You are on page 1/ 282

1

Smart Industrial Control Panel Digital Power Meter


Main Industrial Control Panel Module

Accura 2500M Front Accura 2500M Rear

Industrial Control Panel HMI Module

Accura 2500D Front Accura 2500D Rear

Main Industrial Control Panel Module + Industrial Control Panel HMI Module

Accura 2500D/2500M Front Accura 2500D/2500M Rear


Three-Phase Power Measuring Module

Accura 2550CM-3P-800A-210 Accura 2550CM-3P-800A Accura 2550CM-3P-630A-145 Accura 2550CM-3P-630A


-210-ZCT -145-ZCT

Accura 2550CM-3P-400A-140 Accura 2550CM-3P-400A Accura 2550CM-3P-5A Accura 2550CM-3P-5A-ZCT


-140-ZCT
Three-Phase Power Three-Phase Terminal Block Three-Phase Power Three-Phase Terminal Block
Measuring Module Measuring Module

Accura 2550CM-3P-250A TM-CM-3P-105 Accura 2550CM-3P-125A TM-CM-3P-90


TM-CM-BC-3P-105 1

Accura 2550CM-3P-100A TM-CM-3P-75L Accura 2550CM-3P-60A TM-CM-3P-75

1. This terminal block allows for the insertion of barriers.


Three-Phase Power/Leakage Current Measuring Module

Accura 2550CMZ-3P-800A-220 Accura 2550CMZ-3P-630A-155 Accura 2550CMZ-3P-400A-155

Three-Phase Power/Leakage Three-Phase Terminal Block


Current Measuring Module

Accura 2550CMZ-3P-250A TM-CMZ-3P-105 TM-CMZ-BC-3P-105 1

Three-Phase Power/Leakage Three-Phase Terminal Block


Current Measuring Module

Accura 2550CMZ-3P-125A TM-CMZ-3P-90

1. This terminal block allows for the insertion of barriers.


Three-Phase Power/Leakage Current Three-Phase Terminal Block
Measuring Module

Accura 2550CMZ-3P-100A TM-CMZ-3P-75L

Accura 2550CMZ-3P-60A TM-CMZ-3P-75

Three-Phase 4-wire Power/Leakage Three-Phase Terminal Block


Current Measuring Module

Accura 2550CMZ-3P4W-250A-145 TM-CMZ-BC-3P4W-140 1

Three-Phase Power/Leakage Current Measuring Module for MCBs

Accura 2550CMM-3P-60A Accura 2550CMMZ-3P-60A


Single-Phase Power/Leakage Single-Phase Terminal Block Single-Phase Power/Leakage Single-Phase Terminal Block
Current Measuring Module Current Measuring Module

Accura 2550CM-1P-250A TM-CM-1P-105 Accura 2550CMZ-1P-250A TM-CMZ-1P-105

Accura 2550CM-1P-125A TM-CM-1P-60 Accura 2550CMZ-1P-125A TM-CMZ-1P-60

Accura 2550CM-1P-100A TM-CM-1P-50L Accura 2550CMZ-1P-100A TM-CMZ-1P-50L

Accura 2550CM-1P-60A TM-CM-1P-50 Accura 2550CMZ-1P-60A TM-CMZ-1P-50


Split-Core Power/Leakage Current Measuring Module

Accura 2550CMS-3P4W-60A Accura 2550CMS-1P3F-60A Accura 2550CMS-1P2F-60A

Accura 2550ZM-3P4W-60A-DI Accura 2550ZM-1P3F-60A-DI Accura 2550ZM-1P2F-60A-DI


Special-Purpose Modules

Accura 2550DCM-500V-80A Accura 2550DCM-50V-80A

Accura 2550TEMP Accura TSEN/THSEN Accura 2550GW Accura 2550GWM

Accura 2550SAL Accura 2550VOL

Accura 2550IO-DI1 Accura 2550IO-DI2 Accura 2550IO-DO1 Accura 2550IO-DO2


Special-Purpose Modules

Accura 2550IO-AI1 Accura 2550IO-AI2 Accura 2550IO-RTD1 Accura 2550IO-RTD2

Accura 2550PS
Accura 2500/2550 User Guide [AC] Notice

Notice
Symbols
Caution
Indicates the presence of dangerous voltage which can cause severe injury or death if proper
precautions are not followed.

Caution
Alerts users of the presence of hazards which can cause injury to persons, property damage
or damage to the device if proper precautions are not followed.

Note
Indicates major instructions for the installation, operation, and maintenance of the product.

Indicates alternative voltage or current.

Indicates direct voltage or current.

Installation Considerations
The installation, operation, and maintenance of the product should be performed only by qualified,
competent personnel that have received appropriate training for high voltage and current devices.

Caution
If hazardous voltages are mishandled while installing and operating the product in the field, it can cause
serious injury or death.

◼ This device must be installed and serviced only by qualified personnel who have in-depth knowledge of
installing, commissioning and operating the device and have had appropriate training. He or she should
have read and understood the various safety measures and warnings stated in the instructions.
◼ Before carrying out any work on the device, switch off the power supply to the device.
◼ Always use an appropriate voltage detection device to confirm the absence of voltage.
◼ Always power the device with the correct rated voltage.
◼ Install the device in a suitable electrical cabinet by following recommended installation instructions.
Failure to take these precautions could cause serious injuries or death.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 11


Notice Accura 2500/2550 User Guide [AC]

Caution
Observe the following instructions, or permanent damage may occur to the product.

To ensure proper device operation, make sure the following:


◼ The device is correctly installed.
◼ The power specifications indicated on the product are met.

About the Manual


Rootech Inc. reserves the right to make changes in the device specifications shown in this User Guide without
notice. Therefore, we recommend that customers should check the latest information on specifications of
the device before placing orders.

In the absence of written agreements, Rootech Inc. assumes no liability for applications assistance,
customer’s system design, or infringement of patents or copyrights induced by third parties arising from
the use of the products described herein.

We are committed to providing accurate information in this document. However, we assume no responsibility
for any errors in the document and reserves the right to make changes without notice.

Limitation of Liability
Where applicable law allows and does not prohibit or restrict such limitation, Rootech, Inc’s liability for this
product shall be limited to the amount actually paid by customers for the product.

Page 12 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Warranty

Warranty
Rootech Inc. provides a warranty for two years from the product receipt date, applicable only to the original
purchaser of the products and software sold or licensed by the company.

To obtain warranty service, the purchased products should be free from serious defects in material and
workmanship.

Software products are provided in an up-to-date version, therefore, we do not offer any warranty for software
product.

In order to make a product claim under the warranties described above, the original purchaser should
immediately contact Rootech headquarters. When we receive a claim, we will inspect the product either at
the purchaser's location or at the company’s facility after receiving the product from the customer. The
customer is responsible for the cost of shipping the product. After inspecting the product, we will provide
repair or replacement services for the product.

Rootech Inc. reserves the right to determine, at its discretion, whether to repair or replace the product or
issue a refund for the product when the warranty period has expired or issues are not covered by warranty
terms and conditions.

Limitation of Warranty
The warranty does not apply to the uninterrupted or error-free operation of the product and does not cover
normal wear and tear. It also does not cover costs associated with the removal, installation, or
troubleshooting of the customer's electrical systems.

Defects caused by any of the following factors are not covered under the warranty.
◼ Improper use(alteration, accident, misuse, abuse) or failure to act in accordance with installation,
operation or maintenance instructions
◼ Unauthorized modifications, changes or repair attempts
◼ Failure to comply with applicable safety standards and regulations
◼ Damages incurred during transportation or storage of the product
◼ Damages caused by the force majeure event, including fire, flood, earthquakes, storm damage,
overvoltage and lightning
◼ Defacing, altering, or removal of the original identification marks(trademark, serial number, etc.)

ⓒ 2019 Rootech Inc. All Rights Reserved Page 13


Warranty Accura 2500/2550 User Guide [AC]

Rootech Inc. shall not be liable for any claims other than those made by customers, including the original
purchaser, their employees, agents, or contractors for any loss, damage, or expense incurred related to the
purchased product when the above warranty terms and conditions are not fulfilled.

Any technical assistance provided by Rootech's personnel or representatives in system design shall be
considered a suggestion. The original purchaser is responsible for determining the feasibility of such
suggestions and should conduct tests to verify their feasibility

It is the original purchaser’s responsibility to determine the suitability of any product and associated
documentation. The original purchaser should acknowledge that 100% uptime is not achievable due to
possible hardware or software defects. The original purchaser should also recognize that such defects and
failures may cause inaccuracies or malfunctions.

No agency, corporate entity, or employee of Rootech Inc. or any other companies has the authority to amend,
modify or extend the terms and conditions of this warranty in any way without express written authorization
from Rootech, Inc.

Standards Compliance

Process Control Equipment, Electrical E324900

R-R-RTE-Accura2500

Page 14 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide Revision History

Revision History
The revision history of the Accura 2500/2550 User Guide[AC] is as follows.

Revision Date Description


Revision 1.00 March 20, 2020 First issue
Revision 1.10 October 14, 2020 Updated content related to AC measurement
Updated content related to events
Modified content about accuracy
Revision 1.20 December 3, Added Appendix B Module Connection
2020 Added A2550CMZ modules with the basic current ≤ 250A
Changed S description of accuracy
Added bolt caps as a component of A2500M and updated content on
product installation
Added content on the start event of power quality events
Revision 1.21 January 8, 2021. Changed errors in set values for the aggregation of the Max/Min values
Revision 1.30 June 14, 2021 Divided the product manual into the AC and DC versions of Accura 2550CM
modules
Added Accura 2550CMZ models, as well as content on leakage current
measurement
Modified content on user-defined events
Added content on accuracy in power quality measurement and necessary
setup steps, including the PT rating and the reference voltage
Added the LCD screen image of Accura 2550CM[Z]-1P-250A model
Changed the type of the internal communication cable for the display module
Added the Locale item to system setup items
Added content on the accuracy of leakage current measured by the ZCT for
models with a current rating of 250 A or less
Revision 1.40 October 22, 2021 Changed the frequency measurement range
Revision 1.50 March 30, 2022 Modified content on module connection
Added special-purpose modules, as well as the demand sync mode
Added several models to the Accura 2550CM module lineup and removed
some of the existing Accura 2550CMZ modules
Changed content on event settings
Added content on standards, as well as the network setup parameter
Changed the displacement power factor data to be provided via
communication
Revision 1.51 July 18, 2022 Updated data on the product certifications
Deleted residual current values measured by Accura 2550CM modules

ⓒ 2019 Rootech Inc. All Rights Reserved Page 15


Revision History Accura 2500/2550 User Guide [AC]

Revision Date Description


Revision 1.60 January 13, 2023 Changed the panel cutout dimensions of Accura 2550CMZ modules
Specified the minimum measured value of leakage current for Accura
2550CMZ modules
Specified the sizes for Accura 2550CM modules with ratings of 400 A or
greater
Added descriptions of energy
Added Accura 2550CMZ-3P-800A/400A modules
Revision 1.61 March 8, 2023 Specified Accura 2550 CMZ-3P module does not support load mode setup

Revision 1.70 April 12, 2024 Added CMZ-3P4W-250A, CMS/ZM, and CMM modules
Deleted CM-3P-630A-210/400A-145 modules
Added content on transient voltage events
Updated descriptions of the Aggregation section
Updated information on UL certifications
Added special modules, including Accura 2550SAL/VOL/GWM
Extended the setup range for the LCD screen of Accura 2500D
Added the image and description related to RS-485 shielded cables
Changed the low level range of the LCD backlight brightness
Added content on the residual current measurement function of all three-
phase modules.
Revision 1.80 June 28, 2024 Added Accura 2500M-AC220V/DC110V, Accura 2500M-DC24V options
Updated information on UL certifications
Changed measured voltage range
Changed terminal block torque of voltage input terminal
Updated the measurement parameters provided via communication
Added description of pickup event and changed definition of Duration
Changed range of backup/setup energy
Revision 1.90 October 25, 2024 Added CM-3P modules, which can connect an external ZCT (800A, 630A,
400A, 5A)
Added CMZ-3P-630A-155, CMMZ-3P-60A modules
Added DCM, IO Special purpose modules
Added installation method for CM[Z]-3P module without clear distance
between panels
Added a usage guide table for the leakage current measurement module by
load type
Added Status view description
Changed Appendix B module power consumption

Page 16 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Contents

Contents
Chapter 1 Introduction .................................................................................................................................................... 27
Overview .................................................................................................................................................................................................................. 27
Product Information ........................................................................................................................................................................................... 29
Smart Industrial Control Panel Digital Power Meter/Power & Leakage Current Measuring Modules ............. 29
Special-Purpose Modules ....................................................................................................................................................................... 33
Installation Example .................................................................................................................................................................................. 34
Product Features ......................................................................................................................................................................................... 36

Chapter 2 Installation ....................................................................................................................................................... 45


Conditions for Installation ............................................................................................................................................................................... 45
Product Appearance ........................................................................................................................................................................................... 46
Components ........................................................................................................................................................................................................... 52
Dimensions ............................................................................................................................................................................................................. 60
Accura 2500D/2500M............................................................................................................................................................................... 62
Accura 2550CM-3P .................................................................................................................................................................................... 63
Accura 2550CM-1P .................................................................................................................................................................................... 66
Accura 2550CMZ-3P ................................................................................................................................................................................. 67
Accura 2550CMZ-3P4W .......................................................................................................................................................................... 68
Accura 2550CMZ-1P ................................................................................................................................................................................. 69
Accura 2550CMS......................................................................................................................................................................................... 70
Accura 2550ZM ........................................................................................................................................................................................... 70
Accura 2550CMM ....................................................................................................................................................................................... 71
Accua 2550CMMZ...................................................................................................................................................................................... 71
TM-CM-3P ..................................................................................................................................................................................................... 72
TM-CM-1P ..................................................................................................................................................................................................... 74
TM-CMZ-3P................................................................................................................................................................................................... 75
TM-CMZ-3P4W............................................................................................................................................................................................ 76
TM-CMZ-1P................................................................................................................................................................................................... 77
Installation Example............................................................................................................................................................................................ 78
Installation of Accura 2500M/2500D/2550 Power Measuring Modules .......................................................................... 78
Installation of Accura 2500M/2500D/2550CMM[Z] ................................................................................................................... 80
Step 1: Installation ............................................................................................................................................................................................... 81
Installing of Accura 2500D..................................................................................................................................................................... 81
Installation of Accura 2500M ................................................................................................................................................................ 82
Installation of Accura 2550CM[Z]-3P ................................................................................................................................................ 84
Installation of Accura 2550CMZ-3P4W ............................................................................................................................................ 97
Installation of Accura 2550CM[Z]-1P ................................................................................................................................................ 99
Installation of Accura 2550CMS/ZM on the Panel .................................................................................................................. 104
Installation of Accura 2550CMM[Z] on the Panel.................................................................................................................... 107

ⓒ 2019 Rootech Inc. All Rights Reserved Page 17


Contents Accura 2500/2550 User Guide [AC]

Step 2: Wiring Accura 2500M Module ................................................................................................................................................... 110


Voltage Wiring of Accura 2500M .................................................................................................................................................... 110
Wiring Considerations ........................................................................................................................................................................... 111
Power Supply/Ground Wiring............................................................................................................................................................ 114
Step 3: Connecting Accura 2500M to Accura 2500D via the Communication Cable ..................................................... 116
Step 4: Through-Hole Wiring of Accura 2550CM[Z]/CMS/ CMM[Z] Modules ................................................................... 118
Accura 2550CM[Z]-3P ........................................................................................................................................................................... 121
Accura 2550CMZ-3P4W ....................................................................................................................................................................... 123
Accura 2550CM[Z]-1P ........................................................................................................................................................................... 124
Accura 2550CMS/ZM-3P4W............................................................................................................................................................... 125
Accura 2550CMS/ZM-1P3F................................................................................................................................................................. 126
Accura 2550CMS/ZM-1P2F................................................................................................................................................................. 127
Accura 2550CMM-3P-60A................................................................................................................................................................... 128
Accura 2550CMMZ-3P-60A ................................................................................................................................................................ 128
Step 5: Connecting Accura 2550CM-3P with External ZCTs ........................................................................................................ 129
Step 6: Connecting Accura 2500M to Accura 2550 Modules ..................................................................................................... 130
Connection for Internal Communication ..................................................................................................................................... 131
Step 7: Connecting Accura 2500M Modules for External Communication .......................................................................... 132
Ethernet Communication ..................................................................................................................................................................... 132
RS-485 Communication ....................................................................................................................................................................... 134

Chapter 3 Accura 2500M ............................................................................................................................................... 135


Device Composition ........................................................................................................................................................................................ 135
Power Supply............................................................................................................................................................................................. 136
Voltage Terminal Block ......................................................................................................................................................................... 138
Ethernet Ports for External Communication ............................................................................................................................... 139
RS-485 Port for External Communication.................................................................................................................................... 141
HMI DISPLAY Communication Port ................................................................................................................................................ 142
Communication Ports for Connection with Accura 2550 Modules................................................................................. 143
LED Status Indicators ............................................................................................................................................................................. 144
Functions............................................................................................................................................................................................................... 145
External Communication with the Host System ....................................................................................................................... 145
Measurements........................................................................................................................................................................................... 145
Power Quality ............................................................................................................................................................................................ 146
Events ............................................................................................................................................................................................................ 146
Management of Accura 2550 Modules......................................................................................................................................... 149
Accura 2500D HMI Interface Module............................................................................................................................................ 149

Chapter 4 Accura 2500D ................................................................................................................................................ 150


Device Composition ........................................................................................................................................................................................ 150
Device Connection ........................................................................................................................................................................................... 152
DISPLAY(HOME) Mode ................................................................................................................................................................................... 153

Page 18 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Contents

Screen Composition ............................................................................................................................................................................... 153


Chain View Screen .................................................................................................................................................................................. 154
Status View Screen ................................................................................................................................................................................. 156
Display .......................................................................................................................................................................................................... 159
SETUP Mode ....................................................................................................................................................................................................... 165
Screen Composition ............................................................................................................................................................................... 165
Accura 2500M Setup ............................................................................................................................................................................. 166
Accura 2550 Setup.................................................................................................................................................................................. 175
EVENT Mode ....................................................................................................................................................................................................... 179
Screen Composition ............................................................................................................................................................................... 179
MEASUREMENT Events ......................................................................................................................................................................... 180
Power Quality Events ............................................................................................................................................................................. 181
SYSTEM Events.......................................................................................................................................................................................... 183
Necessary Steps for Device Setup ............................................................................................................................................................ 184
Step 1: Setup for the Type of Voltage Measurements of Accura 2500M .................................................................... 184
Step 2: Setup for the Voltage Wiring of Accura 2500M, PT Rating, and Reference Voltage ............................. 184
Step 3: Module ID Setup of Accura 2550 Modules ................................................................................................................ 185
Step 4: Ethernet Setup of Accura 2500M .................................................................................................................................... 185

Chapter 5 Accura 2550................................................................................................................................................... 186


Operation Mode ...................................................................................................................................................................................... 186
Button Operation..................................................................................................................................................................................... 186
Accura 2550CM[Z]-3P/CMZ-3P4W Modules ....................................................................................................................................... 187
Applied Models ........................................................................................................................................................................................ 187
LCD Display ................................................................................................................................................................................................ 188
Display Mode ............................................................................................................................................................................................ 188
Setup Mode ............................................................................................................................................................................................... 189
Accura 2550CM[Z]-1P Module ................................................................................................................................................................... 193
Applied Models ........................................................................................................................................................................................ 193
LCD Display ................................................................................................................................................................................................ 193
Display Mode ............................................................................................................................................................................................ 194
Setup Mode ............................................................................................................................................................................................... 195
Accura 2550CMS/ZM-3P4W Module ...................................................................................................................................................... 198
Applied Models ........................................................................................................................................................................................ 198
LCD Display ................................................................................................................................................................................................ 199
Display Mode ............................................................................................................................................................................................ 199
Setup Mode ............................................................................................................................................................................................... 200
Accura 2550CMS/ZM-1P3F/1P2F Modules .......................................................................................................................................... 203
Applied Models ........................................................................................................................................................................................ 203
LCD Display ................................................................................................................................................................................................ 204
Display Mode ............................................................................................................................................................................................ 204
Setup Mode ............................................................................................................................................................................................... 205

ⓒ 2019 Rootech Inc. All Rights Reserved Page 19


Contents Accura 2500/2550 User Guide [AC]

Accura 2550CMM[Z]-3P Module............................................................................................................................................................... 209


Applied Model .......................................................................................................................................................................................... 209
LCD Display ................................................................................................................................................................................................ 209
Display Mode ............................................................................................................................................................................................ 210
Setup Mode ............................................................................................................................................................................................... 210

Chapter 6 Functions ......................................................................................................................................................... 214


Voltage/Current Sampling ............................................................................................................................................................................ 214
Voltage Sensing........................................................................................................................................................................................ 214
Current Sensing ........................................................................................................................................................................................ 214
Measuring Time ....................................................................................................................................................................................... 215
Measurements Per Cycle...................................................................................................................................................................... 215
Measurements .................................................................................................................................................................................................... 216
Measurement Parameters.................................................................................................................................................................... 216
Voltage Wiring .......................................................................................................................................................................................... 218
Residual Voltage....................................................................................................................................................................................... 223
Residual Current....................................................................................................................................................................................... 223
Leakage Current ....................................................................................................................................................................................... 224
Power Per Phase ...................................................................................................................................................................................... 225
Three-Phase Power ................................................................................................................................................................................. 226
Power Factor(PF) ...................................................................................................................................................................................... 228
Energy ........................................................................................................................................................................................................... 229
Demand........................................................................................................................................................................................................ 231
Harmonics ................................................................................................................................................................................................... 234
Unbalance (NEMA MG1) ...................................................................................................................................................................... 235
Negative-Sequence/Zero-Sequence Unbalance ....................................................................................................................... 236
Events ..................................................................................................................................................................................................................... 237
Power Quality Events ............................................................................................................................................................................. 237
Measurement Events ............................................................................................................................................................................. 242
System Events ........................................................................................................................................................................................... 245
Providing Event Notifications and Resetting Notification Settings ................................................................................. 246
Aggregation......................................................................................................................................................................................................... 247
Fixed Aggregation................................................................................................................................................................................... 248
User-Defined Aggregation .................................................................................................................................................................. 248
Collection of Aggregation Data ....................................................................................................................................................... 249

Appendix A Specifications ............................................................................................................................................. 250


General Specifications ........................................................................................................................................................................... 250
Accura 2500M Main Industrial Control Panel Module .......................................................................................................... 250
Accura 2500D Industrial Control Panel HMI Module............................................................................................................. 254
Accura 2550CM[Z]-3P/CMZ-3P4W Three-phase Power/Leakage Current Measuring Module ......................... 255
Accura 2550CM[Z]-1P Power/Leakage Current Measuring Module ............................................................................... 258

Page 20 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Contents

Accura 2550CMS/ZM-3P4W Split-Core Power/Leakage Measuring Module ............................................................. 260


Accura 2550CMS/ZM-1P3F/1P2F Split-Core Power/Leakage Measuring Module ................................................... 262
Accura 2550CMM[Z] Three-Phase Power/Leakage Current Measuring Module for MCBs ................................. 264

Appendix B Module Connection .................................................................................................................................. 266


Limitation in the Length of the Communication Cable due to Voltage Drops......................................................... 266
Limitation in the Number of Connectable Modules due to Power Consumption .................................................. 267
Limitation in the Number of Connectable Modules in a Single Group........................................................................ 268
Connecting Modules in Two Groups ............................................................................................................................................. 269

Appendix C Standards .................................................................................................................................................... 270


IEC 61557-12: 2018 Performance Measuring and Monitoring Devices (PMD) ........................................................ 271
IEC 62053-21:2020 Static Meters for AC Active Energy (Classes 0.5, 1 and 2) ......................................................... 273
IEC 62053-22:2020 Static Meters for AC Active Energy (Classes 0.1S, 0.2S and 0.5S)........................................... 273
IEC 62053-24:2020 Static Meters for Fundamental Reactive Energy (Classes 0.5S, 1S, 1, 2 and 3) .......................... 273

Appendix D Accuracy/Reliability .................................................................................................................................. 274


Accuracy....................................................................................................................................................................................................... 274
Reliability ..................................................................................................................................................................................................... 276

Appendix E Line-to-Neutral Voltage for Common Main Supply Systems............................................................. 277


Wiring Modes............................................................................................................................................................................................ 277

Appendix F Ordering Information ................................................................................................................................. 278


Accura 2500/2550 Smart Industrial Control Panel Digital Power Meter ...................................................................... 278
Special-Purpose Modules .................................................................................................................................................................... 281

ⓒ 2019 Rootech Inc. All Rights Reserved Page 21


Figures Accura 2500/2550 User Guide [AC]

Figures
Fig 1.1 Accura 2550 Modules Compatible with MCCBs with Various Ratings............................................................... 28
Fig 1.2 Through-Hole Type Current Sensing Structure of Accura 2550 Modules ........................................................ 28
Fig 1.3 Combined Installation of Accura 2500D and 2500M ................................................................................................. 34
Fig 1.4 Connection of Accura 2500D and 2500M Using Communication Cables ....................................................... 35
Fig 2.1 Accura 2500M Front ................................................................................................................................................................... 46
Fig 2.2 Accura 2500M Side ..................................................................................................................................................................... 46
Fig 2.3 Accura 2500M Rear .................................................................................................................................................................... 46
Fig 2.4 Accura 2500D Front .................................................................................................................................................................... 47
Fig 2.5 Accura 2500D Side...................................................................................................................................................................... 47
Fig 2.6 Accura 2500D Rear ..................................................................................................................................................................... 47
Fig 2.7 Accura 2550CM-3P/1P .............................................................................................................................................................. 48
Fig 2.8 Accura 2550CMZ-3P/1P ........................................................................................................................................................... 49
Fig 2.9 Accura 2550CMZ-3P4W............................................................................................................................................................ 49
Fig 2.10 Accura 2550CMS-3P4W/1P3F/1P2F ................................................................................................................................. 49
Fig 2.11 Accura 2550ZM-3P4W/1P3F/1P2F .................................................................................................................................... 50
Fig 2.12 Accura 2550CMM...................................................................................................................................................................... 50
Fig 2.13 Accura 2550CMMZ ................................................................................................................................................................... 50
Fig 2.14 TM-CM[Z]-3P............................................................................................................................................................................... 51
Fig 2.15 TM-CM[Z]-1P............................................................................................................................................................................... 51
Fig 2.16 TM-CM[Z]-BC-3P ....................................................................................................................................................................... 51
Fig 2.17 TM-CM[Z]-BC-3P4W ................................................................................................................................................................ 51
Fig 2.18 Accura 2500M Components ................................................................................................................................................ 52
Fig 2.19 Accura 2500D Components ................................................................................................................................................. 52
Fig 2.20 Accura 2550CM-3P-800A/630A/400A Components ................................................................................................ 52
Fig 2.21 Accura 2550CMZ-3P 800A/630A/400A Components .............................................................................................. 53
Fig 2.22 Accura 2550CM[Z]-3P-250A/125A/100A/60A Components................................................................................. 53
Fig 2.23 Accura 2550CM-3P-800A/630A/400A/5A-ZCT Components............................................................................... 54
Fig 2.24 Accura 2550CMZ-3P4W-250A Components ................................................................................................................ 54
Fig 2.25 Accura 2550CM[Z]-1P-250A Components .................................................................................................................... 55
Fig 2.26 Accura 2550CM[Z]-1P-125A/100A/60A Components ............................................................................................. 55
Fig 2.27 Accura 2550CMS-3P4W/1P2F Components................................................................................................................. 55
Fig 2.28 Accura 2550CMS-1P3F Components ............................................................................................................................... 56
Fig 2.29 Accura 2550ZM-3P4W Components ............................................................................................................................... 56
Fig 2.30 Accura 2550ZM-1P3F Components.................................................................................................................................. 56
Fig 2.31 Accura 2550ZM-1P2F Components.................................................................................................................................. 57
Fig 2.32 Accura 2550CMM Components ......................................................................................................................................... 57
Fig 2.33 Accura 2550CMMZ Components ...................................................................................................................................... 57
Fig 2.34 TM-CM[Z]-3P Components .................................................................................................................................................. 58

Page 22 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Figures

Fig 2.35 TM-CM[Z]-BC-3P Components .......................................................................................................................................... 58


Fig 2.36 TM-CMZ-BC-3P4W Components ...................................................................................................................................... 58
Fig 2.37 TM-CM[Z]-1P-105 Components ........................................................................................................................................ 59
Fig 2.38 TM-CM[Z]-1P-60/50L/50 Components ........................................................................................................................... 59
Fig 2.39 Accura 2500D/2500M Dimensions ................................................................................................................................... 62
Fig 2.40 Accura 2500D Dimensions .................................................................................................................................................... 62
Fig 2.41 Accura 2550CM-3P Dimensions......................................................................................................................................... 63
Fig 2.42 Accura 2550CM-1P Dimensions......................................................................................................................................... 66
Fig 2.43 Accura 2550CMZ-3P Dimensions ...................................................................................................................................... 67
Fig 2.44 Accura 2550CMZ-3P4W Dimensions ............................................................................................................................... 68
Fig 2.45 Accura 2550CMZ-1P Dimensions ...................................................................................................................................... 69
Fig 2.46 Accura 2550CMS Dimensions ............................................................................................................................................. 70
Fig 2.47 Accura 2550ZM Dimensions ................................................................................................................................................ 70
Fig 2.48 Accura 2550CMM Dimensions............................................................................................................................................ 71
Fig 2.49 Accura 2550CMMZ Dimensions ......................................................................................................................................... 71
Fig 2.50 TM-CM-3P Dimensions .......................................................................................................................................................... 72
Fig 2.51 TM-CM-1P Dimensions .......................................................................................................................................................... 74
Fig 2.52 TM-CMZ-3P Dimensions ....................................................................................................................................................... 75
Fig 2.53 TM-CMZ-BC-3P4W Dimensions ......................................................................................................................................... 76
Fig 2.54 TM-CMZ-1P Dimensions ....................................................................................................................................................... 77
Fig 2.55 Installation Diagram of Accura 2500M/2500D/2550 Modules............................................................................ 78
Fig 2.56 Installation Diagram of Accura 2500M/2550CMS+ZM Modules ....................................................................... 79
Fig 2.57 Installation Diagram of Accura 2500M/2500D/2550CMM[Z] .............................................................................. 80
Fig 2.58 Mounting Accura 2500D on the Panel ........................................................................................................................... 81
Fig 2.59 Mounting Accura 2500M on the Panel .......................................................................................................................... 82
Fig 2.60 Combined Installation of Accura 2500M and 2500D .............................................................................................. 83
Fig 2.61 Mounting Accura 2550CM-3P Module on the Panel .............................................................................................. 84
Fig 2.62 Mounting Accura 2550CM-3P Module on the Panel through Mounting Holes (Mounting Wings) /
clear distance exists .......................................................................................................................................................................... 85
Fig 2.63 Mounting Accura 2550CM-3P Module on the Panel through Mounting Holes (Mounting Wings) /
without clear distance...................................................................................................................................................................... 87
Fig 2.64 Mounting the Module on the Panel through Mounting Holes (Mounting Plate/Terminal Block) .... 89
Fig 2.65 Mounting the Module on the Panel through Mounting Holes (Mounting Wings) / clear distance
exists......................................................................................................................................................................................................... 91
Fig 2.66 Mounting the Module on the Panel through Mounting Holes (Mounting Wings) / without clear
distance ................................................................................................................................................................................................... 93
Fig 2.67 Mounting the Module on the Panel through Mounting Holes (Mounting Plate/Terminal Block) .... 95
Fig 2.68 Mounting Accura 2550CMZ-3P4W Module on the Panel .................................................................................... 97
Fig 2.69 Mounting the Module on the Panel through Mounting Holes.......................................................................... 98
Fig 2.70 Mounting Accura 2550CM-1P Module on the Panel .............................................................................................. 99

ⓒ 2019 Rootech Inc. All Rights Reserved Page 23


Figures Accura 2500/2550 User Guide [AC]

Fig 2.71 Mounting the Module on the Panel through Mounting Holes (Mounting Plate/Terminal Block) ..100
Fig 2.72 Mounting the Module on the Panel through Mounting Holes with the Terminal Block.....................102
Fig 2.73 Mounting Accura 2550CMS/ZM Modules on the Panel ......................................................................................104
Fig 2.74 Mounting the Modules on the Panel through Mounting Holes (Mounting Wings) ..............................105
Fig 2.75 Mounting the Modules on the Panel through Mounting Holes (Mounting Wings) ..............................105
Fig 2.76 Mounting the Modules on the Panel through Mounting Holes (Mounting Wings) ..............................106
Fig 2.77 Mounting Accura 2550CMM Modules on the Panel .............................................................................................107
Fig 2.78 Mounting Accura 2550CMMZ Modules on the Panel ..........................................................................................108
Fig 2.79 Mounting the Module on the Panel through Mounting Holes........................................................................109
Fig 2.80 Mounting the Accura 2550CMMZ-3P-60A Module on the Panel through Mounting Holes ............109
Fig 2.81 Voltage Wiring of Accura 2500M ....................................................................................................................................110
Fig 2.82 3P4W Connection with 3 PTs ............................................................................................................................................112
Fig 2.83 3P3W Connection with 2 PTs ............................................................................................................................................112
Fig 2.84 1P3W Connection with 2 PTs ............................................................................................................................................113
Fig 2.85 1P2W Connection with 1 PT ..............................................................................................................................................113
Fig 2.86 Accura 2500M Power Supply/Ground Wiring of Accura 2500M-AC220V/DC110V ................................114
Fig 2.87 Accura 2500M Power Supply/Ground Wiring of Accura 2500M-DC24V .....................................................115
Fig 2.88 DISPLAY Port on Accura 2500M ......................................................................................................................................116
Fig 2.89 Accura 2500D Rear .................................................................................................................................................................116
Fig 2.90 Connecting Accura 2500M to Accura 2500D Using the Communication Cable ......................................117
Fig 2.91 3P4W/3P3W Through-Hole Wiring ................................................................................................................................121
Fig 2.92 3P3W Through-Hole Wiring ..............................................................................................................................................121
Fig 2.93 3P4W/3P3W Through-Hole Wiring with 3CTs...........................................................................................................122
Fig 2.94 3P3W Through-Hole Wiring with 2 CTs .......................................................................................................................122
Fig 2.95 3P4W Through-Hole Wiring ..............................................................................................................................................123
Fig 2.96 Single-Phase Line-to-Neutral Through-Hole Wiring (250A)...............................................................................124
Fig 2.97 Single-Phase Line-to-Neutral Through-Hole Wiring ..............................................................................................124
Fig 2.98 Split-Core 3P4W Power/Leakage Current Measuring Module ..........................................................................125
Fig 2.99 Split-Core 1P3F Power/Leakage Current Measuring Module ............................................................................126
Fig 2.100 Split-Core 1P2F Power/Leakage Current Measuring Module ..........................................................................127
Fig 2.101 Three-Phase Power Measuring Module for MCBs................................................................................................128
Fig 2.102 Three-Phase Power/Leakage Current Measuring Module for MCBs ...........................................................128
Fig 2.103 Connecting the Cable for Connection with the ZCT to the External ZCT.................................................129
Fig 2.104 Connecting Accura 2550CM-3P Module with the External ZCT ....................................................................129
Fig 2.105 Connecting Accura 2500M to Accura 2550CM Using Internal Communication Cables ....................131
Fig 2.106 Ethernet Ports on Accura 2500M..................................................................................................................................132
Fig 2.107 Connecting Accura 2500M Modules via Ethernet Communication .............................................................133
Fig 2.108 RS-485 Port on Accura 2500M ......................................................................................................................................134
Fig 2.109 Connecting Accura 2500M Modules via RS-485 Communication................................................................134
Fig 3.1 Device Composition of Accura 2500M............................................................................................................................135

Page 24 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Figures

Fig 3.2 Accura 2500M-AC220V/DC110V Power Supply ..........................................................................................................136


Fig 3.3 Accura 2500M-DC24V Power Supply ...............................................................................................................................137
Fig 3.4 Voltage Wiring of Accura 2500M.......................................................................................................................................138
Fig 3.5 Ethernet Ports on Accura 2500M .......................................................................................................................................139
Fig 3.6 Connecting Accura 2500M Modules with Ethernet Cables for External Communication ......................140
Fig 3.7 RS-485 Port on Accura 2500M ...........................................................................................................................................141
Fig 3.8 Connecting Accura 2500M Modules with RS-485 Cables for External Communication .........................141
Fig 3.9 Combing Accura 2500M with Accura 2500D ...............................................................................................................142
Fig 3.10 Connecting Accura 2500M to Accura 2500D Using the Communication Cable ......................................142
Fig 3.11 Connection Example of Accura 2500 and Accura 2550 Modules ...................................................................143
Fig 3.12 Block Diagram of User-Defined Events.........................................................................................................................148
Fig 4.1 Accura 2500D Device Composition ..................................................................................................................................150
Fig 4.2 Combining Accura 2500M with Accura 2500D ...........................................................................................................152
Fig 4.3 Connecting to Accura 2500M Using the Communication Cable .......................................................................152
Fig 4.4 Daisy-Chained Module Screen (Normal State) ............................................................................................................154
Fig 4.5 Daisy-Chained Module Screen (Inspection Required)..............................................................................................155
Fig 4.6 Status View Screen (Normal State)....................................................................................................................................156
Fig 4.7 Status View Screen (Fault occured) ...................................................................................................................................157
Fig 4.8 Status View Screen (No modules connected) ..............................................................................................................158
Fig 4.9 SUMMARY Measurement Screen .......................................................................................................................................159
Fig 4.10 Line-to-Line Voltage Measurement Screen ................................................................................................................160
Fig 4.11 Current Measurement Screen ...........................................................................................................................................161
Fig 4.12 Active Power Measurement Screen ................................................................................................................................162
Fig 4.13 Active Energy Measurement Screen ..............................................................................................................................162
Fig 4. 14 Phasor Screen..........................................................................................................................................................................163
Fig 4.15 Description Screen ..................................................................................................................................................................164
Fig 4.16 SUMMARY Setup Screen .....................................................................................................................................................166
Fig 4.17 Voltage Setup Screen ............................................................................................................................................................166
Fig 4.18 Changed Item Displayed .....................................................................................................................................................168
Fig 4.19 Dip Event Setup Screen........................................................................................................................................................168
Fig 4.20 Ethernet Communication Setup Screen .......................................................................................................................170
Fig 4.21Main CM Setup Screen ..........................................................................................................................................................171
Fig 4.22 Reset Screen ..............................................................................................................................................................................172
Fig 4.23 Description Setup Screen ....................................................................................................................................................173
Fig 4.24 SUMMARY Setup Screen .....................................................................................................................................................175
Fig 4.25 Current Setup Screen ............................................................................................................................................................176
Fig 4.26 Current Event Setup Screen ...............................................................................................................................................177
Fig 4.27 Description Setup Screen ....................................................................................................................................................178
Fig 4.28 SUMMARY Event Screen ......................................................................................................................................................180
Fig 4.29 MEASUREMENT Event Screen ...........................................................................................................................................180

ⓒ 2019 Rootech Inc. All Rights Reserved Page 25


Figures Accura 2500/2550 User Guide [AC]

Fig 4.30 RMS Trend Screen...................................................................................................................................................................181


Fig 4.31 Power Quality Events Screen .............................................................................................................................................181
Fig 4.32 RMS Trend Screen...................................................................................................................................................................182
Fig 4.33 PQ Curve Graph Screen .......................................................................................................................................................182
Fig 4.34 SYSTEM Event Screen............................................................................................................................................................183
Fig 6.1 Voltage Sensing and Signal Processing ..........................................................................................................................214
Fig 6.2 Current Sensing and Signal Processing ..........................................................................................................................214
Fig 6.3 Voltage Wiring with 3 PTs (3P4W).....................................................................................................................................218
Fig 6.4 Voltage Wiring with 2 PTs (3P3W).....................................................................................................................................219
Fig 6.5 Voltage Wiring with 2 PTs (1P3W).....................................................................................................................................221
Fig 6.6 Voltage Wiring with 1 PT (1P2W) ......................................................................................................................................222
Fig 6.7 Vector Sum of the Total Apparent Power ......................................................................................................................226
Fig 6.8 Arithmetic Sum of the Total Apparent Power ..............................................................................................................227
Fig 6.9 PF Sign and Phase Angle (Lead/Lag) ...............................................................................................................................228
Fig 6.10 Four Quadrant Diagram of Reactive Energy ..............................................................................................................229
Fig 6.11 Demand Calculation...............................................................................................................................................................231
Fig 6.12 Predicted Demand Calculation .........................................................................................................................................232
Fig 6.13 Hourly Auto Sync ....................................................................................................................................................................233
Fig 6.14 Manual Sync ..............................................................................................................................................................................233
Fig 6.15 Symmetrical Components ...................................................................................................................................................236
Fig 6.16 Voltage Dip Detection ..........................................................................................................................................................238
Fig 6.17 SEMI F47-0706 Curve (@ 60 Hz) .....................................................................................................................................239
Fig 6.18 IEC 61000-4-11/34 Class 3 Curve (@ 60 Hz) ............................................................................................................239
Fig 6.19 ITIC Curve (for 60 Hz) ...........................................................................................................................................................240
Fig 6.20 Transient Voltage Detection ...............................................................................................................................................241
Fig 6.21 Block Diagram of User-Defined Events.........................................................................................................................243
Fig 6.22 “Over” Condition Detection ...............................................................................................................................................244
Fig 6.23 “Under” Condition Detection ............................................................................................................................................245
Fig 6.24 Aggregation Process for Avg/Max/Min Values .........................................................................................................247
Fig 6.25 Aggregation Process for the Last Latched Values ...................................................................................................247
Fig B.1 Module Connection Diagram in a Single Group........................................................................................................269
Fig B.2 Module Connection Diagram in Two Groups ..............................................................................................................269

Page 26 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Chapter 1 Introduction
Overview
Voltage, Current, and Power Measurement in AC/DC Industrial Control Panels
Accura 2500M module measures both AC and DC voltage. However, Accura 2550 modules are divided into
the modules that measure AC current and DC current, respectively. Therefore, you should use the Accura
2550 module that suits your needs according to the AC/DC voltage specifications of industrial control panels.

