CIMR-G7B
CIMR-G7B
Varispeed G7
INSTRUCTION MANUAL
GENERAL PURPOSE INVERTER (ADVANCED VECTOR CONTROL)
MODEL: CIMR-G7B
200V CLASS 0.4 to 110kW (1.2 to 160kVA)
400V CLASS 0.4 to 300kW (1.4 to 460kVA)
Upon receipt of the product and prior to initial operation, read these instructions
thoroughly, and retain for future reference.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system,
or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording,
or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed
with respect to the use of the information contained herein. Moreover, because Yaskawa is con-
stantly striving to improve its high-quality products, the information contained in this manual is
subject to change without notice. Every precaution has been taken in the preparation of this
manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is
any liability assumed for damages resulting from the use of the information contained in this
publication.
Preface
This manual is designed to ensure correct and suitable
application of Varispeed G7-Series Inverters. Read
this manual before attempting to install, operate, main-
tain, or inspect an Inverter and keep it in a safe, conve-
nient location for future reference. Be sure you
understand all precautions and safety information
before attempting application.
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details.
Be sure to restore covers or shields before operating the Units and run the Units according to the
instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only
and may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the
manual may be changed without notice to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa represen-
tatives or the nearest Yaskawa sales office and provide the manual number shown on the front
cover.
• If nameplates become warn or damaged, order new ones from your Yaskawa representatives or
the nearest Yaskawa sales office.
i
Safety Information
The following conventions are used to indicate precautions in this manual. Failure to heed pre-
cautions provided in this manual can result in serious or possibly even fatal injury or damage to
the products or to related equipment and systems.
Indicates precautions that, if not heeded, could possibly result in loss of life or serious injury.
WARNING
Indicates precautions that, if not heeded, could result in relatively serious or minor injury, damage
CAUTION to the product, or faulty operation.
Failure to heed a precaution classified as a caution can result in serious consequences depending
on the situation.
IMPORTANT
ii
Safety Precautions
CAUTION
• Never install an Inverter that is damaged or missing components.
Doing so can result in injury.
Installation
CAUTION
• Always hold the case when carrying the Inverter.
If the Inverter is held by the front cover, the main body of the Inverter may fall, possibly resulting in injury.
• Attach the Inverter to a metal or other noncombustible material.
Fire can result if the Inverter is attached to a combustible material.
• Install a cooling fan or other cooling device when installing more than one Inverter in the same
enclosure so that the temperature of the air entering the Inverters is below 45°C.
Overheating can result in fires or other accidents.
Wiring
WARNING
• Always turn OFF the input power supply before wiring terminals.
Otherwise, an electric shock or fire can occur.
• Wiring must be performed by an authorized person qualified in electrical work.
Otherwise, an electric shock or fire can occur.
• Be sure to ground the ground terminal. (200 V Class: Ground to 100 Ω or less, 400 V Class:
Ground to 10 Ω or less)
Otherwise, an electric shock or fire can occur.
• Always check the operation of any emergency stop circuits after they are wired.
Otherwise, there is the possibility of injury. (Wiring is the responsibility of the user.)
• Never touch the output terminals directly with your hands or allow the output lines to come into con-
tact with the Inverter case. Never short the output circuits.
Otherwise, an electric shock or ground short can occur.
• If the power supply is turned ON during the FWD (or REV) Run Command is given, the motor will
start automatically.
Turn the power supply ON after verifying that the RUN signal is OFF.
Failure to observe this warning may result in injury.
• When the 3-wire sequence is set, do not make the wiring for the control circuit unless the multi-
function input terminal constant is set.
Failure to observe this warning may result in injury.
CAUTION
• Check to be sure that the voltage of the main AC power supply satisfies the rated voltage of the
Inverter.
Injury or fire can occur if the voltage is not correct.
• Do not perform voltage withstand tests on the Inverter.
Otherwise, semiconductor elements and other devices can be damaged.
• Connect braking resistors, Braking Resistor Units, and Braking Units as shown in the I/O wiring
examples.
Otherwise, a fire can occur and the Inverter, braking resistors, Braking Resistor Units, and Braking Units can be damaged.
iii
CAUTION
• Tighten all terminal screws to the specified tightening torque.
Otherwise, a fire may occur.
• Do not connect AC power to output terminals U, V, and W.
The interior parts of the Inverter will be damaged if voltage is applied to the output terminals.
• Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits.
The Inverter can be damaged or interior parts burnt if these devices are connected.
• Do not connect magnetic contactors to the output circuits.
If a load is connected while the Inverter is operating, surge current will cause the overcurrent protection circuit inside the
Inverter to operate.
CAUTION
• Disconnect the load (machine, device) from the motor before performing rotational autotuning.
The motor may turn, possibly resulting in injury or damage to equipment. Also, motor constants cannot be correctly set
with the motor attached to a load.
• Stay clear of the motor during rotational autotuning.
The motor repeats running and stopping until autotuning has been completed, possibly resulting in injury.
• In stationary autotuning 1, when the motor is first operated in the drive mode after tuning, the
remaining motor constants E2-02 (Motor rated slip) and E2-03 (Motor no-load current) are set auto-
matically. To perform an operation immediately after stationary autotuning 1, use the following pro-
cedure under the recommended conditions.
(1) Check the values of E2-02 and E2-03 in verify mode or advanced programming mode.
(2) Run the motor once in drive mode under the following conditions.
• The Inverter and the motor are connected.
• The motor shaft is not locked with a mechanical brake or other stopping mechanism (or function).
• A motor-load ratio of 30% or less is maintained.
• A speed of 30% or more of the base frequency set at E1-06 (default = highest frequency) is maintained at
a constant speed for one second or more.
(3) After stopping the motor, check the values of E2-02 and E2-03 again in verify mode or advanced program-
ming mode. If the values of E2-02 and E2-03 differ from the ones before the first operation was carried out,
the settings have been successfully completed. Next, check if the values are suitable or not.
If the values of E2-02 and E2-03 differed greatly from the reference data of the motor in the test report or the instruction
manual (TOE-S616-60.1), hunting, motor vibrations, insufficient motor torque, or an overcurrent may occur because the
motor is operated although the aforementioned conditions have not been fulfilled after stationary autotuning 1. For eleva-
tors, failure to observe this caution may result in the cage falling or injury. If so, perform stationary autotuning 1 again and
run the motor using the aforementioned procedure under the recommended conditions or perform stationary autotuning 2
or rotational autotuning.
Usually the standard setting for E2-02 is 1 Hz to 3 Hz, and that for E2-03 is 30% to 65% of the rated current for a general-
purpose motor. Generally, the larger the motor capacity is, the smaller the rated slip and the ratio of the no-load current to
the rated current become. Use the data given in Factory Settings that Change with the Inverter Capacity (o2-04) of Chap-
ter 5 User Constants as a reference.
Trial Operation
WARNING
• Check to be sure that the front cover is attached before turning ON the power supply.
An electric shock may occur.
• Do not come close to the machine when the fault reset function is used. If the alarmed is cleared,
the machine may start moving suddenly.
Also, design the machine so that human safety is ensured even when it is restarted.
Injury may occur.
• Provide a separate emergency stop switch; the Digital Operator STOP Key is valid only when its
function is set.
Injury may occur.
iv
WARNING
• Reset alarms only after confirming that the RUN signal is OFF.
Injury may occur.
CAUTION
• Don't touch the radiation fins (heatsink), braking resistor, or Braking Resistor Unit. These can
become very hot.
Otherwise, a burn injury may occur.
• Be sure that the motor and machine is within the applicable ranges before starting operation.
Otherwise, an injury may occur.
• Provide a separate holding brake if necessary.
Always construct the external sequence to confirm that the holding brake is activated in the event
of an emergency, a power failure, or an abnormality in the Inverter.
Failure to observe this caution can result in injury.
• If using an Inverter with an elevator, take safety measures on the elevator to prevent the elevator
from dropping.
Failure to observe this caution can result in injury.
• Don't check signals while the Inverter is running.
Otherwise, the equipment may be damaged.
• Be careful when changing Inverter settings. The Inverter is factory set to suitable settings. For the
Inverters in the 400 V class of 55 kW or more, however, select the correct power supply voltage
jumper according to the input voltage.
Otherwise, the equipment may be damaged.
WARNING
• Do not touch the Inverter terminals. Some of the terminals carry high voltages and are extremely
dangerous.
Doing so can result in electric shock.
• Always have the protective cover in place when power is being supplied to the Inverter. When
attaching the cover, always turn OFF power to the Inverter through the MCCB.
