GENERAL TECHNICAL SPECIFICATIONS

1. DESIGN:
Oil Immersed, Core Type Double Wound Transformer with Class “A” Insulation, designed
for continuous duty at rated capacity with particular reference to tropical conditions
confirming to IS 1180 /IS 2026 / IEC 60076.

2. STANDARDS:
IS 1180 / IEC 60076 : Distribution Transformers.
IS 2026 / IEC 60076 : Power Transformers.
IS 3639 / IEC : Fittings & Accessories for Power Transformer
IS 335 / IEC 60296 : Transformer Oil.
IS 1271/ IEC 60085 : Insulating Material.
IS 3347 / IEC 60137 : Bushings.

3. CONSTRUCTIONS:

 CORE: The core shall be C.R.G.O. Steel Material having Low Losses and good grain
properties, bolted together to the frame firmly to prevent vibration and noise. Special
Step lap core assembly method is used to further lower the losses.

 WINDING: Winding shall be made out of 100 % Electrolytic Grade


Copper/Aluminum Wires / Strips. Generally, H.V. Winding shall be crossover or disc
type and the L.V. Winding shall be Cylindrical Type / Disc Type or Helical Type
depending up on the Voltage and currents.

 TANK: Transformer Tank shall be of Robust Construction and shall be fabricated with
M.S.Plates. Proper reinforcement shall be provided to ensure no bulging occur during
service. The Tank shall be pressure and Vacuum Tested. All joints of tank & fittings
shall be leak proof.

 FITTINGS & ACCESSORIES: All the fittings and accessories shall be of good quality
and conforming to relevant IS Specifications.

 OIL: The Transformer shall be supplied with first filling of oil as per IS 335 (Apar or
Savita make).

 PAINTING: Tank inside shall be painted by heat and oil resistant paint. The exterior of
the Transformer shall be painted with one coat of Epoxy Primer and top coat of Epoxy
/ PU paint.
GUARANTEED TECHNICAL PARTICULARS

S.No PATICULARS Details


1 Manufacturer’s Name and Address ABC TRANSFORMERS PVT LTD
2 Country Of Origin India
3 Reference Standard IS-2026
4 Continuous max. Rating 3000 KVA
5 Duty Inverter Duty Transformer
6 Installation Outdoor
7 Winding Material: HV Electrolytic Copper
8 Winding Material: LV Electrolytic Copper
9 Rated Voltage : HV 11 KV
10 Rated Voltage : LV 0.800 KV
11 Rated Current : HV 157.46 Amp
12 Rated Current : LV 2165.13 Amp
13 Number of Phases 3 Phase
14 Rated frequency 50 Hz
15 Vector group reference Dyn-11
16 Connection
16.1 HV Side Delta
16.2 LV Side Star
17 Tapping Range +10% to -10% @1.25%
18 No. of steps 16 Steps and 17 Positions
19 Connected on HV Side
OLTC
20 Type of Tapping Switch
(On Load Tap Changer)
21 Type of cooling ONAN
22 Ambient Temperature 50˚C
23 Maximum Temperature rise of top oil 50˚C
24 Maximum Temperature rise of winding 55˚C
25 Insulation Class A Class
26 Max. flux density at rated voltage and rated 1.69 Tesla (Max)
27 frequency
No Load Losses at rated voltage and rated frequency 3000 W (Tol. as per IS)
28 Load Losses at rated current at principal tapping( @ 30000 W (Tol. as per IS)
75 °C)
Efficiency at 75˚C :- At U.P.F.
29 i) At 100% of full load 98.91 %
ii) At 75% of full load 99.12 %
iii) At 50% of full load 99.30 %

Efficiency at 75˚C :- At 0.8 P.F.


30 iv) At 100% of full load 98.64 %
v) At 75% of full load 98.91 %
vi) At 50% of full load 99.13 %

% regulation at full load & at 75˚C:


31 a) At unity power factor 1.031 %
b) At 0.8 power factor 4.502 %

32 Percentage Impedance at full load and at 75˚C 6.25 % ( Tol. as per IS)
33 Insulation level ( Impulse withstand )(kVpeak)
33.1 HV 75 KVp
33.2 LV 40 KVp
34 Insulation level ( power frequency withstand )
(kVrms)
34.1 HV 28 KV
34.2 LV 10 KV
35 Core Grade M-4 Grade or better
36 Core Lamination Material CRGO
37 Thickness of lamination 0.27 mm or better
38 Insulation of lamination Carlite
39 Class of insulation A Class
40 Type Of Oil Mineral Oil
41 First filling of oil Conforms to IS-335
42 Overloading Capacity As per IS-6600
43 Porcelain Bushing IS-3347
44 Induced Over Voltage
44.1 HV Side 22 KV
44.2 LV Side 1.6 KV
45 Thickness of transformer tank plate (mm)
45.1 Sides 5 mm
45.2 Bottom 6 mm
45.3 Cover 6 mm
46 Thickness of Radiator sheet 1.2 mm
Note: 1-All electrical performances are subject to tolerance as per IS-1180, IS-2026, IEC-76.
2-Weights & dimension are subject to tolerance of ±10%.
3. Shielding Provided Between HV & LV.
4. Special design parameter have been considered to reduce the effect of harmonics.
List of Accessories

1. Name, Rating & Diagram Plate 1 No


2. 12 KV, 250 A porcelain bushing 3 Nos.
3. 3.6 KV, 2500 A Epoxy bushing 4 Nos.
4. Conservator with filling hole 1 No.
5. On Load Tap Changer 1 No.
6. Breather (silica gel) 1 No.
7. Lifting lugs 1 Set.
8. Earthing terminals 2 Nos.
9. Oil Drain valve 1 No.
10. Top Filter Valve 1 No.
11. PRV 1 No.
12. Base Channel 2 Nos.
13. Rollers 4 Nos.
14. Radiators APD
15. Air Release hole with plug 1 No.
16. Marshalling Box 1 No.
17. WTI 1 No.
18. OTI 1 No.
19. M.O.G 1 No.
20. Buchholz Relay 1 No.
21. Inspection Cover 1 No.