Accurate Measurement of Leakage Current


With the built-in ZCT(Zero-sequence Current Transformer), Accura 2550CMZ-3P/1P modules and Accura
2550CMMZ modules measure leakage current directly and provide accurate leakage current (RMS and
fundamental) values. Accura 2550CMS, the split-core power measuring module measures leakage current
accurately by connecting it to Accura 2550ZM, the leakage current measuring module with a built-in ZCT.
Additionally, Accura 2550CM-3P module, which can connect an external ZCT, measures leakage current by
connecting an externally installed voltage-type ZCT to its ZCT connection port.

A Variety of Data, including Dip(Sag)/Swell and PQ Curve Available for Power Quality Analysis
Accura 2500/2550 provide a wide variety of data, including Dip, Swell, PQ Curve, harmonics(up to the 50th
order), Crest factor, K-factor, and unbalance for power quality analysis. It allows energy managers to easily
identify changes in power quality in various industrial control panels at power facilities, enabling effective
power quality management.

Accurate Measurements of Voltage, Current, Active Power and Active Energy (IEC 61557-12
Class 0.5)
Recently, it has become essential to establish enterprise-wide energy management systems for efficient
energy usage at sites such as plants, factories, and buildings due to greenhouse gas emission regulations.
A key factor determining reliability of energy management systems is the measurement accuracy of meters.
Accura 2500/2550 meet the requirements of the IEC 61557-12 Class 0.5 standard for voltage/current/active
power/active energy measurement, enabling accurate analysis and diagnosis of various problems in energy
management at power facilities.

Max/Min/Average Values Available within Aggregation Intervals


Accura 2500/2550 provide measured values for every 0.2-second frame based on voltage, current, and power
values measured each cycle. It also provides the maximum/minimum/average values for various aggregation
intervals, including 1 second, 5 seconds, 1 minute, 5 minutes, 1 hour and 6 hours, as well as timestamped
data for the maximum/minimum values. Since it offers measurement data that change instantaneously in
aggregation intervals, it allows for accurate trend analysis of voltage, current and power. It also helps to
reduce workload on data collection and calculation of the host system.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 27


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Proven Safety and Reliability with CE/UL/KC Certifications


Accura 2500/2550's internal and external structures(product and circuit design) meet safety and reliability
requirements for CE(EN 55011, EN IEC 61326-1, EN IEC 61326-2-1, EN IEC 61000-3-2, EN 61000-3-3),
UL(UL61010-1 3rd edition, UL 61010-2-030 2nd edition), and KC(EN 55011, EN IEC 61326-1, EN IEC 61326-
2-1) standards.

Compatible with MCCBs with Various Ratings / Compact Size


Accura 2550 modules are compatible with MCCBs with various current ratings since they have identical
installation dimensions and wiring hole positions. Thus, it can be installed with existing MCCBs in industrial
control panels. Its compact size with minimized width also allows for easy installation.

Fig 1.1 Accura 2550 Modules Compatible with MCCBs with Various Ratings

Through-Hole Type Current Sensing Structure for Easier and Safer Installation
Accura 2550 modules feature the through-hole type current sensing structure, which does not require
electrical contact with cables(busbars). Therefore, it ensures safety from electrical accidents, as well as easy
installations. TM-CM[Z]-3P/1P terminal blocks allow for easier electrical wiring.

Fig 1.2 Through-Hole Type Current Sensing Structure of Accura 2550 Modules

Page 28 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Product Information
Smart Industrial Control Panel Digital Power Meter/Power & Leakage Current Measuring
Modules
The Smart Industrial Control Panel Digital Power Meter product line consists of Accura 2500D(Industrial
Control Panel HMI Module) installed at the front of the industrial control panel, Accura 2500M(Main Industrial
Control Panel Module) installed inside the industrial control panel or at the rear of Accura 2500D, Accura
2550CM(Power Measuring Module) and Accura 2550CMZ(Power/Leakage Current Measuring Module),
Accura 2550CMS/ZM(Split-core Power/Leakage Current Measuring Module), Accura 2550CMM[Z](Three-
phase Power/Leakage Current Measuring Module for an MCB) installed at incoming/branch lines in the
industrial control panel.
Accura 2500M module receives measurement data from multiple Accura 2550 modules via internal
communication cables and provides the data through Accura 2500D. Accura 2500M can be combined with
Accura 2500D. Thus, users can install it by connecting it to the back of Accura 2500D, or it can be installed
separately in the industrial control panel.

Module Type Model Option Description Weight


Main industrial Accura 2500M -AC220V/DC110V AC 100 – 240 V, DC 100 – 300 V 500 g
control panel -DC24V DC 20 – 30 V
module Measures the voltage of the incoming line in
the AC/DC industrial control panel
Transmits the sampled voltage data to
Accura 2550 modules
Receives measurement data from Accura
2550 modules
Sends/receives set values and measured data
to/from Accura 2500D
Communicates with the host system
Can be connected to the back of Accura
2500D
Industrial control Accura 2500D 5” Color TFT LCD (built-in touch panel) 400 g
panel
HMI module Sends/receives set values and measured data
to/from Accura 2500M
Displays measured values and allows users
to set up parameters on the LCD screen
Accura 2500M can be connected to the back
of Accura 2500D.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 29


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Three-phase power Accura 2550CM-3P -800A -210 Basic current 800 A 1,500 g
measuring module -630A -145 Basic current 630 A 1,000 g
-400A -140 Basic current 400 A 1,000 g
-250A Basic current 250 A 140 g
-125A Basic current 125 A 130 g
-100A Basic current 100 A 115 g
-60A Basic current 60 A 115 g
-5A 1
Basic current 5 A 155 g
Single-phase power Accura 2550CM-1P -250A Basic current 250 A 125 g
measuring module -125A Basic current 125 A 85 g
-100A Basic current 100 A 80 g
-60A Basic current 60 A 80 g
Three-phase power/ Accura 2550CMZ-3P -800A -220 Basic current 800 A 2,500 g
-630A -155 Basic current 630 A 1,500 g
leakage current -400A -155 Basic current 400 A 1,500 g
measuring module 3 -250A Basic current 250 A 300 g
-125A Basic current 125 A 235 g
-100A Basic current 100 A 175 g
-60A Basic current 60 A 175 g
Three-phase 4-wire Accura 2550CMZ-3P4W -250A-145 Basic current 250 A 330 g
power/leakage current
measuring module
Single-phase power/ Accura 2550CMZ-1P -250A Basic current 250 A 270 g
leakage current -125A Basic current 125 A 155 g
measuring module -100A Basic current 100 A 125 g
-60A Basic current 60 A 125 g
Split-core power Accura -3P4W -60A Basic current 60 A 430 g
measuring module 2550CMS -1P3F -60A Basic current 60 A 430 g
-1P2F -60A Basic current 60 A 350 g
Leakage current Accura 2550ZM -3P4W -60A-DI Basic current 60 A 210 g
measuring module -1P3F -60A-DI Basic current 60 A 330 g
-1P2F -60A-DI Basic current 60 A 230 g
Three-phase power Accura -3P -60A Basic current 60 A 100 g
measuring module for 2550CMM
MCBs
Three-phase Accura -3P -60A Basic current 60 A 150 g
power/leakage current 2550CMMZ
measuring module for
MCBs
Three-phase terminal TM-CM-BC-3P 3 -105 Accura 2550CM-3P-250A terminal block 325 g
block
for Accura 2550CM 2 TM-CM-3P -105 Accura 2550CM-3P-250A terminal block 320 g
-90 Accura 2550CM-3P-125A terminal block 195 g
-75L Accura 2550CM-3P-100A terminal block 185 g
-75 Accura 2550CM-3P-60A terminal block 140 g

Page 30 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Single-phase TM-CM-1P -105 Accura 2550CM-1P-250A terminal block 240 g


terminal block
for Accura 2550CM -60 Accura 2550CM-1P-125A terminal block 135 g
2

-50L Accura 2550CM-1P-100A terminal block 125 g


-50 Accura 2550CM-1P-60A terminal block 90 g
Three-phase TM-CMZ-BC-3P 3 -105 Accura 2550CMZ-3P-250A terminal 390 g
terminal block block
for Accura TM-CMZ-3P -105 Accura 2550CMZ-3P-250A terminal 385 g
2550CMZ 2
block
-90 Accura 2550CMZ-3P-125A terminal 220 g
block
-75L Accura 2550CMZ-3P-100A terminal 200 g
block
-75 Accura 2550CMZ-3P-60A terminal block 150 g
Three-phase 4-wire TM-CMZ-BC-3P4W 3 -1403 Accura 2550CMZ-3P4W-250A terminal 510 g
terminal block for block
CMZ module 2

Single-phase TM-CMZ-1P -105 Accura 2550CMZ-1P-250A terminal 310 g


terminal block
block for Accura -60 Accura 2550CMZ-1P-125A terminal 145 g
2550CMZ 2 block
-50L Accura 2550CMZ-1P-100A terminal 135 g
block
-50 Accura 2550CMZ-1P-60A terminal block 100 g
1. Accura 2550CM-3P-5A module can be used by externally installing CTs(the secondary current rating: 5 A).
2. The weight of the terminal block includes its cover.
3. The 250A terminal block allows for the insertion of barriers.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 31


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

The abbreviated names of Accura 2500/2550 modules are shown in the table below.

Abbreviated Name Description


A2500M Accura 2500M
A2500D Accura 2500D
A2550CM-3P CM 3P module Accura 2550CM-3P
A2550CM-1P CM 1P module Accura 2550CM-1P
A2550CM CM module Accura 2550CM
A2550CMZ-3P CMZ 3P module Accura 2550CMZ-3P
A2550CMZ-3P4W CMZ 3P4W module Accura 2550CMZ-3P4W
A2550CMZ-1P CMZ 1P module Accura 2550CMZ-1P
A2550CMZ CMZ module Accura 2550CMZ
A2550CM[Z] CM/CMZ module Accura 2550CM or Accura 2550CMZ
A2550CMS-3P4W CMS 3P4W module Accura 2550CMS-3P4W
A2550CMS-1P3F CMS 1P3F module Accura 2550CMS-1P3F
A2550CMS-1P2F CMS 1P2F module Accura 2550CMS-1P2F
A2550CMS CMS module Accura 2550CMS-3P4W or Accura 2550CMS-1P3F or
Accura 2550CMS-1P2F
A2550ZM-3P4W ZM 3P4W module Accura 2550ZM-3P4W
A2550ZM-1P3F ZM 1P3F module Accura 2550ZM-1P3F
A2550ZM-1P2F ZM 1P2F module Accura 2550ZM-1P2F
A2550ZM ZM module Accura 2550ZM-3P4W or Accura 2550ZM -1P3F or
Accura 2550ZM -1P2F
A2550CMM-3P CMM 3P module Accura 2550CMM-3P
A2550CMMZ-3P CMMZ 3P module Accura 2550CMMZ-3P

Page 32 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Special-Purpose Modules

The following table shows special-purpose modules with other functions except for the power measuring
function. For details on special-purpose modules, refer to the User Guide for each module.

Module Type Model Description


DCM Accura 2550DCM- Basic voltage 500 Vdc/ Basic current 80Adc
(DC power measuring meter) 500V-80A 1
Accura 2550DCM-
Basic voltage 50 Vdc/ Basic current 80Adc
50V-80A
TEMP(Temperature) module Accura 2550TEMP Measures the external temperature of the panel where the
module is installed
Temperature Accura TSEN Collects data on the temperature measured in the panel where
measuring device it is installed
Temperature/ Humidity Accura THSEN Collects data on the temperature and humidity measured in
measuring the panel where it is installed
device
GW(Gateway) module Accura 2550GW Collects data from the peripheral devices supporting RS-485
communication
GWM(Multi-channel Accura 2550GWM Collects data from peripheral devices supporting RS-485
communication gateway) module communication with its 4 ports
SA(Surge Arrester) leakage Accura 2550SAL Measures the leakage current of the surge arrester
current measuring module
VOL(Mixed Power Voltage) Accura 2550VOL Measures the voltage of multiple auxiliary power supplies
measuring module
IO module DI1 module Accura 2550IO-DI1 11 DI channels
DI2 module Accura 2550IO-DI2 22 DI channels
DO1 module Accura 2550IO-DO1 6 DO channels
DO2 module Accura 2550IO-DO2 12 DO channels
AI1 module Accura 2550IO-AI1 6 AI channels (DC 4 – 20 mA)
AI2 module Accura 2550IO-AI2 12 AI channels (DC 4 – 20 mA)
RTD1 module Accura 2550IO-RTD1 4 channels, RTD temperature sensor input
RTD2 module Accura 2550IO-RTD2 8 channels, RTD temperature sensor input
PS module Accura 2550PS Used for additional power supply
(Auxiliary power supply module)
1. This module is not UL certified.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 33


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Installation Example
Combined Installation of Accura 2500D and 2500M
The following figure shows a commonly used example of installing the power measuring module in the
industrial control panel. Accura 2500D is installed at the front of the industrial control panel, and Accura
2500M is installed by being attached to the rear of Accura 2500D.

Fig 1.3 Combined Installation of Accura 2500D and 2500M

Installation
Front panel Accura 2500D/2500M Industrial control panel HMI module /
Main industrial control panel module
Incoming line Accura 2550CMZ-3P-800A-220 Three-phase power/leakage current measuring module
Branch line Accura 2550CMZ-3P Three-phase power/leakage current measuring module
Accura 2550CMZ-1P 1 Single-phase power/leakage current measuring module
Internal Internal cable 2 Dedicated communication with the measuring module
communication
External Ethernet cable Ethernet communication with the host system
communication
1. Accura 2550CMZ-1P modules measure leakage current from both line-to-neutral and line-to-line loads.
2. It is provided with the product. Additional cables needed for a ring topology are sold separately. The conducting wire
should be at least 0.205 mm2 (24 AWG). It is recommended to keep a distance of over 5 mm from power lines
generating high levels of noise.

Page 34 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Separate Installation of Accura 2500D and 2500M


The following figure shows an example of installing Accura 2500M module in the industrial control panel,
Accura 2500D module at the front of the panel, and connecting them using communication cables.

Fig 1.4 Connection of Accura 2500D and 2500M Using Communication Cables

Installation
Front panel Accura 2500D Industrial control panel HMI module
Inside the panel Accura 2500M Main industrial control panel module
Incoming line Accura 2550CMZ-3P-800A-220 Three-phase power/leakage current measuring module
Branch line Accura 2550CMZ-3P Three-phase power/leakage current measuring module
Accura 2550CMZ-1P 1 Single-phase power/leakage current measuring module
Internal Internal cable for the display Communication with the HMI module
communication module 2

Internal cable 3
Communication with the measuring module
External Ethernet cable Ethernet communication with the host system
communication

1. Accura 2550CMZ-1P modules measure leakage current from both line-to-neutral and line-to-line loads
2. It is provided with the product.
3. It is provided with the product. Additional cables needed for a ring topology are sold separately. The conducting wire
of the communication cable should be at least 0.205 mm2 (24 AWG). It is recommended to keep a distance of over
5 mm from power lines generating high levels of noise

ⓒ 2019 Rootech Inc. All Rights Reserved Page 35


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Product Features

Accura 2500M Main Industrial Control Panel Module

Installed at the incoming line of the industrial control panel, Accura 2500M module performs the main
function of the industrial control panel. It senses the voltage of the incoming line in the industrial control
panel and sends the sampled voltage data to all Accura 2550 modules connected with internal
communication cables, enabling to measure power at each branch line. Accura 2500M shows measurement
and operational status data collected from multiple Accura 2550 modules through Accura 2500D module’s
TFT LCD screen. Accura 2500M connects with the host system via Ethernet or external RS-485 communication.
Because Accura 2500M module can be combined with Accura 2500D module, it can be installed by being
attached to the back of Accura 2500D. It can also be installed separately in the industrial control panel.

Voltage Measurement on the Incoming Line


Measures voltage on the incoming line in the industrial control panel
Measurement Parameters
Voltage Line-to-neutral voltage, Line-to-line voltage, and Frequency
Fundamental voltage, Vector diagram (phasor), Voltage waveforms
THD, Harmonics 1

Symmetrical components (positive-, negative-, zero-sequence components)


Unbalance according to symmetrical components/ the NEMA standard
Residual voltage 2

Power Quality
Dip/Swell 1
RMS voltage refreshed every cycle
PQ Curve 1
RMS voltage refreshed every cycle
Supports SEMI F47-0706, IEC 61000-4-11/34 Class 3, and ITIC
Harmonics Harmonics up to the 50th order 1

Unbalance Line-to-neutral/Line-to-line voltage unbalance, Unbalance according to symmetrical components


Events
Power quality Dip/Swell events
events PQ Curve events SEMI F47-0706, IEC 61000-4-11/34 Class 3, ITIC
Transient voltage events (512 samples/cycle)
Up to 100 power quality events can be saved.
Measurement Voltage connection Phase open 3 Events on failures in voltage connection
events events Fuse fail 3 Events on fuse failures on the line where voltage is measured
Current events Events on current values measured by Accura 2550CM[Z] modules
Events for each module can be configured on Accura 2500D’s screen.
Leakage current Events on leakage current values measured by Accura 2550CMZ modules
events 4 Events for each module can be configured on Accura 2500D’s screen.
User-defined Events for which users can set event input data and event operations
events Users can set up to 40 events via communication.
Up to 100 measurement events can be saved.

Page 36 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

System events Events on module control, communication status, and setup


Up to 1,000 system events can be saved.
Internal Communication with Accura 2500D
Dedicated Sends/receives data to/from Accura 2500D via its own protocol
communication
Internal Communication with Accura 2550
Dedicated Sends the sampled voltage data on the incoming line to multiple Accura 2550 modules
communication Collects measurement and operational status data from multiple Accura 2550 modules
Internal protocol
Number of connectable modules 5
In a group Up to 30
In two groups Up to 40
Supports communication redundancy through ring connection using 2 ports in group 1 & 2
External Communication with the Host System
Ethernet Communicates with the host system with Modbus TCP protocol at 100Mbps
communication Sends measurement data collected from multiple Accura 2550 modules to the host system
Supports communication redundancy through ring connection using 2 Ethernet switch ports
Wiring method: star, daisy-chain, ring connection (supports RSTP 6)
RS-485 Communicates with the host system via the Modbus RTU protocol at 1,200 / 2,400 / 4,800 / 9,600 /
communication 19,200 / 38,400 / 57,600 / 115,200 bps 7

Sends measurement data collected from multiple Accura 2550 modules to the host system
Power Supply
Power supply AC 100 – 240 V 50/60 Hz, DC 100 – 300 V, CAT II Accura 2500M-AC220V/DC110V 8

voltage(Us) DC 24 V, CAT II Accura 2500M-DC24V


Operating voltage 0.9 x Us – 1.1 x Us Accura 2500M-AC220V/DC110V
range DC 20 – 30 V Accura 2500M-DC24V
1. It is calculated with line-to-line voltage in 3P3W connection and with line-to-neutral voltage in 3P4W connection.
2. Residual voltage is calculated by summing up three-phase line-to-neutral voltages.
3. It is not supported when there is any phase connected to the ground in 3P3W connection.
4. Leakage current events are available with Accura 2550CMZ and Accura 2550CMS(connected to Accura 2550ZM)
modules.
5. The number of modules that can be connected varies by module type. Refer to 「Appendix B Module Connection」
for details about module connection.
6. RSTP(Rapid Spanning Tree Protocol), IEEE 802.1D-2004
7. At 115,200 bps, a master can communicate with up to 16 slave devices, and the maximum distance between
the master and the slave is 600 m
8. The device conforms to UL standards for the tested AC power supply voltage.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 37


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Accura 2500D Industrial Control Panel HMI Module

Accura 2500D is installed at the front of the industrial control panel. Users can install it either by connecting
with Accura 2500M using a communication cable or by attaching Accura 2500M to the back of the device.
The 5" TFT Color LCD screen on the front of the device provides users with measurement and operational
status data collected from multiple Accura 2550 modules. In addition, all functions of Accura 2500M and
Accura 2550 can be set through the TFT Color LCD screen, which has the touch function.

Connection to Accura 2500M


Connection using the Can be connected to Accura 2500M by attaching Accura 2500M to the back of Accura 2500D
built-in connector using its built-in connector
Connection using Can be connected to Accura 2500M using the RJ45 communication cable
communication cables
Internal Communication with Accura 2500M
Dedicated Sends/receives data to/from Accura 2500M via its own protocol
communication Displays data on Accura 2500M as well as measurement and operational status data collected
from multiple Accura 2550 modules
Users can set functions of Accura 2500M and multiple Accura 2550 modules on Accura 2500D.
Display
LCD 5” (108.0 x 64.8 mm) Color TFT LCD
800 x 480 pixels
LED backlight and touch panel (Users can touch the front of the LCD screen.)
Power Supply
Power supply voltage Receives power from Accura 2500M

Page 38 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Accura 2550CM[Z]-3P/CMZ-3P4W Three-Phase Power/Leakage Current Measuring Modules

Accura 2550CM[Z]-3P/CMZ-3P4W modules are installed on the incoming/branch lines in industrial control
panels and sense currents. It measures various power characteristics of individual loads based on the voltage
data of the incoming line received from Accura 2500M module, as well as current data.
Accura 2550CMZ-3P/CMZ-3P4W modules have built-in ZCTs(Zero-sequence Current Transformers) and
directly measure the leakage current of three-phase 3-wire or three-phase 4-wire loads.

Power & Leakage Current 1 Measurement on the Incoming/Branch Line


Measures various power characteristics of individual loads and leakage current based on the sampled current data on
the incoming line/branch line and the voltage data of the incoming line received from Accura 2500M module
Model Basic Current Note
Accura 2550CM-3P -800A-210 800 A Leakage current is not measured.
-630A-145 630 A
-400A-140 400 A
-250A 250 A
-125A 125 A
-100A 100 A
-60A 60 A
-5A 1
5A
-800A-210-ZCT 800 A Additional external ZCT connection port 2

-630A-145-ZCT 630 A
-400A-140-ZCT 400 A
-5A-ZCT 1 5A
Accura 2550CMZ-3P -800A-220 800 A Leakage current is measured for three-phase
-630A-155 630A 3-wire loads.

-400A-155 400 A
-250A 250 A
-125A 125 A
-100A 100 A
-60A 60 A
Accura 2550CMZ-3P4W -250A-145 250A Leakage current is measured for three-phase
4-wire loads.
Measurement Parameters
Current RMS, Fundamental, Harmonics, THD, TDD, Vector diagram (phasor), Current waveforms
Symmetrical components, Unbalance according to symmetrical components, Current
unbalance, Crest factor, K-factor
Residual current (RMS, fundamental)
Leakage current Measured by the built-in ZCT Accura 2550CM-3P modules, which can
connect an external ZCT
Accura 2550CMZ modules
Power Active power, Reactive power, Apparent power
Energy Received/Delivered active energy, 4-quadrant reactive energy, Apparent energy
Power factor Power factor, Displacement power factor 3

ⓒ 2019 Rootech Inc. All Rights Reserved Page 39


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Demand Current/Power demand, Peak current/power demand, Predicted current/power demand


Events
Current events “Over” or “Under” event on measured current values
Leakage current events “Over” event on leakage current values Accura 2550CM-3P modules, which can
connect an external ZCT
Measured by Accura 2550CMZ modules
Internal Communication with Accura 2500M
Dedicated Receives the sampled voltage data on the incoming line from Accura 2500M
communication Sends measurement and operational status data to Accura 2500M
Number of connectable In a group Up to 30
modules 4 In two groups Up to 40
Supports communication redundancy through a ring topology
Display
LCD features 13 x 18 mm Customized Mono LCD, LED backlight
Power Supply
Power supply voltage Receives power from Accura 2500M

1. Accura 2550CM-3P-5A module can be used by externally installing CTs (the rated secondary current: 5 A).
2. Accura 2550CM-3P, which can connect an external ZCT, module measures leakage current by connecting an externally
installed voltage-type ZCT to its ZCT connection port. The user must purchase the ZCT separately from the
ZCT manufacturer.
3. The data are available only via communication.
4. The number of modules that can be connected varies by module type. Refer to 「Appendix B Module Connection」
for details about module connection.

Page 40 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Accura 2550CM[Z]-1P Single-Phase Power/Leakage Current Measuring Module

Accura 2550CM[Z]-1P modules are installed on the single-phase branch line of the industrial control panel
to sense currents. It measures various power characteristics of individual loads based on the measured
current values and the voltage data on the incoming line received from Accura 2500M module. Accura
2550CMZ-1P modules have built-in ZCTs(Zero-sequence Current Transformers) and directly measure leakage
current in a line-to-line or line-to-neutral configuration for single-phase loads.

Power & Leakage Current Measurement on the Branch Line


Measures various power characteristics of individual loads and leakage current based on the sampled current data
directly sensed on the branch line and the voltage data of the incoming line received from Accura 2500M module.
Model Basic Current Note
Accura 2550CM-1P -250A 250 A Leakage current is not measured.
-125A 125 A
-100A 100 A

-60A 60 A
Accura 2550CMZ-1P -250A 250 A Leakage current is directly measured with
-125A 125 A the built-in ZCT.

-100A 100 A
-60A 60 A
Measurement Parameters
Current RMS, Fundamental, Harmonics, THD, TDD, Vector diagram (phasor), Current waveforms
Crest factor, K-factor
Leakage current Measured by the built-in ZCT Accura 2550CMZ modules
Power Active power, Reactive power, Apparent power
Energy Received/Delivered active energy, 4-quadrant reactive energy, Apparent energy
Power factor Power factor, Displacement power factor 1

Demand Current/Power demand, Peak current/power demand, Predicted current/power demand


Events
Current events “Over” or “Under” event on measured current values
Leakage current events “Over” event on leakage current values Measured by Accura 2550CMZ modules
Internal Communication with Accura 2500M
Dedicated Receives the sampled voltage data on the incoming line from Accura 2500M
communication Sends measurement and operational status data to Accura 2500M
Number of connectable In a group Up to 30
modules 2
In two groups Up to 40
Supports communication redundancy through a ring topology
Display
LCD features 13 x 18 mm / 12 x 10 mm Customized Mono LCD, LED backlight

Power Supply
Power supply voltage Receives power from Accura 2500M
1. The data are available only via communication.
2. The number of modules that can be connected varies by module type. Refer to 「Appendix B Module Connection」
for details about module connection.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 41


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Accura 2550CMS/ZM Split-Core Power/Leakage Measuring Modules

Accura 2550CMS-3P4W modules are installed on branch lines in a three-phase 4-wire configuration in
industrial control panels and sense three-phase currents. Accura 2550CMS-1P3F/1P2F split-core power
measuring modules are installed on consecutive branch lines in a single-phase configuration and sense
single-phase currents in three or two feeders in industrial control panels. The modules measure various
power characteristics based on the sensed current information and incoming voltage information received
from the Accura 2500M Main module.
Accura 2550ZM-3P4W/1P3F/1P2F leakage measuring modules are equipped with Zero-phase Current
Transformers(ZCTs) for individual feeders to measure leakage currents from three-phase or three or two
single-phase loads. They also have digital input terminals to monitor the operation and trip status of the
MCCBs(Molded Case Circuit Breakers) for each feeder. The Accura 2550ZM-3P4W leakage current measuring
module is connected to the Accura 2550CMS-3P4W split-core power measuring module, and the Accura
2550ZM-1P3F leakage current measuring module is connected to the Accura 2550CMS-1P3F split-core power
measuring module using communication cables. Also, the Accura 2550ZM-1P2F leakage current measuring
module is connected to the Accura 2550CMS-1P2F split-core power measuring module.

Power & Leakage Current Measurement on the Incoming/Branch Line


Measures various power characteristics of individual loads and leakage current based on the sampled current data
directly sensed on the branch line and the voltage data of the incoming line received from Accura 2500M module.
Model Feeder Basic current
Accura 2550CMS -3P4W-60A Three-phase 4-wire 60 A
split-core power -1P3F-60A Single-phase 3 feeders
measuring module -1P2F-60A Single-phase 2 feeders
Accura 2550ZM -3P4W-60A-DI Three-phase 4-wire 60 A
leakage current -1P3F-60A-DI Single-phase 3 feeders
measuring module -1P2F-60A-DI Single-phase 2 feeders
Measurement Parameters
Current RMS, Fundamental, Harmonics, THD, TDD, Vector diagram(phasor), Current waveforms
Crest factor, K-factor
Symmetrical components 1, Unbalance according to symmetrical components 1,
Current unbalance 1

Residual current (RMS, fundamental) 1

Leakage current Measured by the built-in ZCT Accura 2550ZM modules


Power Active power, Reactive power, Apparent power
Energy Received/Delivered active energy, 4-quadrant reactive energy, Apparent energy
Power factor Power factor, Displacement power factor 2

Demand Current/Power demand, Peak current/power demand, Predicted current/power demand


Events
Current events “Over” or “Under” event on measured current values
Leakage current events “Over” event on leakage current values Accura 2550ZM modules

Page 42 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 1 Introduction

Internal Communication with Accura 2500M


Dedicated Receives the sampled voltage data on the incoming line from Accura 2500M
communication Sends measurement and operational status data to Accura 2500M
Number of connectable In a group Up to 30
modules 3
In two groups Up to 40
Supports communication redundancy through a ring topology
Display
LCD features 13 x 18 mm Customized Mono LCD, LED backlight
Power Supply
Power supply voltage Receives power from Accura 2500M
1. It is only available with the Accura 2550CMS-3P4W module.
2. The data are available only via communication.
3. The number of modules that can be connected varies by module type. Refer to 「Appendix B Module Connection」
for details about module connection.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 43


Chapter 1 Introduction Accura 2500/2550 User Guide [AC]

Accura 2550CMM[Z] Three-Phase Power/Leakage Current Measuring Module for MCBs

The Accura 2550CMM-3P module is installed at either the main or branch lines of the industrial control
panel to sense the current. Based on the incoming voltage information received from the Accura 2500M,
it measures various power characteristics of the corresponding load. The Accura 2550CMM-3P module
supports measurements of multiple single-phase feeders. When connecting the module to the load, the hot
line should pass through the main hole(Ø 10.4) of the module, and the Neutral line should pass through
its sub-hole(Ø 5.9). Accura 2550CMMZ-3P module is equipped with a built-in ZCT (Zero-sequence Current
Transformer), allowing it to directly measure the leakage current of three-phase 3-wire or three-phase 4-
wire loads. Additionally, the Accura 2550CMMZ-3P with a built-in ZCT does not support multi-feeder
measurement functionality.

Power Measurement of Incoming/Branch Line


Measures various power characteristics based on the sampled current data on the incoming line/branch line and
the sampled voltage data on the incoming line received from Accura 2500M module
Module Feeder Basic Current
Accura 2550CMM -3P-60A Three phase 60 A
Accura 2550CMMZ -3P-60A Three phase 60 A
Measurement Parameters
Current RMS, Fundamental, Harmonics, THD, TDD, Vector diagram (phasor), Current waveforms
Crest factor, K-factor
Symmetrical components, Unbalance according to symmetrical components,
Current unbalance
Residual current (RMS, Fundamental)
Power Active power, Reactive power, Apparent power
Energy Received/Delivered active energy, 4-quadrant reactive energy, Apparent energy
Power factor Power factor, Displacement power factor 1

Demand Current/Power demand, Peak current/power demand, Predicted current/power demand


Events
Current events “Over” or “Under” event on measured current values
Leakage current events “Over” event on leakage current values Accura 2550CMMZ modules
Internal Communication with Accura 2500M
Dedicated Receives the sampled voltage data on the incoming line from Accura 2500M
communication Sends measurement and operational status data to Accura 2500M
Number of connectable In a group Up to 30
modules 2 In two groups Up to 40
Supports communication redundancy through a ring topology
Display
LCD features 13 x 18 mm Customized Mono LCD, LED backlight
Power Supply
Power supply voltage Receives power from Accura 2500M
1. The data are available only via communication.
2. The number of modules that can be connected varies by module type. Refer to 「Appendix B Module Connection」
for details about module connection.

Page 44 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Chapter 2 Installation
Conditions for Installation
Accura 2500/2550 should be installed at the locations that are not affected by high temperatures and high
electric fields. To operate the products properly, you should install it under the environmental conditions as
below.

Environmental Conditions Description


Installation location Indoors
Operating temperature -20 – 70 C (-4 – 158 ℉)
Safe operating temperature 1 -20 – 60 C (-4 – 140 ℉)
Storage temperature -40 – 85 C (-40 – 185 ℉)
Operating humidity 5 – 95 % (non-condensing)
Operating altitude Up to 2,000 m
Ingress protection against dust and water IEC 60529 IP54 (Accura 2500D)
1. Compliant with UL 61010-1(3rd edition)

Caution
The meter should be installed in an industrial control cabinet or similar enclosure to prevent users from
accessing the terminal strips on the meter and to minimize exposure to external environments after
installation. Install the product in a dry location free from dirt, oil and corrosive vapors. When installing
the product, there is no need to clean it.

Before installing Accura 2500/2550, observe the following instructions and safety precautions.

Caution
You should power up the device after voltage and current wiring is completed.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 45


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Product Appearance
Fig 2.1 Accura 2500M Front Fig 2.2 Accura 2500M Side

Fig 2.3 Accura 2500M Rear

Page 46 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.4 Accura 2500D Front Fig 2.5 Accura 2500D Side

Fig 2.6 Accura 2500D Rear

ⓒ 2019 Rootech Inc. All Rights Reserved Page 47


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Fig 2.7 Accura 2550CM-3P/1P

A2550CM-3P-800A/630A/400A A2550CM-3P-800A/630A/400A-ZCT

A2550CM-3P-250A/125A/100A/60A/5A A2550CM-3P-5A-ZCT

A2550CM-1P-250A/125A/100A/60A
1. The Accura 2550CM-3P-5A-ZCT module, which allows for external ZCT connections, has the same dimensions as the
Accura 2550CM-3P-5A module but features an additional external ZCT connection terminal on the side.

Page 48 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.8 Accura 2550CMZ-3P/1P

A2550CMZ-3P-800A/630A/400A A2550CMZ-3P-250A/125A/100A/60A A2550CMZ-1P-250A/125A/100A/60A

Fig 2.9 Accura 2550CMZ-3P4W

A2550CMZ-3P4W-250A-145

Fig 2.10 Accura 2550CMS-3P4W/1P3F/1P2F

A2550CMS-3P4W/1P3F/1P2F-60A

ⓒ 2019 Rootech Inc. All Rights Reserved Page 49


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Fig 2.11 Accura 2550ZM-3P4W/1P3F/1P2F

A2550ZM-3P4W-60A-DI A2550ZM-1P3F-60A-DI A2550ZM-1P2F-60A-DI

Fig 2.12 Accura 2550CMM

A2550CMM-3P-60A

Fig 2.13 Accura 2550CMMZ

A2550CMMZ-3P-60A

Page 50 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.14 TM-CM[Z]-3P Fig 2.15 TM-CM[Z]-1P

TM-CM[Z]-3P-105/90/75L/75 TM-CM[Z]-1P-105 TM-CM[Z]-1P-60/50L/50

Fig 2.16 TM-CM[Z]-BC-3P Fig 2.17 TM-CM[Z]-BC-3P4W

TM-CM[Z]-BC-3P-105 TM-CM[Z]-BC-3P4W-140

ⓒ 2019 Rootech Inc. All Rights Reserved Page 51


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Components
Fig 2.18 Accura 2500M Components

3 m x 1 EA, 75 cm x 1 EA

Accura 2500M Mounting 2 bolt caps 4 mounting screws Internal communication cables 1

wings(L/S)
1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Fig 2.19 Accura 2500D Components

3 m x 1 EA

Accura 2500D Mounting wheel Internal cable for the display module

Fig 2.20 Accura 2550CM-3P-800A/630A/400A Components

30 cm x 1 EA

Accura 2550CM-3P 4 mounting wings 4 mounting screws Internal communication cable 1

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Page 52 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.21 Accura 2550CMZ-3P 800A/630A/400A Components

30 cm x 1 EA

Accura 2550CMZ-3P 4 mounting wings 6 mounting screws Internal communication cable 1

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Fig 2.22 Accura 2550CM[Z]-3P-250A/125A/100A/60A Components

10 cm x 1 EA

Accura 2550CM[Z]-3P Mounting plate 2 mounting screws Internal communication cable 1

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 53


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Fig 2.23 Accura 2550CM-3P-800A/630A/400A/5A-ZCT Components

Accura 2550CM-3P-800A/630A/400A-ZCT Accura 2550CM-3P-5A-ZCT Mounting plate 2 mounting screws

10 cm x 1 EA

Internal communication cable 1 ZCT connection cable

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Fig 2.24 Accura 2550CMZ-3P4W-250A Components

10 cm x 1 EA

Accura 2550CMZ-3P4W-250A Mounting plate 2 mounting screws Internal communication cable 1

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Page 54 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.25 Accura 2550CM[Z]-1P-250A Components

10 cm x 1 EA

Accura 2550CM[Z]-1P-250A Mounting plate 2 mounting screws Internal communication cable 1

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Fig 2.26 Accura 2550CM[Z]-1P-125A/100A/60A Components

10 cm x 1 EA

Accura 2550CM[Z]-1P- Mounting plate 2 mounting screws Internal communication cable 1

125A/100A/60A
1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Fig 2.27 Accura 2550CMS-3P4W/1P2F Components

10 cm x 1 EA

Accura 2550CMS-3P4W/1P2F 4 mounting wings 2 mounting screws Internal communication cable 1

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 55


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Fig 2.28 Accura 2550CMS-1P3F Components

20 cm x 1 EA

Accura 2550CMS-1P3F 4 mounting wings 2 mounting screws Internal communication cable 1

1. Additional cables for connection with Accura 2550 modules in a ring topology are sold separately.

Fig 2.29 Accura 2550ZM-3P4W Components

20 cm x 1 EA
50 cm x 1 EA

Accura 2550ZM-3P4W Mounting plate 2 mounting screws RJ12 Internal Digital input cables
communication cable

Fig 2.30 Accura 2550ZM-1P3F Components

20 cm x 1 EA

50 cm x 3 EA

Accura 2550ZM-1P3F Mounting plate 2 mounting screws RJ12 Internal Digital input cables
communication cable

Page 56 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.31 Accura 2550ZM-1P2F Components

20 cm x 1 EA
50 cm x 2 EA

Accura 2550ZM-1P3F Mounting plate 2 mounting screws RJ12 Internal Digital input cables
communication cable

Fig 2.32 Accura 2550CMM Components

20 cm x 1 EA

Accura 2550CMM Standard DIN rail mounting 2 mounting RJ12 Internal communication cable
mounting plate plate screws

Fig 2.33 Accura 2550CMMZ Components

50 cm x 2 EA
20 cm x 1 EA

Accura 2550CMMZ mounting plate 2 mounting RJ12 Internal communication Digital input cables
screws cable

ⓒ 2019 Rootech Inc. All Rights Reserved Page 57


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Fig 2.34 TM-CM[Z]-3P Components

TM-CM[Z]-3P Cover 2 mounting screws

Fig 2.35 TM-CM[Z]-BC-3P Components

TM-CM[Z]-BC-3P-105 Cover 2 mounting screws

Fig 2.36 TM-CMZ-BC-3P4W Components

TM-CMZ-BC-3P4W-140 Cover 3 mounting screws

Page 58 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.37 TM-CM[Z]-1P-105 Components

TM-CM[Z]-1P-105 Cover 2 mounting screws

Fig 2.38 TM-CM[Z]-1P-60/50L/50 Components

TM-CM[Z]-1P-60/50L/50 Cover 1 mounting screws

ⓒ 2019 Rootech Inc. All Rights Reserved Page 59


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Dimensions
Product Type Model Dimensions [mm] Weight
W x H x D
Main industrial control panel Accura 2500M 148.6 x 126.8 x 60.8 500 g
module
Industrial control panel HMI Accura 2500D 151.5 x 129.6 x 32.6 400 g
module
Three-phase power Accura 2550CM-3P -800A-210 45.0 x 210.0 x 93.7 1,500 g
measuring module -800A-210-ZCT 45.0 x 210.0 x 93.7 1,500 g
-630A-145 45.0 x 145.0 x 93.7 1,000 g
-630A-145-ZCT 45.0 x 145.0 x 93.7 1,000 g
-400A-140 45.0 x 140.0 x 93.7 1,000 g
-400A-140-ZCT 45.0 x 140.0 x 93.7 1,000 g
-250A 25.0 x 105.0 x 61.7 140 g
-125A 25.0 x 90.0 x 61.7 130 g
-100A 25.0 x 75.0 x 61.7 115 g
-60A 25.0 x 75.0 x 61.7 115 g
-5A 1 25.0 x 75.0 x 61.7 155 g
-5A-ZCT 1 25.0 x 75.0 x 61.7 155 g
Single-phase power Accura 2550CM-1P -250A 25.0 x 105.0 x 61.7 125 g
measuring module -125A 25.0 x 60.0 x 61.7 85 g
-100A 25.0 x 50.0 x 61.7 80 g
-60A 25.0 x 50.0 x 61.7 80 g
Three-phase Accura 2550CMZ-3P -800A-220 80.0 x 219.6 x 94.2 2,500 g
power/leakage current -630A-155 80.0 x 154.6 x 94.2 1,500 g
measuring module -400A-155 80.0 x 154.6 x 94.2 1,500 g
-250A 45.0 x 105.0 x 61.7 300 g
-125A 40.0 x 90.0 x 61.7 235 g
-100A 35.0 x 75.0 x 61.7 175 g
-60A 35.0 x 75.0 x 61.7 175 g
Accura 2550CMZ-3P4W -250A-145 45.0 x 140.0 x 61.7 330 g
Single-phase power/leakage Accura 2550CMZ-1P -250A 45.0 x 105.0 x 61.7 270 g
current measuring module -125A 35.0 x 60.0 x 61.7 155 g
-100A 35.0 x 50.0 x 61.7 125 g
-60A 35.0 x 50.0 x 61.7 125 g
Split-core Accura 2550CMS -3P4W -60A 53.0 x 100.0 x 85.0 430 g
power measuring module -1P3F -60A 53.0 x 100.0 x 85.0 430 g
-1P2F -60A 53.0 x 100.0 x 85.0 430 g
Leakage current Accura 2550ZM -3P4W -60A-DI 49.9 x 100.0 x 79.9 210 g
measuring module -1P3F -60A-DI 49.9 x 150.0 x 64.9 330 g
-1P2F -60A-DI 49.9 x 100.0 x 64.9 230 g
Three-phase power Accura 2550CMM -3P -60A 25.0 x 52.5 x 54.3 100 g
measuring module for MCBs

Page 60 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Three-phase power/leakage Accura 2550CMMZ -3P -60A 25.0 x 57.0 x 83.9 150 g
current measuring module for
MCBs
Three-phase terminal block for TM-CM-BC-3P -105 68.8 x 105.0 x 54.0 325 g
CM modules TM-CM-3P -105 68.8 x 105.0 x 54.0 320 g
(The weight includes the cover -90 62.8 x 90.0 x 54.0 195 g
for the terminal block.) -75L 62.5 x 75.0 x 54.0 185 g
-75 57.2 x 75.0 x 54.0 140 g
Single-phase terminal block TM-CM-1P -105 68.8 x 105.0 x 54.0 240 g
for CM modules -60 62.8 x 60.0 x 54.0 135 g
(The weight includes the cover -50L 62.5 x 50.0 x 54.0 125 g
for the terminal block.) -50 57.2 x 50.0 x 54.0 90 g
Three-phase terminal block for TM-CMZ-BC-3P -105 88.8 x 105.0 x 54.0 390 g
CMZ modules TM-CMZ-3P -105 88.8 x 105.0 x 54.0 385 g
(The weight includes the cover -90 77.8 x 90.0 x 54.0 220 g
for the terminal block.) -75L 72.5 x 75.0 x 54.0 200 g
-75 67.2 x 75.0 x 54.0 150 g
Three-phase 4-wire TM-CMZ-BC-3P4W 2, 3
-140 88.8 x 140.0 x 54.0 510 g
terminal block for CMZ
modules
Single-phase terminal block TM-CMZ-1P -105 88.8 x 105.0 x 54.0 310 g
for CMZ modules -60 72.8 x 60.0 x 54.0 145 g
(The weight includes the cover -50L 72.5 x 50.0 x 54.0 135 g
for the terminal block.) -50 67.2 x 50.0 x 54.0 100 g

1. Accura 2550CM-3P-5A module can be used by externally installing CTs (the secondary current rating: 5 A).
2. The weight of the terminal block includes its cover.
3. The 250A terminal block allows for the insertion of barriers.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 61


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2500D/2500M

Fig 2.39 Accura 2500D/2500M Dimensions

Accura 2500D/2500M Front Accura 2500M Front

Fig 2.40 Accura 2500D Dimensions

Front Rear

Page 62 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CM-3P

The Accura 2550CM-3P-800A/630A/400A/5A and the Accura 2550CM-3P-800A/630A/400A/5A-ZCT modules


have the same dimensions, with the difference being the presence of external ZCT connection terminals.

