CABLES
INSTRUMENTATION CABLE
Document ID: TE/QMS/F/02 DESIGN CODE : ICIS04TYSFYL010P1.5SA
Particulars 10P X 1.5 Sqmm
Name of Manufacturer Polycab India Ltd
Type of Cable Overall Screened
No of Elements X Size in mm² 10P X 1.5
Voltage Grade (V) 500
Conductor
a) Material Annealed Tinned Copper as per Class 2 of IS:8130/2013
b) Maximum d.c. resistance of conductor at 20° C 12.4
(Ω/km)
c) Shape of conductor Stranded Circular
Insulation
a) Material PVC Type A as per IS:5831
b) Minimum Thickness mm 0.44
c) Pair identification White & Blue with number printing on any one core of pair
Collective Screen
a) Material Aluminium mylar tape
b) Nominal Thickness mm 0.018
c) Material of Drain Wire Flexible ATC
d) Size of Drain Wire (Approx.) 0.5 mm²(16/0.2 mm)
Inner sheath
a) Material Extruded PVC Type ST1 to IS: 5831, Latest
b) Minimum Thickness mm 0.30
Armouring
a) Material Galvanised Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
CABLES
Outer sheath
a) Material Extruded FR-LSH PVC Type ST1 to IS: 5831, Latest
b) Thickness mm 1.40 (Min.)
c) colour of sheath Blue
Maximum conductor temperature under normal 70
operating conditions °C
Minimum bending radius 12 times Overall diameter
Electrical Parameters
a) Mutual capacitance nf/km <250
b) Insulation resistance MΩ/km 10
c) Inductance to resistance ratio (L/R) µH/Ω <40
d) Dielectric strength for 1 minute (H.V Test) kV 2
Max. tensile strength for Cables pulled with 9 x D², D is the cable OD in mm
stocking (Newtons)
Approximate Overall diameter of cable mm 23.5 ± 2.0
Applicable Standard Generally as per IS 1554 Part I/88 & BS EN 50288-7
Standard Drum Length (Mtr.) 1000 ± 5%
Non-Standard Drum Length (Mtr.) Maximum 5% of order quantity and Min Individual Non-
Standard Drum 200 meters
Embossing POLYCAB 500 VOLTS GRADE FR-LSH
YEAR POLYCAB 500 VOLTS GRADE FR-LSH CABLE SIZE
Printing SCREENED with SEQUENTIAL LENGTH MARKING at EVERY
ONE METER INTERVAL
FR-LSH PROPERTIES
a) Oxygen Index Min. 29% as per ASTM D- 2863
b) Temperature Index Min. 250 Deg.C as per ASTM D- 2863
c) Smoke Density Rating Max. 60% as per ASTM D- 2843
d) Acid Gas Generation Max. 20% as per IEC- 754- 1
e) Flammability Test As per IEC:332-I
Rev. No.: 01 Issued Date : 10/06/2021
Note:-The values given above are subject to tolerances as per the relevant standards