Product datasheet
Specifications
Anti Harmonic detuned reactor
100kvar 190Hz (3.8) 7% 50Hz
400V
LVR07X00A40T
Main
Range PowerLogic
Device short name DR
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Detuned reactor
Network frequency 50 Hz
Reactive power rating 100 kvar for 400 V AC 50 Hz
Network rated voltage 400 V AC 50 Hz
Tuning order 3.8 - 190 Hz - 7 % - 50 Hz
Complementary
power losses (max) 480 W
Value of inductance 0.375 mH
Inductance tolerance - 5 % to 5 % per phase
Fundamental current rating 144.3 A
RMS current rating 155.9 A
Electrical insulation class Class H
[Ui] rated insulation voltage 1.1 kV
Dielectric test voltage 4 kV 50 Hz 1 minute
[Imp] maximum permanent 1.2 x I1
current
Harmonic current spectrum 3.7 % x I3
38.2 % x I5
13.6 % x I7
4.9 % x I11
Dynamic withstand current 2.2 x Isc
[Ith] conventional free air thermal 2 A at 250 V AC 50 Hz
current
Type of installation Indoor installation
Type of cooling Forced convection
Connections - terminals Pad terminal
Fixing center 200 x 125 mm
Height 350 mm
Width 350 mm
Depth 220 mm
Net weight 37 kg
25 Oct 2024 1
Environment
Standards IEC 60068
IP degree of protection IP00
Operating altitude <= 2000 m
Ambient air temperature for 0…55 °C at <= 1000 m
operation 0…50 °C at > 1000...2000 m
Average ambient air temperature 50 °C at <= 1000 m (average over 24 hours)
for operation 40 °C at <= 1000 m (average over 1 year)
45 °C at > 1000...2000 m (average over 24 hours)
35 °C at > 1000...2000 m (average over 1 year)
Climatic withstand Relative humidity: 20...80 %
Salt mist (400 V/50 Hz) : 250 hours
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 56.0 cm
Package 1 Width 40.0 cm
Package 1 Length 60.0 cm
Package 1 Weight 44.0 kg
Unit Type of Package 2 P06
Number of Units in Package 2 2
Package 2 Height 50.0 cm
Package 2 Width 80.0 cm
Package 2 Length 60.0 cm
Package 2 Weight 96.5 kg
2 25 Oct 2024
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Reach Free Of Svhc
Rohs Exemption Information Yes
Certifications & Standards
Reach Regulation REACh Declaration
Eu Rohs Directive Compliant
EU RoHS Declaration
China Rohs Regulation China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure Product Environmental Profile
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
Circularity Profile No need of specific recycling operations
25 Oct 2024 3