Fig 2.41 Accura 2550CM-3P Dimensions

Accura 2550CM-3P-800A-210 Accura 2550CM-3P-800A-210-ZCT

Accura 2550CM-3P-630A-145 Accura 2550CM-3P-630A-145-ZCT

ⓒ 2019 Rootech Inc. All Rights Reserved Page 63


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2550CM-3P-400A-140 Accura 2550CM-3P-400A-140-ZCT

Accura 2550CM-3P-250A Accura 2550CM-3P-125A

Page 64 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CM-3P-100A/60A Accura 2550CM-3P-5A

Accura 2550CM-3P-5A-ZCT

ⓒ 2019 Rootech Inc. All Rights Reserved Page 65


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2550CM-1P

Fig 2.42 Accura 2550CM-1P Dimensions

Accura 2550CM-1P-250A 1
Accura 2550CM-1P-125A

Accura 2550CM-1P-100A/60A

1. The hole in the middle of the module is not used when passing cables through the holes of the module.

Page 66 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CMZ-3P

Fig 2.43 Accura 2550CMZ-3P Dimensions

Accura 2550CMZ-3P-800A-220 Accura 2550CMZ-3P-630A-155

Accura 2550CMZ-3P-400A-155 Accura 2550CMZ-3P-250A

ⓒ 2019 Rootech Inc. All Rights Reserved Page 67


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2550CMZ-3P-125A Accura 2550CMZ-3P-100A/60A

Accura 2550CMZ-3P4W

Fig 2.44 Accura 2550CMZ-3P4W Dimensions

Accura 2550CMZ-3P4W-250A-145

Page 68 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CMZ-1P

Fig 2.45 Accura 2550CMZ-1P Dimensions

Accura 2550CMZ-1P-250A 1
Accura 2550CMZ-1P-125A

Accura 2550CMZ-1P-100A/60A
1. The hole in the middle of the module is not used when passing cables through the holes of the module.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 69


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2550CMS

Fig 2.46 Accura 2550CMS Dimensions

Accura 2550CMS-3P4W/1P3F/1P2F-60A

Accura 2550ZM

Fig 2.47 Accura 2550ZM Dimensions

Accura 2550ZM-3P4W-60A-DI Accura 2550ZM-1P3F-60A-DI

Page 70 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550ZM-1P2F-60A-DI

Accura 2550CMM

Fig 2.48 Accura 2550CMM Dimensions

Accura 2550CMM-3P-60A Accura 2550CMM-3P-60A


(When attaching the mounting plate for panel mounting) (When attaching the mounting plate for DIN rail mounting)

Accua 2550CMMZ

Fig 2.49 Accura 2550CMMZ Dimensions

Accura 2550CMMZ-3P-60A

ⓒ 2019 Rootech Inc. All Rights Reserved Page 71


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

TM-CM-3P

Fig 2.50 TM-CM-3P Dimensions

TM-CM-BC-3P-105 1
TM-CM-BC-3P-105 Cover

TM-CM-3P-105 TM-CM-3P-105 Cover

TM-CM-3P-90 TM-CM-3P-90 Cover


1. The terminal block allows for the insertion of barriers.

Page 72 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

TM-CM-3P-75L TM-CM-3P-75L Cover

TM-CM-3P-75 TM-CM-3P-75 Cover

ⓒ 2019 Rootech Inc. All Rights Reserved Page 73


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

TM-CM-1P

Fig 2.51 TM-CM-1P Dimensions

TM-CM-1P-105 TM-CM-1P-105 Cover

TM-CM-1P-60 TM-CM-1P-60 Cover

TM-CM-1P-50L TM-CM-1P-50L Cover

TM-CM-1P-50 TM-CM-1P-50 Cover

Page 74 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

TM-CMZ-3P

Fig 2.52 TM-CMZ-3P Dimensions

TM-CMZ-BC-3P-105 1 TM-CMZ-BC-3P-105 Cover

TM-CMZ-3P-105 TM-CMZ-3P-105 Cover

TM-CMZ-3P-90 TM-CMZ-3P-90 Cover

ⓒ 2019 Rootech Inc. All Rights Reserved Page 75


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

TM-CMZ-3P-75L TM-CMZ-3P-75L Cover

TM-CMZ-3P-75 TM-CMZ-3P-75 Cover


1. The terminal block allows for the insertion of barriers.

TM-CMZ-3P4W

Fig 2.53 TM-CMZ-BC-3P4W Dimensions

TM-CMZ-BC-3P4W-140 1 TM-CMZ-BC-3P4W-140 Cover


1. The terminal block allows for the insertion of barriers.

Page 76 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

TM-CMZ-1P

Fig 2.54 TM-CMZ-1P Dimensions

TM-CMZ-1P-105 TM-CMZ-1P-105 Cover

TM-CMZ-1P-60 TM-CMZ-1P-60 Cover

TM-CMZ-1P-50L TM-CMZ-1P-50L Cover

TM-CMZ-1P-50 TM-CMZ-1P-50 Cover

ⓒ 2019 Rootech Inc. All Rights Reserved Page 77


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation Example
Installation of Accura 2500M/2500D/2550 Power Measuring Modules
The following figure shows an example of the installation method frequently used in industrial control panels.

Fig 2.55 Installation Diagram of Accura 2500M/2500D/2550 Modules

Installation
Front panel Accura Main industrial control panel
2500M/2500D /HMI module
Incoming line Accura 2550CMZ- Three-phase power/leakage
3P-800A-220 current measuring module
Branch line Accura 2550CMZ-3P Three-phase power/leakage
current measuring module
Accura 2550CMZ-1P Single-phase power/leakage
current measuring module
Auxiliary device TM-CMZ-3P 3-phase terminal block
TM-CMZ-1P 1-phase terminal block
Internal Internal cable 1 Communication with power
communication measuring modules

1. Accura 2550CMZ-1P modules measure leakage current from both line-to-neutral and line-to-line loads.
2.It is provided with the product. Additional cables needed for a ring topology are sold separately. Its conducting wire
should be at least 0.205 mm2(24 AWG). It is recommended to keep a distance of over 5 mm from the power lines
generating high levels of noise.

Page 78 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.56 Installation Diagram of Accura 2500M/2550CMS+ZM Modules

ⓒ 2019 Rootech Inc. All Rights Reserved Page 79


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2500M/2500D/2550CMM[Z]

The following figure shows an example of installing Accura 2550CMM[Z]-3P modules with MCBs(Miniature
Circuit Breakers) in an industrial control panel at a data center.

Fig 2.57 Installation Diagram of Accura 2500M/2500D/2550CMM[Z]

Page 80 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Step 1: Installation

Installing of Accura 2500D

Accura 2500D module is installed at the front of the industrial control panel.
① Fit the module into the panel cutout.
② Cover the back of the module with the mounting wheel.
③ Fix the module onto the panel by turning the mounting wheel.

Fig 2.58 Mounting Accura 2500D on the Panel

ⓒ 2019 Rootech Inc. All Rights Reserved Page 81


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2500M

Separate Installation of Accura 2500M


Accura 2500M module is installed at the front of or inside the industrial control panel.
① Insert the mounting wings into the module.
② Insert the bolt caps into the module. And then position it onto the mounting holes of the panel.
③ Fix the module onto the panel using screws.

Fig 2.59 Mounting Accura 2500M on the Panel

Page 82 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Combined Installation of Accura 2500M and Accura 2500D


Accura 2500D module is installed at the front of the industrial control panel.
① Fit Accura 2500D module into the panel cutout.
② Cover the back of the module with the mounting wheel.
③ Fix the module onto the panel by turning the mounting wheel.
④ Attach Accura 2500M to the back of Accura 2500D.
⑤ Fix Accura 2500M onto the back of Accura 2500D using the two bolts of Accura 2500M module.

Fig 2.60 Combined Installation of Accura 2500M and 2500D

ⓒ 2019 Rootech Inc. All Rights Reserved Page 83


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2550CM[Z]-3P

① Place the mounting plate on the location where you want to install the device.
② Tighten screws on the mounting plate diagonally.
③ Attach Accura 2550CM[Z]-3P module to the mounting plate.
④ Connect the three-phase terminal block with Accura 2550CM[Z]-3P module.
⑤ Fix the three-phase terminal block.
⑥ Connect the busbar with the MCCB.
⑦ Attach the cover to the three-phase terminal block.
Accura 2550CM[Z]-3P modules with the basic current ≥ 400 A can be fixed to the panel using mounting
wings instead of the mounting plate.

Fig 2.61 Mounting Accura 2550CM-3P Module on the Panel

A tolerance of 0.5 mm
between devices is required.

Page 84 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Installation of Accura 2550CM-3P Module through Mounting Holes


Accura 2550CM-3P modules with a basic current rating of ≥ 400 A can be attached to the panel using
mounting wings instead of the mounting plate. However, Accura 2550CM-3P modules with a basic current
rating of ≤ 250 A can be installed on the panel using the mounting plate.

Fig 2.62 Mounting Accura 2550CM-3P Module on the Panel through Mounting Holes (Mounting Wings) /
clear distance exists

Applied Model
Accura 2550CM-3P-800A-210

Applied Model
Accura 2550CM-3P-630A-145

ⓒ 2019 Rootech Inc. All Rights Reserved Page 85


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Applied Model
Accura 2550CM-3P-400A-140

Page 86 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.63 Mounting Accura 2550CM-3P Module on the Panel through Mounting Holes (Mounting Wings) /
without clear distance

Applied Model
Accura 2550CM-3P-800A-210

Applied Model
Accura 2550CM-3P-630A-145

ⓒ 2019 Rootech Inc. All Rights Reserved Page 87


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Applied Model
Accura 2550CM-3P-400A-140

Page 88 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.64 Mounting the Module on the Panel through Mounting Holes (Mounting Plate/Terminal Block)

Applied Model
Accura 2550CM-3P-250A
TM-CM-3P-105

Applied Model
Accura 2550CM-3P-125A
TM-CM-3P-90

ⓒ 2019 Rootech Inc. All Rights Reserved Page 89


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Applied Model
Accura 2550CM-3P-100A
TM-CM-3P-75L

Applied Model
Accura 2550CM-3P-60A
TM-CM-3P-75

Page 90 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Installation of Accura 2550CMZ-3P Module through Mounting Holes


Accura 2550CMZ-3P modules with a basic current rating of ≥ 400 A can be attached to the panel using
mounting wings instead of the mounting plate. However, Accura 2550CMZ-3P modules with a basic current
rating of ≤ 250A can be installed on the panel using the mounting plate.

Fig 2.65 Mounting the Module on the Panel through Mounting Holes (Mounting Wings) / clear distance
exists

Applied Model
Accura 2550CMZ-3P-800A-220

Applied Model
Accura 2550CMZ-3P-630A-155

ⓒ 2019 Rootech Inc. All Rights Reserved Page 91


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Applied Model
Accura 2550CMZ-3P-400A-155

Page 92 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.66 Mounting the Module on the Panel through Mounting Holes (Mounting Wings) / without clear
distance

Applied Model
Accura 2550CMZ-3P-800A-220

Applied Model
Accura 2550CMZ-3P-630A-155

ⓒ 2019 Rootech Inc. All Rights Reserved Page 93


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Applied Model
Accura 2550CMZ-3P-400A-155

Page 94 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.67 Mounting the Module on the Panel through Mounting Holes (Mounting Plate/Terminal Block)

Applied Model
Accura 2550CMZ-3P-250A
TM-CMZ-3P-105

Applied Model
Accura 2550CMZ-3P-125A
TM-CMZ-3P-90

ⓒ 2019 Rootech Inc. All Rights Reserved Page 95


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Applied Model
Accura 2550CMZ-3P-100A
TM-CMZ-3P-75L

Applied Model
Accura 2550CMZ-3P-60A
TM-CMZ-3P-75

Page 96 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Installation of Accura 2550CMZ-3P4W

① Place the mounting plate on the location where you want to install the device.
② Tighten screws on the mounting plate diagonally.
③ Attach Accura 2550CMZ-3P4W module to the mounting plate.
④ Connect the three-phase 4-wire terminal block with Accura 2550CMZ-3P4W module.
⑤ Fix the three-phase 4-wire terminal block.
⑥ Connect the busbar with the MCCB.
⑦ Attach the cover to the three-phase terminal block.

Fig 2.68 Mounting Accura 2550CMZ-3P4W Module on the Panel

ⓒ 2019 Rootech Inc. All Rights Reserved Page 97


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2550CMZ-3P4W Module through Mounting Holes


Accura 2550CMZ-3P4W module can be fixed to the panel using the mounting plate.

Fig 2.69 Mounting the Module on the Panel through Mounting Holes

Applied Model
Accura 2550CMZ-3P4W-250A-145
TM-CMZ-BC-3P4W-140

Page 98 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Installation of Accura 2550CM[Z]-1P

① Place the mounting plate on the location where you want to install the device.
② Tighten screws on the mounting plate diagonally.
③ Attach Accura 2550CM[Z]-1P module to the mounting plate .
④ Connect the single-phase terminal block with Accura 2550CM[Z]-1P module.
⑤ Fix the single-phase terminal block.
⑥ Connect the busbar with the MCCB.
⑦ Attach the cover to the terminal block.

Fig 2.70 Mounting Accura 2550CM-1P Module on the Panel

A tolerance of 0.5 mm
between devices is required.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 99


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2550CM-1P Module through Mounting Holes


Accura 2550CM-1P module can be fixed to the panel using the mounting plate.

Fig 2.71 Mounting the Module on the Panel through Mounting Holes (Mounting Plate/Terminal Block)

Applied Model
Accura 2550CM-1P-250A
TM-CM-1P-105

Applied Model
Accura 2550CM-1P-125A
TM-CM-1P-60

Page 100 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Applied Model
Accura 2550CM-1P-100A
TM-CM-1P-50L

Applied Model
Accura 2550CM-1P-60A
TM-CM-1P-50

ⓒ 2019 Rootech Inc. All Rights Reserved Page 101


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2550CMZ-1P Module through Mounting Holes


Accura 2550CMZ-1P module can be fixed to the panel using the mounting plate.

Fig 2.72 Mounting the Module on the Panel through Mounting Holes with the Terminal Block

Applied Model
Accura 2550CMZ-1P-250A
TM-CMZ-1P-105

Applied Model
Accura 2550CMZ-1P-125A
TM-CMZ-1P-60

Page 102 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Applied Model
Accura 2550CMZ-1P-100A
TM-CMZ-1P-50L

Applied Model
Accura 2550CMZ-1P-60A
TM-CMZ-1P-50

ⓒ 2019 Rootech Inc. All Rights Reserved Page 103


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2550CMS/ZM on the Panel

① Place the Accura 2550ZM’s mounting wings on the location where you want to install the device.
② Tighten screws on the mounting plate diagonally.
③ Place the Accura 2550CMS’s mounting wings on the location where you want to install the device.
④ Tighten screws on the mounting plate diagonally, and then connect Accura 2550CMS modules to
Accura 2550ZM modules using communication cables.
⑤ Connect the Accura 2550CMS and Accura 2550ZM using a communication cable.

Fig 2.73 Mounting Accura 2550CMS/ZM Modules on the Panel

* A clearance of 30 mm is required for


cable installation.

Page 104 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Installation of Accura 2550CMS/ZM-3P4W Module through Mounting Holes


Accura 2550CMS/ZM-3P4W modules can be fixed to the panel using mounting wings.

Fig 2.74 Mounting the Modules on the Panel through Mounting Holes (Mounting Wings)

Applied Model
Accura 2550CMS-3P4W-60A
Accura 2550ZM-3P4W-60A-DI

* A clearance of 30 mm is
required for cable installation.

Installation of Accura 2550CMS/ZM-1P3F Module through Mounting Holes


Accura 2550CMS/ZM-1P3F modules can be fixed to the panel using mounting wings.

Fig 2.75 Mounting the Modules on the Panel through Mounting Holes (Mounting Wings)

Applied Model
Accura 2550CMS-1P3F-60A
Accura 2550ZM-1P3F-60A-DI

* A clearance of 30 mm is
required for cable installation.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 105


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Installation of Accura 2550CMS/ZM-1P2F Module through Mounting Holes


Accura 2550CMS/ZM-1P2F modules can be fixed to the panel using mounting wings.

Fig 2.76 Mounting the Modules on the Panel through Mounting Holes (Mounting Wings)

Applied Model
Accura 2550CMS-1P2F-60A
Accura 2550ZM-1P2F-60A-DI

* A clearance of 30 mm is
required for cable installation.

Page 106 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Installation of Accura 2550CMM[Z] on the Panel

Installing the Module with the Standard Mounting Plate


① Place the mounting plate on the location where you want to install the device.
② Tighten screws on the mounting plate diagonally.
③ Attach the Accura 2550CMM[Z]-3P module to the mounting plate.

Installing the Module with the DIN Rail Mounting Plate


① Insert the DIN rail mounting plate into the mounting groove on the left side of the DIN rail.
② Insert the DIN rail mounting plate into the mounting groove on the right side of the DIN rail.
③ Attach the Accura 2550CMM module to the DIN rail mounting plate.

Fig 2.77 Mounting Accura 2550CMM Modules on the Panel

Installing the Module with


the Standard Mounting Plate

Installing the Module with


the DIN Rail Mounting Plate

ⓒ 2019 Rootech Inc. All Rights Reserved Page 107


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Fig 2.78 Mounting Accura 2550CMMZ Modules on the Panel

* A clearance of 30 mm is required for


cable installation.

Page 108 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Installation of Accura 2550CMM Module through Mounting Holes


Accura 2550CMM-3P module can be fixed to the panel using the standard mounting plate or DIN rail
mounting plate.

Fig 2.79 Mounting the Module on the Panel through Mounting Holes

Applied Model
Accura 2550CMM-3P-60A

Accura 2550CMMZ Module through Mounting Holes


Accura 2550CMMZ-3P module can be fixed to the panel using the standard mounting plate.

Fig 2.80 Mounting the Accura 2550CMMZ-3P-60A Module on the Panel through Mounting Holes

Applied Model
Accura 2550CMMZ-3P-60A

* A clearance of 30 mm is
required for cable installation.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 109


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Step 2: Wiring Accura 2500M Module


Voltage Wiring of Accura 2500M
Fig 2.81 Voltage Wiring of Accura 2500M

Voltage Input
Item Description
Port name V1, V2, V3, VN
Connector type Terminal block 1 (M4/bolt head Ø7)
Wire specification 0.75 – 6.0 mm2 (18 – 10 AWG), copper
Wire temperature rating Above 70 ˚C
Measuring range (accuracy guaranteed)
2 AC 35 – 347 V L-N (Line-to-neutral)
AC 60 – 600 V L-L (for unearthed Delta & Y systems)
Measurement accuracy IEC 61557-12 Class 0.5 ±0.5 % Reading
Minimum measured value 5 V Line-to-neutral
Frequency range 42 – 65 Hz
Voltage wiring method 3P4W, 3P3W, 1P3W, 1P2W
Burden 0.01 VA/phase @ 220 V
Withstand voltage AC 3,000 V RMS, 60 Hz for 1 minute
Impedance 10 MΩ/phase
Measurement category Category Ⅲ
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.8 Nm(18.4 kgf-cm, 16 lbf-in).
2. It indicates the input voltage range of the device. Thus, when a PT is used externally, primary voltage is calculated by
multiplying it by the PT ratio.

Note
If the voltage input gets out of the measurement range, it can affect accuracy. External PTs(Potential
Transformer) should be used when measuring voltages greater than voltage input specifications.

Caution
When installing fuses on the power line, it is recommended to use fuses that are UL-listed with an RK5
class or higher and are rated at 2 A/500 V. In case of using external PTs, a fuse should be installed at the
PT secondary.

Page 110 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Wiring Considerations

Caution
Failure to observe the following instructions may result in severe injury or death.

◼ During normal operation of Accura 2500, hazardous voltages are present on its terminal strips that
connect the PT(Potential Transformer), voltage input, power, and external I/O circuits. The secondary of
the PT may generate fatal voltages/currents resulting from the primary of the PT.
◼ Standard safety precautions should be followed while installing or maintaining the product, including
removing PT fuses.
◼ Install the product in a panelboard to prevent users from accessing terminal strips after completing
wiring of the product.

Caution
Observe the following instructions, or permanent damage may occur to the product.

◼ Do not apply voltages and currents that exceed the input ratings of the PT to the product.
◼ Using the device for purposes not specified by the manufacturer can cause severe damage to the
product.
◼ Connect the ground terminal to the earth ground to protect the device from noise and surge. Failure
to properly connect the chassis ground will void the warranty of the product.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 111


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

3P4W Connection
Set the voltage wiring mode to 3P4W. If the voltage value is within the measuring range, it allows for direct
wiring without the need for a PT.

Fig 2.82 3P4W Connection with 3 PTs

3P3W Connection
Set the voltage wiring mode to 3P3W. If the voltage value is within the measuring range, it allows for direct
wiring without the need for a PT.

Fig 2.83 3P3W Connection with 2 PTs

Page 112 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

1P3W Connection
Set the voltage wiring mode to 1P3W. The L1 and L2 line voltages should be connected to the V1 and V3
ports, and the N line should be connected to the VN port. If the voltage value is within the measuring range,
it allows for direct wiring without the need for a PT.
Fig 2.84 1P3W Connection with 2 PTs

1P2W Connection
Set the voltage wiring mode to 1P2W. The L1 line voltage should be connected to the V1 port, and the N
line should be connected to the VN port. If the voltage value is within the measuring range, it allows for
direct wiring without the need for a PT.
Fig 2.85 1P2W Connection with 1 PT

ⓒ 2019 Rootech Inc. All Rights Reserved Page 113


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Power Supply/Ground Wiring

Wiring of Accura 2500M-AC220V/DC110V

Fig 2.86 Accura 2500M Power Supply/Ground Wiring of Accura 2500M-AC220V/DC110V

Item Description
Port name L+, N-, (Ground)
Connector type Terminal block 1 (M3.5/bolt head Ø6)
Wire specification 0.34 – 4.0 mm2 (22 – 12 AWG), copper
Wire temperature rating Above 70 ˚C
Power supply voltage (Us) 2
AC 100 – 240 V 50/60 Hz, DC 100 – 300 V, CAT II
Operating voltage range 0.9 x Us – 1.1 x Us
Power consumption 3
Maximum 20 W
Inrush current 4 Peak 31 A, duration : no more than 1 msec (AC 220 V)
Peak 11 A, duration : no more than 0.2 msec (DC 110 V)
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.4 Nm(14 kgf-cm, 12 lbf-in).
2. The device conforms to UL standards for the tested AC power supply voltage.
3. It refers to the maximum power consumption based on the power supply input voltage when Accura 2500D is
connected with Accura 2550 modules.
4. When installing fuses on the power line, it is recommended to use fuses that are UL-listed with an RK5 class or
higher and are rated at 2 A/500 V.

Note
The ground terminal of Accura 2500M is connected to the earth ground of the panel.

Page 114 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Wiring of Accura 2500M-DC24V

Fig 2.87 Accura 2500M Power Supply/Ground Wiring of Accura 2500M-DC24V

Item Description
Port name L+, N-, (Ground)
Connector type Terminal block 1 (M4.0/bolt head Ø7)
Wire specification 0.75 – 6.0 mm2 (18 – 10 AWG), copper
Wire temperature rating Above 70 ˚C
Power supply voltage (Us) DC 24 V, CAT II
Operating voltage range DC 20 – 30 V
Power consumption 2 Maximum 20 W
Inrush current 3
Peak 6 A, duration : no more than 1 msec (DC 24 V)
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.2 Nm(12 kgf-cm, 10.6 lbf-in).
2. It refers to the maximum power consumption based on the power supply input voltage when Accura 2500D is
connected with Accura 2550 modules.
3. When installing fuses on the power line, it is recommended to use fuses that are UL-listed with an RK5 class or
higher and are rated at 2 A/500 V.

Note
The ground terminal of Accura 2500M is connected to the earth ground of the panel.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 115


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Step 3: Connecting Accura 2500M to Accura 2500D via the


Communication Cable
When attaching Accura 2500M to the back of Accura 2500D, there is no need to follow Step 3 as the
modules are directly connected. When separately installing Accura 2500M in the panel, it should be
connected with Accura 2500D using a communication cable. The internal communication cable for the
display module is connected to the DISPLAY port of Accura 2500M. Accura 2500M supplies power to Accura
2500D via the internal communication cable for the display module.

Fig 2.88 DISPLAY Port on Accura 2500M

Fig 2.89 Accura 2500D Rear

Page 116 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Item Description
Port name Accura 2500M DISPLAY
Accura 2500D DISPLAY
Communication cable Internal communication cable for the display module 1 (Cat 5e 24 AWG FTP)
Protocol Internal protocol
Communication cable length Up to 3 m
Power supply Supplies power via the communication cable
1. It is provided with the product.

Fig 2.90 Connecting Accura 2500M to Accura 2500D Using the Communication Cable

ⓒ 2019 Rootech Inc. All Rights Reserved Page 117


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Step 4: Through-Hole Wiring of Accura 2550CM[Z]/CMS/


CMM[Z] Modules
Item Description
Connector type Through-hole type (using the cable/busbar)
Wire specification Varies by hole size
Measuring range Model Minimum
Basic Measuring Range
Measured
Current(Ib) (Accuracy Guaranteed)
Value
Three-phase Accura 2550CM-3P -800A-210 800 A 16.0 A − 960 A 0.80 A
modules -800A-210-ZCT 800 A 16.0 A − 960 A 0.80 A
-630A-145 630 A 12.6 A − 756 A 0.63 A
-630A-145-ZCT 630 A 12.6 A − 756 A 0.63 A
-400A-140 400 A 8.0 A − 480 A 0.40 A
-400A-140-ZCT 400 A 8.0 A − 480 A 0.40 A
Accura 2550CMZ-3P -800A-220 800 A 16.0 A − 960 A 0.80 A
-630A-155 630 A 12.6 A − 756 A 0.63 A
-400A-155 400 A 8.0 A − 480 A 0.40 A
Accura 2550CM[Z]-3P -250A 250 A 5.0 A − 300 A 0.25 A
-125A 125 A 2.5 A − 150 A 0.13 A
-100A 100 A 2.0 A − 120 A 0.10 A
-60A 60 A 1.2 A − 72 A 0.06 A
Accura 2550CM-3P -5A 1 5A 0.1 A − 6A 0.01 A
-5A-ZCT 1
5A 0.1 A − 6A 0.01 A
Three-phase Accura 2550CMZ-3P4W -250A-145 250 A 5.0 A − 300 A 0.25 A
4-wire module
Single-phase Accura 2550CM[Z]-1P -250A 250 A 5.0 A − 300 A 0.25 A
modules -125A 125 A 2.5 A − 150 A 0.13 A
-100A 100 A 2.0 A − 120 A 0.10 A
-60A 60 A 1.2 A − 72 A 0.06 A
Split-core 2 Accura -3P4W -60A 60 A 3.0 A − 72 A 0.24 A
modules 2550CMS -1P3F -60A 60 A 3.0 A − 72 A 0.24 A
-1P2F -60A 60 A 3.0 A − 72 A 0.24 A
Three-phase Accura -3P -60A 60 A 1.2 A − 72 A 0.06 A
modules for 2550CMM
MCBs Accura -3P -60A 60 A 1.2 A − 72 A 0.06 A
2550CMMZ
Current measurement accuracy 3 IEC 61557-12 Class 0.5 ±0.5 % Reading

Page 118 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Leakage Fundamental current CM-3P-800A/630A/400A/5A-ZCT 5 ±2 % Reading ± 2 mA


current measurement accuracy CMZ-3P-800A ±0.5 % Reading ± 60 mA
measurement CMZ-3P-630A/400A/250A ±0.5 % Reading ± 30 mA
accuracy CMZ-3P4W-250A
CMZ-1P-250A
CMZ-3P-125A/100A/60A ±0.5 % Reading ± 20 mA
CMZ-1P-125A/100A/60A
CMS-3P4W-60A/ZM-3P4W-60A ±0.5 % Reading ± 10 mA
CMS-1P3F-60A/ZM-1P3F-60A ±0.5 % Reading ± 5 mA
CMS-1P2F-60A/ZM-1P2F-60A ±0.5 % Reading ± 5 mA
Measuring range 1 mA − 2 A
Active power measurement accuracy 3 IEC 61557-12 Class 0.5
Active energy measurement accuracy 3 IEC 62053-21 Class 0.5
Impedance Not applicable since the model is a through-hole type device
Frequency range 42 – 65 Hz
Hole dimensions Model Hole Dimensions Weight [g]
/ Weight [mm] CM/CMZ
Three-phase Accura 2550CM-3P -800A-210 46.0 x 23.0 1,500 /-
modules -800A-210-ZCT 46.0 x 23.0 1,500 /-
-630A-145 32.0 x 22.4 1,000 /-
-630A-145-ZCT 32.0 x 22.4 1,000 /-
-400A-140 32.0 x 22.4 1,000 /-
-400A-140-ZCT 32.0 x 22.4 1,000 /-
Accura 2550CMZ-3P -800A-220 46.0 x 22.9 - / 2,500
-630A-155 35.0 x 25.4 - / 1,500
-400A-155 35.0 x 25.4 - / 1,500
Accura 2550CM[Z]-3P -250A Ø 21.0 x 22.0 140 / 300
-125A Ø 16.5 x 20.5 130 / 235
-100A Ø 13.5 x 17.5 115 / 175
-60A Ø 13.5 x 17.5 115 / 175
Accura 2550CM-3P -5A 1 Ø 10.0 155 /-

-5A-ZCT 1 Ø 10.0 155 /-

Three-phase Accura 2550CMZ- -250A-145 Ø 21.0 x 22.0 - / 330


4-wire 3P4W
modules
Single-phase Accura 2550CM[Z]-1P -250A Ø 21.0 x 22.0 125 / 270
modules -125A Ø 16.5 x 20.5 85 / 155
-100A Ø 13.5 x 17.5 80 / 125
-60A Ø 13.5 x 17.5 80 / 125

ⓒ 2019 Rootech Inc. All Rights Reserved Page 119


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Split-core Accura -3P4W -60A 10.4 x 20.3 430


modules 2550CMS -1P3F -60A 10.4 x 20.3 430
-1P2F -60A 10.4 x 20.3 350
Leakage Accura -3P4W -60A-DI 70.0 x 20.5 210
current 2550ZM
measuring -1P3F -60A-DI Ø 21.0 330
modules -1P2F -60A-DI Ø 21.0 230
Three-phase Accura -3P -60A Ø 10.4 / Ø 5.9 100
module for 2550CMM 4

MCBs
Accura -3P -60A Ø 10.5 150
2550CMMZ

1. Accura 2550CM-3P-5A module can be used by externally installing CTs (the secondary current rating: 5 A).
2. The split-core module refers to the split-core CMS module whose core part is separated vertically.
3. The split-core CMS module has been calibrated under the condition where the power line passes through the top
center position of its hole. As the location of the power line is away from the top center position of the hole, errors in
current, power, and energy measurements can increase by up to 1 %.
4. Install the module by passing the Hot line through its main hole(Ø 10.4) and passing the Neutral line through its
subhole(Ø 5.9).
5. It is only supported in Accura 2550CM-3P module, which can connect to an external ZCT. And It indicates the
measurement accuracy when the measurement error of an external ZCT is zero.

Caution
It is recommended you should use CTT terminal blocks in order to prevent accidents caused by current
transformers and identify device failures in advance. If current is flowing in the primary winding of a CT,
opening the CT secondary can cause serious accidents resulting from high voltages.

Page 120 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CM[Z]-3P

The phase sequence in which the current passes through the cable can be set to A-B-C or C-B-A, and the
direction of current flow to the load can be set to ▶ or ◀.

Fig 2.91 3P4W/3P3W Through-Hole Wiring

Applied Model
Three-phase power measuring module
Accura 2550CM-3P-800A-210
Accura 2550CM-3P-800A-210-ZCT
Accura 2550CM-3P-630A-145
Accura 2550CM-3P-630A-145-ZCT
Accura 2550CM-3P-400A-140
Accura 2550CM-3P-400A-140-ZCT
Accura 2550CM-3P-250A
Accura 2550CM-3P-125A
Accura 2550CM-3P-100A
Accura 2550CM-3P-60A

Fig 2.92 3P3W Through-Hole Wiring

Applied Model
Three-phase power/leakage current measuring module
Accura 2550CMZ-3P-800A-220
Accura 2550CMZ-3P-630A-155
Accura 2550CMZ-3P-400A-155
Accura 2550CMZ-3P-250A
Accura 2550CMZ-3P-125A
Accura 2550CMZ-3P-100A
Accura 2550CMZ-3P-60A

ⓒ 2019 Rootech Inc. All Rights Reserved Page 121


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Fig 2.93 3P4W/3P3W Through-Hole Wiring with 3CTs

Applied Module
Three-phase power measuring module
Accura 2550CM-3P-5A 1

Accura 2550CM-3P-5A-ZCT 1, 2

1. Accura 2550CM-3P-5A module can be used by externally installing CTs (the secondary current rating: 5 A).
2. Accura 2550CM-3P, which can connect an external ZCT, module measures leakage current by connecting an
externally installed voltage-type ZCT to its ZCT connection port. The user must purchase the ZCT separately from
the ZCT manufacturer.

Fig 2.94 3P3W Through-Hole Wiring with 2 CTs

Applied Model
Three-phase power measuring module
Accura 2550CM-3P-5A 1

Accura 2550CM-3P-5A-ZCT 1, 2

1. Accura 2550CM-3P-5A module can be used by externally installing CTs (the secondary current rating: 5 A).
2. Accura 2550CM-3P, which can connect an external ZCT, module measures leakage current by connecting an externally
installed voltage-type ZCT to its ZCT connection port. The user must purchase the ZCT separately from the ZCT
manufacturer.

Page 122 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CMZ-3P4W

The phase sequence in which the current passes through the cable can be set to A-B-C or C-B-A (The N line
should pass through the fourth hole of the module), and the direction of current flow to the load can be set
to ▶ or ◀.

Fig 2.95 3P4W Through-Hole Wiring

Applied Model
Three-phase 4-wire power/leakage current
measuring module
Accura 2550CMZ-3P4W-250A-145

Caution
When wiring the CMZ-3P4W module through its holes, the N line should pass through the fourth hole at
the bottom of the module.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 123


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2550CM[Z]-1P

When wiring the module, the cable should pass through the first hole of the module because the hole has
the built-in current sensor. The phase sequence in which the current passes through the cable can be selected
among AN / BN / CN / AB / BC / CA. The direction of current flow to the load can be set to ▶ or ◀.

Fig 2.96 Single-Phase Line-to-Neutral Through-Hole Wiring (250A)

Applied Model
Single-phase power measuring module
Accura 2550CM[Z]-1P-250A
(The cable does not pass through the hole located
in the middle of the device.)

Fig 2.97 Single-Phase Line-to-Neutral Through-Hole Wiring

Applied Model
Single-phase power/leakage current
measuring module
Accura 2550CM[Z]-1P-125A
Accura 2550CM[Z]-1P-100A
Accura 2550CM[Z]-1P-60A

Page 124 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CMS/ZM-3P4W

The split-core CMS-3P4W module senses three-phase current to measure the power of three-phase 4-wire
feeders. The ZM-3P4W module connected to the CMS-3P4W module via communication cables measures
the leakage current of three-phase 4-wire feeders using its built-in ZCT. It is also equipped with digital input
terminals for receiving data on the On/Off/trip status of the MCCB.
The phase sequence in which the current passes through the cable can be set to A-B-C or C-B-A(The N line
should pass through the fourth hole of the module), and the direction of current flow to the load can be set
to ▶ or ◀.

Fig 2.98 Split-Core 3P4W Power/Leakage Current Measuring Module

Applied Model
Split-core 3P4W power/leakage current
measuring module
Accura 2550CMS-3P4W-60A
Accura 2550ZM-3P4W-60A-DI

* Through-hole wiring of ZM-3P4W module:


To ensure accurate measurements of
leakage current when wiring the 3P4W
module, you should put together all four
power lines and make them pass through
the center of its hole.

Caution
When wiring the CMS-3P4W module through its holes, the N line should pass through the fourth hole
at the bottom of the module.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 125


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2550CMS/ZM-1P3F

The split-core CMS-1P3F module senses the current of three single-phase feeders and measures the power
of each of the three feeders separately. The ZM-1P3F module connected to the CMS-1P3F module via
communication cables measures the leakage current of three single-phase feeders individually using its three
built-in ZCTs. It is also equipped with digital input terminals for each feeder for receiving data on the
On/Off/trip status of each MCCB.
The phase sequence in which the current passes through the cable can be set to AN / BN / CN / AB / BC /
CA, and the direction of current flow to the load can be set to ▶ or ◀.

Fig 2.99 Split-Core 1P3F Power/Leakage Current Measuring Module

Applied Model
Split-core 1P3F power/leakage current
measuring module
Accura 2550CMS-1P3F-60A
Accura 2550ZM-1P3F-60A-DI

Page 126 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Accura 2550CMS/ZM-1P2F

The split-core CMS-1P2F module senses the current of two single-phase feeders and measures the power
of each of the two feeders separately. The ZM-1P2F module connected to the CMS-1P2F module via
communication cables measures the leakage current of the two single-phase feeders individually using its
two built-in ZCTs. It is also equipped with digital input terminals for each feeder for receiving data on the
On/Off/trip status of each MCCB.
The phase sequence in which the current passes through the cable can be set to AN / BN / CN / AB / BC /
CA, and the direction of current flow to the load can be set to ▶ or ◀.