Doing so can result in electric shock.
• After turning OFF the main circuit power supply, wait until the CHARGE indicator light goes out
before performing maintenance or inspections.
The capacitor will remain charged and is dangerous.
• Maintenance, inspection, and replacement of parts must be performed only by authorized person-
nel.
Remove all metal objects, such as watches and rings, before starting work. Always use grounded tools.
Failure to heed these warning can result in electric shock.
• Provide a separate holding brake if necessary.
Always make any adjustments other than those involving the operation of the Inverter with the holding brake released.
Failure to observe this caution may result in injury.
• If using an Inverter with an elevator, take safety measures on the elevator to prevent the elevator
from dropping.
Failure to observe this caution can result in injury.
v
CAUTION
• A CMOS IC is used in the control board. Handle the control board and CMOS IC carefully.
The CMOS IC can be destroyed by static electricity if touched directly.
• Do not change the wiring, or remove connectors or the Digital Operator, during operation.
Doing so can result in personal injury.
Other
WARNING
• Do not attempt to modify or alter the Inverter.
Doing so can result in electrical shock or injury.
CAUTION
• Do not subject the Inverter to halogen gases, such as fluorine, chlorine, bromine, and iodine, at any
time even during transportation or installation.
Otherwise, the Inverter can be damaged or interior parts burnt.
vi
Warning Information and Position
There is warning information on the Inverter in the position shown in the following illustration.
Always heed the warnings.
Warning
information
position
Warning
information
position
Warning Information
! WARNING
Risk of electric shock.
yRead manual before installing.
yWait 5 minutes for capacitor discharge
after disconnecting power supply.
! AVERTISSEMENT
y
y
vii
Warranty Information
Warranty Period
This product is warranted for twelve months after being delivered to Yaskawa’s customer or if
applicable eighteen months from the date of shipment from Yaskawa’s factory whichever comes
first.
Scope of Warranty
Inspections
Periodic inspections must be conducted by the customer. However, upon request, Yaskawa or
one of Yaskawa’s Service Centers can inspect the product for a fee. In this case, if after confer-
ring with the customer, a Yaskawa product is found to be defective due to Yaskawa workman-
ship or materials and the defect occurs during the warranty period, then this fee will be waived
and the problem remedied free of charge.
Repairs
If a Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the
defect occurs during the warranty period, Yaskawa will provide a replacement, repair the defec-
tive product, and provide shipping to and from the site free of charge.
However, if the Yaskawa Authorized Service Center determines that the problem with a
Yaskawa product is not due to defects in Yaskawa’s workmanship or materials, then the cus-
tomer will be responsible for the cost of any necessary repairs. Some problems that are outside
the scope of this warranty are:
• Problems due to improper maintenance or handling, carelessness, or other reasons where the
customer is determined to be responsible.
• Problems due to additions or modifications made to a Yaskawa product without Yaskawa’s
understanding.
• Problems due to the use of a Yaskawa product under conditions that do not meet the recom-
mended specifications.
• Problems caused by natural disaster or fire.
• Or other problems not due to defects in Yaskawa workmanship or materials.
Warranty service is only applicable within Japan.
However, after-sales service is available for customers outside of Japan for a reasonable fee.
Contact your local Yaskawa representative for more information.
Exceptions
Any inconvenience to the customer or damage to non-Yaskawa products due to Yaskawa's
defective products whether within or outside the warranty period are NOT covered by this war-
ranty.
Restrictions
• The Varispeed G7 was not designed or manufactured for use in devices or systems that may
directly affect or threaten human lives or health.
• Customers who intend to use the product described in this manual for devices or systems
relating to transportation, health care, space aviation, atomic or electric power, or underwater
use must contact their Yaskawa representatives or the nearest Yaskawa sales office before-
hand.
• This product has been manufactured under strict quality-control guidelines. However, if this
product is to be installed in any location where failure of this product could involve or result
in a life-and-death situation or loss of human life or in a facility where failure may cause a
serious accident or physical injury, safety devices must be installed to minimize the likelihood
of any accident.
viii
Registered Trademarks
The following registered trademarks are used in this manual.
• DeviceNet is a registered trademark of the ODVA (Open DeviceNet Vendors Association,
Inc.).
• InterBus is a registered trademark of Phoenix Contact Co.
• ControlNet is a registered trademark of ControlNet International, Ltd.
• LONWORKS is a registered trademark of the Echelon.
ix
Contents
Safety Information ............................................................................................ii
Safety Precautions ..........................................................................................iii
Warning Information and Position ..................................................................vii
Warranty Information..................................................................................... viii
Registered Trademarks...................................................................................ix
2 Wiring .......................................................................................2-1
Connections to Peripheral Devices .............................................................. 2-2
Connection Diagram .................................................................................... 2-3
Terminal Block Configuration ....................................................................... 2-5
Wiring Main Circuit Terminals....................................................................... 2-6
x
Applicable Wire Sizes and Closed-loop Connectors ......................................................2-6
Main Circuit Terminal Functions ...................................................................................2-13
Main Circuit Configurations........................................................................................... 2-14
Standard Connection Diagrams.................................................................................... 2-15
Wiring the Main Circuits................................................................................................ 2-16
xi
Loaded Operation......................................................................................................... 4-16
Check and Recording User Constants ......................................................................... 4-17
Adjustment Suggestions ............................................................................ 4-18
xii
Adjusting Frequency References ...............................................................6-28
Adjusting Analog Frequency References .....................................................................6-28
Operation Avoiding Resonance (Jump Frequency Function) .......................................6-31
Adjusting Frequency Reference Using Pulse Train Inputs ........................................... 6-33
Speed Limit (Frequency Reference Limit Function) ...................................6-34
Limiting Maximum Output Frequency ...........................................................................6-34
Limiting Minimum Frequency........................................................................................ 6-34
Improved Operating Efficiency ...................................................................6-36
Reducing Motor Speed Fluctuation (Slip Compensation Function) ..............................6-36
Compensating for Insufficient Torque at Startup and Low-speed Operation
(Torque Compensation) ................................................................................................ 6-38
Hunting-prevention Function.........................................................................................6-40
Stabilizing Speed (Speed Feedback Detection Function) ............................................6-41
Machine Protection.....................................................................................6-42
Reducing Noise and Leakage Current.......................................................................... 6-42
Limiting Motor Torque (Torque Limit Function).............................................................6-46
Preventing Motor Stalling During Operation ................................................................. 6-49
Changing Stall Prevention Level during Operation Using an Analog Input .................. 6-50
Using Frequency Detection: L4-01 to L4-05 ................................................................. 6-50
Detecting Motor Torque ................................................................................................ 6-53
Changing Overtorque and Undertorque Detection Levels Using an Analog Input ....... 6-56
Motor Overload Protection............................................................................................6-57
Setting Motor Protection Operation Time...................................................................... 6-59
Motor Overheating Protection Using PTC Thermistor Inputs........................................ 6-60
Limiting Motor Rotation Direction.................................................................................. 6-62
Continuing Operation..................................................................................6-63
Restarting Automatically After Power Is Restored ........................................................ 6-63
Speed Search ...............................................................................................................6-64
Continuing Operation at Constant Speed When Frequency Reference Is Lost............ 6-71
Restarting Operation After Transient Fault (Auto Restart Function)............................. 6-72
Operation Selection After Cooling Fan Fault ................................................................6-73
xiii
Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG) .............................................................................................................. 6-84
Stopping the Inverter by Notifying Programming Device Errors to the Inverter
