Zone Load Summary 1-1 Analytical Space COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 404.44 W/m2
Time at Peak: 10/21 14:00:00
Floor Area per Capacity: 2.4726 m2/kW
Outside Outdoor Air Percentage: 1.59 %
DB: 40.2 C Airflow per Floor Area: 36.599764 l/s-m2
HR: 0.0041 kg/kg Airflow per Capacity: 90.494832 l/s-kW
WB: 17.4 C Number of People: 1.0

Zone
DB: 23.9 C
HR: 0.0084 kg/kg
RH: 42.3 %

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - 824 - 824 24.1
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 323 - - 323 9.4
Glass - Solar - 1,676 - 1,676 48.9
Door - 0 - 0 0.0
Wall - 187 - 187 5.4
Below-grade Wall - 0 - 0 0.0
Partition - 0 - 0 0.0
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 30 - 30 0.9
Other - Floor - 0 - 0 0.0
Infiltration 91 - -62 29 0.8
Subtotal 414 2,717 -62 3,069 89.6

Internal Gains
People 51 13 59 123 3.6
Lights 91 0 - 91 2.7
Return Air - Lights 0 - - 0 0.0
Equipment 119 0 0 119 3.5
Subtotal 261 13 59 332 9.7

Systems
Zone Ventilation 83 - -57 26 0.8
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 83 0 -57 26 0.8

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 -0.0
Grand Total 758 2,728 -61 3,426 100.0
Zone Load Summary 1-1 Analytical Space HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -93.69 W/m2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null m2/kW
Outside Outdoor Air Percentage: 1.59 %
DB: 9.1 C Airflow per Floor Area: 4.722550 l/s-m2
HR: 0.0078 kg/kg Airflow per Capacity: null l/s-kW
WB: 9.1 C Number of People: 1.0

Zone
DB: 21.1 C
HR: 0.0055 kg/kg
RH: 32.6 %

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - -463 - -463 58.3
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction -230 - - -230 29.0
Glass - Solar - 0 - 0 0.0
Door - 0 - 0 0.0
Wall - -67 - -67 8.4
Below-grade Wall - 0 - 0 0.0
Partition - 0 - 0 0.0
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 24 - 24 -3.0
Other - Floor - 0 - 0 0.0
Infiltration -76 - 36 -40 5.0
Subtotal -306 -505 36 -775 97.7

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -36 - 17 -19 2.4
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -36 0 17 -19 2.4

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 1 - 1 -0.1
Grand Total -342 -505 53 -794 100.0