We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3
PRESTRESSING OPERATION A.
Preparation for Stressing Inspection One of
the most essential preparations for stressing inspection is the calculation of theoretical elongations due to jacking. Recommended practice is to calculate 80% of theoretical elongation, to compare with field measurements taken between 20% and 100% of jacking force. A measurement taken at 20% should eliminate the effect of dead end seating loss, cable slack, and variation in the modulus of elasticity (E) of the strand at lower stress ranges. If variations are encountered or long cable lengths are to be stressed, one can base comparisons on a calculated 70% or 75% of the theoretical elongation. It is the responsibility of the Contractor to submit elongation calculations as part of the shop drawings. Structure Design and the Structure Representative then check the Contractor’s calculations. Appendix D gives an acceptable method of calculating elongations as well as force factors. Tendon elongations are calculated on the basis of an assumed modulus of elasticity (E) – usually 28,000 ksi (193,000 MPa) for strand. The strand area is commonly assumed to be 0.153 in2 for 0.5- inch strand, and 0.207 in2 for 0.6-inch strand. The actual Young’s modulus (E) and cross-sectional area (A) for the individual strand packs must be used to re-calculate tendon elongations. While the values of (E) and (A) from the quality assurance testing performed by METS will be recorded on the materials release tag for the prestressing steel, these values represent averages as determined from the limited samples performed on the lots. The current policy is to utilize the actual values for (E) and (A) provided by the strand fabricator on the individual strand packs to calculate elongations. Often packs of strand arrive with varying (E) and (A). In this case, it is best to separate the strand packs so that all strand in a given tendon are the same. If the variations are small, tracking the varying strands in each tendon and using an average (E) and (A) is acceptable. Appendix D gives examples of elongation calculations. Prior to stressing, it is also necessary to make preparations for monitoring the jacking force. The Standard Specifications24 requires the Contractor to have two pressure gages or one pressure gage and a load cell for each jack. During the stressing operation, the Contractor does not have to use both pressure gages at the same time. The intent of the extra gage requirement is to have a calibrated back-up gage on hand if needed. Re-certification of the Contractor’s gages and jacks is required every 12 months. State pressure cells usually monitor the Contractor’s jack and gage during the stressing operation. Up-to-date information regarding jack calibration is available by accessing the Structure
administrative instructions relevant to the pressure cell. B. Field Inspection
The practice of stressing both simple-span and shorter continuous frames from one end only is common, and must be shown on the contract plans or specifications. When two-end stressing is required, the Contractor must stress both ends to Pjack and show the actual method and sequence of stressing on the shop drawings. In order to minimize the possibility of undesirable construction stresses, the Standard Specifications26 states, “Sequence the stressing of post-tensioned bridge girders such that no more than 1/2 of the prestressing force in any girder is applied before an equal force is stressed in the adjacent girders. The maximum temporary force variation between girders must not exceed the prestressing force of the largest tendon used in all girders. Do not apply an eccentric force about the centerline of the structure that exceeds 1/6 of the total prestressing force at any time during the prestressing.” Structure Design is responsible for checking for compliance to the requirements of Standard Plan B8-5. In addition, Structures Design will check the shop drawings to confirm the correct duct profiles, prestressing force, elongation calculations, and anchorage systems used before approval. If compliance with these requirements is overly difficult because of field conditions, Structure Design should be consulted before deviating in any manner from the authorized shop drawings. Duct ties are always required in girder flares near the exterior girder prestress anchorages. Refer to Standard Plan B8-5 for limits and details of these ties. Bridge Memos to Designers, 11-31, Curved Post-Tensioned Bridges, applies to girders with horizontal radii of 2,000 ft. or less.27 The limits of, and details of these ducts ties and stirrup ties should be included in the contract plans. See Figure 8- 1. If the
In order to efficiently monitor stressing operations, a record in chart form
must be kept for each tendon stressed. Figure 8-2 shows form SC-4301 (formerly DS-C87) titled Post-Tensioning Field Monitoring Chart.28 Note that some of the information shown can be entered prior to stressing. Remember, that this form is a guide. You may custom design your own chart. After completion, place this form in the job files. Each individual strand should be marked or painted at both ends of the structure to measure elongation and check for slippage. Tendons should be checked during and after stressing for any strand slippage or dead end seating loss. The actual area of ½″ prestressing strand typically varies between 0.151 (97.4 mm2 ) and 0.154 (99.4 mm2 ) square inches. However, some strands have been received with an area as small as 0.149 square inches (96.1 mm2 ). Such small strand has presented problems with proper seating of the wedges. Particular care should be used when stressing any strand with an area below 0.151 square inches (97.4 mm2 ). With the Dywidag bar system, counting the turns of the anchor nut during stressing can also monitor the elongation. An important requirement of prestressing inspection is obtaining the anchor set shown on the plans. Anchor set is the amount of strand movement at the time of force transfer to the bridge. This is usually 3/8″ (10 mm) for continuous structures and per shop plans for simple spans. In most prestress systems, elongation of the tendon occurs within the jack itself. At 0.75 f’s the tendon elongates approximately 1/12″ per foot (0.72% strain) of jack measured from the anchorage to the pulling head. When measuring or computing anchor set loss, do not include the length of the tendon within the jack. Refer to Appendix D for calculating the effect that anchor set has on tendon stress. For a complete jacking sequence including anchor set, see Figure 8-3, which is provided by the VSL Corporation. Structure Construction procedures state that the pressure cell is used at the start of stressing to verify the Contractor’s calibration chart and at least one calibration curve must be made per structure of frame. The Structure Representative may require additional monitoring of the prestressing operation as needed. Figures 8-4 and 8-5 are examples of completed forms SC-4302 and SC- 4202A29 for recording the Contractor’s gage readings versus pressure cell readings. After completion, place these forms in the job files.