(External Fault Function) .............................................................................................. 6-85
Options..................................................................................................... 6-158
Performing Speed Control with PG ............................................................................ 6-158
Using Digital Output Boards ....................................................................................... 6-162
Using an Analog Reference Board............................................................................. 6-164
Using a Digital Reference Board ................................................................................ 6-165
xiv
Confirming Startup Current and Reducing Carrier Frequency....................................6-179
Overvoltage Inhibit Function .......................................................................................6-180
Current Alarm Function ............................................................................6-181
Peak Hold Current Monitoring Function ...................................................6-182
Maintenance Timer Display Function .......................................................6-183
Settings Required to Use Maintenance Timer Display Function................................. 6-183
Settings Required After Replacement of Cooling Fan or Electrolytic Capacitor ......... 6-184
Troubleshooting ..........................................................................................7-24
If Constant Constants Cannot Be Set ...........................................................................7-24
If the Motor Does Not Operate......................................................................................7-25
If the Direction of the Motor Rotation is Reversed ........................................................ 7-28
If the Motor Does Not Put Out Torque or If Acceleration is Slow .................................. 7-28
If the Motor Operates Higher Than the Reference .......................................................7-28
If the Slip Compensation Function Has Low Speed Precision......................................7-29
If There is Low Speed Control Accuracy at High-speed Rotation in Open-loop
Vector Control Method .................................................................................................. 7-29
If Motor Deceleration is Slow ........................................................................................ 7-29
If the Motor Overheats .................................................................................................. 7-30
If There is Noise When the Inverter is Started or From an AM Radio .......................... 7-31
If the Ground Fault Interrupter Operates When the Inverter is Run..............................7-31
If There is Mechanical Oscillation .................................................................................7-31
If the Torque Generated for the Motor is Insufficient (Insufficient Power) ..................... 7-33
If the Torque Reference (U1-09) at Low Speeds in Open-loop Vector 2 Control is
Large Compared to That at Medium and High Speeds ................................................ 7-33
If Shock Occurs Near the Speed Estimator Switching Frequency in Open-loop
Vector 2 Control ............................................................................................................7-33
If Torque Ripple Occurs at Very Low Speeds in Open-loop Vector 2 Control ............... 7-34
If the Motor Rotates Even When Inverter Output is Stopped........................................ 7-34
If OV is Detected When the Fan is Started, or Fan Stalls ............................................. 7-34
If Output Frequency Does Not Rise to Frequency Reference ......................................7-34
Acoustic Noise From the Motor .................................................................................... 7-35
xv
Periodic Inspection ......................................................................................................... 8-2
Periodic Maintenance of Parts ....................................................................................... 8-3
Procedure for Adjusting Constants after Replacement of Control Board ....................... 8-3
Types and Number of Cooling Fans Used in the Drive .................................................. 8-5
Cooling Fan Replacement Outline ................................................................................. 8-6
Circulation Fan Replacement Outline........................................................................... 8-16
Removing and Mounting the Control Circuit Terminal Board ....................................... 8-21
9 Specifications ..........................................................................9-1
Standard Inverter Specifications................................................................... 9-2
Specifications by Model.................................................................................................. 9-2
Common Specifications.................................................................................................. 9-4
Specifications of Options and Peripheral Devices........................................ 9-6
10 Appendix ................................................................................10-1
Varispeed G7 Control Methods .................................................................. 10-2
Control Methods and Features..................................................................................... 10-2
Control Methods and Applications................................................................................ 10-4
Inverter Application Precautions ................................................................ 10-6
Selection....................................................................................................................... 10-6
Installation .................................................................................................................... 10-7
Settings ........................................................................................................................ 10-7
Handling ....................................................................................................................... 10-8
xvi
User Constants .........................................................................................10-29
INDEX
Revision History
xvii
Handling Inverters
This chapter describes the checks required upon receiving or installing an Inverter.
Varispeed G7 Models
The Varispeed-G7 Series of Inverters included two Inverters in two voltage classes: 200 V and 400 V. Maximum
motor capacities vary from 0.4 to 300 kW (41 models).
Specifications
Maximum Varispeed G7
(Always specify through the protective structure when ordering.)
Voltage Motor
Class Capacity Output Open Chassis Enclosed Wall-mounted
Capacity Basic Model Number (IEC IP00) [IEC IP20, NEMA 1 (Type 1)]
kW
kVA CIMR-G7B CIMR-G7B
0.4 1.2 CIMR-G7B20P4 20P41
0.75 2.3 CIMR-G7B20P7 20P71
1.5 3.0 CIMR-G7B21P5 21P51
2.2 4.6 CIMR-G7B22P2 Remove the top and bottom cov- 22P21
3.7 6.9 CIMR-G7B23P7 ers from the Enclosed Wall- 23P71
5.5 10 CIMR-G7B25P5 mounted model. 25P51
7.5 13 CIMR-G7B27P5 27P51
11 19 CIMR-G7B2011 2011
15 25 CIMR-G7B2015 20151
200 V Class
18.5 30 CIMR-G7B2018 20180 20181
22 37 CIMR-G7B2022 20220 20221
30 50 CIMR-G7B2030 20300 20301
37 61 CIMR-G7B2037 20370 20371
45 70 CIMR-G7B2045 20450 20451
55 85 CIMR-G7B2055 20550 20551
75 110 CIMR-G7B2075 20750 20751
90 140 CIMR-G7B2090 20900 -
110 160 CIMR-G7B2110 21100 -
0.4 1.4 CIMR-G7B40P4 40P41
0.75 2.6 CIMR-G7B40P7 40P71
1.5 3.7 CIMR-G7B41P5 41P51
2.2 4.7 CIMR-G7B42P2 Remove the top and bottom cov- 42P21
3.7 6.9 CIMR-G7B43P7 ers from the Enclosed Wall- 43P71
5.5 11 CIMR-G7B45P5 mount model. 45P51
7.5 16 CIMR-G7B47P5 47P51
11 21 CIMR-G7B4011 40111
15 26 CIMR-G7B4015 40151
18.5 32 CIMR-G7B4018 40180 40181
22 40 CIMR-G7B4022 40220 40221
400 V Class 30 50 CIMR-G7B4030 40300 40301
37 61 CIMR-G7B4037 40370 40371
45 74 CIMR-G7B4045 40450 40451
55 98 CIMR-G7B4055 40550 40551
75 130 CIMR-G7B4075 40750 40751
90 150 CIMR-G7B4090 40900 40901
110 180 CIMR-G7B4110 41100 41101
132 210 CIMR-G7B4132 41320 41321
160 250 CIMR-G7B4160 41600 41601
185 280 CIMR-G7B4185 41850 -
220 340 CIMR-G7B4220 42200 -
300 460 CIMR-G7B4300 43000 -
1-2
Confirmations upon Delivery
Checks
Check the following items as soon as the Inverter is delivered.
If you find any irregularities in the above items, contact the agency from which you purchased the Inverter or
your Yaskawa representative immediately.
Nameplate Information
There is a nameplate attached to the side of each Inverter. The nameplate shows the model number, specifica-
tions, lot number, serial number, and other information on the Inverter.
Example Nameplate
The following nameplate is an example for a standard domestic (Japan) Inverter: 3-phase, 200 VAC, 0.4 kW,
IEC IP20 and NEMA 1 (Type 1) standards
Output
specifications
Lot number O/N : Mass
1-3
Inverter Model Numbers
The model number of the Inverter on the nameplate indicates the specification, voltage class, and maximum
motor capacity of the Inverter in alphanumeric codes.
CIMR - G7 B 2 0P4
Inverter
Varispeed G7
No. Specification No. Max. Motor Capacity
B China domestic model 0P4 0.4 kW
0P7 0.75 kW
to to
300 *
No. Voltage Class 300 kW
2 AC input, 3-phase, 200 V "P" indicates the decimal point.
4 AC input, 3-phase, 400 V
Inverter Specifications
The Inverter specifications (“SPEC”) on the nameplate indicate the voltage class, maximum motor capacity,
the protective structure, and the revision of the Inverter in alphanumeric codes.
2 0P4 1 A
No. Voltage Class
2 AC input, 3-phase, 200 V Design revision order
4 AC input, 3-phase, 400 V
1-4
Confirmations upon Delivery
Component Names
The external appearance and component names of the Inverter are shown in Fig 1.4. The Inverter with the ter-
minal cover removed is shown in Fig 1.5.
Terminal
Nameplate Terminal
cover Nameplate
cover
Charge indicator
Control circuit
terminals
Main circuit
terminals
Charge indicator
Ground terminal
1-5
Exterior and Mounting Dimensions
W1 W1 4-d
4-d
H1
H
H1
t1
H2
D1
t1 (5)* W (5)* (5) D
W D1
400 V Class Inverters of 55 to 160 kW.
3 D
200 V/400 V Class Inverters of 0.4 to 15 kW 200 V Class Inverters of 18.5 to 110 kW
400 V Class Inverters of 18.5 to 160 kW
6-d
W1
W2
H1
H
H2
W3 t1
W1 D1
W D
1-6
Exterior and Mounting Dimensions
W1 4-d W1 4-d
H1
H0
H
H1
H0
H2
t1
H3
Max.10
t1 D1
H2
H3
1-7
Table 1.3 200 VAC and 400 VAC (0.4 kW to 300 kW) Inverter Dimensions (mm) and Masses (kg)
Max. Heat Genera-
Dimensions (mm)
Appli- tion (W)
Voltage cable Open Chassis (IP00) Enclosed Wall-mounted [NEMA1 (Type 1)] Total Cooling
Class Motor Heat Method
Mount- Exter Inter-
Gen-
Output W H D W1 H1 H2 D1 t1 Approx.
