Precast concrete column rectangular example
Precast concrete column rectangular example
z
300 mm
Link diameter; v = 8 mm
Total number of longitudinal bars; N=6
No. of bars per face parallel to y axis; Ny = ;2
No. of bars per face parallel to z axis; Nz = ;3
Area of longitudinal reinforcement; As = N 2 / 4 = 2945 mm2
Characteristic yield strength; fyk = 500 N/mm2
Partial safety factor for reinft (2.4.2.4(1)); S = 1.15
Modulus of elasticity of reinft (3.2.7(4)); Es = 200 kN/mm2
Fire resistance details
Fire resistance period; R = 60 min
Exposure to fire; Exposed on more than one side
Ratio of fire design axial load to design resistance; fi = 0.70
Strain limits
Compression strain limit (Table 3.1); cu3 = 0.00350
Pure compression strain limit (Table 3.1); c3 = 0.00175
Frame analysis moments about z axis combined with moments due to imperfections (cl. 5.2 & 6.1(4))
Ecc. due to geometric imperfections (z axis); eiz = l0z /400 = 7.5 mm
Min end moment about z axis; M01z = min(abs(Mtopz), abs(Mbtmz)) + eiz NEd = 65.0 kNm
Max end moment about z axis; M02z = max(abs(Mtopz), abs(Mbtmz)) + eiz NEd = 65.0 kNm
Slenderness limit for buckling about y axis (cl. 5.8.3.1)
Factor A; A = 0.7
Mechanical reinforcement ratio; = As fyd / (Ac fcd) = 0.471
Factor B; B = (1 + 2 ) = 1.393
Moment ratio; rmz = M01z / M02z = ;1.000
Factor C; Cz = 1.7 - rmz = 0.700
Relative normal force; n = NEd / (Ac fcd) = 0.735
Slenderness limit; limz = 20 A B Cz / (n) = 15.9
z>=limz - Second order effects must be considered
Local second order bending moment about y axis (cl. 5.8.8.2 & 5.8.8.3)
Relative humidity of ambient environment; RH = 50 %
Column perimeter in contact with atmosphere; u = 1400 mm
Age of concrete at loading; t0 = 28 day
Parameter nu; nu = 1 + = 1.471
Approx value of n at max moment of resistance; nbal = 0.4
Axial load correction factor; Kr = min(1.0 , (nu - n) / (nu - nbal)) = 0.687
Reinforcement design strain; yd = fyd / Es = 0.00217
Basic curvature; curvebasic_y = yd / (0.45 dy) = 0.0000152 mm-1
Notional size of column; h0 = 2 Ac / u = 171 mm
Factor 1 (Annex B.1(1)); 1 = (35 MPa / fcm)0.7 = 0.802
Factor 2 (Annex B.1(1)); 2 = (35 MPa / fcm)0.2 = 0.939
Relative humidity factor (Annex B.1(1)); RH = [1 + ((1 - RH / 100%) / (0.1 mm-1/3 (h0)1/3)) 1] 2 = 1.616
Concrete strength factor (Annex B.1(1)); fcm = 16.8 (1 MPa)1/2 / (fcm) = 2.425
Concrete age factor (Annex B.1(1)); t0 = 1 / (0.1 + (t0 / 1 day)0.2) = 0.488
Notional creep coefficient (Annex B.1(1)); 0 = RH fcm t0 = 1.914
Final creep development factor; (at t = ; c = 1.0
Final creep coefficient (Annex B.1(1)); = 0 c = 1.914
Ratio of SLS to ULS moments; rMy = 0.80
Effective creep ratio; efy = rMy = 1.531
Factor ; y = 0.35 + fck / 200 MPa - y / 150 = 0.377
Project Job Ref.
Biaxial bending
Determine if a biaxial bending check is required (5.8.9(3))
Ratio of column slenderness ratios; ratio = max(y, z) / min(y, z) = 1.33
Eccentricity in direction of y axis; ey = MEdz / NEd = 50.7 mm
Eccentricity in direction of z axis; ez = MEdy / NEd = 59.8 mm
Equivalent depth; heq = iy (12) = 400 mm
Equivalent width; beq = iz (12) = 300 mm
Relative eccentricity in direction of y axis; erel_y = ey / beq = 0.169
Relative eccentricity in direction of z axis; erel_z = ez / heq = 0.150
Ratio of relative eccentricities; ratioe = min(erel_y, erel_z) / max(erel_y, erel_z) = 0.885
ratioe > 0.2 - Biaxial bending check is required
Biaxial bending (5.8.9(4))
Design axial resistance of section; NRd = (Ac fcd) + (As fyd) = 4000.5 kN
Ratio of applied to resistance axial loads; ratioN = NEd / NRd = 0.500
Exponent a; a = 1.33
Biaxial bending utilisation; UF = (MEdy / MRdy)a + (MEdz / MRdz)a = 0.961