Pamphlet On Meggering of Signalling Cable English
Pamphlet On Meggering of Signalling Cable English
MINISTRY OF RAILWAYS
(For official use only)
CAMTECH/ S /2004/MSC/1.0
AUGUST 2004
Centre
for
Advanced
Maintenance
TECHnology Excellence in Maintenance
PREPARATORY STEPS
1. Before commencement of cable Meggering necessary
disconnection from traffic shall be obtained.
2. All working circuits and power supply shall be disconnected
from the cable at both ends.
3. Communication between the ends of cable under test shall be
established by magneto telephones with other cable which is
not under test if possible, otherwise by VHF sets.
4. Competent staff, required instruments and material shall be
available at both the ends.
5. Meggering shall be carried out when conductors and
insulated parts like terminal blocks are clean and dry.
6. Cable conductors shall be shorted/earthed momentarily to
discharge the accumulated charge, if any, before the
commencement and after the end of Meggering.
Multimeter Armour
Earth
1 1
2 2
E 3 3
4 4
5 5
6 6
LOCATION A LOCATION B
This test is carried out to confirm that the core under test is either
showing break between both ends or continuous. Testing can be
commenced as per the following procedure:
• Set the knob of multimeter to check resistance at 200 ohm
range. (At Location A)
• Connect one probe of multimeter to earth and other probe to
the end of the cable conductor to be tested, as shown in above
figure.
• Instruct staff at the other end (at Location B) to connect earth
to same conductor of the cable.
• If earth is light at both ends, connect earth to armour also at
both the ends.
• Deflection of multimeter needle shows that the conductor
under test is OK; otherwise there is a break in the conductor.
• Then test continuity of all other conductors with respect to
this tested conductor. For example to test conductor 2,
500 V Line
CONDUCTOR
Meggar
Earth
Earth