W H D W1 H0 H1 H2 H3 D1 t1 Approx. ing nal nal
era-
Mass Mass Holes
[kW] d* tion
0.4 21 36 57
Natu-
0.75 157 39 3 157 39 3 43 42 85
ral
1.5 140 280 126 266 7 5 140 280 126 280 266 7 5 M5 58 47 105
2.2 83 53 136
177 59 4 177 0 59 4
3.7 122 64 186
5.5 6 6 187 87 274
200 300 197 186 285 8 65.5 200 300 197 186 300 285 8 65.5
7.5 7 7 263 112 375
11 350 357 136 493
240 350 207 216 335 78 2.3 11 240 207 216 350 335 78 2.3 11 M6
200 V 15 380 30 473 174 647
7.5 7.5
(3-phase) 18.5 250 400 195 385 21 254 535 195 400 385 135 24 599 242 839
258 100 258
22 275 450 220 435 24 279 615 220 450 435 165 100 27 679 257 936 Fan
30 298 100 57 298 62 878 362 1240
375 600 250 575 380 809 250 600 575 209
37 328 63 328 68 1080 434 1514
12.5 3.2 12.5 3.2 M10
45 86 94 1291 510 1801
450 725 348 325 700 130 453 1027 348 325 725 700 302 130
55 87 95 1474 607 2081
75 500 850 358 370 820 108 504 1243 358 370 850 820 15 393 4.5 114 2009 823 2832
90 15 4.5 M12 1660 871 2531
575 885 378 445 855 140 150 ---
110 2389 1194 3583
0.4 10 39 49 Natu-
157 39 3.5 157 39 3.5
0.75 21 44 65 ral
1.5 140 280 126 266 7 5 140 280 126 280 266 7 5 M5 33 46 79
2.2 177 59 4.5 177 59 4.5 41 49 90
3.7 0 76 64 140
5.5 132 79 211
200 300 197 186 285 8 65.5 7 200 300 197 186 300 285 8 65.5 7
7.5 198 106 304
11 246 116 362
240 350 207 216 335 78 10 240 350 207 216 350 335 78 10
15 311 135 446
18.5 2.3 2.3 M6 354 174 528
275 450 258 220 435 100 26 279 535 258 220 450 435 100 29
22 7.5 7.5 516 210 726
400 V 85 Fan
30 633 246 879
(3-phase) 635 39
37 325 550 283 260 535 105 37 329 283 260 550 535 105 737 285 1022
45 715 165 40 929 340 1269
55 90 98 1239 488 1727
450 725 348 325 700 12.5 3.2 453 1027 348 325 725 700 12.5 302 3.2 M10
75 91 99 1554 596 2150
130 130
90 109 127 1928 762 2690
500 850 358 370 820 15 504 1243 358 370 850 820 15 393
110 127 137 2299 928 3227
4.5 4.5 M12
132 165 175 2612 1105 3717
575 916 378 445 855 46 140 579 1324 378 445 916 855 46 408 140
160 175 185 3614 1501 5115
185
220 See Table 1.4
300
Table 1.4 400 VAC (185 to 300 kW) Inverter Dimensions (mm) and Masses (kg)
Max. Dimensions (mm) Heat Generation (W)
Appli- Open Chassis (IP00) Enclosed Wall-mounted [NEMA (Type1)]
Voltage cable Total Cooling
Mount- Exter- Inter- Heat
Class Motor Approx. Approx. ing
Method
W H D W1 W2 W3 H1 H2 D1 t1 W H D W1 W2 W3 H1 H2 D1 t1 nal nal Gener-
Output Mass Mass Holes ation
[kW] d*
300 916 1475 413 730 365 365 1440 15 125.5 4.5 415 6749 2941 9690
1-8
Checking and Controlling the Installation Site
Installation Site
Install the Inverter under the following conditions and a pollution level of 2 or less (UL standard).
1-9
Installation Orientation and Space
Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter, always
provide the following installation space to allow normal heat dissipation.
A mm min. B mm min.
Air
200 V Class Inverters of 110 kW or 400 V Class Inverters of 160 to 220 kW*: A = 120, B = 120
400 V Class Inverters of 300 kW*: A = 300, B = 300
All other Inverters*: A = 50, B = 120
*If, however, there is a fan in the top of the control panel with sufficient exhaust capacity, the following
dimensions may be used: A = 50, B = 120.
Fig 1.8 Inverter Installation Orientation and Space
1. The same space is required horizontally and vertically for both Open Chassis (IP00) and Enclosed Wall-
mounted [IP20, NEMA 1 (Type 1)] Inverters.
2. Always remove the protection covers before installing a 200 or 400 V Class Inverter with an output of
IMPORTANT 15 kW or less in a panel. Refer to Page 1-17 on how to remove the protection covers.
Always provide enough space for suspension eye bolts and the main circuit lines when installing a 200 or
400 V Class Inverter with an output of 18.5 kW or more in a panel.
1-10
Removing and Attaching the Terminal Cover
Inverters of 15 kW or Less
Loosen the screws at the bottom of the terminal cover, press in on the sides of the terminal cover in the direc-
tion indicated by arrow 1, and then lift the terminal cover up to an angle of about 30 degrees in the direction
indicated by arrow 2.
Remove the terminal cover in the direction indicated by arrow 3.
2
1 Approx. 30°
Fig 1.9 Removing the Terminal Cover (Model CIMR-G7B23P7 Shown Above)
1
2
Fig 1.10 Removing the Terminal Cover (Model CIMR-G7B2018 Shown Above)
1-11
Attaching the Terminal Cover
When wiring the terminal block has been completed, attach the terminal cover by reversing the removal proce-
dure.
For Inverters with an output of 15 kW or less, insert the tab on the top of the terminal cover into the grove on
the Inverter and press in on the bottom of the terminal cover until it clicks into place.
1-12
Removing/Attaching the Digital Operator and Front Cover
Inverters of 15 kW or Less
To attach optional boards or change the terminal board connector, remove the Digital Operator and front cover
in addition to the terminal cover. Always remove the Digital Operator from the front cover before removing
the terminal cover.
The removal and attachment procedures are given below.
2
1
Fig 1.11 Removing the Digital Operator (Model CIMR-G7B43P7 Shown Above)
1-13
Removing the Front Cover
Press the left and right sides of the front cover in the directions of arrows 1 and lift the bottom of the cover in
the direction of arrow 2 to remove the front cover as shown in the following illustration.
1
2
Fig 1.12 Removing the Front Cover (Model CIMR-G7B43P7 Shown Above)
1-14
Removing/Attaching the Digital Operator and Front Cover
A
1
B
1. Do not remove or attach the Digital Operator or mount or remove the front cover using methods other than
those described above, otherwise the Inverter may break or malfunction due to imperfect contact.
2. Never attach the front cover to the Inverter with the Digital Operator attached to the front cover. Imperfect
IMPORTANT contact can result.
Always attach the front cover to the Inverter by itself first, and then attach the Digital Operator to the front
cover.
1-15
Inverters of 18.5 kW or More
For Inverter with an output of 18.5 kW or more, remove the terminal cover and then use the following proce-
dures to remove the Digital Operator and front cover.
Fig 1.14 Removing the Front Cover (Model CIMR-G7B2018 Shown Above)
1-16
Removing and Attaching the Protection Cover
Slot
Fig 1.15 Removing the Top Protection Cover (Model CIMR-G7B43P7 Shown Above)
Terminal Cover
Screws
Bottom Protection
Cover
Fig 1.16 Removing the Bottom Protection Cover (Model CIMR-G7B43P7 Shown Above)
1-17
Attaching the Protection Cover
Fig 1.17 Attaching the Top Protection Cover (Model CIMR-G7B43P7 Shown Above)
1-18
Wiring
This chapter describes wiring terminals, main circuit terminal connections, main circuit termi-
nal wiring specifications, control circuit terminals, and control circuit wiring specifications.
Power supply
Molded-case
circuit breaker
or ground fault
interrupter
Magnetic con-
tactor (MC)
Braking resistor
Inverter
Ground
Output noise filter
Motor
Ground
2-2
Connection Diagram
Connection Diagram
The connection diagram of the Inverter is shown in Fig 2.2.
When using the Digital Operator, the motor can be operated by wiring only the main circuits.
