Busbar Protection - An Overview - ScienceDirect Topics
Busbar Protection - An Overview - ScienceDirect Topics
On this page
Protection Relays
Omar Salah Elsayed Atwa, in
Practical Power System and Protective Relays
Commissioning
, 2019
Very fast;
URL: https://www.sciencedirect.com/science/article/pii/B9780128168585000186
Protection
In Electrical Systems and Equipment (Third Edition), 1992
The CEGB has not used busbar protection on any 660 MW unit
power station other than Drax where, having been installed in the
late 1960s on the first half, it was repeated for consistency on the
second half. It has been considered for many years that to
introduce a separate form of protection specifically to cover
busbar faults reduces the overall reliability of the electrical
system, since it complicates the protection scheme and increases
the risk of malfunction. This would result in shutting down the
complete switchboard, causing severe operational inconvenience
and would be costly in lost production. This is particularly so for
unit boards, which supply all the motors essential for the running
of the main unit. At 11 kV for example, it would possibly result in
the loss of a boiler feed pump, cooling water pumps, induced
draught and forced draught fan motors and would inevitably
result in the tripping of the main unit. The risk of losing such
strategic items of plant, with the consequential loss of generation,
due to the possible malfunction of a busbar protection scheme is
unacceptable. For this reason, busbar protection is no longer fitted
to auxiliary switchboards in this way.
There is, however, still a need to guard against any faults likely to
affect the busbars. The method adopted to cover for busbar faults
uses the protection arrangements already discussed under
transformer protection, i.e., the standby earth fault protection will
operate for any busbar fault involving earth, and the back-up
overcurrent protection fitted to the HV side of the transformer
will operate for any busbar phase to phase faults. At 415 V, where
busbar faults have been caused by human error when using
multirange instruments, the back-up protection is set down to 150
ms. This can only be achieved by eliminating all forms of
overcurrent protection using inverse time relays on the 415 V
supply system. This method of protection at 415 V is helped
considerably by the design of that system. This is explained in
Section 12.9 of this chapter.
URL: https://www.sciencedirect.com/science/article/pii/B9780080405148500197
Protection Relays
Omar Salah Elsayed Atwa, in
Practical Power System and Protective Relays
Commissioning
, 2019
V relay=I1×(RCT1+RL1), V relay=IR×R
𝑅 = 𝐼1 ×
(𝑅CT1 + 𝑅𝐿1 )
𝐼𝑅 , 𝑅st = 𝑅 − 𝑅 relay
𝑉𝑠 > 𝑉𝑅
𝐼𝑅 𝑅 > 𝐼1 (𝑅CT + 𝑅𝐿1 ) then 𝑅 > 𝐼1 / 𝐼𝑅 (𝑅CT + 𝑅𝐿1 )
𝑅ST = 𝑅 − 𝑅 relay
The CT should have a knee point voltage equal to twice the relay
setting voltage, as shown in Fig. 18.9.8. IM is the magnetizing
current taken by the CT at the setting voltage, N is the CT turns
ratio, Im is the current taken by the voltage-limiting device,
Metrosil resistance (nonlinear resistance) at voltage Vs, ISR is the
current taken by the fault setting resistor at the setting voltage,
n=number of CTs in the busbar protection scheme, and Iv is the
current taken by the supervision relay at setting voltage.
Iop is the relay operating current and should be at least 30% of the
minimum fault current to insure relay operation.
URL: https://www.sciencedirect.com/science/article/pii/B9780128168585000186
Protection Relays
Omar Salah Elsayed Atwa, in
Practical Power System and Protective Relays
Commissioning
, 2019
URL: https://www.sciencedirect.com/science/article/pii/B9780128168585000186
Relay Protection
DrC.R. Bayliss CEng FIET, B.J. Hardy CEng FIET, in
Transmission and Distribution Electrical Engineering (Fourth
Edition)
, 2012
URL: https://www.sciencedirect.com/science/article/pii/B9780080969121000101
Relay Protection
DrC.R. Bayliss CEng FIET, B.J. Hardy CEng FIET, in
Transmission and Distribution Electrical Engineering (Fourth
Edition)
, 2012
10.5.5.1 Introduction
Busbar reliability is of paramount importance since failure will
result in the loss of many circuits. In practice, busbar faults are
rare and usually involve phase to earth faults. Such faults may be
due to:
URL: https://www.sciencedirect.com/science/article/pii/B9780080969121000101
Protective Relays Testing and
Commissioning
Omar Salah Elsayed Atwa, in
Practical Power System and Protective Relays
Commissioning
, 2019
Inject this module with current and check the pickup value is
within ±5% of the nominal pickup value. This is done after
opening the trip link of the Breaker Failure (BF) system of the
substation.
URL: https://www.sciencedirect.com/science/article/pii/B9780128168585000204
Relay Protection
DrC.R. Bayliss CEng FIET, B.J. Hardy CEng FIET, in
Transmission and Distribution Electrical Engineering (Fourth
Edition)
, 2012
URL: https://www.sciencedirect.com/science/article/pii/B9780080969121000101
URL: https://www.sciencedirect.com/science/article/pii/B9780128161395000011
Relay Protection
DrC.R. Bayliss CEng FIET, B.J. Hardy CEng FIET, in
Transmission and Distribution Electrical Engineering (Fourth
Edition)
, 2012
URL: https://www.sciencedirect.com/science/article/pii/B9780080969121000101
Related terms:
Circuit Breaker, Transformer Protection,
Recommended publications
Journal
Journal
Book • 2019
Book • 2011