Fig 2.100 Split-Core 1P2F Power/Leakage Current Measuring Module

Applied Model
Split-core 1P2F power/leakage current
measuring module
Accura 2550CMS-1P2F-60A
Accura 2550ZM-1P2F-60A-DI

ⓒ 2019 Rootech Inc. All Rights Reserved Page 127


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Accura 2550CMM-3P-60A
The phase sequence in which the current passes through the cable can be set to A-B-C or C-B-A, and the
direction of current flow to the load can be set to ▶ or ◀.

Fig 2.101 Three-Phase Power Measuring Module for MCBs

Applied Model
Three-phase power measuring module
for MCBs
Accura 2550CMM-3P-60A

Accura 2550CMMZ-3P-60A

The phase sequence in which the current passes through the cable can be set to A-B-C or C-B-A, and the
direction of current flow to the load can be set to ▶ or ◀.

Fig 2.102 Three-Phase Power/Leakage Current Measuring Module for MCBs

Applied Model
Three-phase power/leakage current
measuring module for MCBs
Accura 2550CMMZ-3P-60A

Page 128 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Step 5: Connecting Accura 2550CM-3P with External ZCTs


Accura 2550CM-3P, which can connect an external ZCT, module measures leakage current by connecting
an externally installed voltage-type ZCT to its ZCT connection port. The user must purchase the ZCT
separately from the ZCT manufacturer.
.

① Install a voltage-type ZCT outside the module


② Connect the cable for connection with the ZCT 1 to the ports of the external ZCT.
③ Connect the cable for connection with the ZCT to the ZCT input port at the side of the Accura
2550CM-3P module.
1. It is provided when you select the ZCT connection option when ordering the product.

Item Description
Leakage current input External voltage-output ZCT 200 mA/100 mV @1.2 kΩ burden
Measurement accuracy /range
1 ±2 % Reading + 2 mA Up to 2 A
1. It is the accuracy when the measurement error of the external ZCT is zero.

Fig 2.103 Connecting the Cable for Connection with the ZCT to the External ZCT

ZCT connection port

Fig 2.104 Connecting Accura 2550CM-3P Module with the External ZCT

Accura 2550

ⓒ 2019 Rootech Inc. All Rights Reserved Page 129


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Step 6: Connecting Accura 2500M to Accura 2550 Modules


Accura 2500M communicates with multiple Accura 2550 modules through communication cables and
sends/receives measurement data to/from Accura 2550 modules. For communication redundancy, Accura
2500M supports a ring(daisy-chain) topology with Accura 2550 modules using two ports. Ports in the Group
1 include RJ45-1/RJ45-2 ports, while ports in the Group 2 include RJ45-3/RJ45-4 ports. Modules should be
connected in a ring topology by using two ports in the same group.
Accura 2500M can be connected to up to 30 Accura 2550 modules in a group. The number of connectable
modules varies by module type since the power consumption of each module is different. If modules cannot
be connected in a single group, you should connect modules with ports in both groups.

Note
Check connectivity of modules in advance by referring to 「Appendix B Module Connection」 due to
limitations in the length of the communication cable and the number of connectable modules according
to the power consumption of modules.

Page 130 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Fig 2.105 Connecting Accura 2500M to Accura 2550CM Using Internal Communication Cables

Number of connectable modules Maximum 30 1

in a group
Number of connectable modules Maximum 40
in two groups
Cable length in each group Total length: up to 50 m
(Each cable: up to 10 m)

Installation
Front panel Accura 2500M Industrial control panel digital
power meter
Incoming line Accura 2550CM-3P-5A Three-phase power measuring
module Ring topology
Branch line Accura 2550CM-3P Three-phase power measuring
module
Accura 2550CM-1P Single-phase power measuring
module
Internal Internal cable Internal communication cable 2

communication

1. The number of modules that can be connected varies by module type. Refer to 「Appendix B Module Connection」
for details on module connection.
2. It is provided with the product. Additional cables needed for a ring topology are sold separately. The conducting wire
of the communication cable should be at least 0.205 mm2 (24 AWG). It is recommended to keep a distance of
over 5 mm from power lines generating high levels of noise.

Connection for Internal Communication


Number of connectable Accura 2550 modules 1
In a group Maximum 30

In two groups Maximum 40


Cable length in each group Total cable length: up to 50 m / Each cable: up to 10 m
Connector type RJ45
Dedicated Accura 2500M Group 1 (RJ45-1, RJ45-2), Group 2 (RJ45-3, RJ45-4)
communication ports Accura 2550 2 ports (RJ45A, RJ45B) 2

1. It varies by module type. Refer to 「Appendix B Module Connection」 for details on module connection.
2. The RJ45A and RJ45B ports have the same function.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 131


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

Step 7: Connecting Accura 2500M Modules for External


Communication

Ethernet Communication

Accura 2500M supports communication with the host system using Ethernet cables for high-speed
transmission of large-capacity measurement data received from multiple Accura 2550 modules. The built-in
Ethernet switch of Accura 2500M enables Ethernet connectivity between Accura 2500M modules using two
Ethernet ports, without the need for a separate external switch. Up to 20 Accura 2500M modules can be
connected in star, daisy chain, and ring topologies. It supports Modbus TCP, the standard protocol for
transmission of measurement data.
Since Accura 2500M supports RSTP(Rapid Spanning Tree Protocol), devices can be connected in a ring
topology. Thus, even if one end of the line is disconnected in a ring topology, communication can be
resumed in the other end of the line within a short period of time, minimizing data loss.

Note
When wiring devices in a ring topology, use the Ethernet switch supporting the RSTP(Rapid Spanning Tree
Protocol) for quick recovery from communication failures, and the switch should be used as the main route
for communication.

Fig 2.106 Ethernet Ports on Accura 2500M

Page 132 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 2 Installation

Two Ethernet Ports


Item Description
Port name ETHERNET1, ETHERNET2
Connector type RJ45 connector
Communication cable Ethernet cable Cat 5e FTP, STP, SFTP 1

Protocol Modbus TCP


Cable type 100Base-TX (100 Mbps/Full Duplex)
Function Ethernet switching 2, RSTP 3

Supports communication redundancy via a ring topology


Wiring method Star, daisy-chain, ring topology
1. FTP(Foiled Shielded Twisted Pairs), STP(Braided Shielded Twisted Pairs), SFTP(Braided Foiled Shielded Twisted Pairs)
2. The built-in Ethernet switch allows for daisy-chain Ethernet connections between Accura 2500M modules without
the need for a separate external switch.
3. RSTP(Rapid Spanning Tree Protocol), IEEE 802.1D-2004

Fig 2.107 Connecting Accura 2500M Modules via Ethernet Communication

When wiring devices in a ring topology, use


the Ethernet cable supporting RSTP, and the
switch should be used as the main route for
communication. Ethernet cable length:
up to 100 m

Up to 20 Accura 2500M modules can be connected in a daisy chain.

Note
Accura 2500 provides a lower bridge priority value of 49152(C000h) instead of a default bridge priority
value of 32768(8000h). If the bridge priority value of a switch is configured as 32768(8000h), the switch
has a higher priority over Accura 2500.

Caution
At sites where industrial control panels are installed, a large number of electromagnetic waves are emitted
due to multiple power cables. This can have a serious impact on Ethernet communication quality.
Therefore, you should use shielded cables.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 133


Chapter 2 Installation Accura 2500/2550 User Guide [AC]

RS-485 Communication

Fig 2.108 RS-485 Port on Accura 2500M

One RS-485 Port


Item Description
Port name Ta(TRX+), Tb(TRX-)
Connector type Terminal block 1 (M3.5/bolt head Ø6) Accura 2500M-AC220V/DC110V
Terminal block (M4.0/bolt head Ø7)
2 Accura 2500M-DC24V
Protocol Modbus RTU
Communication cable UL2919 RS-485 1P/2P 24AWG, Shielded twisted pairs
Communication cable length Up to 1,219 m (4,000 ft)
Bit rate 1,200/ 2,400/ 4,800/ 9,600/ 19,200/ 38,400/ 57,600/ 115,200 3 bps
Maximum number of connectable 32 for each bus 3
modules
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.4 Nm (14 kgf-cm, 12 lbf-in).
2. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.2 Nm (12 kgf-cm, 10.6 lbf-in).
3. At 115,200 bps, a master can communicate with up to 16 slave devices, and the maximum distance between
the master and the slave is 600 m.
Fig 2.109 Connecting Accura 2500M Modules via RS-485 Communication

* To minimize noise caused by ground loops,


a shielded cable should be grounded at
only one end.

Page 134 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

Chapter 3 Accura 2500M


Accura 2500M, the main industrial control panel module, is installed at the incoming line of the industrial
control panel and performs the major function of the smart industrial control panel digital power meter. It
sends the sampled voltage data obtained by sensing the voltage of the incoming line of the industrial
control panel to all Accura 2550 modules connected with internal communication cables. It enables to
measure power of individual branch lines. In addition, it collects the measurement data of the power
measuring module on the branch line using the internal communication cables. Measurement data is sent
to Accura 2500D module, enabling users to check the operational status of the entire industrial control panel
in front of the panel. Accura 2500M is also connected to the host system via external communication using
Ethernet or RS-485 cables.

Device Composition
Fig 3.1 Device Composition of Accura 2500M

ⓒ 2019 Rootech Inc. All Rights Reserved Page 135


Chapter 3 Accura 2500M Accura 2500/2550 User Guide [AC]

Power Supply

Accura 2500M uses power supply generated by receiving AC or DC power. It supplies power to Accura
2500D using the built-in connector or communication cable.

Accura 2500M-AC220V/DC110V Power Supply

Fig 3.2 Accura 2500M-AC220V/DC110V Power Supply

Item Description
Port name L+, N-, (Ground)
Connector type Terminal block 1 (M3.5/bolt head Ø6)
Wire specification 0.34 – 4.0 mm2 (22 – 12 AWG), copper
Wire temperature rating Above 70 ˚C
Power supply voltage (Us) 2
AC 100 – 240 V 50/60 Hz, DC 100 – 300 V, CAT II
Operating voltage range 0.9 x Us – 1.1 x Us
Power consumption 3 Maximum 20 W
Inrush current 4 Peak 31 A, duration : no more than 1 msec (AC 220 V)
Peak 11 A, duration : no more than 200 μsec (DC 110 V)
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.4 Nm (14 kgf-cm, 12 lbf-in).
2. The device conforms to UL standards for the tested AC power supply voltage.
3. It refers to the maximum power consumption based on the power supply input voltage when Accura 2500D is
connected with Accura 2550 modules.
4. When installing fuses on the power line, it is recommended to use fuses that are UL-listed with an RK5 class or
higher and are rated at 2 A/500 V.

Page 136 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

Accura 2500M-DC24V Power Supply

Fig 3.3 Accura 2500M-DC24V Power Supply

Item Description
Port name L+, N-, (Ground)
Connector type Terminal block 1 (M4.0/bolt head Ø7)
Wire specification 0.75 – 6.0 mm2 (18 – 10 AWG), copper
Wire temperature rating Above 70 ˚C
Power supply voltage (Us) DC 24 V, CAT II
Operating voltage range DC 20 – 30 V
Power consumption 2
Maximum 20 W
Inrush current 3 Peak 6 A, duration : no more than 1 msec (DC 24 V)
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.2 Nm (12 kgf-cm, 10.6 lbf-in).
2. It refers to the maximum power consumption based on the power supply input voltage when Accura 2500D is
connected with Accura 2550 modules.
3. When installing fuses on the power line, it is recommended to use fuses that are UL-listed with an RK5 class or
higher and are rated at 2 A/500 V.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 137


Chapter 3 Accura 2500M Accura 2500/2550 User Guide [AC]

Voltage Terminal Block

Fig 3.4 Voltage Wiring of Accura 2500M

Item Description
Port name V1, V2, V3, VN
Connector type Terminal block 1 (M4/bolt head Ø7)
Wire specification 0.75 – 6.0 mm2 (18 – 10 AWG), copper
Wire temperature rating Above 70 ˚C
Withstand voltage AC 3,000 V RMS, 60 Hz for 1 minute
Impedance 10 MΩ (V1 / V2 / V3 / VN)
Burden 0.01 VA/phase @220 V
Measurement category Category III

Voltage Measurement Description


Voltage wiring method 3P4W, 3P3W, 1P3W, 1P2W
Measuring range AC 35 – 347 V L-N (Line-to-neutral)
AC 60 – 600 V L-L (for unearthed Delta & Y systems)
Frequency 50/60 Hz
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.8 Nm(18.4 kgf-cm, 16 lbf-in).

Page 138 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

Ethernet Ports for External Communication

Accura 2500M has built-in Ethernet switches, and it enables a daisy-chain connection between Accura 2500M
modules with two Ethernet ports. It eliminates the need for an additional external switch. Ethernet connection
can be made through star, daisy-chain, ring topologies. Up to 20 Accura 2500M modules can be connected
in a daisy chain.
It supports Modbus TCP as the standard communication protocol for data transfer. The ETHERNET1 and
ETHERNET2 ports have the same function. It allows for the redundant device configuration of the host
system by connecting two host systems at the same time.

Fig 3.5 Ethernet Ports on Accura 2500M

Item Description
Port name ETHERNET1, ETHERNET2
Connector type RJ45 connector
Communication cable Ethernet cable Cat 5e FTP, STP, SFTP 1

Protocol Modbus TCP


Type 100Base-TX (100 Mbps/Full Duplex)
Function Ethernet switching 2, RSTP 3

Supports communication redundancy through a ring topology


Wiring method of the communication cable Star, daisy-chain, ring topology
1. FTP(Foiled Shielded Twisted Pairs), STP(Braided Shielded Twisted Pairs), SFTP(Braided Foiled Shielded Twisted Pairs)
2. The built-in Ethernet switches allow for daisy-chain connections between Accura 2500M modules without the need
for separate external switches.
3. RSTP(Rapid Spanning Tree Protocol), IEEE 802.1D-2004

ⓒ 2019 Rootech Inc. All Rights Reserved Page 139


Chapter 3 Accura 2500M Accura 2500/2550 User Guide [AC]

Fig 3.6 Connecting Accura 2500M Modules with Ethernet Cables for External Communication
(Daisy-Chain & Ring Topology)

Daisy-chain &
Ring topology (RSTP protocol)

Page 140 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

RS-485 Port for External Communication

Accura 2500M supports one RS-485 port for external communication.

Fig 3.7 RS-485 Port on Accura 2500M

Item Description
Port name Ta(TRX+), Tb(TRX-)
Connector type Terminal block 1 (M3.5/bolt head Ø6) Accura 2500M-AC220V/DC110V

Terminal block (M4.0/bolt head Ø7)


2
Accura 2500M-DC24V
Protocol Modbus RTU
Communication cable UL2919 RS-485 1P/2P 24 AWG, Shielded twisted pairs
Communication cable length Up to 1,219 m (4,000 ft)
Bit rate 1,200 / 2,400/ 4,800 / 9,600/ 19,200 / 38,400 / 57,600 / 115,200 3 bps
Maximum number of 32 for each bus 3

connectable modules
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.4 Nm(14 kgf-cm, 12 lbf-in).
2. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.2 Nm(12 kgf-cm, 10.6 lbf-in).
3. At 115,200 bps, a master can communicate with up to 16 slave devices, and the maximum distance between
the master and the slave is 600 m.

Fig 3.8 Connecting Accura 2500M Modules with RS-485 Cables for External Communication

* To minimize noise caused by ground loops,


a shielded cable should be grounded at
only one end.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 141


Chapter 3 Accura 2500M Accura 2500/2550 User Guide [AC]

HMI DISPLAY Communication Port

Accura 2500M allows users to perform setup for Accura 2550 modules on Accura 2500D via internal
communication. Measured values of each module are shown on the screen of Accura 2500D module. It also
supplies power to Accura 2500D using the built-in connector or internal cable for the display module.

Fig 3.9 Combing Accura 2500M with Accura 2500D

Fig 3.10 Connecting Accura 2500M to Accura 2500D Using the Communication Cable

Item Description
Port name DISPLAY
Connector type RJ45 connector
Communication cable Internal cable for the display module 1 (Cat 5e 24 AWG FTP)
Protocol Internal protocol
Communication cable length Up to 3 m
Power supply Supplies power to Accura 2500D module using the communication cable
1. It is provided with the product.

Page 142 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

Communication Ports for Connection with Accura 2550 Modules

Accura 2500M is connected to Accura 2550 modules using two groups of RJ-45 ports (Group 1: RJ45-1/RJ45-
2, Group 2: RJ45-3/RJ45-4). Devices can be connected in a ring topology using two ports in a group, which
have the same functions. The ring topology supports communication redundancy and therefore increases
reliability of communication.
Up to 30 Accura 2550 modules can be connected in a single group. The number of modules that can be
connected varies by module type since the power consumption of each module is different. If modules
cannot be connected in a single group, they should be connected using ports in two groups.

Note
Check connectivity of modules in advance by referring to 「Appendix B Module Connection」 due to
limitations in the length of the communication cable and the number of connectable modules according
to the power consumption of modules.

Fig 3.11 Connection Example of Accura 2500 and Accura 2550 Modules

Ring Topology
(Communication Redundancy)

ⓒ 2019 Rootech Inc. All Rights Reserved Page 143


Chapter 3 Accura 2500M Accura 2500/2550 User Guide [AC]

Item Description
Port name Group 1: RJ45-1/RJ45-2, Group 2: RJ45-3/RJ45-4
(communication redundancy supported via a ring topology)
Connector type RJ45 connector
Protocol Internal protocol
Communication cable Internal communication cable 1

Maximum number of In a group 30


connectable modules 2
In two groups 40
Communication cable length The total cable length in a group : up to 50 m (each cable: up to 10 m)
1. It is provided with the product. Additional cables needed for a ring topology are sold separately. The conducting wire
of the communication cable should be at least 0.205 mm2 (24 AWG). It is recommended to keep a distance of
over 5 mm from power lines generating high levels of noise.
2. The number of modules that can be connected varies by module type. Refer to 「Appendix B Module Connection」
for details about module connection.

LED Status Indicators

The following table shows the three LED functions indicating the operational status of the main industrial
control panel module.

Item Color Description


POWER Green It is turned on when control power supply operates properly.
DEVICE Green It blinks when the device operates properly.
(It can be set to be turned on).
RS485 Orange It blinks when Accura 2500M module performs RS-485 communication
with Accura 2550 module. (It can be set to be turned on.)

Page 144 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

Functions

External Communication with the Host System

Accura 2500M supports two Ethernet ports and one RS-485 port for external communication with the host
system.

Measurements

Accura 2500M monitors voltage dip(sag)/swells by sensing the voltage of the incoming line in the industrial
control panel. It enables power measurement of each branch line by sending the sampled voltage data to
all Accura 2550 modules connected with the internal communication cable.
Voltage sensing supports 3P3W, 3P4W, 1P3W, and 1P2W connections. When measuring voltage greater than
the measuring range, an external PT should be used for voltage wiring. For details regarding voltage
measurement, refer to 「Chapter 6 Functions> Measurement > Voltage Wiring」.

Measurement Description
Parameters
Voltage wiring method 3P4W, 3P3W, 1P2W, 1P3W
Frequency 50/60 Hz
Sampling rate 512 samples/cycle
Measurement cycle Basic measurement Frame: 0.2 sec (12 cycles @60 Hz, 10 cycles @50 Hz)
(gapless) Dip/Swell measurement 1 1 cycle
PQ Curve measurement 1
Voltage Measuring range AC 35 – 347 V L-N (Line-to-neutral)

(Accuracy guaranteed) AC 60 – 600 V L-L (Line-to-line)

Accuracy IEC 61557-12 Class 0.5 ±0.5 % Reading


Minimum measured value 5 V Line-to-neutral
Measurement data Line-to-neutral voltage, Line-to-line voltage
Fundamental, Harmonics (up to the 50th order) 1

Vector diagram (phasor), waveforms, THD


Symmetrical components(positive-, negative-, zero-sequence
components)
Unbalance according to symmetrical components/the NEMA
standard
Residual voltage Measuring method Calculation of the sum of 3-phase line-to-neutral voltages
Measurement data RMS, fundamental voltage
Frequency Measuring range 42 – 65 Hz
1. It is calculated with line-to-line voltage in 3P3W mode and with line-to-neutral voltage in 3P4W mode.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 145


Chapter 3 Accura 2500M Accura 2500/2550 User Guide [AC]

Power Quality

Accura 2500M monitors Dip(Sag)/Swell voltages by sensing the voltage of the incoming line in industrial
control panels. It also supports power quality standards, including SEMI F47-0706, IEC 61000-4-11/34 Class
3, and ITIC Curve for power quality evaluation of voltages. For details regarding the PQ(Power Quality) curve,
refer to 「Chapter 6 Functions> Measurements > Power Quality Events」.

Item Description
Dip/Swell 1 Measured values / RMS voltage (refreshed every cycle) Threshold set by users
Threshold
PQ Curve 1 Measured values / RMS voltage (refreshed every cycle) Dip/swell threshold: 90 % /
Threshold 110 % of Vref
Curve type SEMI F47-0706, IEC 61000-4-11/34 Class 3, ITIC
Transient voltage Measured values / Differences between sampled voltage Threshold set by users
Threshold values (512 samples/cycle)
THD, voltage harmonics 1
Harmonic order Up to the 50th order

Measurement data THD, the magnitude of each harmonic


Voltage unbalance Measurement data LN voltage/ LL voltage unbalance (NEMA standard)
Zero-sequence/negative-sequence voltage unbalance
1. It is calculated with line-to-line voltage in 3P3W mode and with line-to-neutral voltage in 3P4W mode.

Events

All events that occur in Accura 2500M/2550 modules are managed by Accura 2500M module. Each event is
recorded in event logs. Events are divided into power quality, measurement, and system events.
For power quality and measurement events, the last 100 events are stored respectively. For system events,
the last 1,000 events are stored, and the event index for each event is indicated with numbers from 0 to
9,999, allowing users to check recent events with ease.
When an event occurs, the EVENT LED at the bottom left corner of Accura 2500D flashes, and the color of
the bell icon on the upper right side of the screen changes to give notifications. The number of new events
that occur also appears with the bell icon.
Once you press the EVENT button at the bottom right corner of the device or the bell icon on the screen,
you can enter the event mode, and the EVENT LED is reset. In the event mode, you can check detailed event
information by selecting individual events, and the bell icon is reset.

Page 146 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

Item Description
Power quality Dip/Swell, Type PQ Curve (SEMI F47, IEC 61000-4-11/34 Class 3, ITIC)
events 1 PQ Curve Measured value RMS data measured over 1 cycle
Transient voltage Measured value Differences between sampled voltage values
(512 samples/cycle)
Measurement Voltage connection Type Phase open/Fuse fail events 2
events events Measured value RMS data measured at 0.2 sec intervals
Time delay 1 second
Current events Measured value RMS data measured at 0.2 sec intervals
Leakage current Measured value RMS data measured at 0.2 sec intervals
events
User-defined Input data Data measured at 0.2 sec intervals, selectable among
events 3 voltage/current/power/leakage current / Etc.
Number of event 40
channels
1. It is calculated with line-to-line voltage in 3P3W mode and with line-to-neutral voltage in 3P4W mode.
2. When connected to a grounded 3P3W system, the device does not detect phase open and fuse fail events.
3. The event can be configured only via communication.

The following table shows items for measurement events provided via communication and Accura 2500D.

Event Items Start Events End Events


Start value End value Peak value 1 Duration
Power quality Dip ▣ ▣ ▣ ▣
Swell ▣ ▣ ▣ ▣
SEMI F47-0706 ▣ ▣ ▣ ▣
IEC 61000-4-11/34 Class 3 ▣ ▣ ▣ ▣
ITIC ▣ ▣ ▣ ▣
Transient voltage 2 - - ▣ -
Voltage connection Phase open 3 - - - ▣
Fuse fail 3 - - - ▣
Current ▣ ▣ ▣ ▣
Leakage current 4 ▣ ▣ ▣ ▣
User-defined 5 Voltage ▣ ▣ ▣ ▣
Current ▣ ▣ ▣ ▣
Power ▣ ▣ ▣ ▣
Leakage current 4 ▣ ▣ ▣ ▣
Etc. ▣ ▣ ▣ ▣
1. For “Over” events with values greater than the threshold, it indicates the maximum value during the event interval.
For “Under” events with values smaller than the threshold, it indicates the minimum value during the event interval.
2. The waveform data measured over one half cycle are provided as data on transient voltage events.
3. When connected to a grounded 3P3W system, the device does not detect phase open and fuse fail events.
4. The data are available with Accura 2550CMZ modules.
5. The event can be configured only via communication.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 147


Chapter 3 Accura 2500M Accura 2500/2550 User Guide [AC]

Power Quality(PQ) Events


Accura 2500M supports Dip/Swell measurement functions to assess the power quality of the supplied power.
It also supports PQ events on the PQ curve according to standards such as SEMI F47, IEC 61000-4-11/34
Class 3, and ITIC, as well as PQ events on transient voltage. It provides RMS trend data measured over 1
cycle for 0.6 seconds before and after an event occurs, allowing for power quality analysis. For transient
voltage events, it provides the waveform data measured over one half cycle at a sampling rate of 512
samples per cycle, allowing for the analysis of transient phenomena. By providing data on the last 100 events,
it also enables a comprehensive assessment of PQ events that occurred on the PQ curve graph.

Measurement Events
There are voltage connection, current, leakage current, and user-defined events in measurement events.
Voltage connection events include phase open and fuse fail events. When connected with a grounded 3P3W
system, the device does not detect phase open and fuse fail events.
Current events refer to the events on the current values measured by Accura 2550 modules, and leakage
current events refer to the events on the leakage current values measured by Accura 2550CMZ modules.
Users can set up the event detection function, threshold, and hysteresis values for the events on each module
from Accura 2500D’s screen. For user-defined events, users can configure input data and event operation
methods via communication. Up to 40 user-defined events are supported with channels ranging from 1 to
40. User-defined event data for each channel is as shown below. For details about user-defined events, refer
to 「Chapter 6 Functions> Events > Measurement Events > User-Defined Events」.

Fig 3.12 Block Diagram of User-Defined Events

System Events
System events include events on module management, communication status, and setup changes and are
recorded in event logs. When an event requiring inspection occurs, the device provides users with
notifications through the EVENT LED.

Page 148 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 3 Accura 2500M

Management of Accura 2550 Modules

Accura 2500M automatically detects the connection status of all Accura 2550 modules connected with the
internal communication cable. It can also assign a communication ID to each module. The IDs of Accura
2550 modules connected to Accura 2500M should be set to enable communication with numbers ranging
from 0 to 39, and they should not be duplicated.
Accura 2500M sends the sampled voltage data to all Accura 2550 modules connected, enabling users to
measure power at individual branch lines. With internal communication cables, Accura 2500M receives
measurement data from multiple Accura 2550 modules.

Accura 2500D HMI Interface Module

Accura 2500D shows data on Accura 2500M, as well as measurement and operational status data of multiple
2550 modules collected by Accura 2500M. It enables users to check the entire operational status of the
devices in front of the industrial control panel via Accura 2500D’s TFT Color LCD screen. Users can set all
functions of Accura 2500M and Accura 2550 on the TFT Color LCD screen with the touch functionality.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 149


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Chapter 4 Accura 2500D


Installed at the front of the industrial control panel, Accura 2500D can be combined with Accura 2500M with
its built-in connector or internal communication cable for the display module. It receives power from Accura
2500M module. It provides users with data on Accura 2500M and the measurement and operational status
of multiple Accura 2500 modules collected from Accura 2500M through the TFT Color LCD screen on the
front of Accura 2500D module. Users can set all functions of Accura 2500M and Accura 2550 modules on
the TFT Color LCD screen with the touch function.

Device Composition
The device composition of Accura 2500D is as follows.

Fig 4.1 Accura 2500D Device Composition


Front Rear

The front panel of Accura 2500D consists of a 5” TFT LCD display, 4 LEDs, and 4 buttons. Accura 2500D has
one communication port and a built-in connector located at the back. Accura 2500D can be connected to
Accura 2500M by either using its built-in connector or the internal communication cable for the display
module.

Page 150 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

LCD Display
Module LCD
Accura 2500D 5” (108.0 x 64.8 mm) Color TFT LCD (touch panel and backlight), 800 x 480 pixels

The LCD display consists of the following three operational modes.


Mode Description

HOME (Display) mode Displays measured values

SETUP mode Enables users to check setup items and change it

EVENT mode Displays data on measurement/power quality/system events

LED Status Indicators


Item Color Description
POWER Green It is turned on when the device is powered on.
EVENT Red It blinks when events on measurement, power quality, and system events
requiring inspections occur (It can be set to be turned on).
ETHERNET Orange It blinks when Accura 2500M communicates with the host system via Ethernet
connection (It can be set to be turned on).
MODULE Orange It blinks when Accura 2500M communicates with Accura 2550 via internal
communication (It can be set to be turned on).

Button Functions
Item Operation Description
HOME Press Used to move to HOME>SUMMARY measurement screen.
SETUP Press Used to move to SETUP> SUMMARY setup screen.
EVENT Press Used to move to EVENT>SUMMARY event screen.
BACK Press Used to move to the previous screen.

Communication Port
Item Description
Port name DISPLAY (1 port)
Connector type RJ45 connector
Communication cable Internal communication cable for the display module 1 (Cat 5e 24 AWG FTP)
Protocol Internal protocol
Communication cable length Up to 3 m
Power supply Receives power from Accura 2500M through the built-in connector or
communication cable
1. It is provided with the product.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 151


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Device Connection
Accura 2500D receives power from Accura 2500M through its built-in connector or internal communication
cable for the display module.

Combined Connection with Accura 2500M

Fig 4.2 Combining Accura 2500M with Accura 2500D

Connection with Accura 2500M Using the Communication Cable

Fig 4.3 Connecting to Accura 2500M Using the Communication Cable

Page 152 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

DISPLAY(HOME) Mode

Screen Composition

Top Menu Bar


There are the module selection window, AC/DC mode, and event notification window in the top menu bar.
By pressing the arrow(◀/▶) icon on the module selection window, users can select the previous(◀) or next
(▶) module. By pressing the next(▶) module button, users can move to Main module, single-phase power
measuring module, and three-phase power measuring module in sequence and can move to the module ID
with a greater number on the selected power measuring module.
Users can move to the module connection screen by pressing the middle of the module selection window.
It enables users to check the connection and operational status of all modules connected with the daisy-
chain method and move to the measurement screen of the selected module. When an event occurs, the
bell icon on the event notification window gets brightened, and the number of new events appear at the
same time. By pressing the event notification window, users can move to the relevant event screen and
check detailed event data.

Main Menu/Submenu
The main menu is located right below the top menu bar. Sub-menus for the main menu are provided on
the left in the vertical direction, allowing users to select the detail screen. Sub-menus are unavailable on the
SUMMARY measurement screen accessed by pressing the HOME button. By tapping each of six individual
sections on the measurement screen, users can directly move to the detail screen of the selected
measurement parameter and check detailed measurement data.

Measured Values
Accura 2500M/2550 perform gapless measurements of voltage and current at intervals of 0.2 seconds,
generating data for each time frame. Measured values for 1-second aggregation intervals are provided by
aggregating data from 5 consecutive frames. For details on Aggregation, refer to 「Chapter 6 Functions>
Aggregation」.

Maximum/Minimum Values
The maximum and minimum values and timestamp data for the values appear on the screen with the
Max/Min buttons on the upper right side of the device. The Max and Min values indicate the maximum
and minimum values among the measured values for each 0.2-second frame after the data have been cleared.
If the maximum and minimum values have never been updated since initialization, the timestamp data for
the values at the time of initialization are provided.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 153


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Chain View Screen

When you press the middle part of the module selection screen, you will navigate to the module connection
screen where you can check the connection status and operation status of all modules connected in the
daisy chain. From this screen, you can directly move to the measurement screen of the desired module by
pressing the desired module.

Fig 4.4 Daisy-Chained Module Screen (Normal State)

Page 154 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

When modules are connected properly and communication IDs are successfully assigned for normal
communication, users can save the modules’ connection status. If the saved status differs from the current
connection status, the screen displays the difference, enabling inspection.

Fig 4.5 Daisy-Chained Module Screen (Inspection Required)

ⓒ 2019 Rootech Inc. All Rights Reserved Page 155


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Status View Screen

When the leakage current measurement module is connected, the connection status and leakage current
measurement values of the module can be monitored through the Status View. You can directly navigate
to the leakage current measurement screen of the desired module by pressing the corresponding module
ID on the screen, and the module IDs are displayed in ascending order within the Group. If the connection
status of the leakage current measurement module is good and the communication ID is correctly assigned,
the leakage current measurement values will be displayed. The digital input status is only shown for the
CMS/ZM split-core measurement module and the CMMZ MCB three-phase power/leakage measurement
module. Additionally, the feeder name is displayed as the string set in "SETUP > SYSTEM > Description >
User-Defined Info"; if not set, it will appear blank.

Fig 4.6 Status View Screen (Normal State)

Page 156 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

If there is a problem with the connection status of the leakage current measurement module, a warning
will be displayed in other areas to facilitate inspection. At this time, the ID number of the module with the
issue will blink in red, allowing the user to immediately identify and address the problem. Additionally, if
the ZM leakage measurement module is not connected and only the CMS split-core power measurement
module is connected, the module status will not be displayed in the Status View.

Fig 4.7 Status View Screen (Fault occured)

ⓒ 2019 Rootech Inc. All Rights Reserved Page 157


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Fig 4.8 Status View Screen (No modules connected)

The table below shows the statuses displayed in the Status View. Users should review this information and
take appropriate action.

Status Indicator Status description Solution


1 DI contact ON state -
1 DI contact oFF state -
1 Fault occurred state Check DI Contact Status
ZM Mismatched Connection between CMS/ZM modules Is not proper Verify Connection Between
CMS/ZM Module
ZM Disconnected 2
ZM module is not connected contrary to the saved status Check ZM Module
Connection Status
ID Conflict 2 Module ID duplication status Reset Module ID
No modules connected No connected modules -
1. The DI input status is displayed only for the CMS/ZM split-core measurement module and the CMMZ MCB three-
phase power/leakage measurement module.
2. If both module ID duplication and ZM disconnection occur simultaneously, only “ID Conflict” will be displayed.

Page 158 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

Display

It indicates the measurement screen that appears when AC is selected as voltage type on the main module
(indicated as Main) via 「SETUP > MEASUREMENT > AC/DC > Mode」 menu.

SUMMARY Measurement Screen

Once the HOME button is pressed, the SUMMARY measurement screen of the selected module appears.
When you press measurement parameters or measured values on the screen, you can move to the detail
screen of the relevant measurement parameter. By pressing the BACK button on the bottom of the device,
you can return to the SUMMARY measurement screen. Measurement parameters unavailable in certain
modules appear as “–“.
If you activate the 「Main A2550CM Assignment」 item and set “Main A2550CM ID” on the screen via
「SETUP > DEVICE > Main CM> Main A2550CM Assignment」 menu, the voltage measurement parameters
of the main module and the current/power/energy measurement parameters of the selected Accura 2550
power measuring modules appear on the measurement screen of the main module.

Fig 4.9 SUMMARY Measurement Screen

ⓒ 2019 Rootech Inc. All Rights Reserved Page 159


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

VOLTAGE Measurement Screen


It provides detailed measured values of voltage.

Fig 4.10 Line-to-Line Voltage Measurement Screen

Submenu Description Note


RMS Voltage per phase/ average RMS voltage Line-to-line voltage / Line-to-
neutral voltage / Max/Min
values
Fundamental Voltage per phase / Average fundamental voltage Line-to-line voltage / Line-to-
neutral voltage / Max/Min
values
THD % Line-to-neutral voltage THD % Line-to-line voltage / Line-to-
neutral voltage / Max values
Frequency Frequency Max/Min values
Residual Residual voltage calculated by summing up three-phase Max/Min values
voltages (RMS/fundamental)

Page 160 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

CURRENT Measurement Screen


It provides detailed measured values of current.

Fig 4.11 Current Measurement Screen

Submenu Description Note


RMS RMS current Max/Min values
Fundamental Fundamental current Max/Min values
Demand Demand current 1 Peak demand 2

THD % Total Harmonic Distortion Max value


TDD % Total Demand Distortion Max value
Crest Factor Crest Factor Max value
K-Factor K-Factor Max value
Leakage. & Residual Leakage / Residual current (Fundamental/RMS) Max/Min values
1. Users can clear demand values of all Accura 2550 modules via the 「SETUP > CONTROL > Reset > Demand」 menu.
2. Users can clear peak demand values of all Accura 2550 modules via the 「SETUP > CONTROL > Reset > Peak
Demand」 menu.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 161


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

POWER Measurement Screen

Fig 4.12 Active Power Measurement Screen

Submenu Description Note


Active(P) Active power Max/Min values
Reactive(Q) Reactive power Max/Min values
Apparent(S) Apparent power Max/Min values
PF Power factor Max/Min values 1

Demand Demand power 2 Peak demand 3

1. They indicate the Max/Min values when the sign of the power factor is removed.
2. Users can clear demand values of all Accura 2550 modules via the 「SETUP > CONTROL > Reset > Demand」 menu.
3. Users can clear peak demand values of all Accura 2550 modules via the 「SETUP > CONTROL > Reset > Peak
Demand」 menu.

ENERGY Measurement Screen


Fig 4.13 Active Energy Measurement Screen

Submenu Description Note


Energy(P) Active energy (Received, Delivered, Sum, Net) 1 -
Energy(Q) Reactive energy (Quadrant 1/2/3/4) 2 -
Energy(S) Apparent energy -
1. “Sum” indicates the value calculated by adding the delivered energy to the received energy. “Net” indicates the value
calculated by subtracting the delivered energy from the received energy.
2. Reactive energy is calculated respectively by dividing reactive power into four quadrants.

Page 162 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

ANALYSIS Screen
Fig 4. 14 Phasor Screen

Submenu Description Note


Phasor Voltage/Current phasor, magnitude and phase angle LN / LL
voltage
Harmonics 1 Spectrum of voltage/current harmonics up to the 50th order Graph/text
provided
Waveform 1
2 cycles of instantaneous voltage/current waveforms -
Volt. Symm. Magnitude of positive/negative-sequence components of 3-phase LN/LL voltage Max. value
Volt. Unbal. % Voltage unbalance, Unbalance(zero-/ negative-sequence component) 2 Max. value
Curr. Symm. Magnitude of positive/negative/zero-sequence components of 3-phase current Max. value
Curr. Unbal. % Current unbalance, Unbalance(zero-/negative-sequence component) Max. value
1. Line-to-neutral voltage and line-to-line voltage data are provided in 3P4W and in 3P3W mode, respectively.
2. The zero-sequence value of the LL voltage is 0. The negative-sequence unbalance values of LL/LN voltages are always
the same.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 163


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

SYSTEM Information Screen


Fig 4.15 Description Screen

Submenu Description
Description Indicates the device name, installation location and date, and description of the device
Local Time Indicates the local time and GMT offset
Network State Indicates the ethernet communication state
A2500M Indicates information on Accura 2500M module
A2500D Indicates information on Accura 2500D module
A2550CMZ Indicates information on Accura 2500CMZ module

Page 164 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

SETUP Mode

Screen Composition

Top Menu Bar


There are the module selection window, AC/DC mode, and event notification window in the top menu bar.
By pressing the arrow(◀/▶) icon on the module selection window, users can select the previous(◀) or next
(▶) module. By pressing the next(▶) module button, users can move to Main module, single-phase power
measuring module, and three-phase power measuring module in sequence and can move to the module ID
with a greater number on the selected power measuring module.
Users can move to the module connection screen by pressing the middle of the module selection window.
It enables users to check the connection and operational status of all modules connected with the daisy-
chain method and move to the measurement screen of the selected module. When an event occurs, the
bell icon on the event notification window gets brightened, and the number of new events appear at the
same time. By pressing the event notification window, users can move to the relevant event screen and
check detailed event data.

Main Menus/Submenus
The main menus are located right below the top menu bar. Sub menus for the main menus are provided on
the left in the vertical direction, allowing users to select the detail screen. Sub menus are unavailable on the
SUMMARY measurement screen accessed by pressing the SETUP button. By tapping each of six individual
sections on the measurement screen, users can directly move to the detail screen of the selected
measurement item and check detailed measurement data.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 165


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Accura 2500M Setup

If users select MAIN on the module selection window in the menu bar at the top, the setup screen of the
main module appears. By tapping setup items on the screen, users can change preset values.

SUMMARY Setup Screen


If the SETUP button is pressed, the SUMMARY setup screen of the selected module appears. By tapping
setup items or values on the screen, users can move to the detail screen of the selected setup item. Users
can return to the SUMMARY setup screen by pressing the BACK button at the bottom of the screen.

Fig 4.16 SUMMARY Setup Screen

MEASUREMENT Setup
The MEASUREMENT setup screen consists of Voltage, Demand, Power, and AC/DC setup items.