Thermal relay
Thermal switch contact trip contact
Braking Unit 3 4 1 2
(optional) + +0 P
Level
detector -0 B
Motor
2MCCB Braking Resistor Unit
FU - (optional)
FU Cooling fan
FV
FW FV IM
+1 +3 -
FW
1MCCB MC
3-phase power R R/L1 Inverter U/T1 U
200 to 240 V V
S S/L2 CIMR-G7B2018 V/T2 IM
50/60 Hz
T T/L3 W
W/T3
ON
Forward Run/Stop S1
2MCCB THRX OFF MC (Ground to 100 max.)
MC PG-B2 TA1
SA Reverse Run/Stop S2
Thermal relay trip contact (optional) 1 C
for Braking Resistor Unit Thermal switch contact 2 H
THRX for Braking Unit 3 B
1 2 4 G
Thermal relay trip contact SA External fault 3 4
S3 5 A
PG
for motor cooling fan 6 F
1 2
Fault reset S4 TA3 D
Ammeter adjustment
Acc/dec time 1 S11 AM 20 kΩ
Multi-function analog output 2
-10 to 10 V 2 mA
Emergency stop (NO) S12 − + Default: Output current
AM 0 to +10 V
CN5 (NPN setting) +24V 8mA
Ammeter adjustment
FM 20 kΩ
SC Multi-function analog output 1
AC ? -10 to 10 V 2 mA
FM Default: Output frequency
0 to +10 V
+24V
E (G) E(G)
Shield wire
connection terminal
Error contact output
Pulse train input Master speed MA
RP pulse train
MAA 250 VAC, 10 mA min.
Frequency setting ?
0 to 32 kHz (3 kΩ) MB 1 A max. Min. load
2 k Ω adjustment High level: 3.5 to 13.2 V input 30 VAC, 10 mA min. 5 VDC, 10 mA
MC
Frequency MCC 1 A max.
setter +V Frequency setting power
3 +15 V, 20 mA
2kΩ
0 to 10 V M1
External A1 Master speed reference Multi-function contact oputput
2
frequency 1 4 to 20 mA P 0 to 10 V (20 kΩ) 250 VAC, 10 mA min. 1 A max. Min. load
M2
references A2 Master speed reference 30 VAC, 10 mA min. 1 A max. 5 VDC, 10 mA
4 to 20 mA (250 Ω) Default: Running
[0 to 10 V (20 kΩ) input] signal
0 to 10 V P
A3 Multi-function anlog input
0 to 10 V (20 kΩ)
?
P1
P AC Open collector 1
Factory setting:
0V Auxiliary frequency
Default: Zero
command speed
-V (15V 20mA) P2
Open collector 2
Default: Frequency
Terminating agree signal
resistance
PC
Multi-function
R+ open-collector outputs
P3 48 VDC 50 mA max.
R- Open collector 3
MEMOBUS
Factory setting:
communications S+ C3 Inverter operation
RS-485/422 ready
S- P4
Open collector 4
Factory setting:
( C4 minor fault
IG
2-3
1. Control circuit terminals are arranged as shown below.
IMPORTANT
2. The output current capacity of the +V and −V terminals are 20 mA. Do not short-circuit between the +V, −V,
and AC terminals. Doing so may result in a malfunction or a breakdown of the Inverter.
3. Disable the stall prevention during deceleration (set constant L3-04 to 0) when using a Braking Resistor
Unit. If this user constant is not changed to disable stall prevention, the system may not stop during decel-
eration.
4. Main circuit terminals are indicated with double circles and control circuit terminals are indicated with single
circles.
5. The wiring for a motor with a cooling fan is not required for self-cooling motors.
6. PG circuit wiring (i.e., wiring to the PG-B2 Board) is not required for control without a PG.
7. Sequence input signals S1 to S12 are labeled for sequence connections (0 V common and sinking mode)
for no-voltage contacts or NPN transistors. These are the default settings.
For PNP transistor sequence connections (+24V common and sourcing mode) or to provide a 24-V exter-
nal power supply, refer to Table 2.13.
8. The multi-function analog output is a dedicated meter output for an analog frequency meter, ammeter, volt-
meter, wattmeter, etc. Do not use this output for feedback control or for any other control purpose.
9. DC reactors to improve the input power factor are built into 200 V Class Inverters for 18.5 to 110 kW and
400 V Class Inverters for 18.5 to 300 kW. A DC reactor is thus an option only for Inverters for 15 kW or
less.
10.Set constant L8-01 to 1 when using a breaking resistor (model ERF). When using a Braking Resistor Unit,
a shutoff sequence for the power supply must be made using a thermal relay trip.
11.The minimum permissible load of a multi-function contact output and an error contact output is 10 mA. Use
a multi-function open-collector output for a load less than 10 mA.
12.Do not ground nor connect the AC terminal on the control circuit to the unit. Doing so may result in a mal-
function or a breakdown of the Inverter.
13.If turning off the power only for the main circuit but leaving the power ON for the control circuit, use a sep-
arate power supply for the control circuit and a specially designed Inverter, which are sold as options.
14. indicates shield wire and P indicates twisted-pair shield wire.
2-4
Terminal Block Configuration
Charge indicator
Ground terminal
Fig 2.3 Terminal Arrangement (200 V Class Inverter for 0.4 kW Shown Above)
Charge indicator
Ground terminal
Fig 2.4 Terminal Arrangement (200 V Class Inverter for 18.5 kW Shown Above)
2-5
Wiring Main Circuit Terminals
2-6
Wiring Main Circuit Terminals
2-7
Table 2.1 200 V Class Wire Sizes (Continued)
Inverter Tightening Possible Recom-
Termi- mended
Model Terminal Symbol nal Torque Wire Sizes Wire Size Wire Type
Screws
CIMR- (N•m) mm2(AWG) mm2 (AWG)
200 × 2P, or
200 to 325 50 × 4P
R/L1, S/L2, T/L3, , 1 M12 31.4 to 39.2
(350 to 600) (350 × 2P,
or 1/0 × 4P)
150 × 2P, or Power cables,
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/ 150 to 325 50 × 4P e.g., 600 V
M12 31.4 to 39.2
L31 (300 to 600) (300 × 2P, vinyl power
G7B2110
or 1/0 × 4P) cables
5.5 to 60
3 M8 8.8 to 10.8 -
(10 to 2/0)
150 150 × 2P
M12 31.4 to 39.2
(300) (300 × 2P)
0.5 to 5.5 1.25
r/ 1, / 2 M4 1.3 to 1.4
(20 to 10) (16)
* The wire thickness is set for copper wires at 75°C.
