. The POWER indicator blinks during this
operation.
COOL : Provides efficient comfort cooling to suit your needs.
DRY : Unit operates at low fan speed to give a gentle cooling operation.
FAN : To circulate air in the room.
i AUTO-X : The fast cooling is ideal when you come home on a hot day.
Energy saving temperature setting
Operating the unit within the recommended temperature range may save energy.
HEAT : 20.0 °C ~ 24.0 °C / 68 °F ~ 75 °F.
COOL : 26.0 °C ~ 28.0 °C / 79 °F ~ 82 °F.
Air flow direction
In COOL/DRY mode:
If AUTO is set, the flaps swings left/right and up/down automatically.
In i AUTO-X mode:
If AUTO is set, the horizontal flap is fixed at the lower position and shift to the upper position
after reaches set temperature and the vertical flap swing according to activity detection. If
manual is set, the horizontal flap and vertical flap are fixed at the predetermined position.
In HEAT mode:
If AUTO is set, the horizontal flap is fixed at the predetermined position. The vertical flap
swings left/right after the temperature rises.
Auto restart control
If power is resumed after a power failure, the operation will restart automatically after a
period of time with previous operation mode and airflow direction.
• This control is not applicable when TIMER is set.
nanoe X
■To enjoy freshness and cleaner environment
This operation provides clean air, moisturises your skin and hair, reduces and neutralises
odours in the room.
Operating conditions
Use this air conditioner in the temperature range indicated in the table.
Indoor Outdoor
Temperature °C (°F)
DBT WBT DBT WBT
Max. 32 (89.6) 23 (73.4) 46 (114.8) 26 (78.8)
COOL
Min. 16 (60.8) 11 (51.8) 5 (41.0) -
Max. 30 (86.0) - 24 (75.2) 18 (64.4)
HEAT
Min. 16 (60.8) - -15 (5.0) -
DBT: Dry bulb temperature, WBT: Wet bulb temperature
14
Cleaning instructions
To ensure optimal performance of the unit, Indoor unit
cleaning has to be carried out at regular Aluminium fin
intervals. Dirty unit may cause malfunction and Front panel
you may see error code “H99”. Please consult
authorised dealer.
• Switch off the power supply and unplug before
cleaning.
• Do not touch the aluminium fin, sharp parts may
cause injury.
• Do not use benzine, thinner or scouring powder.
• Use only soap ( pH 7) or neutral household
detergent.
• Do not use water hotter than 40 °C / 104 °F.
Air filters
Indoor unit
Wipe the unit gently with a
soft, dry cloth. Air filters
Coils and fans should be clean
for at least every 6 months by an Once every 2 weeks
authorised dealer. • Wash/rinse the filters gently
Front panel
Wash gently and dry.
Remove the front panel
2 Pull out and lift up
Insert into the unit
1 Release the
hooks at
English
both ends
Close it securely
2 Push in
1 Insert
at both
sides
3 Close down
4 Press both ends and center of the front panel
15
Troubleshooting
The following symptoms do not indicate malfunction.
Symptom Cause
POWER indicator blinks before the unit is • This is a preliminary step in preparation for the
switched on. operation when the ON timer has been set.
• When ON Timer is set, the unit may start earlier (up
to 35 minutes) before the actual set time in order to
achieve the desired temperature on time.
POWER indicator blinks during HEAT • The unit is in defrost mode (and AIR SWING is set
mode with no warm air supply (and flap is to AUTO).
closed).
TIMER indicator is always on. • The timer setting repeats daily once set.
Operation is delayed a few minutes after • The delay is a protection to the unit’s compressor.
restarting.
Indoor fan stops occasionally during • To avoid unintended cooling effect.
heating operation.
Indoor fan stops occasionally during • This helps to remove the surrounding odour.
automatic fan speed setting.
Airflow continues even after operation has • Extraction of remaining heat from the indoor unit
stopped. (maximum 30 seconds).
The room has a peculiar odour. • This may be due to damp smell emitted by the wall,
carpet, furniture or clothing.
Cracking sound during operation. • Changes of temperature caused the expansion/
contraction of the unit.
Water flowing sound during operation. • Refrigerant flow inside the unit.
Mist emerges from indoor unit. • Condensation effect due to cooling process.
Outdoor unit emits water/steam. • Condensation or evaporation occurs on pipes.
Louder noise at outdoor unit during early • The compressor and fan rotate at higher speed to
operation of i AUTO-X. boost cooling performance during initial operation.
Discoloration of some plastic parts. • Discoloration is subject to material types used in
plastic parts, accelerated when exposed to heat,
sun light, UV light or environmental factor.
Check the following before calling for servicing.
Symptom Check
Operation in HEAT/COOL mode is not • Set the temperature correctly.
working efficiently. • Close all doors and windows.
• Clean or replace the filters.
• Clear any obstruction at the air inlet and air outlet
vents.
Noisy during operation. • Check if the unit has been installed at an incline.
• Close the front panel properly.
Remote control does not work. • Insert the batteries correctly.
(Display is dim or transmission signal is • Replace weak batteries.
weak.)
The unit does not work. • Check if the circuit breaker is tripped.
• Check if timers have been set.
The unit does not receive the signal from • Make sure the receiver is not obstructed.
the remote control. • Certain fluorescent lights may interfere with signal
transmitter. Please consult authorised dealer.
16
When...
■The remote control is missing or a malfunction has occurred
1.Raise the front panel.
2.Press the button once to use in i AUTO-X mode.
3.Press and hold the button until you hear 1 beep, then release to use in
AUTO
forced COOL mode.
OFF/ON 4.Repeat step 3. Press and hold the button until you hear 2 beeps, then
release to use in forced HEAT mode.
5.Press the button again to turn off.
■The units are not going to be used for a long period of time
• Activate HEAT mode for 2~3 hours to remove moisture left in the internal parts thoroughly to
prevent mould growth.
• Turn off the power supply and unplug.
Troubleshooting
• Remove the remote control batteries.
17
Troubleshooting
How to retrieve error codes
If the unit stops and the TIMER indicator blinks, use the remote control to retrieve the error code.
1 Press for 2 Press until you hear beep
5 seconds ON SET
sound, then write down the
TIMER
error code
OFF CANCEL
* Some error code may not be applicable to your model. Consult authorised dealer for clarification.
18
Information
Information for Users on Collection and Disposal of Old Equipment and used Batteries
[Information on Disposal in other Countries outside the European Union]
These symbols are only valid in the European Union. If you wish to discard
these items, please contact your local authorities or dealer and ask for the
correct method of disposal.
Note for the battery symbol (bottom two symbol examples):
This symbol might be used in combination with a chemical symbol. In this case
it complies with the requirement set by the Directive for the chemical involved.
Pb
This symbol shows that this This symbol shows that the
equipment uses a flammable Operation Instructions should
refrigerant. If the refrigerant is be read carefully.
Troubleshooting / Information
leaked, together with an external This symbol shows type of
WARNING ignition source, there is a flammable refrigerant contained
possibility of ignition. in the system.
This symbol shows that a service This symbol shows that there
personnel should be handling this is information included in the
equipment with reference to the Operation Instructions and/or
Installation Instructions. Installation Instructions.
English
19
Panasonic Corporation
1006 Kadoma, Kadoma City,
Osaka, Japan
Website: http://www.panasonic.com