Fig 4.17 Voltage Setup Screen

Page 166 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

Setup Items Range Default


Voltage
Wiring 3P4W / 3P3W / 1P2W / 1P3W 3P4W
Min. Meas. Secondary L-N Volt. [V] 1
0 – 50 V 5V
PT Primary L-L Voltage [V] 1 – 999,999 V 380 V
PT Secondary L-L Voltage [V] 1 – 999 V 380 V
Reference Voltage [V] 2
Line-to-Line / Line-to-Neutral Line to Line
1 – 999,999 V 380 V
Volt. Phase Selection ABC: V1-V2-V3/ ABC: V1-V3-V2/ ABC: ABC: V1-V2-V3
V2-V1-V3/ ABC: V2-V3-V1/ ABC: V3-V1-
V2/ ABC: V3-V2-V1
Demand
Sync Mode 4 Hourly Auto Sync / Manual Sync Hourly Auto Sync
Subinterval Time [min] 1 – 60 min 15 min
Number of Subintervals 1 – 12 1
Power Type Received / Net Received
Thermal Response Index [%] 0 – 100 % 90 %
Power
Phase Power Calculation Fundamental / RMS Fundamental
Total Power Calculation Vector sum / Arithmetic sum Vector sum
PF Sign Unsigned PF / Signed PF Signed PF
PF Value at No-Load PF=0 / PF=1 PF=1
AC/DC
Mode AC/DC AC
1.It is set based on the line-to-neutral voltage of the device.
2. It can be set in “3P4W” mode.
3. For the reference primary voltage value, users should enter line-to-line voltage values in “3P3W” mode.
In “3P4W” mode, line-to-line voltage or line-to-neutral voltage values can be entered.
4. In Sync Mode, users can set the method for synchronizing the starting time of a demand subinterval. In “Hourly Auto
Sync” mode, automatic synchronization is performed every hour, and in “Manual Sync” mode, the starting time of
the demand subinterval is synchronized to the time users issue a sync command. Refer to 「Chapter 6 Functions >
Measurements > Demand」 for details.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 167


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

When changing a value by selecting a setup item, the changed setup item is stored in the temporary
memory, and the Apply/Cancel button appears at the top right side of the screen.

Fig 4.18 Changed Item Displayed

EVENT Setup
The EVENT Setup screen consists of Dip(Sag), Swell, PQ Curve, Volt. Connection, and Transient Volt. setup
items.
Fig 4.19 Dip Event Setup Screen

Setup Items Range Default


Dip
Trigger Disable / Enable Disable
Threshold [%] 1 1.0 – 99.0 % 90.0 %
Hysteresis [%] 1.0 – 99.0 % 2.0 %
DO Notification Not Used / DO.1 – DO.12 Not Used
Swell
Trigger Disable / Enable Disable
Threshold [%] 1
101.0 – 999.0 % 110.0 %
Hysteresis [%] 1.0 – 99.0 % 2.0 %
DO Notification Not Used / DO.1 – DO.12 Not Used

Page 168 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

PQ Curve (Power Quality Curve)


SEMI F47-0706 Disable / Enable Disable
ITIC Disable / Enable Disable
IEC 61000-4-11/34 Class 3 Disable / Enable Disable
DO Notification Not Used / DO.1 – DO.12 Not Used
Volt. Connection (Voltage Connection)
Fuse Fail Disable / Enable Disable
Phase Open Disable / Enable Disable
DO Notification Not Used / DO.1 – DO.12 Not Used
Transient Voltage
Trigger Disable / Enable Disable
Delta Voltage [V] 2 10 − 999,999 20
DO Notification Not Used / DO.1 – DO.12 Not Used
1. It indicates the percentage of the reference primary voltage value.
2. Voltage sampling is performed at a rate of 512 samples per cycle, and it indicates the difference between sampled
voltage values.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 169


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

NETWORK Setup
The NETWORK setup screen consists of Ethernet, RS-485, and Advanced setup items.

Fig 4.20 Ethernet Communication Setup Screen

Setup Items Range Default


Ethernet
IP Address d1.d2.d3.d4 1 10.10.10.100
Subnet Mask 255.255.0.0 / 255.255.128.0 / ... / 255.255.255.0
255.255.255.248 / 255.255.255.252
Gateway d1.d2.d3.d4 1 10.10.10.1
MAC Address 2 h1:h2:h3:h4:h5:h6 3 -
RS-485
Device Address 0 – 247 0
Bit Rate 1,200 / 2,400 / 4,800 / 9,600 / 19,200 / 9,600
38,400 / 57,600 / 115,200 4

Parity None / Odd / Even Even


Stop Bit 1/2 1
Etc.
Modbus TCP Timeout [sec] 5 – 600 sec 600 sec
RSTP Mode Disable / Enable Disable
Storm Control Mode Disable / Enable Disable
Port 502 Map Accura 2500 / Accura 2300 Accura 2500
Port 503 Map Accura 2500 / Accura 2300 Accura 2300
RS-485 Map Accura 2500 / Accura 2300 Accura 2500
Remote Control Lock Mode Each Connection Lock / Always Unlock Each Connection Lock
1. They indicate decimal numbers between 0 and 255.
2. It indicates the characteristic value of the device (Read-only property).
3. They indicate hexadecimal numbers between 0 and 255.
4. At 115,200 bps, a master can communicate with up to 16 slave devices, and the maximum distance between
the master and the slave is 600 m.

Page 170 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

DEVICE Setup
The DEVICE setup screen consists of Main CM, Module ID and MCCB Status setup items.

Fig 4.21Main CM Setup Screen

Setup Items Range Default


Main CM[Z]
Main A2550CM Assignment Disable / Enable Disable
Main A2550CM ID 0 – 39 0
Module ID
Auto Assignment 1 Enter / Cancel 2 -
Module ID Clear 3 Enter / Cancel 2 -
MCCB Status
All MCCBs Status DI.1 Not Used / ON,OFF / Fault(Trip) -
All MCCBs Status DI.2 Not Used / ON,OFF / Fault(Trip) -
1. Module IDs are automatically assigned according to the order of modules connected to the RJ45-1 port and
the RJ45-3 port, and the assigned ID number increases by 1 from zero. A new ID is not given to the module with
an existing ID, which is excluded from automatic ID assignment to avoid ID redundancy.
2. A confirmation window asking to choose “Confirm” or “Cancel” appears on the screen.
3. The IDs of all Accura 2550 modules connected to Accura 2500M are changed to the standby ID 255.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 171


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

CONTROL Setup
The CONTROL setup screen consists of Data Reset, Demand Sync and Test Mode setup items.

Fig 4.22 Reset Screen

Setup Items Range Default


Data Reset
Demand Confirm / Cancel 1 -
Peak Demand Confirm / Cancel 1
-
Max/Min Confirm / Cancel 1
-
Energy Confirm / Cancel 1 -
Measurement & PQ Event Confirm / Cancel 1
-
System Event Confirm / Cancel 1
-
DI/DO Counter Confirm / Cancel 1

Demand Sync
Demand Sync 2 Confirm / Cancel 1

Test Mode
Test Mode Off / Balance / Unbalance Off
Timeout [min] 1 – 1440 min / Infinite 3 60 min
Fault Test Mode Off / Measurement / Module 1 / Off
Module 2 / Module 3 / Module 4 /
Ethernet 1 / Ethernet 2 / Loop / NTP
/ Heart Beat
1. A confirmation window asking to choose “Confirm” or “Cancel” appears on the screen.
2. If the Demand Sync mode accessed via 「SETUP > MEASUREMENT > Demand > Sync Mode」 is set to
“Manual Sync”, the starting time of the demand subinterval is synchronized to the time users issue
a sync command.
3. If the Timeout value is set to “Infinite”, the test mode continues.

Page 172 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

SYSTEM Setup
The SYSTEM setup screen consists of Description, Local Time, Summer Time, NTP, LED, LCD & Buzzer, Module
LCD, and Locale setup items.

Fig 4.23 Description Setup Screen

Setup Items Setup Range Default


Description
Device Name 30 Characters Null
User-Defined Info 30 Characters Null
Location 30 Characters Null
Installation Year 1970 – 9999 1970
Installation Month 1 – 12 1
Installation Day 1 – 31 1
Local Time
Year 1970 – 2037 현재 시간
Month 1 – 12 현재 시간
Day 1 – 31 현재 시간
Hour 0 – 23 현재 시간
Minute 0 – 59 현재 시간
Second 0 – 59 현재 시간
Summer Time
Summer Time Disable / Enable Disable
Time Offset [min] 0 – 1,439 min 60 min
Start Month January / February / ... / December March
Start Nth Weekday 1st / 2nd / ... / 5th 2nd
Start Weekday Sunday / Monday / ... / Saturday Sunday
Start Minute 0 – 1,439 min 120 min
End Month January / February / ... / December November
End Nth Weekday 1st / 2nd / ... / 5th 1st
End Weekday Sunday / Monday / ... / Saturday Sunday
End Minute 0 – 1,439 min 120 min
NTP (Network Time Protocol)
Server IP Address d1.d2.d3.d4 1 10.10.10.1
Sync Mode Disable / Auto / Periodical Auto
Sync Period [sec] 60 – 999 sec 600 sec

ⓒ 2019 Rootech Inc. All Rights Reserved Page 173


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Sync Max Drift [msec] 1 – 1,000 msec 1 msec


LED
Ethernet LED Period [sec] 0.2 – 5.0 sec 1.0 sec
Ethernet LED On Time [sec] 0.1 – 5.0 sec 0.5 sec
Module LED Period [sec] 0.2 – 5.0 sec 1.0 sec
Module LED On Time [sec] 0.1 – 5.0 sec 0.5 sec
Event LED Period [sec] 0.2 – 5.0 sec 1.0 sec
Event LED On Time [sec] 0.1 – 5.0 sec 0.5 sec
Event LED Hold Time [sec] Continuous 2 / Self-Resetting 3 / Definite Time Continuous 2
LCD & Buzzer
LCD Backlight Timeout [sec] 10 – 999 sec 300 sec
LCD Backlight Low Level [%] 0 – 30 % 10 %
Buzzer for Button Disable / Enable Enable
Setup Exit Timeout [sec] 60 – 3,600 600
Module LCD
Screen Selection 4
Auto Rotation 순차적 자동회전 Auto Rotation
Module ID 모듈 ID
A Phase 5
A상 계측값
B Phase 5
B상 계측값
C Phase 6
C상 계측값
ABC Total 6
삼상 계측값
Rated Current 정격전류
Phase Information 상 정보
CT Ratio 7 CT 권선비율
ZCT Current ZCT 전류
LCD Backlight Timeout [sec] 10 – 999 sec 60 sec
Setup Exit Timeout [sec] 5 – 60 sec 30 sec
Locale
Temperature Unit 8 Celsius / Fahrenheit Celsius
Timezone Offset [min] -720 – 840 min 540 min
Energy Unit 9 kWh / Wh kWh
DI/DO Closed Status Color Red / Green Red
DI/DO Counter No Display / Display No Display
Comm. Event Log Disable / Enable Enable
1. They indicate decimal numbers between 0 and 255.
2. If the “Event LED Hold Time” is set to “Continuous”, the EVENT LED remains on until users check it.
3. If the “Event LED Hold Time” is set to “Self-Resetting”, the EVENT LED is turned off automatically when the
event ends.
4. It indicates users can select data displayed on the LCD screens of all power measuring modules connected to
Accura 2500M simultaneously. Terms regarding different screen selections are based on the terms appearing on
the three-phase power measuring module
5. It indicates the measured current value of the single-phase power measuring module.
6. It indicates the measured power value of the single-phase power measuring module.
7. The data are available with Accura 2550CM-3P-5A module. Other modules display the module ID.
8. Temperature is measured by Accura 2550TEMP module.
9. When the unit of active energy is changed, the units of reactive energy and apparent energy are also changed.

Page 174 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

Accura 2550 Setup

If you select the three-phase or single-phase power measuring module on the module selection window at
the top menu bar, the setup screen of the selected module appears. By pressing a setup item on the screen,
you can change values.

SUMMARY Setup Screen


If the SETUP button is pressed, the SUMMARY setup screen of the selected module appears. By tapping
setup items or values on the screen, you can move to the detail screen of the selected setup item. Users
can return to the SUMMARY setup screen by pressing the BACK button at the bottom of the screen.

Fig 4.24 SUMMARY Setup Screen

ⓒ 2019 Rootech Inc. All Rights Reserved Page 175


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

MEASUREMENT Setup
The MEASUREMENT setup screen consists of Current, Leakage and Load Wiring setup items.

Fig 4.25 Current Setup Screen

Setup Items Range Default


Current
Rated Current [A] 1
1 – Basic current Basic current
Min. Measured Current [%] 2 0.00 – 20.00 % 0.10 %
TDD Reference Selection TDD Nominal Current / Peak Demand Current Peak Demand Current
TDD Nominal Current [A] 1 1 – 기본전류 / Rated Current 기본전류
CT Ratio 3 1 – 9,999 1
Leakage
Trend Data Type RMS / Fundamental Fundamental
Min. Measured Current [mA] 0 – 100 1
Load Wiring
Load Direction >>> (left-to-right) / <<< (right-to-left) >>> (left-to-right)
Load Mode 4
3-phase mode / 1-phase mode 3-phase mode
Phase Sequence 4 A-B-C / C-B-A A-B-C
Feeder 1 Phase Selection 4, 5 Off / AN / BN / CN / AB / BC / CA / AN
NA / NB / NC / BA / CB / AC
Feeder 2 Phase Selection 4, 5 Off / AN / BN / CN / AB / BC / CA / BN
NA / NB / NC / BA / CB / AC
Feeder 3 Phase Selection 4, 5 Off / AN / BN / CN / AB / BC / CA / CN
NA / NB / NC / BA / CB / AC
Phase Selection 6 Off / AN / BN / CN / AB / BC / CA / AN
NA / NB / NC / BA / CB / AC
1. It can be set to a value below the basic current of Accura 2550 module.
2. It indicates the percentage of the basic current of Accura 2550 module.
3. The setup item is available with Accura 2550CM-3P-5A module.
4. The setup item is available with Accura 2550CM-3P module.
5. The setup item is available if the load mode is set to the “1-phase mode”.
6. The setup item is available with Accura 2550CM[Z]-1P module.

Page 176 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

EVENT Setup
The EVENT setup screen consists of Current and Leakage setup items.

Fig 4.26 Current Event Setup Screen

Setup Items Setup Range Default

Current

Trigger Disable / Over / Under Disable


Threshold [%] 1 5.0 – 200.0 % 80.0 %
Hysteresis [%] 1 1.0 – 20.0 % 2.0 %

Low Limit [%] 1


0.0 – 200.0 % 0.0 %
Time Delay [msec] 2 0 – 10000 msec 0 msec

DO Notification Not Used / DO.1 – DO.12 Not Used


Leakage

Trigger Disable / Over Disable


Threshold [mA] 20 – 2,000 mA 100 mA
Hysteresis [mA] 20 – 200 mA 20 mA

Time Delay [msec] 2


0 – 10000 msec 0 msec

Type 3 Fundamental / RMS Fundamental

DO Notification Not Used / DO.1 – DO.12 Not Used

1. It is the percentage of the rated current.


2. It can be set up in steps of 0.2 seconds.
3. The type of the monitored leakage current can be set up. Users can choose from Fundamental/RMS current.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 177


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

SYSTEM Setup
The SYSTEM setup screen consists of the Description setup item.

Fig 4.27 Description Setup Screen

Setup Items Setup Range Default


Description
Load Name 30 Characters Null
User-Defined Info 30 Characters Null
Location 30 Characters Null

Page 178 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

EVENT Mode

Screen Composition

Top Menu Bar


There are the module selection window, AC/DC voltage mode, and event notification window in the top
menu bar. By pressing the arrow(◀/▶) icon on the module selection window, users can select the previous(◀)
or next (▶) module. By pressing the next(▶) module button, users can move to Main, single-phase power
measuring module, and three-phase power measuring module in sequence and can move to the module ID
with a greater number on the power measuring module.
Users can move to the module connection screen by pressing the middle of the module selection window.
It enables users to check the connection and operational status of all modules connected with the daisy-
chain method and move to the measurement screen of the selected module. When an event occurs, the
bell icon on the event notification window gets brightened, and the number of new events appear at the
same time. By pressing the event notification window, users can move to the relevant event screen and
check detailed event data.

Main Menus/Submenus
There are main menus, including MEASUREMENT, POWER QUALITY , and SYSTEM right below the top menu
bar. The submenus for the main menus are provided on the left in the vertical direction, allowing users to
easily check event data by filtering each event.

SUMMARY Event Screen


When the EVENT button is pressed, the SUMMARY EVENT screen of the selected module appears. The
SUMMARY EVENT screen shows data on measurement, power quality, and system events, including the
number of events that have been saved and can be saved. When new events you have not checked occur,
the number of new events appear with the orange bell icon. By pressing the main menu button at the top
of the screen or tapping each item on the screen, you can enter the relevant event list screen and check
detailed event data. You can save up to the last 100 measurement and power quality events respectively, as
well as up to the last 1,000 system events.

Events Subcategory
Measurement events
1 Voltage / Current / Power / Leakage Current / Etc.
Power Quality events Dip / Swell / SEMI F47 / IEC 61000 / ITIC / Transient Volt
System events Module / Communication / Setup / Etc.
1. Phase open and fuse fail events are categorized into voltage parameters.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 179


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Fig 4.28 SUMMARY Event Screen

MEASUREMENT Events

Accura 2500M saves the last 100 measurement events. If the number of events exceeds 100, the oldest
event gets deleted first. Each index for measurement events is indicated with the number from 0 to 9,999
(a greater index number indicates a more recent event). Thus, through the index number, users can check
the time the event occurred, as well as detailed event data. Using the sub-menus located on the left side of
the screen, users can easily check event data by filtering different types of events. Line open and fuse fail
events are categorized into voltage parameters. If users select one event from the events list, the Trend and
Read All button appear on the upper right side of the screen.

Fig 4.29 MEASUREMENT Event Screen

If users press the Trend button after selecting an event, the RMS trend screens indicating the data obtained
before and after the event occurred are shown. RMS trend data indicate RMS data measured over 1 cycle
for 3 frames before and after the event occurred. A frame consists of 12 cycles of RMS data at 60 Hz and
10 cycles of RMS data at 50 Hz. By using the submenus on the left, users can return to the desired event
list screen.

Page 180 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

Fig 4.30 RMS Trend Screen

Power Quality Events

Accura 2500M saves the last 100 power quality events. If the number of events exceeds 100, the oldest event
gets deleted first. Each index for events is indicated with the number from 0 to 9,999 (a greater index number
indicates a more recent event). Through the index number, users can check the time an event occurred, as
well as detailed event data.
Using the submenus located on the left side of the screen, users can easily check event data by filtering
different types of events. If users select one event from the events list, the Trend and Read All button appear
on the upper right side of the screen. If users select one of SEMI F47-0706, IEC 61000-4-11/34 Class 3, and
ITIC events, the PQ Curve button also appears on the upper right side of screen. For Transient voltage events,
the Waveform button appears instead of the Trend button.

Fig 4.31 Power Quality Events Screen

If users press the Trend button after selecting an event, the RMS trend screen indicating the data obtained
before and after the event occurs is shown. RMS trend data indicate RMS data measured over 1 cycle for 3
frames before and after the event occurred. A frame consists of 12 cycles of RMS data at 60 Hz and 10
cycles of RMS data at 50 Hz. By using the submenus on the left, users can return to the desired event list
screen.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 181


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Fig 4.32 RMS Trend Screen

If users select one of SEMI F47-0706, IEC 61000-4-11/34 Class 3, ITIC events and press the PQ Curve button,
all power quality events that have occurred, including the selected event appear with dots on the graph as
shown below. It enables users to statistically analyze trends in the occurrence of events at a glance. The
selected event appears red on the screen. By using the submenus on the left, users can return to the desired
event list screen.

Fig 4.33 PQ Curve Graph Screen

Page 182 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

SYSTEM Events

Accura 2500M saves the last 1,000 system events. If the number of events exceeds 100, the oldest event
gets deleted first. Each index for events is indicated with the number from 0 to 9,999 (a greater index number
indicates a more recent event). Thus, through the index number, users can check the time the event occurred,
as well as detailed event data. Using the submenus located on the left side of the screen, users can easily
check event data by filtering different types of events.

Fig 4.34 SYSTEM Event Screen

ⓒ 2019 Rootech Inc. All Rights Reserved Page 183


Chapter 4 Accura 2500D Accura 2500/2550 User Guide [AC]

Necessary Steps for Device Setup


Users need to take the following steps in order to properly operate Accura 2500/2550 Smart Industrial
Control Panel Digital Power Meter.

Step 1: Setup for the Type of Voltage Measurements of Accura 2500M

Users should select AC for the measured voltage type of AC industrial control panels. Accura 2550 modules
supporting AC measurement should be used in AC industrial control panels.
How to set up the measured voltage type on Accura 2500D screen is as follows.
▶ Main module (Main): 「SETUP > MEASUREMENT > AC/DC > Mode」

Step 2: Setup for the Voltage Wiring of Accura 2500M, PT Rating, and Reference Voltage

Users should set a voltage wiring mode according to the measured voltage type. Refer to 「Chapter 6
Functions> Measurements > Voltage Wiring」 for details on voltage wiring.
How to set up voltage wiring on the Accura 2500D screen is as follows.
▶ Main module (Main): 「SETUP > MEASUREMENT > Voltage > Wiring」

When using external PTs, users should set the primary voltage and the secondary voltage of the PT. The
ratio of the primary to secondary values is used as the conversion ratio for the primary voltage of the PT.
Regardless of voltage wiring modes, line-to-line voltage values should be entered. In case of 1P2W
connection, the line-to-line voltage is the same as the line-to-neutral voltage. When external PTs are not
used, set the primary voltage and the secondary voltage values of the PT to the same values.
How to set up the reference voltage on the Accura 2500D screen is as follows.
▶ Main module (Main): 「SETUP > MEASUREMENT > Voltage > PT Primary Voltage / PT Secondary Voltage」

Users should also set up the reference voltage used for Dip(Sag)/Swell detection and the evaluation of the
PQ Curve. The reference voltage is the primary voltage of the PT.
▶ Main module (Main): 「SETUP > MEASUREMENT > Voltage > Reference Primary Voltage」

Page 184 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 4 Accura 2500D

Step 3: Module ID Setup of Accura 2550 Modules

The IDs of Accura 2550 modules connected to Accura 2500M should be set to the ID numbers that enable
communication. The ID numbers of Accura 2550 modules should be selected from 0 to 39 and should not
be duplicated. Users can set up the ID with the SET button on Accura 2550 module. Refer to 「Chapter 5
Accura 2550 > Accura 2550CM[Z]-3P/1P Module > Setup Mode> ID Setup」 for details about Module ID
Setup.
▶ Accura 2550 > SET button

Users can also set up the IDs of all Accura 2550 modules at once on the setup screen of Accura 2500D
module. For details about the module ID setup, refer to 「Chapter 4 Accura 2500D > Setup Mode > Setup
of Accura 2500M > DEVICE Setup」. How to set up module IDs on Accura 2500D screen is as follows.
▶ Main module (Main): 「SETUP > DEVICE > Module ID > Auto Assignment」

Step 4: Ethernet Setup of Accura 2500M

IP Address, Subnet Mask, and Gateway should be set up for Ethernet communication with the host system.
How to perform Ethernet setup on the Accura 2500D screen is as follows.
▶ Main module (Main): 「SETUP > NETWORK > Ethernet」

ⓒ 2019 Rootech Inc. All Rights Reserved Page 185


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Chapter 5 Accura 2550

Operation Mode

The front panel of Accura 2550 module consists of an LCD screen displaying measured values and setup
data, as well as one SET button. The LCD screen features the following two operation modes.

Mode Description
Display mode Indicates IDs and measured values (current, power, etc.) in sequence. By setting up the display
mode of Accura 2500D device, users can make specific measured values appear on the screens
of all Accura 2550 modules.
Setup mode In this mode, users can set up IDs, the rated current, and various timeouts. If there is no
button operation for 30 seconds (the operating time can be set), the operation mode
automatically changes to the display mode.

Button Operation
Button Description

Display Mode
Short press 1 Move between screens manually (Each time the button is pressed, the
display screen changes to the next screen).

Long press 2
Enter the setup mode.

Setup Mode
Short press 1 Move between setup screens (Each time the button is pressed, the setup
screen is selected in sequence.)

Long press 2 Enter the edit mode in which you can change settings
A preset value blinks, and you can change it.

Short press 1 Select the value to change.


(Each time the button is pressed, the value increases.)

Long press 2 Save the selected set value (blinking stops) and return to the setup mode.
(Long press the button to change the setting of the next digit.)

1. Short press the button to move to the previous screen. Double press the button within 0.25 seconds to move to
the next screen.
2. Release the button after pressing it for one second.

Note
If there is no button operation for 30 seconds (the operating time can be set) in the setup mode or the
edit mode, the screen automatically returns to the display mode.

Page 186 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Accura 2550CM[Z]-3P/CMZ-3P4W Modules

Applied Models
Model Basic Current Measurement Range Minimum
(lb) (Accuracy Guaranteed) Measured Value
Accura 2550CM-3P -800A-210 800 A 16.0 A − 960 A 0.80 A

-800A-210-ZCT 800 A 16.0 A − 960 A 0.80 A

-630A-145 630 A 12.6 A − 756 A 0.63 A

-630A-145 ZCT 630 A 12.6 A − 756 A 0.63 A

-400A-140 400 A 8.0 A − 480 A 0.40 A

-400A-140-ZCT 400 A 8.0 A − 480 A 0.40 A

Accura 2550CMZ-3P -800A-220 800 A 16.0 A − 960 A 0.80 A

-630A-155 630 A 12.6 A − 756 A 0.63 A

-400A-155 400 A 8.0 A − 480 A 0.40 A

Accura 2550CM[Z]-3P -250A 250 A 5.0 A − 300 A 0.25 A

-125A 125 A 2.5 A − 150 A 0.13 A

-100A 100 A 2.0 A − 120 A 0.10 A

-60A 60 A 1.2 A − 72 A 0.06 A

Accura 2550CM-3P -5A 1


5A 0.1 A − 6A 0.01 A

-5A-ZCT 1
5A 0.1 A − 6A 0.01 A

Accura 2550CMZ-3P4W -250A-145 250 A 5.0 A − 300 A 0.25 A

1. Accura 2550CM-3P-5A module can be used by externally installing CTs (the secondary current rating: 5 A).
2. Accura 2550CM-3P, which can connect an external ZCT, module measures leakage current by connecting an externally
installed voltage-type ZCT to its ZCT connection port. The user must purchase the ZCT separately from the ZCT
manufacturer.

Item Specification
Current Measurement accuracy IEC 61557-12 Class 0.5 ±0.5 % Reading
Leakage current 1
Fundamental current CM-3P-800A/630A/400A/5A-ZCT ±2 % Reading ± 2 mA
measurement accuracy CMZ-3P-800A ±0.5 % Reading ± 60 mA
CMZ-3P-630A/400A/250A ±0.5 % Reading ± 30 mA
CMZ-3P-125A/100A/60A ±0.5 % Reading ± 20 mA

CMZ-3P4W-250A-145 ±0.5 % Reading ± 30 mA


Measuring range 1 mA − 2 A
Active power Measurement accuracy IEC 61557-12 Class 0.5
Active energy Measurement accuracy IEC 62053-21 Class 0.5
1. The data are available with Accura 2550CMZ modules and Accura 2550CM-3P modules, which can connect to an
external ZCT.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 187


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

LCD Display

Indication

ID Module ID 1

SET Setup mode


◀ Load direction 
▶ Load direction →
mA/A/kA Current unit
W/kW Power unit
ms/s Time unit [millisecond/second]

1. Module IDs are divided into three types of IDs as follows.


The standby ID 255 is assigned to all Accura 2550 modules as a factory default value.

Module ID ID Description

Communication ID ID 0 – 39 ID of the module available for communication

Conflict ID Duplicate IDs There are more than 2 identical IDs.


Communication unavailable

Standby ID ID 255 Module ID for checking connection status,


Communication unavailable

Display Mode

Accura 2550CM[Z] module shows the display screen in the following sequence. By short pressing the SET
button, you can manually change the automatic display screen. Long press the SET button to enter the
setup mode.

Average
A Current/ B Current/ C Current/ Leakage
ID Current/
Power Power Power Current 1
Total Power

1. The data are available with Accura 2550CMZ modules and Accura 2550CM-3P modules, which can connect to an
external ZCT.

Page 188 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Setup Mode

Setup Menu
If users short press the SET button, the setup menu appears in the following sequence.

Phase
ID Rated Current Load Direction Load Mode 1 CT Ratio 3
Sequence 2

1. The setup menu is not available on Accura 2550CMZ-3P module.


2. It is the setup screen for a three-phase load. For a single-phase load, the phase setup screen for each of the three
holes appears.
3. The data are available with Accura 2550CM-3P-5A model and Accura 2550CM-3P-ZCT model that can be used by
externally installing CTs (the secondary current rating: 5 A).

Note

If there is no button operation for 30 seconds(the operating time can be set) in the setup mode or the edit
mode, the operation mode automatically returns to the display mode.

ID Setup
Item Range Description
ID [d][d] 1
Module ID 2
setup
0 – 39 (default 255)

1. d → decimal number
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.
Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication
Conflict ID Duplicate IDs There are more than 2 identical IDs.
Communication unavailable

Standby ID ID 255 Module ID for checking connection status,


Communication unavailable

ⓒ 2019 Rootech Inc. All Rights Reserved Page 189


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Rated Current Setup


The rated current should be set to a value less than the basic current of Accura 2550 modules.

Item Range Description


Irt (Rated Current) [d][d][d] 1
Rated current setup
1 – basic current (default: basic current) 2

1. d → decimal number
2. The basic current of the three-phase power measuring module is as follows. The value set by users cannot exceed
the basic current value.

Model Basic Current


Accura 2550CM-3P-800A-210 800 A
Accura 2550CM-3P-800A-210-ZCT
Accura 2550CMZ-3P-800A-220
Accura 2550CM-3P-630A-145 630 A
Accura 2550CM-3P-630A-145-ZCT
Accura 2550CMZ-3P-630A-155
Accura 2550CM-3P-400A-140 400 A
Accura 2550CM-3P-400A-140-ZCT
Accura 2550CMZ-3P-400A-155
Accura 2550CM[Z]-3P-250A 250 A
Accura 2550CMZ-3P4W-250A-145
Accura 2550CM[Z]-3P-125A 125 A
Accura 2550CM[Z]-3P-100A 100 A
Accura 2550CM[Z]-3P-60A 60 A
Accura 2550CM-3P-5A 5A
Accura 2550CM-3P-5A-ZCT

Page 190 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Load Direction Setup


Set the direction of the load depending on whether the load is installed on the left or right side of the
industrial control panel.

Item Range Description


Load direction

Load on the right side(default)

Load on the left side

Load Mode Setup


Set load mode according to the type of the load. For a three-phase load, set the mode to 3-Phase. When
you want to use each hole as an independent load, set the mode to 1-Phase. This setup menu is not
available on Accura 2550CMZ-3P module.
.

Item Range Description


Load mode

Three-phase load (default)

Single-phase load

ⓒ 2019 Rootech Inc. All Rights Reserved Page 191


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Phase Sequence Setup


For three-phase loads, set the phase sequence of three-phase cables passing through the holes of the
module to a-b-c or c-b-a. For single-phase multi-feeder loads, the phase sequence of the single-phase load
is set using two letters. The first letter refers to the phase of the cable passing through the hole of the
module, and the second letter indicates the phase of the cable that does not pass through the hole of the
module. For example, when a B-phase cable is installed to pass through the hole of the power measuring
module for a load connected between B and C phases, set the phase sequence to “bc”.

Item Range Description


Phase sequence
(When the load mode is set
to three-phase load)

Positive sequence (default)

Negative sequence

Phase selection
(When the load mode is set
to single-phase load)1

Single phase setup for each hole

1. Phase selection data for a single-phase load are indicated with two letters. The letter indicating the phase of
the cable passing through the hole of the module comes first.

CT Ratio Setup
The setup screen is available only on Accura 2550CM-3P-5A model that can be used by externally installing
CTs(the secondary current rating: 5 A).

Item Range Description


CT ratio [d][d][d][d] 1 Winding turns ratio of external CTs
1 – 9,999 (default 1)

1. d → decimal number

Page 192 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Accura 2550CM[Z]-1P Module

Applied Models

Model Basic Current Measuring Range Minimum


(lb) (Accuracy Guaranteed) Measured Value
Accura 2550CM[Z]-1P -250A 250 A 5.0 A – 300 A 0.25 A
-125A 125 A 2.5 A – 150 A 0.13 A
-100A 100 A 2.0 A – 120 A 0.10 A
-60A 60 A 1.2 A – 72 A 0.06 A

Item Specification
Current Measurement accuracy IEC 61557-12 Class 0.5 ±0.5 % Reading
Leakage current 1 Fundamental current CMZ-1P-250A ±0.5 % Reading ± 30 mA
measurement accuracy CMZ-1P-125A/100A/60A ±0.5 % Reading ± 20 mA
Measuring range 1 mA – 2 A
Active power Measurement accuracy IEC 61557-12 Class 0.5
Active energy Measurement accuracy IEC 62053-21 Class 0.5
1. The data are available with Accura 2550CMZ modules.

LCD Display
Indication

ID Module ID 1

SET Setup mode


◀ Load direction 
▶ Load direction →
mA/A/kA Current unit
W/kW Power unit

Accura 2550CM[Z]-1P-250A

Accura 2550CM[Z]-1P-125A/100A/60A

1. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 193


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication
Conflict ID Duplicate IDs There are more than 2 identical IDs.
Communication unavailable
Standby ID ID 255 Module ID for checking connection status.
Communication unavailable

Display Mode

Accura 2550CM[Z]-1P-250A module shows the display screen in the following sequence.

ID Current /Power Leakage Current 1

1. The data are available with Accura 2550CMZ modules.

Accura 2550CM[Z]-1P-125A/100A/60A module shows the display screen in the following sequence.

ID Current Power Leakage Current 1

1. The data are available with Accura 2550CMZ modules.

By short pressing the SET button, you can manually change the automatic display screen. Long press the
SET button to enter the setup mode.

Page 194 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Setup Mode

Setup Menu
The setup mode screen of Accura 2550CM[Z]-1P-250A module is as follows. If users short press the SET
button, the setup menu appears in the following sequence.

ID Rated Current Load Direction Phase Selection

The setup mode screen of Accura 2550CM[Z]-1P-125A/100A/60A module is as follows. If users short press
the SET button, the setup menu appears in the following sequence.

ID Rated Current Load Direction Phase Selection

Note

If there is no button operation for 30 seconds(the operating time can be set) in the setup mode or the edit
mode, the operation mode automatically returns to the display mode.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 195


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

ID Setup
Item Range Description
ID [d][d] 1 Module ID 2 setup
0 – 39 (default 255)

1. d → decimal number
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.
Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication
Conflict ID Duplicate There are more than 2 identical IDs.
IDs Communication unavailable
Standby ID ID 255 Module ID for checking connection status.
Communication unavailable

Rated Current Setup


The rated current should be set to only a value less than the basic current of Accura 2550CM[Z]-1P module.

Item Range Description


Irt (Rated Current) [d][d][d] 1
Rated current setup
1 – basic current (default: basic current) 2

1. d → decimal number
2. The basic current of the single-phase power measuring module is as follows. The value set by users cannot exceed
the basic current.

Model Basic Current


Accura 2550CM[Z]-1P-250A 250 A
Accura 2550CM[Z]-1P-125A 125 A
Accura 2550CM[Z]-1P-100A 100 A
Accura 2550CM[Z]-1P-60A 60 A

Page 196 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Load Direction Setup


Set the direction of the load depending on whether the load is installed on the left or right side of the
industrial control panel.

Item Range Description


Load direction

Load on the right side


(default)

Load on the left side

Phase Selection Setup


The phase of a single-phase load is set with two letters. The phase information of the cable passing through
the first hole of the module with a current sensor comes first. For example, when installing an A-phase cable
to pass through the first hole of the power measuring module for a load connected between A and B phases,
set the phase sequence to “ab”.

Item Range Description


Phase selection 1

Select Line-to-Neutral.
(default)

Select Line-to-Line.

1. The phase selection data of a single-phase load are indicated with two letters. The letter indicating the phase of
the cable passing through the first hole of the module comes first.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 197


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Accura 2550CMS/ZM-3P4W Module


Accura 2550CMS-3P4W module is installed on branch lines in a three-phase 4-wire configuration in industrial
control panels and sense three-phase currents. This module measures various power characteristics based
on the sensed current information and incoming voltage information received from the Accura 2500M Main
module. Accura 2550ZM-3P4W leakage measuring module is equipped with Zero-phase Current
Transformers(ZCTs) for individual feeders to measure leakage currents from three-phase loads. It also has
one digital input terminal to monitor the operation and trip status of the MCCBs(Molded Case Circuit
Breakers) for each feeder. The Accura 2550ZM-3P4W leakage current measuring module is connected to the
Accura 2550CMS-3P4W split-core power measuring module using a communication cable.

Applied Models
Module Basic Current Measuring Range Minimum
(Ib) (Accuracy Guaranteed) Measured Value

Accura 2550CMS-3P4W -60A 60 A 3.0 A − 72 A 0.24 A


Accura 2550ZM-3P4W 1 -60A-DI 60 A 0.0 A − 72 A -
1. Accura 2550ZM module measures leakage current with its built-in ZCT.

Item Specification
Current Measurement accuracy 1 IEC 61557-12 Class 0.5 ±0.5 % Reading
Leakage current 2, 3
Fundamental current ZM-3P4W-60A-DI ±0.5 % Reading ± 10 mA
measurement accuracy
Measuring range 1 mA − 2 A
Active power Measurement accuracy 1
IEC 61557-12 Class 0.5

Active energy Measurement accuracy 1 IEC 62053-21 Class 0.5


1. The split-core CMS module has been calibrated under the condition where the power line passes through the top
center position of its hole. As the location of the power line is away from the top center position of the hole, errors in
current, power, and energy measurements can increase by up to 1 %.
2. The data are available with Accura 2550ZM modules.
3. To ensure accurate measurements of leakage current when wiring the ZM-3P4W leakage current measuring module,
you should put together all four power lines and make them pass through the center of its hole.

Page 198 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

LCD Display

Indication

ID Module ID 1

SET Setup mode


◀ Load direction 
▶ Load direction →
mA/A/kA Current unit
W/kW Power unit
ms/s Time unit [milli-second/second]

1. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.

Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication

Conflict ID Duplicate IDs There are more than 2 identical IDs.


Communication unavailable
Standby ID ID 255 Module ID for checking connection status,
Communication unavailable

Display Mode

Accura 2550CMS module shows the display screen in the following sequence. By short pressing the SET
button, you can manually change the automatic display screen. Long press the SET button to enter the
setup mode.

Average
A Current / B Current / C Current / Leakage
ID Current /
Power Power Power Current 1
Total Power

1. Accura 2550CMS module displays leakage current data when Accura 2550ZM module is connected.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 199


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Setup Mode

Setup Menu
If users short press the SET button, the setup menu appears in the following sequence.

ID Rated Current Load Direction Phase Sequence

Note

If there is no button operation for 30 seconds(the operating time can be set) in the setup mode or the edit
mode, the operation mode automatically returns to the display mode.

ID Setup
Item Range Description

ID [d][d] 1
Module ID 2
setup
0 – 39 (default 255)

1. d → decimal number
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.

Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication

Conflict ID Duplicate IDs There are more than 2 identical IDs.


Communication unavailable
Standby ID ID 255 Module ID for checking connection status,
Communication unavailable

Page 200 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Rated Current Setup


The rated current should be set to a value less than the basic current of Accura 2550CMS-3P4W module.

Item Range Description


Irt (Rated Current) [d][d][d] 1 Rated current setup
1 – basic current (default: basic current) 2

1. d → decimal number
2. The basic current of the three-phase power measuring module is as follows. The value set by users cannot exceed
the basic current value.

Model Basic Current


Accura 2550CMS-3P4W-60A 60 A

Load Direction Setup


Set the direction of the load depending on whether the load is installed on the left or right side of the
industrial control panel.

Item Range Description


Load Direction

Load on the right side


(default)

Load on the left side

ⓒ 2019 Rootech Inc. All Rights Reserved Page 201


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Phase Sequence Setup


For three-phase loads, set the phase sequence of the three-phase cables passing through the module’s holes
to a-b-c or c-b-a. For single-phase loads, the phase sequence of the single-phase load is set using two
letters.

Item Range Description


Phase Sequence

Positive sequence (default)

Negative sequence

Page 202 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Accura 2550CMS/ZM-1P3F/1P2F Modules


Accura 2550CMS-1P3F/1P2F split-core power measuring modules are installed on consecutive branch lines
in a single-phase configuration and sense single-phase currents in three or two feeders in industrial control
panels. The modules measure various power characteristics based on the sensed current information and
incoming voltage information received from the Accura 2500M Main module. Accura 2550ZM-1P3F/1P2F
leakage measuring modules are equipped with Zero-phase Current Transformers(ZCTs) for individual feeders
to measure leakage currents from three-phase or three or two single-phase loads. They also have two or
three digital input terminals to monitor the operation and trip status of the MCCBs(Molded Case Circuit
Breakers) for each feeder. Accura 2550ZM-1P3F leakage current measuring module is connected to the
Accura 2550CMS-1P3F split-core power measuring module using communication cables. Also, the Accura
2550ZM-1P2F leakage current measuring module is connected to the Accura 2550CMS-1P2F split-core power
measuring module.

Applied Models

Module Basic current Measuring Range Minimum


(Ib) (Accuracy Guaranteed) Measured Value

Accura 2550CMS-1P3F -60A 60 A 3.0 A − 72 A 0.24 A

Accura 2550CMS-1P2F -60A 60 A 3.0 A − 72 A 0.24 A

Accura 2550ZM-1P3F 1 -60A-DI 60 A 0.0 A − 72 A -


Accura 2550ZM-1P2F 1
-60A-DI 60 A 0.0 A − 72 A -
1. Accura 2550ZM module measures leakage current with its built-in ZCT.