2-8
Wiring Main Circuit Terminals
2-9
Table 2.2 400 V Class Wire Sizes (Continued)
Inverter Tightening Possible Recom-
Termi- mended
Model Terminal Symbol nal Torque Wire Sizes Wire Size Wire Type
Screws
CIMR- (N•m) mm2 (AWG) mm2 (AWG)
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, M8 9.0 to 10.0
50 to 60 50
W/T3, R1/L11, S1/L21, T1/L31 (1 to 1/0) (1)
G7B4045 8 to 22
3 M6 4.0 to 5.0 -
(8 to 4)
22 to 38 22
M8 9.0 to 10.0
(4 to 2) (4)
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, M10 17.6 to 22.5
50 to 100 50
W/T3, R1/L11, S1/L21, T1/L31 (1/0 to 4/0) (1/0)
5.5 to 22
3 M8 8.8 to 10.8 -
G7B4055 (10 to 4)
38 to 60 38
M10 17.6 to 22.5
(2 to 2/0) (2)
0.5 to 5.5 1.25
r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4
(20 to 10) (16)
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, M10 17.6 to 22.5
80 to 100 100
W/T3, R1/L11, S1/L21, T1/L31 (3/0 to 4/0) (4/0)
8 to 22
3 M8 8.8 to 10.8 -
G7B4075 (8 to 4)
50 to 100 50
M10 17.6 to 22.5
(1 to 4/0) (1)
0.5 to 5.5 1.25
r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4
(20 to 10) (16)
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, 50 to 100 50 × 2P
M10 17.6 to 22.5
W/T3, R1/L11, S1/L21, T1/L33 (1/0 to 4/0) (1/0 × 2P)
8 to 60
3 M8 8.8 to 10.8 - Power cables,
G7B4090 (8 to 2/0)
60 to 150 60 e.g., 600 V
M10 17.6 to 22.5 vinyl power
(2/0 to 300) (2/0)
0.5 to 5.5 1.25 cables
r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4
(20 to 10) (16)
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, 60 to 100 80 × 2P
M10 17.6 to 22.5
W/T3, R1/L11, S1/L21, T1/L33 (2/0 to 4/0) (3/0 × 2P)
8 to 60
3 M8 8.8 to 10.8 -
G7B4110 (8 to 2/0)
100 to 150 100
M10 17.6 to 22.5
(4/0 to 300) (4/0)
0.5 to 5.5 1.25
r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4
(20 to 10) (16)
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, 80 to 200 80 × 2P
M12 31.4 to 39.2
W/T3, R1/L11, S1/L21, T1/L31 (3/0 to 400) (3/0 × 2P)
8 to 60
3 M8 8.8 to 10.8 -
G7B4132 (8 to 2/0)
50 to 150 50 × 2P
M12 31.4 to 39.2
(1/0 to 300) (1/0 × 2P)
0.5 to 5.5 1.25
r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4
(20 to 10) (16)
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, 100 to 200 100 × 2P
M12 31.4 to 39.2
W/T3, R1/L11, S1/L21, T1/L31 (4/0 to 400) (4/0 × 2P)
80 to 60
3 M8 8.8 to 10.8 -
G7B4160 (8 to 2/0)
50 to 150 50 × 2P
M12 31.4 to 39.2
(1/0 to 300) (1/0 × 2P)
0.5 to 5.5 1.25
r/ 1, 200/ 2200, 400/ 2400 M4 1.3 to 1.4
(20 to 10) (16)
2-10
Wiring Main Circuit Terminals
2-11
Table 2.3 Closed-loop Connector Sizes (JIS C2805) (200 V Class and 400 V Class)
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:
IMPORTANT Line voltage drop (V) = 3 x wire resistance (W/km) x wire length (m) x current (A) x 10-3
2-12
Wiring Main Circuit Terminals
Table 2.4 Main Circuit Terminal Functions (200 V Class and 400 V Class)
Model: CIMR-G7B
Purpose Terminal Symbol
200 V Class 400 V Class
R/L1, S/L2, T/L3 20P4 to 2110 40P4 to 4300
Main circuit power input
R1/L11, S1/L21, T1/L31 2018 to 2110 4018 to 4300
Inverter outputs U/T1, V/T2, W/T3 20P4 to 2110 40P4 to 4300
Note The 1 and input terminals for the DC power do not conform to UL/cUL standards.
2-13
Main Circuit Configurations
The main circuit configurations of the Inverter are shown in Fig 2.5.
+1
+1
+2 +2
R/L1 U/T1 U/T1
R/L1
S/L2 V/T2 V/T2
S/L2
T/L3 W/T3 W/T3
T/L3
−
−
Power Control
supply circuits Power Control
Cooling fan is provided for supply circuits
Inverters of 2.2 kW or more. Cooling fan is provided for
Inverters of 1.5 kW or more.
+1 +1
R/L1 R/L1
U/T1 U/T1
S/L2 S/L2
T/L3 V/T2 T/L3 V/T2
R1/L11
W/T3 R1/L11 W/T3
S1/L21
S1/L21
T1/L31
T1/L31
− −
+1
a a
b b
R/L1
U/T1
S/L2
T/L3 V/T2
R1/L11 W/T3
S1/L21
T1/L31
−
r/ l 1
*
200/ l 2200 Power Control
Power Control supply circuits
a supply circuits 400/ l 2400 a
b b
2-14
Wiring Main Circuit Terminals
Be sure to remove the short-circuit bar before connecting the DC The DC reactor is built in.
reactor.
When connecting a separately-installed type Braking Unit (model CDBR), connect the B1 terminal of the
Inverter to the + terminal of the Braking Unit and connect the − terminal of the Inverter to the − terminal of the
Braking Unit. The B2 terminal is not used in this case.
IMPORTANT
+1 +3 +1 +3
R/L1 U/T1 R/L1 U/T1
S/L2 V/T2 S/L2 V/T2
IM IM
T/L3 W/T3 T/L3 W/T3
3-phase R1/L11 3-phase R1/L11
200 VAC 400 VAC
S1/L21 S1/L21
T1/L31 T1/L31
r/l1 r/l1
/l2 200/l2200
400/l2400
Control power is supplied internally from the main circuit DC power supply for all Inverter models.
If a Braking Unit or a Braking Resistor Unit is connected to a wrong terminal, the Inverter, Braking Unit, or
Braking Resistor Unit can be damaged.
IMPORTANT
2-15
Wiring the Main Circuits
This section describes wiring connections for the main circuit inputs and outputs.
Inverter
Power
supply
R/L1
20P4 to 2030: 3-phase,
200 to 240 VAC, 50/60 Hz S/L2
2037 to 2110: 3-phase,
200 to 230 VAC, 50/60 Hz T/L3
40P4 to 4300: 3-phase,
380 to 460 VAC, 50/60 Hz
Fault output
(NC)
2-16
Wiring Main Circuit Terminals
Power
supply MCCB
Noise
filter Inverter IM
MCCB
Other
controllers
Use a special-purpose noise filter for Inverters.
2-17
• Incorrect Noise Filter Installation
Power
supply MCCB
Inverter IM
MCCB
General-
purpose Other
noise filter controllers
Power
supply MCCB
General-
purpose Inverter IM
noise filter
MCCB
Other
controllers Do not use general-purpose noise filters. No general-
purpose noise filter can effectively suppress noise
generated from the Inverter.
2-18
Wiring Main Circuit Terminals
operation. If measures for momentary power interrupts are required, use a delayed release the magnetic con-
tactor.
Power
supply MCCB
Inverter Noise
filter IM
Radio noise
AM radio
Inductive
Signal line noise
Controller
Inductive Noise: Electromagnetic induction generates noise on the signal line, causing the controller to malfunction.
Radio Noise: Electromagnetic waves from the Inverter and cables cause the broadcasting radio receiver to make
noise.
30 cm min.
Signal line
Controller
2-19
Countermeasures Against Radio Interference
Radio noise is generated from the Inverter as well as from the input and output lines. To reduce radio noise,
install noise filters on both input and output sides, and also install the Inverter in a totally enclosed steel box.
The cable between the Inverter and the motor should be as short as possible.
Steel box
Power Metal pipe
supply MCCB
Noise Inverter Noise
filter filter IM
Ground Wiring
Observe the following precautions when wiring the ground line.
• Always use the ground terminal of the 200 V Inverter with a ground resistance of less than 100 Ω and that
of the 400 V Inverter with a ground resistance of less than 10 Ω.
• Do not share the ground wire with other devices, such as welding machines or power tools.
• Always use a ground wire that complies with technical standards on electrical equipment and minimize the
length of the ground wire.
Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and the
ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
• When using more than one Inverter, be careful not to loop the ground wire.
OK NO
2-20
Wiring Main Circuit Terminals
Table 2.7
L3-04 (Stall prevention selection during deceleration) 0 (Disables stall prevention function)
(Select either one of them.) 3 (Enables stall prevention function with braking resistor)
The braking resistor connection terminals are B1 and B2. Do not connect to any other terminals. Connecting
to any terminals other than B1 or B2 can cause the resistor to overheat, resulting in damage to the equip-
ment.
IMPORTANT
Connecting the Braking Resistor Unit (LKEB) and Braking Unit (CDBR)
Use the following settings when using a Braking Resistor Unit. Refer to Wiring Examples on page 10-20 for
connection methods for a Braking Resistor Unit.
A Braking Resistor that mounts to the Inverter can also be used with Inverters with outputs from 0.4 to
3.7 kW.
Table 2.8
L3-04 (Stall prevention selection during deceleration) 0 (Disables stall prevention function)
(Select either one of them.) 3 (Enables stall prevention function with braking resistor)
L8-01 is used when a braking resistor without thermal overload relay trip contacts (ERF type mounted to
Inverter) is connected.
The Braking Resistor Unit cannot be used and the deceleration time cannot be shortened by the Inverter if L3-
04 is set to 1 (i.e., if stall prevention is enabled for deceleration).
2-21
Wiring Control Circuit Terminals
Shield terminal
E(G)
2kΩ
2kΩ A1 Master speed reference 0 to 10 V (-10 to 10 V)
2kΩ
2kΩ
A3 Auxiliary reference 0 to 10 V (-10 to 10 V)
Fig 2.14
Table 2.9 Terminal Numbers and Wire Sizes (Same for all Models)
Recom-
Termi- Tightening Possible Wire
mended
Terminals nal Torque Sizes Wire Type
Wire Size
Screws (N•m) mm2(AWG)
mm2(AWG)
FM, AC, AM, P1, P2,
PC, SC, A1, A2, A3, +V,
-V, S1, S2, S3, S4, S5, S6, M3.5 0.8 to 1.0 0.5 to 2*2 0.75
(20 to 14) (18)
S7, S8, MA, MB, MC,
M1, M2 • Shielded, twisted-pair wire*1
Single wire*3: • Shielded, polyethylene-cov-
P3, C3, P4, C4, MP, RP, 0.14 to 2.5 ered, vinyl sheath cable
Phoenix 0.75 (KPEV-S by Hitachi Electri-
R+, R-, S9, S10, S11, 0.5 to 0.6 Stranded wire:
type (18) cal Wire or equivalent)
S12, S+, S-, IG 0.14 to 1.5
(26 to 14)
2-22
Wiring Control Circuit Terminals
d1
d2
Wiring Method
Use the following procedure to connect wires to the terminal block.
1. Loosen the terminal screws with a thin-slot screwdriver.
2. Insert the wires from underneath the terminal block.
3. Tighten the terminal screws firmly.
Control circuit
terminal block
2-23
Control Circuit Terminal Functions
The functions of the control circuit terminals are shown in Table 2.11. Use the appropriate terminals for the
correct purposes.
2-24
Wiring Control Circuit Terminals
P4
Multi-function PHC output 4 Factory setting: Minor fault.
C4
Fault output signal (NO con-
MA
tact) Fault when CLOSED across MA and MC Dry contacts
Fault output signal (NC con- Fault when OPEN across MB and MC Contact capacity:
MB 10 mA min. 1 A max. at
tact)
Relay 250 VAC
outputs Relay contact output com- 10 mA min. 1 A max. at
MC -
mon 30 VDC
Minimum permissible
M1
Multi-function contact output Factory setting: Operating load: 5 VDC, 10 mA*4
(NO contact) Operating when ON across M1 and M2.
M2
2-25
Flywheel diode
CN5 S1
O OFF ON Terminating resistance
F 1
F 2 V I Analog input switch
: Factory settings
Sinking/Sourcing Mode
The input terminal logic can be switched between sinking mode (0-V common) and sourcing mode (+24-V
common) if shunt connector CN5 is used. An external 24-V power supply is also supported, providing more
freedom in signal input methods.
2-26
Wiring Control Circuit Terminals
CN5 CN5
CN5 (NPN set) Factory setting CN5 (EXT set)
Sink-
ing
Mode S1 S1
S2 S2
CN5 CN5
Sourc-
ing
Mode S1 S1
S2 S2
2-27
Control Circuit Terminal Connections
Connections to Inverter control circuit terminals are shown in Fig 2.19.
Inverter
CIMR-G7B2018
Forward Run/Stop S1
Reverse Run/Stop S2
Thermal switch contact
for Braking Unit
3 4
External fault S3
Fault reset S4
Multi-step command 1
(Main speed switching)
S5
Multi-step speed
setting 2 S6
Jog frequency
selection S7
Multi-function External
contact input baseblock command S8 MP
Defaults Pulse train output
Multi-step speed
setting 3 S9 0 to 32 kHz (2.2 kΩ)
AC Default: Output
frequency
Multi-step speed
setting 4 S10
2-28
Wiring Control Circuit Terminals
2-29
Wiring Check
Checks
Check all wiring after wiring has been completed. Do not perform a buzzer check on control circuits. Perform
the following checks on the wiring.
• Is all wiring correct?
• Have any wire clippings, screws, or other foreign material been left?
• Are all screws tight?
• Are any wire ends contacting other terminals?
2-30
Installing and Wiring Option Boards
LONWORKS SI-J
LONWORKS communications support C
Communications Board SI-W1
MECHATROLINK Commu-
SI-T MECHATROLINK communications support C
nication Board
AO-08 8-bit analog outputs, 2 channels D
Analog Monitor Board
AO-12 12-bit analog outputs, 2 channels D
DO-08 Six photocoupler outputs and 2 relay outputs D
Digital Output Board
DO-02C 2 relay outputs D
2-31
Installation
Before mounting an option board, remove the terminal cover and be sure that the charge indicator inside the
Inverter is not lit. After confirming that the charge indicator is not lit, remove the Digital Operator and front
cover and then mount the option board.
The side of the front cover of the Inverter for 200/400 V Class 0.4 to 3.7 kW can be cut out as described in Fig
2.22 to make wiring of the option board easy. If the side of the front cover is cut out, the protective structure
will be open chassis (IEC IP00).
Refer to documentation provided with the option board for actual mounting instructions for option slots A, C,
and D.
4CN
A option board connector
2CN
C option board connector
C option board
Option Clip
(To prevent raising of
C and D option boards)
D option board
3CN
D option board connector D option board mounting spacer
A option board
A option board mounting spacer
Front Cover
Slit
Cut out the slits on the front cover with nippers. Be careful to avoid injury.
2-32
Installing and Wiring Option Boards
PG-A2
The terminal specifications for the PG-A2 are given in the following table.
PG-B2
The terminal specifications for the PG-B2 are given in the following table.
2-33
PG-D2
The terminal specifications for the PG-D2 are given in the following table.
6 Common terminal -
7 Pulse monitor output + terminal
Line driver output (RS-422 level output)
8 Pulse monitor output - terminal
TA2 (E) Shield connection terminal -
* 5 VDC and 12 VDC cannot be used at the same time.
PG-X2
The terminal specifications for the PG-X2 are given in the following table.
2-34
Installing and Wiring Option Boards
Wiring
Wiring examples are provided in the following illustrations for the option boards.
Three-phase,
200 VAC (400 VAC) Inverter
R/L1 U/T1
S/L2 V/T2
T/L3 W/T3
PG-A2
+12 V power supply
1
2 0 V power supply
4CN 4CN
3 (Short circuit across
terminals 3-4)
4
TA1 Pulse input (+)
5
Pulse input (-)
6
E E
7
TA2 (E) Pulse monitor output
8
PG power
supply
+12 V
Pulse input
Short for
open-col-
lector
input
Pulse
monitor
output
Pulse
input
2-35
Wiring the PG-B2
Wiring examples are provided in the following illustrations for the PG-B2.
Inverter
Three-phase 200
VAC (400 VAC)
PG power
supply +12 V
A-phase pulse
monitor output
Division rate circuit
A-phase
A-phase pulse pulses
input
B-phase pulse
monitor output
B-phase
B-phase pulse pulses
input
• When connecting to a voltage-output-type PG (encoder), select a PG that has an output impedance with
a current of at least 12 mA to the input circuit photocoupler (diode).
• The pulse monitor dividing ratio can be changed using constant F1-06 (PG division rate).
A-phase pulses
B-phase pulses
• The pulse monitor emitter is connected to common inside the PG-B2. The emitter common must be used
for external circuits.
2-36
Installing and Wiring Option Boards
Three-phase Inverter
200 VAC (400
VAC) R/L1 U/T1
S/L2 V/T2
T/L3 W/T3
2-37
Wiring Terminal Blocks
Use no more than 100 meters of wiring for PG (encoder) signal lines, and keep them separate from power
lines.
Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield to the
shield connection terminal.
2-38
Installing and Wiring Option Boards
PG-A2/PG-B2
The maximum response frequency is 32,767 Hz.
Use a PG that outputs a maximum frequency of approximately 20 kHz for the rotational speed of the motor.
Some examples of PG output frequency (number of pulses) for the maximum frequency output are shown in
Table 2.21.
PG power supply
Signals
2-39
PG-D2/PG-X2
There are 5 V and 12 V PG power supplies.
Check the PG power supply specifications before connecting.
The maximum response frequency is 300 kHz.
Use the following equation to computer the output frequency of the PG (fPG).
A separate power supply is required if the PG power supply capacity is greater than 200 mA. (If momentary
power loss must be handled, use a backup capacitor or other method.)
PG-X2
PG power
supply
TA1
AC
0V +12V
IP12 1
0V
IG 2
Capacitor for +12 V
IP5 3 momentary
power loss + +
A (+) 4
- PG
A (-) 5
+
B (+) 6
-
B (-) 7
Z (+) 8
Z (-) 9
IG 10
TA3
2-40
Digital Operator and Modes
This chapter describes Digital Operator displays and functions, and provides an overview of
operating modes and switching between modes.
Digital Operator............................................................3-2
Modes ..........................................................................3-5
Digital Operator
This section describes the displays and functions of the Digital Operator.
Keys
ESC Key Returns to the status before the DATA/ENTER Key was pressed.
Enables jog operation when the Inverter is being operated from the
JOG Key
Digital Operator.