Item Specification
Current Measurement accuracy 1 IEC 61557-12 Class 0.5 ±0.5 % Reading
Leakage current 2
Fundamental current ZM-1P3F/1P2F-60A ±0.5 % Reading ± 5 mA
measurement accuracy
Measuring range 1 mA − 2 A
Active power Measurement accuracy 1
IEC 61557-12 Class 0.5
Active energy Measurement accuracy 1 IEC 62053-21 Class 0.5
1. The split-core CMS module has been calibrated under the condition where the power line passes through the top
center position of its hole. As the location of the power line is away from the top center position of the hole, errors in
current, power, and energy measurements can increase by up to 1 %.
2. The data are available with Accura 2550ZM modules.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 203


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

LCD Display

Indication

ID Module ID 1

SET Setup mode


◀ Load direction 
▶ Load direction →
mA/A/kA Current unit
W/kW Power unit
ms/s Time unit [millisecond/second]

1. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.
Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication

Conflict ID Duplicate IDs There are more than 2 identical IDs.


Communication unavailable
Standby ID ID 255 Module ID for checking connection status,
Communication unavailable

Display Mode

Accura 2550CMS module shows the display screen in the following sequence. By short pressing the SET
button, you can manually change the automatic display screen. Long press the SET button to enter the
setup mode.

Feeder 1 Feeder 2 Feeder 3 1


Leakage
ID
Current/Power Current/Power Current/Power Current 2

1. The data are displayed on Accura 2550CMS-1P3F module.


2. Accura 2550CMS module displays leakage current data when it is connected to Accura 2550ZM module.

Page 204 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Setup Mode

Setup Menu
If users short press the SET button, the setup menu appears in the following sequence.

Feeder 1,2,3 1 Feeder 1,2,3 1


ID Load Direction 2
Rated Current Phase Selection

1. The Accura 2550CMS-1P2F module only displays the rated current setup data for Feeder 1 and Feeder 2.
2. The load direction setting applies to feeders 1, 2, and 3.

Note

If there is no button operation for 30 seconds(the operating time can be set) in the setup mode or the edit
mode, the operation mode automatically returns to the display mode.

ID Setup
Item Range Description

ID [d][d] 1 Module ID 2 setup


0 – 39 (default 255)

1. d → decimal number
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.

Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication
Conflict ID Duplicate IDs There are more than 2 identical IDs.
Communication unavailable
Standby ID ID 255 Module ID for checking connection status,
Communication unavailable

ⓒ 2019 Rootech Inc. All Rights Reserved Page 205


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Rated Current Setup


The rated current should be set to a value less than the basic current of Accura 2550 modules.
Item Range Description
Rated current per feeder A [d][d] 1 A Rated current setup for Feeder 1
B [d][d] 1 A Rated current setup for Feeder 2
C [d][d] 1 A Rated current setup for Feeder 3 2

1 – basic current (default: basic current) 3


1. d → decimal number
2. The Accura 2550CMS-1P2F module only displays the rated current setup data for Feeder 1 and Feeder 2.
3. The basic current of Accura 2550CMS-1P3F/1P2F modules is as follows. The value set by users cannot exceed
the basic current value.

Module Basic Current


Accura 2550CMS-1P3F-60A 60 A
Accura 2550CMS-1P2F-60A 60 A

Load Direction Setup


Set the direction of the load depending on whether the load is installed on the left or right side of the
industrial control panel. The load direction setting applies to feeders 1, 2, and 3.

Item Range Description


Load Direction

Load on the right side


(default)

1P3F 1P2F

Load on the left side

1P3F 1P2F

Page 206 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Phase Selection Setup for 1P3F Module


In the 1P3F module, current sensors for individual feeders are located in its first, second, and fourth holes.
Unlike the sensors located in the second and fourth holes, the sensor in the first hole measures reverse
current. Thus, when wiring the module, the Neutral line should pass through the first hole of the module.
The phase selection mode of the module for each feeder can be set to line-to-neutral or line-to-line.

Item Range Description


Phase

Line-to-Neutral selected
(default)

Line-to-Line selected

ⓒ 2019 Rootech Inc. All Rights Reserved Page 207


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Phase Selection Setup for 1P2F Module

In the 1P2F module, current sensors for individual feeders are located in its first and third holes. The two
current sensors measure forward currents, and when wiring the module, the Hot line should pass through
the first and third holes of the module. The phase selection mode of the module for each feeder can be set
to line-to-neutral or line-to-line.

Item Range Description


Phase

Line-to-Neutral selected
(default)

Line-to-Line selected

Page 208 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Accura 2550CMM[Z]-3P Module

Applied Model

Module Basic Current Measuring Range Minimum


(Ib) (Accuracy Guaranteed) Measured Value

Accura 2550CMM[Z]-3P -60A 60 A 1.2 A − 72 A 0.06 A

Item Specification
Current Measurement accuracy IEC 61557-12 Class 0.5 ±0.5 % Reading
Leakage current 1 Fundamental current CMMZ-3P-60A ±0.5 % Reading ± 10 mA
measurement accuracy
Measuring range 1 mA − 2 A
Active power Measurement accuracy IEC 61557-12 Class 0.5
Active energy Measurement accuracy IEC 62053-21 Class 0.5
1. It is only supported on Accura 2550CMMZ-3P module.

LCD Display

Indication

ID Module ID 1

SET Setup mode


◀ Load direction 
▶ Load direction →
mA/A/kA Current unit
W/kW Power unit
ms/s Time unit [millisecond/second]

1. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.

Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication
Conflict ID Duplicate IDs There are more than 2 identical IDs.
Communication unavailable
Standby ID ID 255 Module ID for checking connection status,
Communication unavailable

ⓒ 2019 Rootech Inc. All Rights Reserved Page 209


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Display Mode

Accura 2550CMM[Z] module shows the display screen in the following sequence. By short pressing the SET
button, you can manually change the automatic display screen. Long press the SET button to enter the
setup mode.

Phase A Phase B Phase C Leakage


ID
Current/Power Current/Power Current/Powe Current 1

1. It is only supported on Accura 2550CMMZ-3P module.

Setup Mode

Setup Menu
If users short press the SET button, the setup menu appears in the following sequence. Accura 2550CMM[Z]
module allows users to select and utilize three-phase multi-feeder functionality depending on the load type.
ID Rated Current Load Direction 1
Phase Selection

1. The load direction setting applies to all phases A, B, and C.

Note

If there is no button operation for 30 seconds(the operating time can be set) in the setup mode or the edit
mode, the operation mode automatically returns to the display mode.

Page 210 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

ID Setup
Item Range Description

ID [d][d] 1 Module ID 2 setup


0 – 39 (default 255)

1. d → decimal number
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2550 modules
as a factory default value.

Module ID ID Description
Communication ID ID 0 – 39 ID of the module available for communication
Conflict ID Duplicate IDs There are more than 2 identical IDs.
Communication unavailable
Standby ID ID 255 Module ID for checking connection status,
Communication unavailable

Rated Current Setup


The rated current should be set to a value less than the basic current of Accura 2550CMM module.

Item Range Description


Rated current per feeder A [d][d] 1
A Phase A Rated current setup
B [d][d] 1
A Phase B Rated current setup
C [d][d] 1
A Phase C Rated current setup
1 – basic current (default: basic current) 3

1. The basic current of the three-phase power measuring module is as follows. The value set by users cannot exceed
the basic current value.

Module Basic Current


Accura 2550CMM-3P-60A 60 A
Accura 2550CMMZ-3P-60A

ⓒ 2019 Rootech Inc. All Rights Reserved Page 211


Chapter 5 Accura 2550 Accura 2500/2550 User Guide [AC]

Load Direction Setup


Set the direction of the load depending on whether the load is installed on the left or right side of the
industrial control panel.

Item Range Description


Load Direction

Load on the right side


(default)

Load on the left side

Load Mode Setup


Set the load mode according to the type of the load. For a three-phase load, set the mode to 3-Phase.
When you want to use each hole of the module to connect it to an individual load, set the mode to 1-Phase.
누설전류를 계측하는 Accura 2550CMMZ 모듈은 단상 멀티피더 동작을 지원하지 않는다.

Item Range Description


Load Mode

Three-phase load (default)

Single-phase load

Page 212 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 5 Accura 2550

Phase Sequence Setup


For three-phase loads, set the phase sequence in which cables pass through the holes of the module to a-
b-c or c-b-a. For single-phase loads, the phase sequence is set using two letters. The first letter refers to the
phase in which the cable passing through the hole of the module, and the second letter indicates the phase
of the cable that does not pass through the hole of the module. For example, when the cable of phase B
passes through the hole of the power measuring module for a single-phase load connected between phases
B and C, set the phase sequence to bc.

Item Range Description


Phase sequence
(When the load mode is set
to three-phase load)

Positive sequence (default)

Negative sequence

Phase selection
(When the load mode is set
to single-phase load) 1

Phase setup for each feeder


1. The phase selection mode for a single-phase load is displayed with two letters. The letter indicating the phase of
the cable passing through the hole of the module comes first.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 213


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Chapter 6 Functions
Voltage/Current Sampling
Accura 2500M module measures both AC and DC voltage. However, Accura 2550 modules are divided into
the module that measures AC current and the module that measures DC current. Therefore, you should use
the Accura 2550 module that suits your needs according to the AC/DC voltage specifications of the industrial
control panel.

Voltage Sensing

In Accura 2500M module, voltages drop due to the industrial control of resistance and are converted to the
ADC values through the AAF(Anti-Aliasing Filter). Obtained voltage data are converted into voltage
harmonics up to 50th order with the FFT(Fast Fourier Transform) algorithm. The processed voltage data are
sent to all the three-phase/single-phase power measuring modules connected with internal communication
cables.

Fig 6.1 Voltage Sensing and Signal Processing

Current Sensing

In Accura 2550 module, current values are converted through a Hall-Effect sensor or CT(Current Transformer)
and converted to ADC values through the AAF(Anti-Aliasing Filter). Obtained current data are converted into
current harmonics up to the 50th order with the FFT algorithm. Data on power and energy are obtained
based on the processed current data and the voltage data received from Accura 2500M module.

Fig 6.2 Current Sensing and Signal Processing

Page 214 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Measuring Time

Gapless sampling and calculation of measured signals are performed per cycle. Frame data are generated
by collecting data obtained over a period of 12 or 10 cycles. These data are aggregated, creating the data
for a period of longer than 0.2 seconds. For details about aggregation, refer to 「Chapter 6 Functions>
Aggregation」.

Frequency Cycle Frame 1 Sec

60 Hz 1 cycle (16.7 ms) 12 cycles (0.2 sec) 5 frames

50 Hz 1 cycle (20.0 ms) 10 cycles (0.2 sec) 5 frames

The frequency of the power source is automatically detected. For frequencies higher than 55 Hz,
measurements are performed at 60 Hz, and for those lower than 55 Hz, measurements are performed at 50
Hz. A frame refers to 0.2 seconds. It consists of 12 cycles at 60 Hz and 10 cycles at 50 Hz.

Measurements Per Cycle

Gapless processing of voltage and current signals is performed per cycle. Voltage sampling includes 512
samples per cycle while current sampling includes 256 samples per cycle. For each cycle, an FFT is performed
for voltage and current signals, and DC, RMS, fundamental, power and energy values are calculated based
on the values obtained during subsequent cycles.

Measured Signals Sampling Rate FFT Calculation Result


Voltage 512 samples/cycle DC, Fundamental waveform, Harmonics
(up to the 50th order)
Current 256 samples/cycle DC, Fundamental waveform, Harmonics
(up to the 50th order)

50

𝑣𝑚 (𝑡) = 𝑉𝑑𝑐,𝑚 + ∑ √2𝑉𝑘,𝑚 𝑐𝑜𝑠(2𝜋𝑘𝑓𝑡 + 𝜃𝑘,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐


𝑘=1

50

𝑖𝑚 (𝑡) = 𝐼𝑑𝑐,𝑚 + ∑ √2𝐼𝑘,𝑚 𝑐𝑜𝑠(2𝜋𝑘𝑓𝑡 + ∅𝑘,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐


𝑘=1

ⓒ 2019 Rootech Inc. All Rights Reserved Page 215


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Measurements

Measurement Parameters

The following table shows measurement parameters. Some of measurement data are provided only via
communication. Measured values displayed on Accura 2500D module are values obtained for 1-second
aggregation intervals generated by aggregating data from 5 frames. Measured values provided via
communication are values obtained for the aggregation intervals of 0.2, 1, and 5 seconds, 1 and 5 minutes,
1 and 6 hours. Users can choose the aggregation interval via communication. The default aggregation
interval is set to 1 second.
The maximum and minimum values provided on the Accura 2500D screen after resetting the max/min values
are stored in non-volatile memory. Thus, the data are maintained even when Accura 2500M is turned off.

▣ Displayed on Accura 2500D and provided via communication □ Available only via communication

Measurement Parameters Phase Average Aggregation Interval After Resetting Unit


/Total Avg. Max. Min. Max. Min.
Voltage RMS values of Line-to-neutral(LN) ▣ ▣ □ □ □ ▣ ▣ V
and Line-to-line(LL) voltages
Fundamental LN/LL voltage ▣ ▣ □ □ □ ▣ ▣ V
THD of LN/LL voltage ▣ □ □ ▣ %
Vector diagram(phasor) ▣ V
LL voltage unbalance (NEMA MG1) ▣ □ □ ▣ %
LN voltage unbalance (NEMA MG1) ▣ □ □ ▣ %
Zero-sequence unbalance ▣ □ □ ▣ %
Negative-sequence unbalance ▣ □ □ ▣ %
Residual voltage 1,
▣ □ □ □ ▣ ▣ V
Fundamental residual voltage
Frequency ▣ □ □ □ ▣ ▣ Hz
Current RMS current ▣ ▣ □ □ □ ▣ ▣ A
Fundamental current ▣ ▣ □ □ □ ▣ ▣ A
THD / TDD ▣ □ □ ▣ %
Vector diagram (phasor) ▣ A
Unbalance (NEMA MG1) ▣ □ □ ▣ %
Zero-sequence unbalance ▣ □ □ ▣ %
Negative-sequence unbalance ▣ □ □ ▣ %
Crest Factor ▣ □ □ ▣ -
K-Factor ▣ □ □ ▣ -
Residual current (fundamental) ▣ □ □ □ ▣ ▣ A
Leakage Fundamental and RMS values ▣ □ □ □ ▣ ▣ A
current

Page 216 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Power Active Power ▣ ▣ □ □ □ ▣ ▣ kW


Reactive Power ▣ ▣ □ □ □ ▣ ▣ kVAR
Apparent Power ▣ ▣ □ □ □ ▣ ▣ kVA
Power Power Factor ▣ ▣ □ □ □ ▣ ▣ -
Factor(PF) Displacement Power Factor □ □ □ □ □ □ □ -
PF Phase Angle (Lead/Lag) ▣ ▣ □ -
Energy Active Energy Received, Delivered, ▣ kWh
Sum, Net
Reactive Energy Quadrant 1/2/3/4 ▣ kVARh
Positive, Negative, □ kVARh
Sum(Total), Net
Apparent Energy ▣ kVAh
Demand Demand Demand/peak demand ▣ ▣ ▣ A
Current Predicted demand □ A
Demand Demand/peak demand ▣ ▣ ▣ kW
Active Power Predicted demand □ □ kW
Demand Demand/peak demand □ □ □ kVAR
Reactive Power Predicted demand □ □ kVAR
Demand Demand/peak demand □ □ □ kVA
Positive Power Predicted demand □ □ kVA
Harmonics Voltage harmonic magnitude ▣ V
(DC, harmonics up to the 50th order)
Current harmonic magnitude ▣ A
(DC, harmonics up to the 50th order)
RMS trend RMS voltage measured over □ V
1 cycle (refreshed every cycle)
RMS current measured over □ A
1 cycle (refreshed every cycle)
Instantaneous Voltage waveforms measured over ▣ V
waveform 2 cycles
Current waveforms measured over ▣ A
2 cycles
1. Residual voltage is calculated by adding up three-phase line-to-neutral voltages.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 217


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Voltage Wiring

3-Phase 4-Wire(3P4W) Connection


The wiring diagram is as follows.

Fig 6.3 Voltage Wiring with 3 PTs (3P4W)

The method of measuring voltage is as follows.


Vector Diagram Item Description

Line-to-neutral ▶ V1, V2, V3 sensing


V3 voltage sensing based on the wired VN terminal voltage
VA = V1

V1 VB = V2
VC = V3

VN Calculation of line-to- VAB = V1 – V2


V2 line voltages VBC = V2 – V3
VCA = V3 – V1

The following measurement data are provided.


Item LN Voltage LL Voltage Current Active/Reactive/Apparent Power

A phase VA VAB IA (I1) PA QA SA

B phase VB VBC IB (I2) PB QB SB

C phase VC VCA IC (I3) PC QC SC

Average/Total (VA+VB+VC)/3 (VAB+VBC+VCA)/3 (IA+IB+IC)/3 Ptot Qtot Stot

Page 218 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

3-Phase 3-Wire (3P3W) Connection


You can use 2 or 3 PTs(Potential Transformer) in 3-phase 3-wire connection. Its installation cost differs
according to the number of PTs. However, regardless of how many PTs are used, Accura 2500 measures
voltage signals in the same way.

Fig 6.4 Voltage Wiring with 2 PTs (3P3W)

ⓒ 2019 Rootech Inc. All Rights Reserved Page 219


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

The method of measuring voltage is as follows.


Vector Diagram Item Description
Calculation of virtual ▶ Virtual line-to-neutral voltage is calculated

V A = V1 – V n line-to-neutral voltage based on the virtual neutral point voltage.


VC
V B = V2 – V n VA = V1 – Vn
VC = V3 – Vn
VB = V2 – Vn
V3 Vn VA VC = V3 – Vn
The residual voltage value of the virtual line-to-
V1
VN neutral voltage is 0.
Calculation of line- VAB = V1 – V2
VB V2
to-line voltage VBC = V2 – V3
VCA = V3 – V1
Line-to-neutral ▶ V1, V2, V3 line-to-neutral voltage sensing
voltage sensing
V3 Calculation of ▶ Residual voltage calculation based on the
Vr = V1 + V2 +V3
residual voltage sensed line-to-neutral voltage
Vr = V1 + V2 + V3
V1
Vn = Vr / 3 Voltage calculation ▶ Virtual neutral-point voltage is calculated by
using the virtual dividing residual voltage by 3.
VN
neutral point Vn = Vr/3
V2 ▶ A newly calculated virtual neutral point is
the center of mass of the triangle consisting of
V1, V2, and V3

There is no actual neutral point in three-phase, three-wire voltage connection mode. Thus only line-to-line
voltage and the total power can be measured, but the actual voltage and power for each phase cannot be
measured. However, by using a virtual neutral point where the residual voltage value of three phase voltages
becomes zero, voltage and power values for each phase can be calculated.

Item LN Voltage LL Voltage Current Active/Reactive/Apparent Power

A phase VA VAB IA (I1) PA QA SA

B phase VB VBC IB (I2) PB QB SB

C phase VC VCA IC (I3) PC QC SC

Average/Total (VA+VB+VC)/3 (VAB+VBC+VCA)/3 (IA+IB+IC)/3 Ptot Qtot Stot

Page 220 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

1-Phase 3-Wire (1P3W) Connection


The wiring diagram is as follows.

Fig 6.5 Voltage Wiring with 2 PTs (1P3W)

The method of measuring voltage is as follows.


Vector Diagram Item Description

Line-to-neutral ▶ V1 and V3 line-to-neutral voltage sensing


V3 VN V1 voltage sensing based on the wired Vn terminal voltage
VA = V1
VB = 0 (The value becomes 0 in 1P3W mode.)
VC = V3

Line-to-line voltage VAB = VBC = 0 (The value becomes 0 in 1P3W


sensing mode.)
VCA = V3 – V1

The following measurement data are provided.


Item LN Voltage LL Voltage Current Active/Reactive/Apparent Power

A phase VA 0 IA (I1) PA QA SA

B phase 0 0 0 0

C phase VC VCA IC (I3) PC QC SC

Average/Total (VA+VC)/2 VCA (IA+IC)/2 Ptot Qtot Stot

ⓒ 2019 Rootech Inc. All Rights Reserved Page 221


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

1-Phase 2-Wire (1P2W) Connection


The wiring diagram is as follows.

Fig 6.6 Voltage Wiring with 1 PT (1P2W)

The method of measuring voltage is as follows.


Vector Diagram Item Description

Line-to-neutral ▶ V1 line-to-neutral voltage sensing based on


V3 VN V1 voltage sensing the wired Vn terminal voltage
VA = V1
VB = VC = 0 (the value becomes 0 in 1P2W
mode.)

Calculation of line-to- VAB = VA


line voltage VBC = VCA = 0 (the value becomes 0 in 1P2W
mode.)

The following measurement data are provided.


Item LN Voltage LL Voltage Current Active/Reactive/Apparent Power

A phase VA VA IA (I1) PA QA SA

B phase 0 0 0 0

C phase 0 0 0 0

Average/Total VA VA IA PA QA SA

Page 222 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Residual Voltage

For three-phase voltage measurement, line-to-neutral voltage for each phase is calculated with the following
formula including harmonic voltages up to the 50th order.
50

𝑣𝑚 (𝑡) = 𝑉𝑑𝑐,𝑚 + ∑ √2𝑉𝑘,𝑚 𝑐𝑜𝑠(2𝜋𝑘𝑓𝑡 + 𝜃𝑘,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐


𝑘=1

Residual voltage is generated by adding up each line-to-neutral voltage for each harmonic order, and the
RMS values are provided.

𝑣𝑟𝑠𝑑 = ∑ 𝑣𝑚 (𝑡)
𝑚=𝑎,𝑏,𝑐

The fundamental residual voltage is calculated by summing up the fundamental voltage of line-to-neutral
voltage on each phase.

𝑣𝑟𝑠𝑑,𝑓𝑢𝑛𝑑 = ∑ √2𝑉1,𝑚 𝑐𝑜𝑠(2𝜋𝑓𝑡 + 𝜃1,𝑚 )


𝑚=𝑎,𝑏,𝑐

Residual Current

For three-phase current measurement, line-to-neutral current for each phase is calculated with the following
formula including harmonic currents up to the 50th order.
.
50

𝑖𝑚 (𝑡) = 𝐼𝑑𝑐,𝑚 + ∑ √2𝐼𝑘,𝑚 𝑐𝑜𝑠(2𝜋𝑘𝑓𝑡 + ∅𝑘,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐


𝑘=1

Residual current is generated by adding up each line-to-neutral current for each harmonic order, and the
RMS values are provided.

𝑖𝑟𝑠𝑑 = ∑ 𝑖𝑚 (𝑡)
𝑚=𝑎,𝑏,𝑐

𝑖𝑟𝑠𝑑,𝑓𝑢𝑛𝑑 = ∑ √2𝐼1,𝑚 𝑐𝑜𝑠(2𝜋𝑓𝑡 + ∅1,𝑚 )


𝑚=𝑎,𝑏,𝑐

ⓒ 2019 Rootech Inc. All Rights Reserved Page 223


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Leakage Current

Accura 2550CMZ power/leakage current measuring modules and Accura 2550ZM leakage current measuring
module have built-in ZCTs. The leakage current sensed by the ZCT is calculated with the following formula
including harmonic currents up to the 50th order. The RMS and fundamental values are provided for the
leakage current.
50

𝑖𝑧 (𝑡) = 𝐼𝑑𝑐,𝑧 + ∑ √2𝐼𝑘,𝑧 𝑐𝑜𝑠(2𝜋𝑘𝑓𝑡 + ∅𝑘,𝑧 )


𝑘=1

AC Three-Phase Load
Load Module Note
Current 3P4W 3P3W
800A A2550CM-3P-800A-210-ZCT + external ZCT A2550CMZ-3P-800A-220 Caution 1

630A A2550CM-3P-800A-210-ZCT + external ZCT A2550CMZ-3P-630A-155


400A A2550CM-3P-800A-210-ZCT + external ZCT A2550CMZ-3P-400A-155
250A A2550CMZ-3P4W-250A-145 A2550CMZ-3P-250A Caution 2

125A A2550CMZ-3P-125A
100A A2550CMZ-3P-100A
60A - A2550CMZ-3P-60A For general
A2550CMZ-3P-60A For MCB
A2550CMS-3P4W-60A + A2550ZM-3P4W-60A-DI Split-core
(Connection of the leakage current measurement module)
5A A2550CM-3P-800A-210-ZCT + external ZCT Caution 1, 3

1. Accura 2550CM-3P module, which can connect an external ZCT, measures leakage current by connecting an externally
installed voltage-type ZCT to its ZCT connection port. The user must purchase the ZCT separately from the
ZCT manufacturer.
2. When applying the 250A leakage current measurement module to a 125A or 100A MCCB, caution is required during
installation because the width of the MCCB and the module do not match.
3. Leakage current measurement modules designed for three-phase 4-wire systems can also be applied to three-phase
3-wire systems during leakage current measurement.

AC Single-Phase Load
Load Module Note
Current
250A A2550CMZ-1P-250A -
125A A2550CMZ-1P-125A
100A A2550CMZ-1P-100A
60A A2550CMZ-1P-60A For general
A2550CMS-1P2F-60A + A2550ZM-1P2F-60A-DI Split-core,
(Connection of the leakage current measurement module) 2 feeder
A2550CMS-1P3F-60A + A2550ZM-1P3F-60A-DI Split-core,
(Connection of the leakage current measurement module) 3 feeder

Page 224 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Power Per Phase

The average active power per phase is calculated by multiplying voltage by current.
50

𝑃𝑚 = 𝑉𝑑𝑐,𝑚 𝐼𝑑𝑐,𝑚 + ∑ 𝑉𝑘,𝑚 𝐼𝑘,𝑚 𝑐𝑜𝑠(𝜃𝑘,𝑚 − ∅𝑘,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐


𝑘=1

There are two methods for calculating the reactive(Q) and apparent power(S) per phase.
1) Calculation from fundamental frequency components: Reactive power is calculated based on the
fundamental voltage and current values.
2) Calculation from RMS values: Reactive power is calculated based on the RMS voltage and current values
(including harmonics).
Reactive power and apparent power values can vary according to the method of calculating reactive power.
As the apparent power value changes, the power factor also changes.

Calculation from Fundamental Frequency Components


Reactive power per phase for the fundamental frequency is calculated.
𝑄𝑚 = 𝑉1,𝑚 𝐼1,𝑚 𝑠𝑖𝑛(𝜃1,𝑚 − ∅1,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐

Apparent power per phase is calculated with the vector sum of active power and reactive power.

𝑆𝑚 = √𝑃𝑚2 + 𝑄𝑚
2
𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐

Calculation from RMS Values


Apparent power per phase is calculated by multiplying the RMS voltage value by the RMS current value.
The RMS voltage and current values include harmonic components.

50 50
2 2 2 2
𝑉𝑟𝑚𝑠,𝑚 = √𝑉𝑑𝑐,𝑚 + ∑ 𝑉𝑘,𝑚 𝐼𝑟𝑚𝑠,𝑚 = √𝐼𝑑𝑐,𝑚 + ∑ 𝐼𝑘,𝑚 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐
𝑘=1 𝑘=1

𝑆𝑚 = 𝑉𝑟𝑚𝑠,𝑚 𝐼𝑟𝑚𝑠,𝑚

The magnitude of reactive power per phase is calculated based on apparent power and active power values
including harmonics. The sign of reactive power is the same as the sign of reactive power calculated with
fundamental frequency components.

2 − 𝑃2
𝑄𝑚 = ±√𝑆𝑚 𝑚

ⓒ 2019 Rootech Inc. All Rights Reserved Page 225


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Three-Phase Power

There are two methods for calculating the total three-phase reactive power(Qt) and apparent power(St).
1) Vector sum: The total apparent power is calculated based on the vector sum of three phase power.
2) Arithmetic sum: The total apparent power is calculated based on the arithmetic sum of three phase
power.
Total apparent and reactive power values can vary according to the method of calculating the total three
phase apparent power. As the total apparent power value changes, the total PF also changes.

Vector Sum Calculation


With the method, users can calculate the total active power, reactive power and apparent power with the
vector sum of three phase power vectors.
The total active power is calculated by adding up the active power for each phase.
𝑃𝑡 = 𝑃𝑎 + 𝑃𝑏 + 𝑃𝑐

The total reactive power is calculated by adding up the reactive power for each phase.
𝑄𝑡 = 𝑄𝑎 + 𝑄𝑏 + 𝑄𝑐

The total apparent power is calculated based on the vector sum of the total active power and reactive power.

𝑆𝑡 = √𝑃𝑡2 + 𝑄𝑡2

Fig 6.7 Vector Sum of the Total Apparent Power

Qt Qc St

Sc Qc

Pc
Qb
Sb Qb
Pb
Qa

Qa
Sa

Pa Pb Pc
Pt | St |

Page 226 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Arithmetic Sum Calculation


With the method, users can calculate the total active power by summing up the active power value for each
phase.
𝑃𝑡 = 𝑃𝑎 + 𝑃𝑏 + 𝑃𝑐

The total apparent power is calculated with the arithmetic sum of three phase apparent power vectors.
𝑆𝑡 = |𝑆𝑎 | + |𝑆𝑏 | + |𝑆𝑐 |

The magnitude of the total reactive power is calculated by calculating the magnitude of vector difference
between the total apparent power and active power. The sign of the total reactive power is the same as that
of the total reactive power calculated with the vector sum calculation method.

𝑄𝑡 = ±√𝑆𝑡2 − 𝑃𝑡2

Fig 6.8 Arithmetic Sum of the Total Apparent Power

Qt St

Sc Qc

Pc
Sb Qb
Pb

Qa
Sa

Pa Pb Pc
Pt | St |

ⓒ 2019 Rootech Inc. All Rights Reserved Page 227


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Power Factor(PF)

PF
Power Factor is the ratio of active power to apparent power. The sign of a power factor value is a positive
or negative value according to the sign of active power. A positive PF indicates the power is in received
status, and a negative PF indicates the power is in delivered status. If the apparent power is 0, the power
factor cannot be calculated. In this case, it can be set to 1.0 or 0.0, and the default value is 1.0.

𝑃𝑎 𝑃𝑏 𝑃𝑐
𝑃𝐹𝑎 = , 𝑃𝐹𝑏 = , 𝑃𝐹𝑐 =
𝑆𝑎 𝑆𝑏 𝑆𝑐

𝑃𝑡
𝑃𝐹𝑡 =
𝑆𝑡

The sign of the power factor can be removed through configuration. In this case, the received/delivered
status cannot be identified only through the power factor. How to calculate the PF when its sign is removed
is as follows.

𝑃𝑎 𝑃𝑏 𝑃𝑐
𝑃𝐹𝑎 = | |, 𝑃𝐹𝑏 = | |, 𝑃𝐹𝑐 = | |
𝑆𝑎 𝑆𝑏 𝑆𝑐

𝑃𝑡
𝑃𝐹𝑡 = | |
𝑆𝑡

Displacement Power Factor


Displacement Power Factor(DPF) is the ratio between the apparent power and reactive power of the
fundamental frequency component. Displacement power factor data are provided via communication.

𝑃1,𝑎 𝑃1,𝑏 𝑃1,𝑐


𝐷𝑃𝐹𝑎 = , 𝐷𝑃𝐹𝑏 = , 𝐷𝑃𝐹𝑐 =
𝑆1,𝑎 𝑆1,𝑏 𝑆1,𝑐

PF Angle (Lead/Lag)
The following figure shows the relationship between the sign of the power factor and Leading/Lagging
power factors for phase angles of voltage and current in the 4 quadrants. When reactive power(Q) is zero,
it is neither in leading nor lagging status.

Fig 6.9 PF Sign and Phase Angle (Lead/Lag)

Page 228 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Energy
Active Energy
Active power is accumulated in the unit of Wh for each sign. Active power data are displayed on the screen
of Accura 2500D and provided via communication in the unit of kWh. If the unit of energy is changed from
kWh to Wh through device setup, active energy is displayed on the screen of Accura 2500D and also
provided via communication in the unit of Wh.
The accumulated value for positive active power refers to received active energy, indicating power is
consumed. However, the accumulated value for negative active power refers to delivered active energy,
indicating power is supplied. Sum(Total) energy refers to the value obtained by adding delivered energy to
received energy. Net energy is the value obtained by subtracting delivered energy from received energy.

Active Energy Integer of the Accumulated Value Unit of Accumulation Available Data
Received 123,456 Wh 123 kWh
Delivered 11,222 Wh 11 kWh
Sum (Total) 134,678 Wh 134 kWh
Net 112,234 Wh 112 kWh

Reactive Energy
Reactive power is accumulated in the unit of VARh for each of the four quadrants. The screen of Accura
2500D displays reactive energy in the unit of kVARh. If the unit of energy is changed from kWh to Wh
through device setup, reactive energy is displayed on the screen of Accura 2500D and also provided via
communication in the unit of VARh.
The accumulated values for positive reactive power in quadrants 1 and 2 indicate positive reactive energy.
The accumulated values for negative reactive power in quadrants 3 and 4 indicate negative reactive energy.

Fig 6.10 Four Quadrant Diagram of Reactive Energy

Reactive Energy Integer of the Accumulated Value Unit of Accumulation Available Data
Quadrant 1 123,456 VARh 123 kVARh
Quadrant 2 22,000 VARh 22 kVARh
Quadrant 3 33,000 VARh 33 kVARh
Quadrant 4 44,000 VARh 44 kVARh

ⓒ 2019 Rootech Inc. All Rights Reserved Page 229


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Apparent Energy
Apparent power is accumulated in the unit of VAh. The screen of Accura 2500D module displays apparent
energy in the unit of kVAh. If the unit of energy is changed from kWh to Wh through device setup, apparent
energy is displayed on the screen of Accura 2500D and also provided via communication in the unit of VAh.

Apparent Energy Integer of the Accumulated Value Unit of Accumulation Available Data
- 123,456 VAh 123 kVAh

Energy Backup and Setup


Active, reactive, and apparent energy values are internally accumulated with 64-bit integers, thus they can
be accumulated for a very long time without a roll-over phenomenon. Energy values provided on the LCD
screen of Accura 2500D or via communication show 9 low-order digits. However, the device supports the
backup/setup function for energy in the 64-bit range to set up energy for maintenance.

Energy that can be Backed Description Setup Range Unit


Up and Set Up
Received active energy Accumulation of positive active power 0 – (263-1) Wh
Delivered active energy Accumulation of negative active power 0 – (263-1) Wh
Reactive energy in quadrant 1 Accumulation of reactive power in quadrant 1 0 – (263-1) VARh
Reactive energy in quadrant 2 Accumulation of reactive power in quadrant 2 0 – (263-1) VARh
Reactive energy in quadrant 3 Accumulation of reactive power in quadrant 3 0 – (263-1) VARh
Reactive energy in quadrant 4 Accumulation of reactive power in quadrant 4 0 – (2 -1)
63
VARh
Apparent energy Accumulation of apparent power 0 – (263-1) VAh

Page 230 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Demand

Demand Measurement
Demand time(Tdmd) is determined by multiplying a demand subinterval(Tsub) by the number of demand
subintervals. The average value of the demand time(Tdmd) is calculated over the sliding demand subinterval.
Peak demand is the maximum value obtained after the reset of the maximum and minimum values.
Demand time(Tdmd) [minute] = demand subinterval (Tsub) x the number of demand subintervals
E.g.) In Korea, 15 minutes is used as a demand subinterval, and the number of demand subintervals is 1.

Fig 6.11 Demand Calculation


source
input Demand Sub-Interval (Tsub=5 min)

Demand Time (Tdmd=Tsub*3=15 min)

Avg 2.6 Avg 3.0 Avg 4.0 Avg 4.8 Avg 4.3 Avg 2.5

1:15 1:20 1:25 1:30 1:35 1:40 1:45 time


(4.8+2.6+3.0)/3 (2.6+3.0+4.0)/3 (3.0+4.0+4.8)/3 (4.0+4.8+4.3)/3 (4.8+4.3+2.5)/3

demand output 3.47 3.20 3.93 4.37 3.87 (updated every Tsub)

Thermal Demand
The thermal demand(Pth) is calculated through the 1st-order LPF(low-pass-filter) as shown in the following
formula that includes the demand value(P) and the t value. The thermal demand(Pth) value is used to calculate
predicted demand.

1 1
𝑃𝑡ℎ [𝑛] = (1 − ) ∙ 𝑃𝑡ℎ [𝑛 − 1] + ∙ 𝑃[𝑛]
𝜏 𝜏

Here, τ refers to the thermal time constant, and it is calculated through the following formula, including the
thermal response index.

100 − (𝑇ℎ𝑒𝑟𝑚𝑎𝑙 𝑅𝑒𝑠𝑝𝑜𝑛𝑠𝑒 𝐼𝑛𝑑𝑒𝑥)


𝜏= ∙ 𝑇𝑠𝑢𝑏 ∙ 60 [𝑠𝑒𝑐]
100

If the thermal time constant τ is less than 1 second, it is calculated as 1 second.

Setup Item Description Setup Range Default


Thermal response index - Determines the response speed for the thermal demand 0 – 100 90
of predicted demand - As a set value gets greater, the thermal demand features
faster response time.
- When the thermal response index is set to 100, the Pth
value refers to the latest P value.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 231


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Predicted Demand
Predicted demand indicates that the demand at the end of the demand subinterval(Tsub) is predicted every
second while the subinterval continues. The average value of the current demand subinterval is calculated
every second, assuming that the thermal demand value remains constant during the remaining subinterval
while the current demand subinterval continues. Based on the average value, the predicted demand value
at the end of the demand subinterval is calculated.

Fig 6.12 Predicted Demand Calculation

Demand Sync
Accura 2500 supports two methods for synchronizing the starting time of a demand subinterval.
1) Hourly Auto Sync: automatically synchronizes the starting time of a demand subinterval every hour
2) Manual Sync: synchronizes the starting time of a demand subinterval at the time users issue a sync
command

For Hourly Auto Sync, synchronization is performed every 60 minutes. Thus, demand calculation is performed
only when the demand subinterval is an integer divided by 60. (demand subinterval(Tsub) = 1 minute, 2
minutes, 3 minutes, 4 minutes, 5 minutes, 6 minutes, 10 minutes, 12 minutes, 15 minutes, 20 minutes, 30
minutes, 60 minutes). A sync command for Manual Sync can be issued via 「SETUP > CONTROL > Reset >
Demand Sync」 menus or communication.

Page 232 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Fig 6.13 Hourly Auto Sync


source
input

Demand Time (T dmd=T sub*Nsub=15 min)

Avg 2.9 Avg 4.6 Avg 4.8 Avg 2.6 Avg 3.9 Avg 3.1

1:00 1:05 1:10 1:15 1:20 2:00 2:05 time

Hourly auto sync Hourly auto sync

Fig 6.14 Manual Sync


source
input

Demand Time (T dmd=T sub*Nsub=15 min)

Avg 4.3 Avg 4.7 Avg 2.9 Avg 3.4 Avg 3.2

1:00 1:04 1:09 1:14 1:19 1:59 2:04 2:09 time

Manual sync command

ⓒ 2019 Rootech Inc. All Rights Reserved Page 233


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Harmonics

Voltage Harmonics
Voltage sampling includes 512 samples per cycle, and the THD is calculated using harmonics up to the 50th
order.
50

𝑣𝑚 (𝑡) = 𝑉𝑑𝑐,𝑚 + ∑ √2𝑉𝑘,𝑚 𝑐𝑜𝑠(2𝜋𝑘𝑓𝑡 + 𝜃𝑘,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐


𝑘=1

The following formula shows how to calculate voltage THD for each phase.

√∑50 2
𝑘=2 𝑉𝑘,𝑚
𝑇𝐻𝐷𝑉,𝑚 =
𝑉1,𝑚

Current Harmonics
Current sampling includes 256 samples per cycle, and THD is calculated using harmonics up to the 50th
order.
50

𝑖𝑚 (𝑡) = 𝐼𝑑𝑐,𝑚 + ∑ √2𝐼𝑘,𝑚 𝑐𝑜𝑠(2𝜋𝑘𝑓𝑡 + ∅𝑘,𝑚 ) 𝑤ℎ𝑒𝑟𝑒 𝑚 = 𝑎, 𝑏, 𝑐


𝑘=1

The following formula shows how to calculate current THD for each phase.

√∑50 2
𝑘=2 𝐼𝑘,𝑚
𝑇𝐻𝐷𝐼,𝑚 =
𝐼1,𝑚

Page 234 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Unbalance (NEMA MG1)

Line-to-Neutral Voltage Unbalance


It indicates the maximum voltage deviation from the average value of three-phase line-to-neutral voltages.
Even when the magnitudes of line-to-neutral voltages are the same and voltage unbalance occurs between
phases, the unbalance value of the line-to-neutral voltage is zero.

𝑀𝑎𝑥(𝛥𝑉𝑝ℎ)
𝑃ℎ𝑎𝑠𝑒 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑈𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 = × 100 [%]
𝑉𝑝ℎ, 𝑎𝑣𝑔

Vph,avg : Average value of the line-to-neutral voltage


Max(ΔVph) : Maximum difference between the line-to-neutral voltage and the average line-to-neutral
voltage ∣Line-to-neutral voltage - the average voltage∣

Line-to-Line Voltage Unbalance


It indicates the maximum voltage deviation from the average value of three-phase line-to-line voltages.
When the magnitudes of line-to-neutral voltages are the same and voltage unbalance occurs between
phases, the unbalance ratio of the line-to-neutral voltage is zero. However, the unbalance value of the line-
to-line voltage is not zero.

𝑀𝑎𝑥(𝛥𝑉𝐿𝐿)
𝐿𝑖𝑛𝑒 𝑡𝑜 𝐿𝑖𝑛𝑒 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑈𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 = × 100 [%]
𝑉𝐿𝐿, 𝑎𝑣𝑔

VLL,avg : Average value of the line-to-line voltage


Max(ΔVLL) : Maximum difference between the line-to- line voltage and the average line-to- line voltage
∣Line-to-line voltage - the average voltage∣

Current Unbalance
It indicates the maximum current deviation from the average value of three-phase currents. Even when the
magnitudes of currents are the same and current unbalance occurs between phases, the current unbalance
value is zero.

𝑀𝑎𝑥(𝛥𝐼𝑝ℎ)
𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝑈𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 = × 100 [%]
𝐼𝑝ℎ, 𝑎𝑣𝑔

Iph,avg : Average value of three-phase currents


Max(ΔIph) : Maximum difference between the three-phase current value and the average value of three-
phase currents ∣Current – the average current∣

ⓒ 2019 Rootech Inc. All Rights Reserved Page 235


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Negative-Sequence/Zero-Sequence Unbalance

The fundamental components of three-phase currents and voltages can be divided into zero-sequence,
positive-sequence and negative-sequence components.

Fig 6.15 Symmetrical Components


Vc1 Vb2
Va0
Vb0
Va1
Vc0
Va2
Vb1 Vc2 Va0=Vb0=Vc0

Positive sequence Negative sequence Zero sequence

Zero-sequence component(U0): the component with the same magnitude and phase angle
Positive-sequence component(U1): three-phase symmetrical components with the phase sequence of A-B-C
Negative-sequence component(U2): three-phase symmetrical components with the phase sequence of
A-C-B

Zero-sequence(U0), positive-sequence(U1), and negative-sequence(U2) components are calculated with the


following formula.

𝑈0 1 1 1 1 𝑈𝑎 2𝜋
𝑗∙
[𝑈1 ] = ∙ [1 𝑎 𝑎2 ] ∙ [𝑈𝑏 ] , 𝑤ℎ𝑒𝑟𝑒 𝑎 = 𝑒 3
3
𝑈2 1 𝑎2 𝑎 𝑈𝑐

Negative-Sequence Unbalance
It is the ratio between the magnitudes of the negative-sequence component and the positive-sequence
component. The negative sequence unbalance of line-to-line voltages is always the same as the negative
sequence unbalance of line-to-neutral voltages.

𝑈2
𝑁𝑒𝑔𝑎𝑡𝑖𝑣𝑒 𝑠𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝑢𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 = × 100 [%]
𝑈1

Zero-Sequence Unbalance
It is the ratio between the magnitudes of the zero-sequence component and the positive-sequence
component. The zero-sequence component of line-to-line voltages is always 0.

𝑈0
𝑍𝑒𝑟𝑜 𝑠𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝑢𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 = × 100 [%]
𝑈1

Page 236 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Events
Power Quality Events
Factories, including semiconductor manufacturing plants need high quality power due to sensitive
manufacturing equipment and demanding manufacturing process control. For assessment of the power
quality of the supplied power, Accura 2500M supports Dip/Swell detection functions and three PQ curves,
such as SEMI F47-0706, IEC 61000-4-11/34 Class 3 and ITIC. It continuously generates RMS voltage values per
cycle to assess power quality. It generates RMS values of line-to-neutral voltages and line-to-line voltages
in 3P4W mode and in 3P3W mode, respectively. For power quality(PQ) events, it provides RMS trend data
measured over 1 cycle, as well as data on depth and duration.
Users can check power quality events through the events list in the event mode on Accura 2500D module.
The graph screen provides data on depth and duration, enabling users to view data on the power quality
events that have occurred at a glance. Also, it offers 1-cycle RMS trend data for three frames (before/when/
after the event occurs), which allows for detailed analysis of the event.

Analysis of Dip/Swell and PQ Curves Description


RMS measurement cycle 1 cycle (gapless)
Voltage LN voltage monitoring 3P4W mode
LL voltage monitoring 3P3W mode
Available data Depth Residual Voltage 1, Swell Voltage 2

Duration Time difference between the pickup time 3 and


the end time 4 of an event
1-cycle RMS trend RMS trend data for three frames
1. “Residual Voltage” indicates the minimum voltage during voltage dips.
2. “Swell Voltage” indicates the maximum voltage during voltage swells.
3. The pickup time of an event indicates the start time of collecting the sampled data over 1 cycle during which it is
presumed that dips/swells occurred.
4. The end time of an event indicates the end time of collecting the sampled data over 1 cycle during which it is
presumed that dips/swells ended.

Accura 2500M also supports the function of detecting transient voltage events to monitor voltage transients
measured in three phases. It performs voltage sampling at a rate of 512 samples per cycle and monitors
differences between sampled voltage values. By providing waveform data measured over one half cycle
before and after a transient voltage event occurs, it allows for analysis of transient voltages. Accura 2500M
monitors line-to-neutral voltages and line-to-line voltages in 3P4W mode and 3P3W mode, respectively.

Analysis of Transient Voltages Description


Sampling rate 512 samples/cycle (gapless)
Voltage LN voltage monitoring 3P4W mode
LL voltage monitoring 3P3W mode
Available event data Max. delta voltage
Waveform Waveforms measured over one half cycle
(512 samples/cycle)

ⓒ 2019 Rootech Inc. All Rights Reserved Page 237


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Dip(Sag)/Swell
Dip/swell functions operate based on the threshold and hysteresis set by users.
Fig 6.16 Voltage Dip Detection

PQ Curve
Accura 2500M provides assessment of PQ curves, including standards such as SEMI F47-0706, IEC 61000-4-
11/34 Class 3 and ITIC. The thresholds of the PQ curve are 90 %/110 % of the reference voltage, and the
hysteresis level is 2 % of the reference voltage. Users can set up the reference voltage of Accura 2500M.

PQ Curve Organization
SEMI F47-0706 SEMI(Semiconductor Equipment and Materials Institute)
IEC 61000-4-11/34 Class 3 IEC(International Electrotechnical Commission)
ITIC ITIC(Information Technology Industry Council)

PQ Curve Items Description Fixed Value


Threshold Critical voltage Dip/swell threshold: 90 % / 110 %
of the reference voltage (Vref)
Hysteresis Hysteresis 2 % of Vref

SEMI F47-0706
The following table and Fig 6.17 indicate the depths and durations of voltage dips.

Required Voltage Dip Immunity


Dip Depth 1 Duration at 50 Hz Duration at 60 Hz
50 % 10 cycles 12 cycles
70 % 25 cycles 30 cycles
80 % 50 cycles 60 cycles
Recommended Voltage Dip Immunity
Dip Depth 1 Duration at 50 Hz Duration at 60 Hz
0% 1 cycle 1 cycle
80 % 500 cycles 600 cycles
1. It is indicated as the Residual Voltage, the minimum voltage during voltage dips.

Page 238 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Fig 6.17 SEMI F47-0706 Curve (@ 60 Hz)


100

90
Percentage of Reference Voltage (% Vref)

80

70

60

50

40

30

20

10

0
0.6 c 1 c 6 c 12 c 30 c 60 c 600 c 6000 c
0.01 s 0.0167 s 0.1 s 0.2 s 0.5 s 1 s 10 s 100 s
Duration

IEC 61000-4-11/34 Class 3

Preferred Test Levels and Durations of Voltage Dips


Class 3 0 % during 0 % during 40 % during 70 % during 80 % during
0.5 cycles 1 cycle 10/12 1 cycles 25/30 1 cycles 250/300 1 cycles
1. n/m cycles means n cycles in the test performed at 50 Hz and m cycles in the test performed at 60 Hz.

Fig 6.18 IEC 61000-4-11/34 Class 3 Curve (@ 60 Hz)


100

90
Percentage of Reference Voltage (% Vref)

80

70

60

50

40

30

20

10

0
0.6 c 1c 6c 12 c 30 c 60 c 300 c 6000 c
0.01 s 0.0167 s 0.1 s 0.2 s 0.5 s 1s 5s 100 s

Duration

ⓒ 2019 Rootech Inc. All Rights Reserved Page 239


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

ITIC
The ITIC curve contains transients shorter than one cycle for voltage swells as shown in the table below.
However, Accura 2500M evaluates voltage swells based on RMS values measured over one cycle, thus, it
does not support measurements of transients.

ITIC (CBEMA) Curve (revised in 2000)


Swell 500 % during 200 % during 140 % during 120 % during
0.01/0.012 1 cycles - - 25/30 1 cycles
0.2 msec 1 msec 3 msec 0.5 sec
Dip - 0 % during 70 % during 80 % during
- 1 cycle 25/30 1 cycles 500/600 1 cycles
- 20 msec 0.5 sec 10 sec
1. n/m cycles means n cycles in the test performed at 50 Hz and m cycles in the test performed at 60 Hz.

Fig 6.19 ITIC Curve (for 60 Hz)


200

180
Percentage of Reference Voltage (% Vref)

160

140

120

100

80

60

40

20

0
0.6 c 1 c 6 c 12 c 30 c 60 c 600 c 6000 c
0.01 s 0.0167 s 0.1 s 0.2 s 0.5 s 1 s 10 s 100 s
Duration

Page 240 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Transient Voltage
Accura 2500M supports the function of detecting transient voltage events to monitor voltage transients
measured in three phases. It performs voltage sampling at a rate of 512 samples per cycle and monitors
differences between sampled voltage values. By providing waveform data measured over one half cycle
before and after a transient voltage event occurs, it allows for analysis of transient voltages. Accura 2500M
monitors line-to-neutral voltages and line-to-line voltages in 3P4W mode and 3P3W mode, respectively.

Fig 6.20 Transient Voltage Detection

ⓒ 2019 Rootech Inc. All Rights Reserved Page 241


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Measurement Events

Measurement events include voltage connection, current, leakage current, and user-defined events. There
are phase open and fuse fail events in voltage connection events. When connected to a grounded 3P3W
system, the device does not detect phase open and fuse fail events.
Current events refer to events on the current values measured by Accura 2550 modules while leakage current
events refer to events on the leakage current values measured by the 2550CMZ module. Users can configure
event detection modes, thresholds, and hysteresis values for current and leakage current events occurring
in each module on the Accura 2500D’s setup screen.
For user-defined events, users can set up input data and event detection methods via communication. Up
to 40 user-defined events are supported and can be set up with channels ranging from 1 to 40.
Accura 2500M module manages all events including events on Accura 2550 modules. Users can check event
data through the events list in the event mode on Accura 2500D module. Since RMS trend data measured
over one cycle are provided for three frames at the time an event occurs(before/when/after the event occurs),
users can conduct detailed analysis of events.

Phase Open Events


If the measured value of the line-to-neutral voltage is below the specific threshold as shown in the table
below, and the current value of the relevant phase remains smaller than the minimum measured value for 1
second, it is presumed that a phase open event occurs. However, if there is no current measuring module,
the occurrence of the event cannot be determined since current measurement data are unavailable.

Voltage Wiring 3P4W, 1P2W, 1P3W 3P3W 1

Threshold of the line-to-neutral voltage 20 % of Vref 65 % of Vref


Hold time 1 second 1 second
1. When connected to a grounded 3P3W system, the device does not detect phase open and fuse fail events.

Fuse Fail Events


If the measured value of the line-to-neutral voltage is below the specific threshold same as that of phase
open events, and the current value of the relevant phase remains greater than the minimum measured value
for 1 second, it is presumed that a fuse fail event occurs for the fuse inserted into the line where voltage is
measured. However, if there is no current measuring module, the occurrence of the event cannot be
determined since current measurement data are unavailable.

Page 242 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Current Events
Current events are divided into “Over” or “Under” events according to the current values measured by Accura
2550 modules at 0.2-second intervals. Users can configure threshold and hysteresis values for each 2550CM[Z]
module on the Accura 2500D’s setup screen. For details about event detection modes, refer to 「Chapter 6
Functions> Events > Measurement Events > User-Defined Events > Event Detection」.

Leakage Current Events


Leakage current events refer to “Over” events according to the leakage current values measured by Accura
2550CMZ modules at 0.2-second intervals. Users can configure threshold and hysteresis values for each
2550CMZ module on the Accura 2500D’s setup screen. For details about event detection modes, refer to
「Chapter 6 Functions> Events > Measurement Events > User-Defined Events > Event Detection」.

User-Defined Events
The following figure shows the block diagram of user-defined events for a channel. A total of 40 channels
can be set up via communication. User-defined events feature “Event Input Data” related to selecting event
input data, “Event Detection” related to processing events, and “Event Notification” sections related to
notifying users of the occurrence of events.

Fig 6.21 Block Diagram of User-Defined Events

Event Input Data


Voltage/Current/Power/Leakage Current items are provided for the selection of input data for processing
events. “Etc.” is provided as an additional item so that users can select data that do not belong to the above
items. Module IDs and phase data can be set up additionally for the provided items. For the “Etc.” item,
module IDs and offset number data and data type based on the communication map can be set up
additionally. Event input data are obtained at a 0.2-second frame time.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 243


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Event Detection
Event detection modes support “Over/Under/Off” items. “Over” refers to detecting events with values greater
than “Threshold” while “Under” refers to detecting events with values smaller than “Threshold”. “Off” refers
to deactivating the event detection function.
When “Over” is selected, if an event input value exceeds the Threshold in steady state, a Pickup Event occurs.
If it remains during “Time delay”, a Start Event occurs. If the input value drops below the “Threshold –
Hysteresis” level and returns to the normal mode, an End Event occurs.

When “Under” is selected, if an event input value exceeds the “Threshold” in steady state, a Pickup Event
occurs. If it remains above the “Low Limit” level during “Time delay”, a Start Event occurs. If the input value
gets back above the “Threshold + Hysteresis” level and returns to the normal mode, an End Event occurs.
If an event input value gets smaller than the “Threshold” and drops below the “Low Limit” within “Time
delay”, a Start Event does not occur. However, if the event input value gets back to the steady state, a Start
Event occurs.

Start, End, and Pickup events are supported by default. However, users can deactivate the function to detect
pickup events only via communication.

Fig 6.22 “Over” Condition Detection

Page 244 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Fig 6.23 “Under” Condition Detection

Threshold Hysteresis
Input data
(0.2 sec data) δ
Time delay

Low Limit

Pickup signal
Start event
End event

Threshold Hysteresis
Input data
(0.2 sec data) Time delay δ
δ
δ
Low Limit

Pickup signal
Start event
End event

Event Notifications
When a user-defined event occurs, it is recorded into an event log, and the device provides users with
notifications. In case of occurrence of an event, the EVENT LED flashes, and the color of the bell icon on the
upper right side of the screen is changed.

System Events

System events include events on module controls, communication status, and setup change. System events
are recorded into event logs, and when an event requiring inspection occurs, the device provides users with
notifications through the EVENT LED.

System Events Type EVENT LED Bell Icon Event Log


Accura 2550 module disconnected in a ring topology - - ○
Accura 2550 module taken out ○ ○ ○
Accura 2550 module added - ○ ○
Accura 2550 module’s connection status saved - - ○
Communication status: connected and disconnected - ○ ○
Setup change - ○ ○

ⓒ 2019 Rootech Inc. All Rights Reserved Page 245


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Providing Event Notifications and Resetting Notification Settings

EVENT LED Notifications


When a start or an end event occurs, it is recorded to the event log, and the number of new events appears
with the bell icon on the upper right side of Accura 2500D module. The EVENT LED on the front of Accura
2500D module also notifies you of the occurrence of the start event.

Setup for the EVENT LED can be performed via the following menu options.
▶ Main: 「SETUP > SYSTEM > LED」

Setup items are as follows.

Setup Items Description Setup Range Default


Event LED Period [sec] Period during which the Event LED is turned on and off 0.2 − 5.0 sec 1.0 sec
Event LED On-time [sec] Time period during which the LED is turned on. 0.1 − 5.0 sec 0.5 sec
If the On-time is equal to or longer than the Period, the LED
is turned on.
Event LED Hold Time [sec] Time period during which the EVENT LED keeps operating. 60,000 60,000
If the time elapses, the EVENT LED is reset. 0 − 59,999 sec

60,000: reset by users


0: automatically reset when an end event occurs
1 – 59,999: automatically reset when the preset time elapses

Resetting Event Notifications


The EVENT LED on the front of Accura 2500D module is automatically reset if you enter the event mode.
The number of new events appearing with the bell icon is reset if you access the events list.

Page 246 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Aggregation
Accura 2500M/2550 modules perform gapless sampling of voltage and current and generate one-cycle data
for each cycle. It also aggregates the data over either 12 cycles (for 60 Hz) or 10 cycles (for 50 Hz) to
generate 0.2-second frame data. Based on the 0.2-second data(Aggregation 0), it provides data aggregated
over intervals of 1 second or longer.
For general measurement parameters including voltage, current, power, and IO modules’ analog input and
output data, Accura 2500M provides the average/maximum/minimum values, and timestamp data for the
maximum/minimum values within an aggregation interval. It enables statistical analysis of measurement data.
The average value indicates the average of the values measured for 0.2 seconds within an aggregation
interval. The maximum and minimum values indicate the maximum and minimum values among the values
measured for 0.2 seconds during the aggregation interval. The timestamp data for the maximum/minimum
values indicate the time difference between the start time of the aggregation interval and the occurrence
time of the maximum/minimum values. Therefore, the actual time data can be obtained by adding the start
time of the aggregation interval to the time difference.
For specific measurement parameters including energy, demand, and IO modules’ digital input/output data,
the device provides the data measured for the last 0.2 seconds by latching the data. It enables users to
collect accurate data measured for the last 0.2 seconds within an aggregation interval with flexibility in time.

Fig 6.24 Aggregation Process for Avg/Max/Min Values

Fig 6.25 Aggregation Process for the Last Latched Values

Accura 2500M provides six fixed aggregation intervals, as well as five user-defined aggregation intervals that
enable users to set up the aggregation interval and the offset time for the start of the aggregation interval.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 247


Chapter 6 Functions Accura 2500/2550 User Guide [AC]

Fixed Aggregation

Accura 2500M provides six fixed aggregation intervals from Aggregation 1 through 6 (1 second, 5 seconds,
1 minute, 5 minutes, 1 hour, and 6 hours). For fixed aggregation intervals, the offset time for the start time
of the aggregation interval is fixed to zero. That is, the start time of the aggregation interval is set to start
at 0 hours 0 minutes 0 seconds. To set the offset time to a non-zero value, you should use the user-defined
aggregation function.
The displayed values on the LCD screen of Accura 2500D module are values measured during the 1-second
aggregation interval. The Max/Min values shown on the LCD screen are the maximum and minimum values
among the frame data obtained after resetting the max/min values, which are also provided via
communication through “Aggregation 255” setup.

Aggregation Name Aggregation Interval Buffer Length [Time] Buffer Index


Aggregation 0 0.2 seconds 60 12 seconds 0 – 9,999
Aggregation 1 1 second 30 30 seconds 0 – 9,999
Aggregation 2 5 seconds 10 50 seconds 0 – 9,999
Aggregation 3 1 minute 10 10 minutes 0 – 9,999
Aggregation 4 5 minutes 10 50 minutes 0 – 9,999
Aggregation 5 1 hour 10 10 hours 0 – 9,999
Aggregation 6 6 hours 10 60 hours 0 – 9,999
Aggregation 255 1 After Max/Min reset 5 - 0 – 9,999
1. The Max/Min values shown on Accura 2500D’s LCD screen are the Max/Min values among values measured for
0.2 seconds after users reset the values.

User-Defined Aggregation

Accura 2500M provides 5 user-defined aggregation intervals from Aggregation 11 to 15 that allow users to
arbitrarily set up the offset time for the aggregation interval and the start time.
If the offset setting is 0, the aggregation interval starts at 0 hours, 0 minutes, 0 seconds. For example, if you
want to collect the average data during 1-hour intervals at 10 minutes of each hour, you need to select one
of the aggregation intervals from Aggregation 11 to 15, set the aggregation interval to 3,600 seconds, and
set its offset time to 600 seconds.

Aggregation Name Aggregation Interval Buffer Length [Time] Buffer Index

Aggregation 11 (default) 3 seconds 10 (default) 30 seconds 0 – 9,999

Aggregation 12 (default) 15 minutes 10 (default) 150 minutes 0 – 9,999

Aggregation 13 (default) 2 hours 10 (default) 20 hours 0 – 9,999

Aggregation 14 (default) 12 hours 10 (default) 120 hours 0 – 9,999

Aggregation 15 (default) 1 day 10 (default) 10 days 0 – 9,999

Page 248 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Chapter 6 Functions

Collection of Aggregation Data

By selecting an aggregation interval, users can collect data on the selected aggregation interval via
communication using the Modbus map. Because the aggregated data are stored in the circular buffer in
Accura 2500M module for a certain period of time, users can collect aggregated measurement values with
greater flexibility.
The above table shows the sizes of the circular buffer for each aggregation interval. The recent circular index
can be easily identified because the circular buffer index is rotated within the range of 0 to 9,999, which is
greater than the buffer length.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 249


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Appendix A Specifications

General Specifications

Environmental Conditions
Installation location Indoors
Operating temperature -20 − 70 C (-4 − 158 ℉)
Safe operating temperature 1 -20 − 60 C (-4 − 140 ℉)
Storage temperature -40 − 85 C (-40 − 185 ℉)
Operating humidity 5 – 95 % (non-condensing)
Operating altitude Up to 2,000 m
Ingress protection against dust and water IEC 60529 IP54 (Accura 2500D)
General
Warranty period 2 years
1. Compliant with UL 61010-1(3rd edition)

Accura 2500M Main Industrial Control Panel Module


Power Supply: Accura 2500M-AC220V/DC110V
Port name L+, N-, (Ground)
Connector type Terminal block 1 (M3.5/bolt head Ø6)
Wire specification 0.34 – 4.0 mm2 (22 – 12 AWG), copper
Wire temperature rating Above 70 ˚C
Power supply voltage (Us) 2 AC 100 – 240 V 50/60 Hz, DC 100 – 300 V, CAT II
Operating voltage range 0.9 x Us – 1.1 x Us
Power consumption 3
Maximum 20 W
Inrush current 4 Peak 31 A, duration : no more than 1 msec (AC 220 V)
Peak 11 A, duration : no more than 0.2 msec (DC 110 V)
Power Supply: Accura 2500M-DC24V
Port name L+, N-, (Ground)
Connector type Terminal block 16 (M4.0/bolt head Ø7)
Wire specification 0.75 – 6.0 mm2 (18 – 10 AWG), copper
Wire temperature rating Above 70 ˚C
Power supply voltage (Us) DC 24 V, CAT II
Operating voltage range DC 20 – 30 V
Power consumption 3 Maximum 20 W
Inrush current 4 Peak 6 A, duration : no more than 1 msec (DC 24 V)
Voltage Input
Port name V1, V2, V3, VN
Connector type Terminal block 17 (M4/bolt head Ø7)
Wire specifications 0.75 – 6.0 mm2 (18 – 10 AWG), copper
Wire temperature rating Above 70 ˚C
Measurement category Category III
Frequency range 42 – 65 Hz
Impedance 10 MΩ/phase

Page 250 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Burden 0.01 VA/phase @AC 220 V


Connection with Accura 2500D via Communication
Dedicated communication Sends/receives data to/from Accura 2500D
Protocol Internal dedicated protocol
Connector type RJ45 connector (for connection with a communication cable)
Communication cable Internal communication cable for the display module 5

(Cat 5e 24 AWG FTP)


Cable length Up to 3 m
Connection with Accura 2550 via Communication
Dedicated communication Sends/receives data to/from Accura 2550 module
Protocol Internal dedicated protocol
Port 2 ports for each group, 4 ports for 2 groups
(The ports have the same function.)
Connector type RJ45 connector
Communication cable Internal communication cable 6, 7

Cable length The total cable length in a group: up to 50 m


(each cable: up to 10 m)
Wiring Device connection in a ring topology with 2 ports within a
group (Communication redundancy supported)
Number of connectable In a group Maximum 30 modules
modules 8
In two groups Maximum 40 modules
Connection with the Host System via External Communication
Ethernet communication Sends/receives data to/from the host system
Protocol Modbus TCP protocol
Port 2 Ethernet switch ports 9

Connector type RJ45 connector


Communication cable Ethernet cable Cat 5e FTP, STP, SFTP 10

Cable length Maximum 100 m


Communication speed 100Base-TX (100Mbps/Full Duplex)
Wiring method Star, daisy-chain, ring topology (RSTP 11 supported)
Number of modules Maximum 20 modules
connectable in a daisy
chain
RS-485 communication Sends/receives data to/from the host system
Protocol Modbus RTU protocol
Port 1 port / Ta(TRX+), Tb(TRX-)
Connector type Terminal block 1 Accura 2500M-AC220V/DC110V
(M3.5/bolt head Ø6)
Terminal block 16 Accura 2500M-DC24V
(M4.0/bolt head Ø7)
Communication cable UL2919 RS-485 1P/2P 24 AWG
Cable length Up to 1,219 m (4,000 ft)
Bit rate 1,200 / 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps12
Maximum number of 32 for each bus 12

connectable modules

ⓒ 2019 Rootech Inc. All Rights Reserved Page 251


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Voltage Measurement
Voltage wiring method 3P4W, 3P3W, 1P3W, 1P2W
Sampling rate 512 samples/cycle
Measurement cycle Basic measurement Frame: 0.2 sec (12 cycles @60 Hz, 10 cycles @50 Hz)
(gapless) Dip/Swell measurement 1 cycle
Voltage Measuring range AC 35 – 347 V L-N (Line-to-neutral)
(accuracy guaranteed) AC 60 – 600 V L-L (for unearthed Delta & Y systems)
Accuracy IEC 61557-12 Class 0.5 ±0.5 % Reading
Min. measured value 5 V Line-to-neutral
Measurement data Line-to-neutral voltage, Line-to-line voltage
Fundamental voltage, harmonics (up to the 50th order) 13

Vector diagram (phasor), waveforms, THD


Symmetrical components(positive/negative/zero sequence)
Unbalance according to symmetrical components/the NEMA
standard
Residual voltage Measuring method Measured by summing up 3-phase line-to-neutral voltages
Measurement data RMS, Fundamental
Accuracy / ±0.5 % Un 14 / Up to 347 V Line-to-neutral
Measuring range
Frequency Measuring range 42 – 65 Hz
Power Quality
Dip/Swell 13
Measured value / RMS voltage(refreshed every cycle) Threshold set by users
Threshold
PQ Curve 13
Measured value / RMS voltage(refreshed every cycle) Dip/swell thresholds:
Threshold 90 % / 110 % of Vref
Curve type SEMI F47-0706, IEC 61000-4-11/34 Class 3, ITIC
Transient voltage Measured value / Differences between sampled Threshold set by users
Threshold voltage values (512 samples/cycle)
THD, Voltage harmonics 13
Harmonic order Up to the 50th order
Measurement data THD, Magnitude of each harmonic
Voltage unbalance Measurement data Line-to-neutral voltage / Line-to-line voltage unbalance
according to the NEMA standard
Zero-sequence/ negative-sequence voltage unbalance
Events
Power quality event Type Dip/Swell, PQ Curve, Transient voltage
Phase open/fuse fail event Measured value RMS data measured at 0.2-sec intervals
Time delay 1 second
Current event Measured value RMS data measured at 0.2-sec intervals
Detection method Users can select either “Over” or “Under” item.
Leakage current event Measured value RMS data measured at 0.2-sec intervals
Detection method Users can select “Over” item.
User-defined event 15 Input data Data measured at 0.2-sec intervals
Selectable among Voltage/Current/Power/Leakage Current/Etc.
Threshold Set by users
Detection method Users can select either “Over” or “Under” item.
Number of event 40
channels

Page 252 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Management Function
Management of Maximum number of connectable modules: 30 in a group / 40 for both groups
Accura 2550 modules Provides data on Accura 2550 modules according to the request from the host system
Automatic detection of module connection status, Assignment of module IDs
Sends the voltage data of the incoming line to multiple Accura 2550 modules
Collects measurement and operational status data from multiple Accura 2550 modules
1. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.4 Nm(14 kgf-cm, 12 lbf-in).
2. The device conforms to UL standards for the tested AC power supply voltage.
3. It refers to the maximum power consumption based on the power supply input voltage when Accura 2500D and
Accura 2550 modules are connected.
4. When installing fuses on the power line, it is recommended to use fuses that are UL-listed with an RK5 class or
higher and are rated at 2 A/500 V.
5. It is provided with the product.
6. It is provided with the product. Additional cables needed for a ring topology are sold separately.
7. The conducting wire of the communication cable should be at least 0.205 mm2 (24 AWG). It is recommended to keep
a distance of over 5 mm from the power lines generating high levels of noise.
8. It varies by the type of the connected module and the cable length between modules.
Refer to 「Appendix B Module Connection」 for details about module connection.
9. The built-in Ethernet switch enables the connection of Accura 2500M modules without the need for a separate switch.
10. FTP(Foiled Shielded Twisted Pairs), STP(Braided Shielded Twisted Pairs), SFTP(Braided Foiled Shielded Twisted Pairs)
11. RSTP(Rapid Spanning Tree Protocol), IEEE 802.1D-2004.
12. At 115,200 bps, a master can communicate with up to 16 slave devices, and the maximum distance between
the master and the slave is 600 m.
13. It is calculated with line-to-line voltage in 3P3W mode and line-to-neutral voltage in 3P4W mode.
14. The basic voltage Un is 277 V line-to-neutral voltage.
15. User-defined events can be configured only via communication.
16. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.2 Nm(12 kgf-cm, 10.6 lbf-in).
17. The max. tightening torque of the terminal screws of the barrier-type terminal block is 1.8 Nm(18.4 kgf-cm, 16 lbf-in).

ⓒ 2019 Rootech Inc. All Rights Reserved Page 253


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Accura 2500D Industrial Control Panel HMI Module

Power Supply
Power supply voltage Receives power from Accura 2500M using its built-in connector or the internal
communication cable for the display module
LCD Display
LCD features 5” (108.0 x 64.8 mm) Color TFT LCD
800 x 480 pixels
LED backlight & touch panel (The LCD screen can be touched.)
LEDs
LEDs on the front POWER Power LED
EVENT Blinks when an event occurs (It can be set to be turned on.)
ETHERNET Blinks when the device communicates with the host system via
Ethernet (It can be set to be turned on.)
MODULE Blinks when Accura 2500M communicates with Accura 2550
(It can be set to be turned on.)
Buttons
Buttons on the front HOME Display mode Used to move to the main Home screen or the
measurement screen of the relevant module
SETUP Setup mode Used to move to the main Setup screen or the
Setup screen of the relevant module
EVENT Event mode Used to move to the main Event screen or the
Event screen of the relevant module
BACK Used to move to the previous screen
Connection with Accura 2500M
Integrated connection Attaches/detaches Accura 2500M to/from the back of Accura 2500D through the built-in
connector
Connection using a cable Connects Accura 2500D to Accura 2500M using the RJ45 internal communication cable
for the display module
Internal Communication with Accura 2500M
Dedicated communication Sends/receives data to/from Accura 2500M
Protocol Internal protocol
Connector type RJ45 connector (for connection with the communication cable)
Communication cable Internal communication cable for the display module 1

(Cat 5e 24 AWG FTP)


Cable length Maximum 3 m
1. It is provided with the product.

Page 254 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Accura 2550CM[Z]-3P/CMZ-3P4W Three-phase Power/Leakage Current Measuring


Module
Power Supply
Power supply voltage Receives power through the internal communication cable
Voltage Input
Voltage input Receives sampled voltage data from Accura 2500M via communication
Current Input
Connector type Through-hole type (using cables/busbars)
Hole Dimensions / Model Hole Dimensions [mm] Weight [g]
Weight CM/CMZ
Three-phase Accura 2550CM-3P -800A-210 46.0 x 23.0 1,500 / -
-800A-210-ZCT 46.0 x 23.0 1,500 / -
-630A-145 32.0 x 22.4 1,000 / -
-630A-145-ZCT 32.0 x 22.4 1,000 / -
-400A-140 32.0 x 22.4 1,000 / -
-400A-140-ZCT 32.0 x 22.4 1,000 / -
Accura 2550CMZ-3P -800A-220 46.0 x 22.9 - / 2,500
-630A-155 35.0 x 25.4 - / 1,500
-400A-155 35.0 x 25.4 - / 1,500
Accura 2550CM[Z]-3P -250A Ø21.0 x 22.0 140 / 300
-125A Ø16.5 x 20.5 130 / 235
-100A Ø13.5 x 17.5 115 / 175
-60A Ø13.5 x 17.5 115 / 175
Accura 2550CM-3P -5A 1 Ø10.0 155 / -
-5A-ZCT 1 Ø10.0 155
Three-phase 4-wire Accura 2550CMZ-3P4W -250A-145 Ø21.0 x 22.0 - / 330
Display
LCD features 13 x 18 mm Customized Mono LCD, LED backlight
Button
SET button Used to move to the measurement screen, enter the SETUP mode, and change settings
Connection with the Module
Dedicated Connects with Accura 2500M or Accura 2550 module
communication Protocol Internal protocol
Connector type RJ45 connector
Communication cable Internal communication cable 2

Measurement
Frequency 50/60 Hz
Sampling rate 256 samples/cycle
Measurement cycle Frame: 0.2 sec (12 cycles @60 Hz, 10 cycles @50 Hz)
(gapless)

ⓒ 2019 Rootech Inc. All Rights Reserved Page 255


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Current Model Measuring Range Minimum


Basic Current
(Accuracy Measured
(Ib)
Guaranteed) Value
Accura 2550CM-3P -800A-210 800 A 16.0 A − 960 A 0.80 A
-800A-210-ZCT 800 A 16.0 A − 960 A 0.80 A
-630A-145 630 A 12.6 A − 756 A 0.63 A
-630A-145-ZCT 630 A 12.6 A − 756 A 0.63 A
-400A-140 400 A 8.0 A − 480 A 0.40 A
-400A-140-ZCT 400 A 8.0 A − 480 A 0.40 A
Accura 2550CMZ-3P -800A-220 800 A 16.0 A − 960 A 0.80 A
-630A-155 630 A 12.6 A − 750 A 0.63 A
-400A-155 400 A 8.0 A − 480 A 0.40 A
Accura 2550CM[Z]-3P -250A 250 A 5.0 A − 300 A 0.25 A
-125A 125 A 2.5 A − 150 A 0.13 A
-100A 100 A 2.0 A − 120 A 0.10 A
-60A 60 A 1.2 A − 72 A 0.06 A
Accura 2550CM-3P -5A 1 5A 0.1 A − 6A 0.01 A
-5A-ZCT 1
5A 0.1 A − 6A 0.01 A
Accura 2550CMZ-3P4W -250A-145 250 A 5.0 A − 300 A 0.25 A
Measurement accuracy IEC 61557-12 Class 0.5 ±0.5 %
Reading
Measurement data RMS, Fundamental, Harmonics (up to the 50th order)
Vector diagram(phasor), waveforms,
THD, TDD, Crest factor, K-factor
Symmetrical components (positive-, negative-, zero-
sequence components)
Unbalance according to symmetrical components /
the NEMA standard
Leakage current 3
Measuring method Measured by the built-in ZCT
Measuring range 1 mA – 2 A
Measurement data Fundamental, RMS
Fundamental current CMZ-3P-800A ±0.5 % Reading ± 60 mA
measurement accuracy CMZ-3P- ±0.5 % Reading ± 30 mA
630A/400A/250A
CMZ-3P-125A/100A/60A ±0.5 % Reading ± 20 mA
CMZ-3P4W-250A-145 ±0.5 % Reading ± 30 mA
Operating range Up to 120 % Ib of phase current
Power Active Measurement IEC 61557-12 Class 0.5
Reactive accuracy IEC 61557-12 Class 1
Apparent IEC 61557-12 Class 0.5
Measurement data Power per phase, the sum of 3-phase power values

Page 256 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Energy Active Measurement IEC 62053-21 Received/delivered active energy


Class 0.5
Reactive accuracy IEC 62053-24 Reactive energy in 4 quadrants
Class 1
Apparent IEC 61557-12 Class 0.5
Power factor Power factor per phase/ total power factor,
Displacement power factor per phase 4

Current demand Peak demand, predicted demand Demand time can be set up according to the
Power demand Peak demand, predicted demand demand subinterval value and the number of
demand subintervals
Current unbalance Measurement data Current unbalance according to the NEMA standard
Zero-sequence, negative-sequence current
unbalance
Power Quality
Current harmonics Harmonic order Up to the 50th order
THD, TDD Measurement data THD, TDD, Magnitude of each harmonic
Event
Current events Measured value RMS value measured at 0.2-sec intervals
Detection method Users can select either “Over” or “Under” item.
Leakage current Measured value RMS value measured at 0.2-sec intervals
events Detection method Users can select “Over” item.
1. Accura 2550CM-3P-5A module can be used by externally installing CTs (the secondary current rating: 5 A).
2. It is provided with the product. Additional cables needed for a ring topology are sold separately. The conducting wire
of the communication cable should be at least 0.205 mm2 (24 AWG). It is recommended to keep a distance of
over 5 mm from the power lines generating high levels of noise.
3. The data are available with Accura 2550CMZ modules with built-in ZCTs.
4. The data are available only via communication.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 257


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Accura 2550CM[Z]-1P Power/Leakage Current Measuring Module

Power Supply
Power supply voltage Receives power through the internal communication cable
Voltage Input
Voltage input Receives sampled voltage data from Accura 2500M via communication
Current Input
Connector type Through-hole type (using cables/busbars)
Hole Dimensions/Weight Model Hole Dimensions [mm] Weight [g] CM/CMZ
Accura 2550CM[Z]-1P -250A Ø21.0 x 22.0 125 / 270
-125A Ø16.5 x 20.5 85 / 155
-100A Ø13.5 x 17.5 80 / 125
-60A Ø13.5 x 17.5 80 / 125
Display
LCD features 12 x 10 mm Customized Mono LCD, LED backlight or
13 x 18 mm Customized Mono LCD, LED backlight
Button
SET button Used to move to the measurement screen, enter the setup mode, and change settings
Connection with the Module
Dedicated communication Connects with Accura 2500M or Accura 2550 module
Protocol Internal protocol
Connector type RJ45 connector
Communication cable Internal communication cable 1

Measurement
Frequency 50/60 Hz
Sampling rate 256 samples/cycle
Measurement cycle(gapless) Frame: 0.2 sec (12 cycles @60 Hz, 10 cycles @50 Hz)
Current Model Basic Measuring Range Minimum
Current (Ib) (Accuracy Guaranteed) Measured Value
Accura 2550CM[Z]-1P -250A 250 A 5.0 A − 300 A 0.25 A
-125A 125 A 2.5 A − 150 A 0.13 A
-100A 100 A 2.0 A − 120 A 0.10 A
-60A 60 A 1.2 A − 72 A 0.06 A
Measurement accuracy IEC 61557-12 Class 0.5 ±0.5 % Reading
Measurement data RMS, Fundamental, Harmonics (up to the 50th order)
Vector diagram (phasor), waveforms
THD, TDD, Crest factor, K-factor
Leakage current 2 Measuring method Measured by the built-in ZCT
Measuring range 1 mA – 2 A
Measurement data RMS, Fundamental
Fundamental current CMZ-1P-250A ±0.5% Reading ± 30 mA
measurement accuracy CMZ-1P-125A/100A/60A ±0.5 % Reading ± 20 mA
Operating range Up to 120 % Ib of phase current

Page 258 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Power Active Measurement IEC 61557-12 Class 0.5


Reactive accuracy IEC 61557-12 Class 1
Apparent IEC 61557-12 Class 0.5
Energy Active Measurement IEC 62053-21 Class 0.5 Received/delivered active energy
Reactive accuracy IEC 62053-24 Class 1 Reactive energy in 4 quadrants
Apparent IEC 61557-12 Class 0.5
Power factor Power factor, Displacement power factor 3

Current demand Peak demand, predicted Demand time is determined by the demand subinterval
demand value and the number of demand subintervals.
Power demand Peak demand, predicted
demand
Power Quality
Current harmonics Harmonic order Up to the 50th order
THD, TDD Measurement data THD, TDD, Magnitude of each harmonic
Events
Current events Measured value RMS value measured at 0.2-sec intervals
Detection method Users can select either “Over” or “Under” item.
Leakage current events 2
Measured value RMS value measured at 0.2-sec intervals
Detection method Users can select “Over” item.
1. It is provided with the product. Additional cables needed for a ring topology are sold separately.
The conducting wire of the communication cable should be at least 0.205 mm2 (24 AWG).
It is recommended to keep a distance of over 5 mm from the power lines generating high levels of noise.
2. The data are available with Accura 2550CMZ modules with built-in ZCTs.
3. The data are available only via communication.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 259


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Accura 2550CMS/ZM-3P4W Split-Core Power/Leakage Measuring Module


Power Supply
Power supply voltage Receives power through the internal communication cable
Voltage Input
Voltage input Receives sampled voltage data from Accura 2500M via communication
Current Input
Connector type Through-hole type (using cables/busbars)
Hole Dimensions/Weight Model Hole Dimensions [mm] Weight [g]
Split-core power Accura 2550CMS-3P4W-60A 10.4 x 20.3 430
measuring module
Split-core leakage current Accura 2550ZM-3P4W-60A-DI 70.0 x 20.5 210
measuring module
Display
LCD features 13 x 18 mm Customized Mono LCD, LED backlight
Button
SET button Used to move to the measurement screen, enter the setup mode, and change settings
Connection with the Module
Dedicated communication Connects to Accura 2500M or Accura 2550 module
Protocol Internal protocol
Connector type RJ45 connector
Communication cable Internal communication cable 1

Measurement
Frequency 50/60 Hz
Sampling rate 256 samples/cycle
Measurement cycle (gapless) Frame: 0.2 sec (12 cycles @60 Hz, 10 cycles @50 Hz)
Current Model Basic Measuring Range Minimum
Current (Ib) (Accuracy Guaranteed) Measured Value

Accura 2550CMS-3P4W-60A 60 A 3.0 A − 72 A 0.24 A


Measurement accuracy 2 IEC 61557-12 Class 0.5 ±0.5 % Reading
Measurement data RMS, Fundamental, Harmonics (up to the 50th order)
Vector diagram (phasor), waveforms
THD, TDD, Crest factor, K-factor
Symmetrical components
(positive-, negative-, zero-sequence components)
Unbalance according to symmetrical components/the NEMA
standard
Residual current (RMS, Fundamental)

Leakage current Measuring method Measured by the built-in ZCT of Accura 2550ZM
Measuring range 1 mA − 2 A
Measurement data Fundamental, RMS
Fundamental current ±0.5 % Reading ± 10 mA
measurement accuracy 3

Operating range Up to 120 % Ib of phase current

Page 260 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Power Active Measurement 2 IEC 61557-12 Class 0.5


Reactive accuracy IEC 61557-12 Class 1
Apparent IEC 61557-12 Class 0.5
Measurement data Power per phase, the sum of 3-phase power values
Energy Active Measurement 2 IEC 62053-21 Class 0.5 Received/delivered active energy
Reactive accuracy IEC 62053-24 Class 1 Reactive energy in 4 quadrants
Apparent IEC 61557-12 Class 0.5
Power factor Power factor per phase/ total power factor,
Displacement power factor per phase 4

Current/Power demand Peak demand, predicted Demand time can be set up according to the demand subinterval
demand value and the number of demand subintervals
Current unbalance Measurement data Current unbalance according to the NEMA standard
Zero-sequence, negative-sequence current unbalance
Power Quality
Current harmonics Harmonic order Up to the 50th order
THD, TDD Measurement data THD, TDD, Magnitude of each harmonic
Digital Input: Available with Accura 2550ZM Module
Connector type SMW250-03D (2.50 mm pitch connector)
Channel/Port name 2 channels / DI 1 DI2 DIG (isolation between channels)
Communication cable length 50 cm (provided with the product)
Input type Internal DC 5 V power supply (self-excitation), isolation between channels
Minimum pulse width 100 msec
Event
Current events Measured value RMS value measured at 0.2-sec intervals
Detection method Users can select either “Over” or “Under” item.
Leakage current events Measured value RMS value measured at 0.2-sec intervals
Detection method Users can select “Over” item.
1. It is provided with the product. Additional cables needed for a ring topology are sold separately.
The conducting wire of the communication cable should be at least 0.205 mm2 (24 AWG).
It is recommended to keep a distance of over 5 mm from the power lines generating high levels of noise.
2. The split-core CMS module has been calibrated under the condition where the power line passes through
the top center position of its hole. As the location of the power line is away from the top center position of the hole,
errors in current, power, and energy measurements can increase by up to 1 %.
3. To ensure accurate measurements of leakage current when wiring the 3P4W leakage current measuring module,
you should put together all four power lines and make them pass through the center of its hole.
4. The data are available only via communication.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 261


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Accura 2550CMS/ZM-1P3F/1P2F Split-Core Power/Leakage Measuring Module


Power Supply
Power supply voltage Receives power through the internal communication cable
Voltage Input
Voltage input Receives sampled voltage data from Accura 2500M via communication
Current Input
Connector type Through-hole type (using cables/busbars)
Hole Dimensions/Weight Model Hole Dimensions [mm] Weight [g]
Split-core power Accura 2550CMS-1P3F-60A 10.4 x 20.3 430
measuring module Accura 2550CMS-1P2F-60A 10.4 x 20.3 350
Split-core leakage current Accura 2550ZM-1P3F-60A-DI Ø21.0 330
measuring module Accura 2550ZM-1P2F-60A-DI Ø21.0 230
Display
LCD features 13 x 18 mm Customized Mono LCD, LED backlight
Button
SET button Used to move to the measurement screen, enter the setup mode, and change settings
Connection with the Module
Dedicated communication Connects to Accura 2500M or Accura 2550 module
Protocol Internal protocol
Connector type RJ45 connector
Communication cable Internal communication cable 1

Measurement
Frequency 50/60 Hz
Sampling rate 256 samples/cycle
Measurement cycle (gapless) Frame: 0.2 sec (12 cycles @60 Hz, 10 cycles @50 Hz)
Current Model Basic Measuring Range Minimum
Current (Ib) (Accuracy Guaranteed) Measured Value
Accura 2550CMS-1P3F-60A 60 A 3.0 A − 72 A 0.24 A

Accura 2550CMS-1P2F-60A 60 A 3.0 A − 72 A 0.24 A

Measurement accuracy 2 IEC 61557-12 Class 0.5 ±0.5 % Reading


Measurement data RMS, Fundamental, Harmonics (up to the 50th order)
Vector diagram(phasor), waveforms
THD, TDD, Crest factor, K-factor
Leakage current Measuring method Measured by the built-in ZCT of Accura 2550ZM
Measuring range 1 mA − 2 A
Measurement data Fundamental, RMS
Fundamental current ±0.5 % Reading ± 5 mA
measurement accuracy
Operating range Up to 120 % Ib of phase current
Power Active Measurement 2 IEC 61557-12 Class 0.5
Reactive accuracy IEC 61557-12 Class 1
Apparent IEC 61557-12 Class 0.5
Measurement data Power per feeder

Page 262 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Energy Active Measurement 2 IEC 62053-21 Class 0.5 Received/delivered active energy
Reactive accuracy IEC 62053-24 Class 1 Reactive energy in 4 quadrants
Apparent IEC 61557-12 Class 0.5
Power factor Power factor per feeder, Displacement power factor per feeder 3
Current/Power demand Peak demand, predicted Demand time can be set up according to the demand subinterval
demand value and the number of demand subintervals
Power Quality
Current harmonics Harmonic order Up to the 50th order
THD, TDD Measurement data THD, TDD, Magnitude of each harmonic
Digital Input: Available with Accura 2550ZM Module
Connector type SMW250-03D (2.50 mm pitch connector)
Channel / Port name 2 channels / DI1 DI2 DIG (isolation between channels)
Communication cable length 50 cm (provided with the product)
Input type Internal DC 5 V power supply (self-excitation), isolation between channels
Minimum pulse width 100 msec
Event
Current events Measured value RMS value measured at 0.2 sec intervals
Detection method Users can select either “Over” or “Under” item.
Leakage current events Measured value RMS value measured at 0.2 sec intervals
Detection method Users can select “Over” item.
1. It is provided with the product. Additional cables needed for a ring topology are sold separately.
The conducting wire of the communication cable should be at least 0.205 mm2 (24 AWG). It is recommended to keep
a distance of over 5 mm from the power lines generating high levels of noise.
2. The split-core CMS module has been calibrated under the condition where the power line passes through
the top center position of its hole. As the location of the power line is away from the top center position of the hole,
errors in current, power, and energy measurements can increase by up to 1 %.
3. The data are available only via communication.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 263


Appendix A Specifications Accura 2500/2550 User Guide [AC]

Accura 2550CMM[Z] Three-Phase Power/Leakage Current Measuring Module for


MCBs
Power Supply
Power supply voltage Receives power through the internal communication cable
Voltage Input
Voltage input Receives sampled voltage data from Accura 2500M via communication
Current Input
Connector type Through-hole type (using cables/busbars)
Hole Dimensions/Weight Model Hole Dimensions [mm] Weight [g]
Three-phase power measuring Accura 2550CMM-3P-60A Ø 10.4 / Ø 5.9 100
module for MCBs
Three-phase power/leakage Accura 2550CMMZ-3P-60A Ø 10.5 150
current measuring module
for MCBs
Display
LCD features 13 x 18 mm Customized Mono LCD, LED backlight
Button
SET button Used to move to the measurement screen, enter the setup mode, and change settings
Connection with the Module
Dedicated communication Connects with Accura 2500M or Accura 2550 module
Protocol Internal protocol
Connector type RJ45 connector
Communication cable Internal communication cable 1

Measurement
Frequency 50/60 Hz
Sampling rate 256 samples/cycle
Measurement cycle (gapless) Frame: 0.2 sec (12 cycles @60 Hz, 10 cycles @50 Hz)
Current Model Basic Measuring Range Minimum
Current (Ib) (Accuracy Guaranteed) Measured Value
Accura 2550CMM[Z]-3P-60A 60 A 1.2 A − 72 A 0.06 A
Measurement accuracy 2 IEC 61557-12 Class 0.5 ±0.5 % Reading
Measurement data RMS, Fundamental, Harmonics (up to the 50th order)
Vector diagram (phasor), waveforms
THD, TDD, Crest factor, K-factor
Symmetrical components (positive-, negative-, zero-sequence
components)
Unbalance according to symmetrical components/
the NEMA standard
Residual current (RMS, Fundamental)
3
Leakage Current Measuring method Measured by the built-in ZCT
Measuring range 1 mA − 2 A
Measured data RMS, fundamental
Accuracy ±0.5 % Reading ± 10 mA
Operating range Up to 120 % of phase current Ib

Page 264 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix A Specifications

Power Active Measurement IEC 61557-12 Class 0.5


Reactive accuracy IEC 61557-12 Class 1
Apparent IEC 61557-12 Class 0.5
Measurement data Power per phase, the sum of 3-phase power values
Energy Active Measurement IEC 62053-21 Class 0.5 Received/delivered active energy
Reactive accuracy IEC 62053-24 Class 1 Reactive energy in 4 quadrants
Apparent IEC 61557-12 Class 0.5
Power factor Power factor per phase/ total power factor, Displacement power
factor per phase 2

Current/Power demand Peak demand, predicted Demand time can be set up according to the demand
demand subinterval value and the number of demand subintervals
Power Quality
Current harmonics Harmonic order Up to the 50th order
THD, TDD Measurement data THD, TDD, Magnitude of each harmonic
Digital Input
Connector type SMW250-03D (2.5 mm pitch connector)
Channel/Port name 2 channels / DI1 DI2 DIG (isolation between channels)
Communication cable length 50 cm (provided with the product)
Input type Internal DC 5 V power supply (self-excitation), isolation between channels
Minimum pulse width 100 msec
Event
Current events Measured value RMS value measured at 0.2-sec intervals
Detection method Users can select either “Over” or “Under” item.
Leakage current events Measured value RMS value measured at 0.2-sec intervals
Detection method Users can select “Over” item.
1. It is provided with the product. Additional cables needed for a ring topology are sold separately.
The conducting wire of the communication cable should be at least 0.205 mm2 (24 AWG).
It is recommended to keep a distance of over 5 mm from the power lines generating high levels of noise.
2. The data are available only via communication.
3. It is only supported in Accura 2550CMMZ module.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 265


Appendix B Module Connection Accura 2500/2550 User Guide [AC]

Appendix B Module Connection


Accura 2500M module supports ports in two groups for communication with multiple Accura 2550 modules.
Modules can be connected in a ring topology with 2 ports in a group. A ring topology supports
communication redundancy, which increases reliability of communication.

Connecting Accura 2500M module to multiple Accura 2550 modules causes the following limitations.
1) Limitation in the length of the communication cable due to voltage drops
2) Limitation in the number of connectable modules due to power consumption
3) Limitation in the number of connectable modules in a group: up to 30 modules

Therefore, check connectivity of modules in advance using the 「Power Supply/Communication Cable
Simulator for Accura 2500/2550」 provided separately for connection of multiple Accura 2550 modules with
different current consumption values. Before connecting modules, you can select the length of each
communication cable, the module type, and the number of connectable modules. If a limitation in connecting
modules occurs due to voltage drops or different power consumption, a warning window appears to inform
users that modules cannot be connected under the selected condition.

Limitation in the Length of the Communication Cable due to Voltage Drops

The entire communication cable length in a group is up to 50 m, and each cable should be up to 10 m.
However, the voltage drop on the cable caused by power consumption of Accura 2550 modules can limit
the cable length and the number of connectable Accura 2550 modules.
It is recommended to connect a module with high power consumption close to Accura 2500M when
connecting multiple Accura 2550 modules. It is because it causes less voltage drop on the communication
cable, enabling users to connect more modules.
The following table shows the power consumption for different types of Accura 2550 modules.

Page 266 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix B Module Connection

Module Type Power Consumption


Accura 2550CM-3P-800A/630A/400A 435 mW
Accura 2550CMZ-3P-800A/630A/400A 445 mW
Accura 2550CM[Z]-3P-250A 405 mW
Accura 2550CM[Z]-3P-125A/100A/60A 300 mW
Accura 2550CM-3P-5A 200 mW
Accura 2550CMZ-3P4W-250A 405 mW
Accura 2550CM[Z]-1P-250A 235 mW
Accura 2550CM[Z]-1P-125A/100A/60A 205 mW
Accura 2550CMS-3P4W-60A 505 mW (When connected to Accura 2550ZM-3P4W-60A-DI module)
Accura 2550CMS-1P3F-60A 515 mW (When connected to Accura 2550ZM-1P3F-60A-DI module)
Accura 2550CMS-1P2F-60A 510 mW (When connected to Accura 2550ZM-1P2F-60A-DI module)
Accura 2550CMM-3P-60A 300 mW
Accura 2550CMMZ-3P-60A 325 mW
Accura 2550DCM-500V-80A 645 mW
Accura 2550DCM-50V-80A
Accura 2550GW 460 mW
Accura 2550GWM 1,500 mW
Accura 2550TEMP 960 mW (When connected to 6 Accura TSEN/THSEN devices)
Accura 2550VOL 380 mW
Accura 2550SAL-3P-DO 2,000 mW
Accura 2550IO -DI1 515 mW
-DI2 590 mW
-DO1 1,070 mW
-DO2 2,015 mW
-AI1 515 mW
-AI2 540 mW
-RTD1 515 mW
-RTD2 580 mW
Accura 2550PS 20,000 mW (supplied)
15,000 mW (consumption)

Limitation in the Number of Connectable Modules due to Power Consumption

Accura 2500M’s power source supplies power up to 15 W based on the output voltage of 5 V. Its power
consumption is up to 7 W. Thus, when connecting modules, you should refer to the power consumption of
each module to ensure that the total power consumption of connected modules does not exceed 8 W.

Device Item Description


Accura 2500M Power supply Up to 15 W
Power consumption of main devices Up to 7 W (including Accura 2500D)
Total power consumption of connected modules Up to 8 W

ⓒ 2019 Rootech Inc. All Rights Reserved Page 267


Appendix B Module Connection Accura 2500/2550 User Guide [AC]

Limitation in the Number of Connectable Modules in a Single Group

The table below shows the number of connectable Accura 2550 modules when the cable length between
the port on Accura 2500M and the first Accura 2550 module is 3 m, and the cable length between the rest
of the modules is 10 cm, 20 cm, or 30 cm in a single group. Even though the total power consumption of
connected modules does not exceed 8 W, up to 30 Accura 2550CM[Z] modules can be connected in a single
group. The following table shows the number of connectable Accura 2550 modules decreases when
connecting modules with higher power consumption.

Module Type Number of Power Communication Cable


Connectable Modules Consumption
in a Single Group of Modules
Accura 2550CM[Z]-1P-125A/100A/60A Up to 30 5.9 W Length between the port on
Accura 2550CM[Z]-1P-250A Up to 30 7.1 W Accura 2500M and the 1st
Accura 2550CM[Z]-3P-125A/100A/60A/5A Up to 26 7.8 W Accura 2550 module: 3 m
Accura 2550CM[Z]-3P-250A Up to 19 7.6 W Length between the rest of
Accura 2550CMZ-3P4W-250A Up to 19 7.6 W connected modules: 10 cm
Accura 2550CM-3P-800A/630A/400A Up to 18 7.8 W Length between the port on
Accura 2550CMZ-3P-800A/400A Up to 18 7.8 W Accura 2500M and the 1st
Accura 2550 module: 3 m

Length between the rest of


connected modules: 30 cm
Accura 2550CMS-3P4W-60A Up to 15 7.8 W Length between the port on
+ Accura 2550ZM-3P4W-60A Accura 2500M and the 1st
Accura 2550 module: 3 m

Length between the rest of


connected modules: 10 cm
Accura 2550CMS-1P3F-60A Up to 15 7.8 W Length between the port on
+ Accura 2550ZM-1P3F-60A Accura 2500M and the 1st
Accura 2550 module: 3 m

Length between the rest of


connected modules: 20 cm
Accura 2550CMS-1P2F-60A Up to 15 7.8 W Length between the port on
+ Accura 2550ZM-1P2F-60A Accura 2500M and the 1st
Accura 2550 module: 3 m
Accura 2550CMM[Z]-3P-60A Up to 25 8.0 W
Length between the rest of
connected modules: 10 cm

Note
Check connectivity of modules in advance using the Power Supply/Communication Cable Simulator for
Accura 2500/2550 provided separately for connection of multiple Accura 2550 modules with different
power consumption values.

Page 268 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix B Module Connection

Fig B.1 Module Connection Diagram in a Single Group

Connection using a single port (No Ring) Connection using two ports (No Ring) Connection using two ports (Ring)

The two ports used in a single group as shown in the above figure have the same functions. A ring topology
enables communication redundancy, which enhances communication reliability.

Connecting Modules in Two Groups

When it is not possible to connect Accura 2500M to all Accura 2550 modules in a single group, connect the
modules that can be connected in a single group and then connect Accura 2500M to the rest of the modules
using ports in the other group. Up to 40 Accura 2550 modules can be connected to Accura 2500M using
ports in two groups.

Fig B.2 Module Connection Diagram in Two Groups

ⓒ 2019 Rootech Inc. All Rights Reserved Page 269


Appendix C Standards Accura 2500/2550 User Guide [AC]

Appendix C Standards
Measurement Accuracy
IEC61557-12 Power metering and monitoring devices (PMD)
IEC62053-21 Static meters for AC active energy (classes 0.5, 1 and 2)
IEC62053-22 Static meters for AC active energy (classes 0.1S, 0.2S and 0.5S)
IEC62053-24 Static meters for fundamental reactive energy (classes 0.5S, 1S, 1, 2 and 3)
Power Quality
IEC 61000-4-30 Power quality measurement methods
Safety
UL 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use
EMC
EN 55011 Conducted emissions
EN 55011 Conducted emissions (asymmetric mode)
EN 55011 Radiated emissions
IEC 61000-3-2 Limits for harmonic current emissions
IEC 61000-3-3 Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply
systems
IEC 61000-4-2 Electrostatic discharge(ESD) immunity test
IEC 61000-4-3 Radiated, radio-frequency, electromagnetic field immunity test
IEC 61000-4-4 Electrical fast transient/burst immunity test
IEC 61000-4-5 Surge immunity test
IEC 61000-4-6 Immunity to conducted disturbances, induced by radio-frequency fields
IEC 61000-4-8 Power frequency magnetic field immunity test
IEC 61000-4-11 Voltage dips, short interruptions and voltage variations immunity test
Certifications
UL UL 61010-1 3rd edition, UL 61010-2-030 2nd edition
CE EN 55011:2009/A1:2010, EN IEC 61326-1:2021, EN IEC 61326-2-1:2021,
EN IEC 61000-3-2:2019/A1:2021, EN 61000-3-3:2013/A2:2021
KC EN 55011:2009/A1:2010, EN IEC 61326-1:2021, EN IEC 61326-2-1:2021

Page 270 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix C Standards

IEC 61557-12: 2018 Performance Measuring and Monitoring Devices (PMD)

Active Power and Active Energy


Voltage Range Current Range Power Factor (cos) Class 0.5
PMD Dx PMD Sx
80 %Un – 120 %Un 2 %Ib – 10 %Ib 1 %In – 5 %In 1.0 ±1.0 %
10 %Ib – Imax. 5 %In – Imax. 1.0 ±0.5 %
5 %Ib – 20 %Ib 2 %In – 10 %In 0.5 inductive ±1.0 %
0.8 capacitive ±1.0 %
20 %Ib – Imax. 10 %In – Imax. 0.5 inductive ±0.6 %
0.8 capacitive ±0.6 %

Reactive Power and Reactive Energy


Voltage Range Current Range Sin Class 1 Class 2

PMD Dx PMD Sx
80 %Un – 120 %Un 5 %Ib – 10 %Ib 2 %In – 5 %In 1.0 ±1.25 % ±2.5 %
10 %Ib – Imax. 5 %In – Imax. 1.0 ±1.0 % ±2.0 %
10 %Ib – 20 %Ib 5 %In – 10 %In 0.5 ±1.25 % ±2.5 %
20 %Ib – Imax. 10 %In – Imax. 0.5 ±1.0 % ±2.0 %
0.25 ±1.25 % ±2.5 %

Apparent Power and Apparent Energy


Voltage Range Current Range Class 0.5

PMD Dx PMD Sx
80 %Un – 120 %Un 5 %Ib – 10 %Ib 2 %In – 5 %In ±1.0 %
10 %Ib – Imax. 5 %In – Imax. ±0.5 %

Frequency
Voltage Range Current Range Frequency Class 0.02

PMD Dx PMD Sx
50 %Un – Umax 20 %Ib – Imax. 10 %In – Imax. 45 – 55 Hz ±0.02 %
55 – 65 Hz

RMS Phase Current


PMD Types Current Range Min. Bandwidth Crest Factor Class 0.5
(Harmonic)
PMD Sx 10 %In – Imax. 45 Hz to 15 times 2 ±0.5 %
PMD Dx 20 %Ib – Imax. rated frequency

ⓒ 2019 Rootech Inc. All Rights Reserved Page 271


Appendix C Standards Accura 2500/2550 User Guide [AC]

Neutral Current Calculated (from Phase Currents)


PMD Types Phase Current Min. Bandwidth Crest Factor Class 0.5
Range (Harmonic)

PMD Sx 10 %In – Imax. 45 Hz to 15 times 2 ±0.5 % 1

PMD Dx 20 %Ib – Imax. rated frequency


1. Uncertainty is indicated as a percentage of the largest phase current value.

Neutral Current Measured (with a Sensor)


PMD Types Neutral Current Min. Bandwidth Crest Factor Class 0.5
Range (Harmonic)
PMD Sx 10 %In – Imax. 45 Hz to 15 times 2 ±0.5 %
PMD Dx 20 %Ib – Imax. rated frequency

RMS Voltage
Voltage Range Min. Bandwidth (Harmonic) Crest Factor Class 0.5

Umin. – Umax. 45 Hz to 15 times rated frequency 1.5 ±0.5 %

Power Factor
Voltage Range Current Range Power Factor Class 0.5
PMD Dx PMD Sx

50 %Un – Umax. 20 %Ib – Imax. 10 %In – Imax. 0.5 inductive – ±0.005 1

0.8 capacitive
1. There is no unit for the value.

Page 272 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix C Standards

IEC 62053-21:2020 Static Meters for AC Active Energy (Classes 0.5, 1 and 2)

Voltage Range Current Range Power Factor Class 0.5


for directly for transformer (cos)
connected meters operated meters
90 %Un – 110 %Un 5 %In – 10 %In 2 %In – 5 %In 1.0 ±1.0 %
10 %In – Imax 5 %In – Imax 1.0 ±0.5 %
10 %In – 20 %In 5 %In – 10 %In 0.5 inductive ±1.0 %
0.8 capacitive ±1.0 %
20 %In – Imax 10 %In – Imax 0.5 inductive ±0.6 %
0.8 capacitive ±0.6 %

IEC 62053-22:2020 Static Meters for AC Active Energy (Classes 0.1S, 0.2S and 0.5S)

Voltage Range Current Range Power Factor Class 0.5S


for only transformer operated meters (cos)
90 %Un – 110 %Un 1 %In – 5 %In 1.0 ±1.0 %
5 %In – Imax. 1.0 ±0.5 %
2 %In – 10 %In 0.5 inductive ±1.0 %
0.8 capacitive ±1.0 %
10 %In – Imax. 0.5 inductive ±0.6 %
0.8 capacitive ±0.6 %

IEC 62053-24:2020 Static Meters for Fundamental Reactive Energy (Classes 0.5S, 1S, 1, 2 and 3)

Voltage Range Current Range Sin Class 1S 1 Class 1


for directly for transformer
connected meters operated meters
90 %Un – 110 %Un 5 %In – 10 %In Imin 2 – 5 % In 1.0 ±1.5 % ±1.5 %
10 %In – Imax. 5 %In – Imax. 1.0 ±1.0 % ±1.0 %
10 %In – 20 %In 5 %In – 10 %In 0.5 ±1.5 % ±1.5 %
20 %In – Imax. 10 %In – Imax. 0.5 ±1.0 % ±1.0 %
0.25 ±2.0 % ±2.0 %
1. It is the value measured by externally installing CTs.
2. Imin value for Class 1S is 1 % In, and Imin value for Class 1 is 2 % In.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 273


Appendix D Accuracy/Reliability Accura 2500/2550 User Guide [AC]

Appendix D Accuracy/Reliability

Accuracy

Measurement by Accura 2500M

Item Accuracy Measuring Range(Accuracy Guaranteed) /


Minimum Measured Value
Voltage Line-to-neutral IEC 61557-12 Class 0.5 35 – 347 V Line-to-neutral /
5 V Line-to-neutral
Line-to-line IEC 61557-12 Class 0.5 60 – 600 V L-L / 9 V L-L
Residual voltage 0.5 % Un 1
Up to 347 V Line-to-neutral
Frequency IEC 61557-12 Class 0.02 (±10 mHz) 42 – 65 Hz
1. The basic voltage Un is 277 V line-to-neutral voltage.

Measurement by Accura 2550CM[Z]

Accura 2550CM[Z] modules meet measurement accuracy within the range broader than the measuring
range required for the IEC 61557-12 standard as shown in the table below.

Item Accuracy Measuring Range(Accuracy Guaranteed)


/ Minimum Measured Value
Current IEC 61557-12 Class 0.5 2 %Ib – 120 %Ib / 0.1 %Ib 1

Power Active IEC 61557-12 Class 0.5 2 %Ib – 120 %Ib


Reactive IEC 61557-12 Class 1 2 %Ib – 120 %Ib
Apparent IEC 61557-12 Class 0.5 2 %Ib – 120 %Ib
Energy Active IEC 62053-21 Class 0.5 2 %Ib – 120 %Ib
Reactive IEC 62053-24 Class 1 2 %Ib – 120 %Ib
Apparent IEC 61557-12 Class 0.5 2 %Ib – 120 %Ib
Power factor IEC 61557-12 Class 0.5 (0.005) 2 %Ib – 120 %Ib
Leakage current 2
CMZ-800A ±0.5 % Reading ± 60 mA 60 mA – 2A / 1mA
CMZ-630A/400A/250A ±0.5 % Reading ± 30 mA 30 mA – 2A / 1mA
CMZ-125A/100A/60A ±0.5 % Reading ± 20 mA 20 mA – 2A / 1mA
1. Ib indicates the basic current of Accura 2550CM[Z] modules.
2. It is measured by Accura 2550CMZ modules and Accura 2550CM-3P modules, which can connect an external ZCT.
The measurement accuracy indicates that of the fundamental component of leakage current.

Page 274 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix D Accuracy/Reliability

Measurement by Accura 2550CMS/ZM

Item Accuracy Measuring Range(Accuracy Guaranteed)


/ Minimum Measured Value
Current IEC 61557-12 Class 0.5 3.0 A – 72 A / 0.24 A
Power Active IEC 61557-12 Class 0.5 3.0 A – 72 A
Reactive IEC 61557-12 Class 1 3.0 A – 72 A
Apparent IEC 61557-12 Class 0.5 3.0 A – 72 A
Energy Active IEC 62053-21 Class 0.5 3.0 A – 72 A
Reactive IEC 62053-24 Class 1 3.0 A – 72 A
Apparent IEC 61557-12 Class 0.5 3.0 A – 72 A
Power factor IEC 61557-12 Class 0.5 (±0.005) 3.0 A – 72 A
Leakage current 1 CMS/ZM-3P4W-60A 2 ±0.5 % Reading ± 10 mA 10 mA – 2 A / 1 mA
CMS/ZM-1P3F-60A ±0.5 % Reading ± 5 mA 5 mA – 2 A / 1 mA
CMS/ZM-1P2F-60A ±0.5 % Reading ± 5 mA 5 mA – 2 A / 1 mA
1. It is measured by Accura 2550ZM modules. The measurement accuracy indicates that of the fundamental component
of leakage current.
2. To ensure accurate measurements of leakage current when wiring the ZM-3P4W leakage current measuring module,
you should put together all four power lines and make them pass through the center of its hole.

Measurement by Accura 2550CMM[Z]


Accura 2550CMM[Z] modules meet measurement accuracy within the range broader than the measuring
range required for the IEC 61557-12 standard as shown in the table below.
Item Accuracy Measuring Range(Accuracy Guaranteed)
/ Minimum Measured Value
Current IEC 61557-12 Class 0.5 1.2 A – 72 A / 0.06 A 1

Power Active IEC 61557-12 Class 0.5 1.2 A – 72 A


Reactive IEC 61557-12 Class 1 1.2 A – 72 A
Apparent IEC 61557-12 Class 0.5 1.2 A – 72 A
Energy Active IEC 62053-21 Class 0.5 1.2 A – 72 A
Reactive IEC 62053-24 Class 1 1.2 A – 72 A
Apparent IEC 61557-12 Class 0.5 1.2 A – 72 A
Power factor IEC 61557-12 Class 0.5 (±0.005) 1.2 A – 72 A
Leakage current 2 CMMZ-3P-60A ±0.5 % Reading ± 10 mA 20 mA – 2 A / 1 mA
1. Ib indicates the basic current of Accura 2550CMM[Z] modules.
2. It is measured by Accura 2550CMMZ modules. The measurement accuracy indicates that of the fundamental
component of leakage current.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 275


Appendix D Accuracy/Reliability Accura 2500/2550 User Guide [AC]

Accuracy of Power Quality Data

Item Accuracy Assessment Criteria


Voltage Dip(Sag)/Swell ±0.5 % Un 1 1-cycle RMS voltage refreshed every cycle
PQ Curve ±0.5 % Un 1-cycle RMS voltage refreshed every cycle
- SEMI F47-0706
- IEC 61000-4-11/34 Class 3
- ITIC
Voltage/Current Harmonics ±0.5 % Un / ±0.5 % Ib 2 Up to the 50th harmonic
Voltage/Current Unbalance ±0.5 % Un / ±0.5 % Ib Unbalance according to symmetrical components /
the NEMA MG1 standard
Voltage/Current Phasor ±0.5 % Un / ±0.5 % Ib 128-point FFT
Voltage THD [%] 3 ±0.5 % Fundamental line-to-neutral voltage Un
Current THD [%] 3 ±0.5 % Fundamental current Ib
Current TDD [%] 3 ±0.5 % Fundamental current Ib
1. The basic voltage Un is 277 V Line-to-neutral.
2. Ib indicates the basic current of Accura 2550CM[Z]/CMS/CMM[Z] modules.
3. It includes harmonics up to the 50th order.

Reliability

Standards Reference Value


EN 55011 Conducted emissions 150 kHz – 30 MHz
EN 55011 Conducted emissions (asymmetric mode) -
EN 55011 Radiated emissions 30 MHz – 6 GHz
IEC 61000-3-2 Limits for harmonic current emissions Equipment input current ≤16 A per phase
IEC 61000-3-3 Limitation of voltage changes, voltage Equipment with rated current ≤16 A per phase and
fluctuations and flicker in public low-voltage not subject to conditional connection
supply systems
IEC 61000-4-2 Electrostatic discharge (ESD) immunity ±4 kV/ ±8 kV contact/air
IEC 61000-4-3 Radiated, radio-frequency, electromagnetic [10 V/m] 80 MHz – 1,000 MHz
field immunity [3 V/m] 1,400 MHz – 6,000 MHz
IEC 61000-4-4 Electrical fast transient/burst immunity ±2 kV mains, ±1 kV IO signal/control
IEC 61000-4-5 Surge immunity ±1 kV/ ±2 kV, line-to-line/line-to-earth
±2 kV mains, ±1 kV IO signal/control
IEC 61000-4-6 Immunity to conducted disturbances, 3 V, 150 kHz – 80 MHz
induced by radio-frequency fields
IEC 61000-4-8 Power frequency magnetic field immunity 30 A/m
IEC 61000-4-11 Voltage dips, short interruptions and Voltage dip, reduction 100/60/30 %, Period R1/12/30
voltage variations immunity Short interruptions, reduction 100 %, Period 300

Page 276 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix E Line-to-Neutral Voltage for Common Main Supply Systems

Appendix E Line-to-Neutral Voltage for Common Main


Supply Systems

Wiring Modes
MAINS systems and nominal voltages Line-to-neutral
Three-phase Three-phase Three-phase Single-phase Single-phase voltage pertinent
four-wire systems three-wire systems three-wire systems two-wire systems (split-phase) to MAINS system
three-wire systems type and nominal
With earthed Unearthed With earthed voltage
neutral phase

V V V V V V
220/380 220, 230, 240 200 240/440 220 300
230/400 260, 277, 347 240/480 230
240/415 380, 400, 415 240
260/440 440, 480
277/480

Refer to 「Chapter 6 Functions > Measurements > Voltage Wiring」 for details about auxiliary connections for
voltage sensing.

ⓒ 2019 Rootech Inc. All Rights Reserved Page 277


Appendix F Ordering Information Accura 2500/2550 User Guide [AC]

Appendix F Ordering Information

Accura 2500/2550 Smart Industrial Control Panel Digital Power Meter

Accura 2500M Main Industrial Control Panel Module/Accura 2500D Main Industrial Control
Panel HMI Module
Name Option Description
Accura 2500M -AC220V/DC110V Main industrial control panel module AC 100 – 240 V, DC 100 – 300 V
-DC24V DC 20 – 30 V
Accura 2500D Industrial control panel HMI module

Accura 2550CM-3P Power Measuring Module


Name - Model Basic Current
Accura 2550CM-3P - 800A - 210 800 A
Accura 2550CM-3P - 800A – 210 - ZCT 800 A
Accura 2550CM-3P - 630A - 145 630 A
Accura 2550CM-3P - 630A – 145- ZCT 630 A
Accura 2550CM-3P - 400A – 140 400 A
Accura 2550CM-3P - 400A - 140- ZCT 400 A
Accura 2550CM-3P - 250A 250 A
Accura 2550CM-3P - 125A 125 A
Accura 2550CM-3P - 100A 100 A
Accura 2550CM-3P - 60A 60 A
Accura 2550CM-3P - 5A 1 5A
Accura 2550CM-3P - 5A-ZCT 1 5A
1. Accura 2550CM-3P-5A and Accura 2550CM-3P-5A-ZCT module can be used by externally installing CTs (the
secondary current rating: 5 A).

Accura 2550CM-1P Power Measuring Module


Name - Model Basic Current
Accura 2550CM-1P - 250A 250 A
Accura 2550CM-1P - 125A 125 A
Accura 2550CM-1P - 100A 100 A
Accura 2550CM-1P - 60A 60 A

Page 278 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix F Ordering Information

Accura 2550CMZ-3P Power/Leakage Current Measuring Module


Name - Model Basic Current
Accura 2550CMZ-3P - 800A - 220 800 A
Accura 2550CMZ-3P - 630A - 155 630 A
Accura 2550CMZ-3P - 400A - 155 400 A
Accura 2550CMZ-3P - 250A 250 A
Accura 2550CMZ-3P - 125A 125 A
Accura 2550CMZ-3P - 100A 100 A
Accura 2550CMZ-3P - 60A 60 A

Accura 2550CMZ-3P4W Power/Leakage Measuring Module


Name Model Basic Current
Accura 2550CMZ-3P4W - 250A - 145 250 A

Accura 2550CMZ-1P Power/Leakage Current Measuring Module


Name - Model Basic Current
Accura 2550CMZ-1P - 250A 250 A
Accura 2550CMZ-1P - 125A 125 A
Accura 2550CMZ-1P - 100A 100 A
Accura 2550CMZ-1P - 60A 60 A

Accura 2550CMS Split-Core Power Measuring Module


Name Model Basic Current Description
Accura 2550CMS-3P4W - 60A 60 A Connected to Accura 2550ZM-3P4W-60A module
Accura 2550CMS-1P3F - 60A 60 A Connected to Accura 2550ZM-1P3F-60A module
Accura 2550CMS-1P2F - 60A 60 A Connected to Accura 2550ZM-1P2F-60A module

Accura 2550ZM Leakage Current Measuring Module


Name Model Basic Current Description
Accura 2550ZM-3P4W - 60A-DI 60 A Connected to Accura 2550CMS-3P4W-60A module
Accura 2550ZM-1P3F - 60A-DI 60 A Connected to Accura 2550CMS-1P3F-60A module
Accura 2550ZM-1P2F - 60A-DI 60 A Connected to Accura 2550CMS-1P2F-60A module

Accura 2550CMM-3P Power Measuring Module for MCBs(Miniature CBs)


Name Model Basic Current
Accura 2550CMM-3P - 60A 60 A

Accura 2550CMMZ-3P Power/Leakage Current Measuring Module for MCBs(Miniature CBs)


Name Model Basic Current
Accura 2550CMMZ-3P - 60A 60 A

ⓒ 2019 Rootech Inc. All Rights Reserved Page 279


Appendix F Ordering Information Accura 2500/2550 User Guide [AC]

TM-CM-3P Three-Phase Terminal Block


Name Size [mm] Description
TM-CM-BC-3P - 105 Terminal block 1 for Accura 2550CM-3P-250A module
TM-CM-3P - 105 Terminal block for Accura 2550CM-3P-250A module
TM-CM-3P - 90 Terminal block for Accura 2550CM-3P-125A module
TM-CM-3P - 75L Terminal block for Accura 2550CM-3P-100A module
TM-CM-3P - 75 Terminal block for Accura 2550CM-3P-60A module
1. The 250A terminal block allows for the insertion of barriers.

TM-CM-1P Single-Phase Terminal Block


Name Size [mm] Description
TM-CM-1P - 105 Terminal block for Accura 2550CM-1P-250A module
TM-CM-1P - 60 Terminal block for Accura 2550CM-1P-125A module
TM-CM-1P - 50L Terminal block for Accura 2550CM-1P-100A module
TM-CM-1P - 50 Terminal block for Accura 2550CM-1P-60A module

TM-CMZ-3P Three-Phase Terminal Block


Name Size [mm] Description
TM-CMZ-BC-3P - 105 Terminal block 1
for Accura 2550CMZ-3P-250A module
TM-CMZ-3P - 105 Terminal block for Accura 2550CMZ-3P-250A module
TM-CMZ-3P - 90 Terminal block for Accura 2550CMZ-3P-125A module
TM-CMZ-3P - 75L Terminal block for Accura 2550CMZ-3P-100A module
TM-CMZ-3P - 75 Terminal block for Accura 2550CMZ-3P-60A module
1. The 250A terminal block allows for the insertion of barriers.

TM-CMZ-3P4W Three-Phase 4-Wire Terminal Block


Name Size [mm] Description
TM-CMZ-BC-3P4W - 140 Terminal block 1 for Accura 2550CMZ-3P4W-250A module
1. The 250A terminal block allows for the insertion of barriers.

TM-CMZ-1P Single-Phase Terminal Block


Name Size [mm] Description
TM-CMZ-1P - 105 Terminal block for Accura 2550CMZ-1P-250A module
TM-CMZ-1P - 60 Terminal block for Accura 2550CMZ-1P-125A module
TM-CMZ-1P - 50L Terminal block for Accura 2550CMZ-1P-100A module
TM-CMZ-1P - 50 Terminal block for Accura 2550CMZ-1P-60A module

Page 280 ⓒ 2019 Rootech Inc. All Rights Reserved


Accura 2500/2550 User Guide [AC] Appendix F Ordering Information

Special-Purpose Modules
Name Description
Accura -500V-80A Basic voltage 500Vdc/ Basic current 80 Adc
2550DCM -50V-80A Basic voltage 50Vdc/ Basic current 80 Adc
Accura 2550TEMP Measures the external temperature of the panel where the module is installed
Accura TSEN Collects data on the temperature measured in the panel where it is installed
Accura THSEN Collects data on the temperature and humidity measured in the panel where it is installed
Accura 2550GW Collects data from peripheral devices supporting RS-485 communication
Accura 2550GWM Collects data from peripheral devices supporting RS-485 communication with its 4 ports
Accura 2550SAL-3P-DO Measures the leakage current of the surge arrester
Accura 2550VOL Measures the voltage of multiple power supplies
Accura 2550IO -DI1 11 DI channels
-DI2 22 DI channels
-DO1 6 DO channels
-DO2 12 DO channels
-AI1 6 AI channels (DC 4 – 20 mA)
-AI2 12 AI channels (DC 4 – 20 mA)
-RTD1 4 channels, RTD temperature sensor input
-RTD2 8 channels, RTD temperature sensor input
Accura 2550PS Used for additional power supply

ⓒ 2019 Rootech Inc. All Rights Reserved Page 281


Accura 2500/Accura 2550

User Guide

Smart Industrial Control Panel Digital Power Meter/


Power Measuring Module

Rootech Inc.
88 Sinwon-ro, Yeongtong-gu, Suwon, Gyeonggi-do, Korea
(102-611 Digital Empire 2)

Tel. +82-31-695-7350
Fax. +82-31-695-7399

Contact us for technical support and purchasing inquiries.

www.rootech.com
[email protected]

ⓒ 2019 Rootech Inc. All Rights Reserved

Accura 2300/2350, Accura 2300S/2350, Accura 2300S/2350-1P3FSC, Accura 2500/2550, Accura 2700/2750, Accura 3000,
Accura 3300E, Accura 3500/3550/3500E, Accura 3700, Accura 5500, and Accura 7500 are trademarks of Rootech Inc. Contact
us for detailed product specifications and ordering information. Information contained herein is subject to change without
notice. CopyrightⓒRootech Inc. Printed In Korea