3-2
Digital Operator
Selects the rotation direction of the motor when the Inverter is being
FWD/REV Key
operated from the Digital Operator.
Selects menu items, sets user constant numbers, and increments set
Increment Key values.
Used to move to the next item or data.
Selects menu items, sets user constant numbers, and decrements set
Decrement Key values.
Used to move to the previous item or data.
Pressed to enter menu items, user constants, and set values.
DATA/ENTER Key Also used to switch from one display to another.
Constants cannot be changed when Undervoltage (UV) is detected.
There are indicators on the upper left of the RUN and STOP Keys on the Digital Operator. These indicators
will light and flash to indicate operating status.
The RUN Key indicator will flash and the STOP Key indicator will light during initial excitation of the
dynamic brake. The relationship between the indicators on the RUN and STOP Keys and the Inverter status is
shown in the Fig 3.2.
RUN
STOP
Lit Blinking Not lit
3-3
The following table shows the relationship between the indicators on the RUN and STOP Keys and the
Inverter conditions.
The indicators are lit, unlit or blinking reflecting the order of priority.
4 Stopped Stopped
3-4
Modes
Modes
This section describes the Inverter's modes and switching between modes.
Inverter Modes
The Inverter's user constants and monitoring functions are organized in groups called modes that make it eas-
ier to read and set user constants.The Inverter is equipped with 5 modes.
The 5 modes and their primary functions are shown in the Table 3.3.
3-5
Switching Modes
The mode selection display will appear when the MENU Key is pressed from a monitor or setting display.
Press the MENU Key from the mode selection display to switch between the modes.
Press the DATA/ENTER Key from the mode selection key to monitor data and from a monitor display to
access the setting display.
Display at Startup
'5,9( 5G\
乥⥛ᣛҸ
8 +]
0(18
Mode Selection
Display Monitor Display Setting Display
'$7$ '$7$
(17(5 (17(5
˚ '$7$
5(6(7 (17(5
'5,9( '5,9( 5G\ '5,9( 5G\ '5,9( 5G\
偅ࡼᓣ ⲥ㾚 乥⥛ᣛҸ 乥⥛ᣛҸ
* *
* 8 +] 8 +] 8 +]
(6& (6& (6&
0(18
'$7$
(17(5 '$7$
48,&. 48,&. (17(5 48,&.
ㅔᯧᑣᓣ ࠊᓣ䗝ᢽ ᮴3*ⶶ䞣ࠊ
* *
* $ $
(6& (6&
0(18
'$7$
(17(5
'$7$ ˚ '$7$
(17(5 5(6(7 (17(5
$'9 $'9 $'9 $'9
催㑻ᑣᓣ ⦃๗䆒ᅮ ᭛ᄫ䗝ᢽ Ё᭛
* *
* $ $ $
(6& (6& (6&
0(18
'$7$
9(5,)<
(17(5
9(5,)< The constant number will be displayed if a
᷵偠ᓣ ᮴ব constant has been changed. Press the
DATA/ENTER Key to enable the change.
* *
*
(6&
0(18
'$7$
(17(5 '$7$
$781( $781( (17(5 $781(
㞾ᄺдᓣ 䗝ᢽ㞾ᄺдᓣ ᮟ䕀ᔶ㞾ᄺд
* *
* 7 7
(6& (6&
When running the Inverter after using Digital Operator, press the MENU Key to select the drive mode (dis-
played on the LCD screen) and then press the DATA/ENTER Key from the drive mode display to bring up the
monitor display. Run Commands can't be received from any other display. (Monitor display in the drive mode
IMPORTANT will appear when the power is turned ON.)
3-6
Modes
Drive Mode
Drive mode is the mode in which the Inverter can be operated. The following monitor displays are possible in
drive mode: The frequency reference, output frequency, output current, and output voltage, as well as fault
information and the fault history.
When b1-01 (Reference selection) is set to 0, the frequency can be changed from the frequency setting display.
Use the Increment, Decrement, and Shift/RESET Keys to change the frequency. The user constant will be
written and the monitor display will be returned to when the DATA/ENTER Key is pressed after changing the
setting.
Example Operations
Key operations in drive mode are shown in the following figure.
Display at Startup
'5,9( 5G\
乥⥛ᣛҸ
8 +]
0(18
'$7$
Mode Selection Monitor Display (17(5 Frequency Setting Display
Display
'$7$
(17(5
$ %
'$7$
˚ (17(5
'5,9( '5,9( 5G\ 5(6(7 '5,9( 5G\ '5,9( 5G\
* *
* 8 +] 8 +] 8 +]
(6&
(6&
0(18 (6&
$'9 ⲥ㾚 ዄֱؐᣕ䕧ߎ乥⥛
催㑻ᑣᓣ 8
+] 8 +]
* (6&
* *
0(18
'$7$
(17(5
9(5,)<
˚
5(6(7
The fault name will be
᷵偠ᓣ '5,9( 5G\ '5,9( 5G\
displayed if the DATA/ENTER
* ᬙ䱰䎳䏾 ᔧࠡᬙ䱰
* * Key is pressed while a constant
8 8 is being displayed for which a
0(18
(6& fault code is being displayed.
˚
$781( 5(6(7 '$7$
'5,9( 5G\ '5,9( 5G\ (17(5 '5,9( 5G\
㞾ᄺдᓣ
ᬙ䱰䎳䏾 䖛এᬙ䱰 Џಲ䏃䖛⬉य़
*
* * 8 29 8 29 8 29
(6& (6&
'$7$
(17(5
˚ '$7$
5(6(7 (17(5
'5,9( '5,9( '5,9(
ᬙ䱰䆄ᔩ ࠡᬙ䱰 䕧ߎ䖛⬉⌕
8 2& 8 2& 8 2&
(6& (6&
˚
5(6(7 '$7$
5G\ (17(5 '5,9( 5G\
'5,9( '5,9( 5G\
ᬙ䱰䆄ᔩ ࠡᬙ䱰 Џಲ䏃䖛⬉य़
8 29 8 29 8 29
(6& (6&
$ %
3-7
Note When changing the display with the Increment and Decrement Keys, the next display after the one for the last parameter number will be the one for the
first parameter number and vise versa. For example, the next display after the one for U1-01 will be U1-40. This is indicated in the figures by the letters
A and B and the numbers 1 to 6.
The display for the first monitor constant (frequency reference) will be displayed when power is turned ON.
The monitor item displayed at startup can be set in o1-02 (Monitor Selection after Power Up).
Operation cannot be started from the mode selection display.
IMPORTANT
Example Operations
Key operations in quick programming mode are shown in the following figure.
3-8
Modes
'5,9(
偅ࡼᓣ
*
* *
$ %
0(18
'$7$
(17(5 '$7$
48,&. 48,&. (17(5 48,&.
9(5,)<
E E
(6&
᷵偠ᓣ
*
* *
'$7$
48,&. (17(5 48,&.
0(18
ッᄤ$0Ⲟ ッᄤ$0Ⲟ
+ +
$781(
(6&
㞾ᄺдᓣ
* '$7$
* * 48,&. (17(5 48,&.
⬉ᴎֱᡸࡳ㛑䗝ᢽ 䗮⫼⬉ᴎ
/ /
(6&
'$7$
48,&. (17(5 48,&.
ޣ䗳䰆ℶ༅䗳䗝ᢽ ᳝ᬜ
/ /
(6&
$ %
3-9
Advanced Programming Mode
In advanced programming mode, all Inverter constants can be monitored and set.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET Keys to
change the frequency. The user constant will be written and the monitor display will be returned to when the
DATA/ENTER Key is pressed after changing the setting.
Refer to Chapter 5 User Constants for details on the constants.
Example Operations
Key operations in advanced programming mode are shown in the following figure.
$ %
'$7$
(17(5
'$7$ ˚
(17(5 5(6(7
$'9 $'9 $'9 $'9
催㑻ᑣᓣ ⦃๗䆒ᅮ ᭛ᄫ䗝ᢽ Ё᭛
* *
* $ $ $
(6& (6& (6&
0(18
'$7$
˚ (17(5
5(6(7
$'9 $'9 $'9
9(5,)< ⦃๗䆒ᅮ ࠊᓣ䗝ᢽ ᮴3*ⶶ䞣ࠊ
᷵偠ᓣ
$ $
(6&
$
*
* * (6&
0(18
$781(
㞾ᄺдᓣ ˚
'$7$
(17(5
5(6(7
* $'9 $'9 $'9
* * 3,'ࠊ 3,'ࠊ䗝ᢽ 3,'᮴ᬜ
0(18 E E E
(6&
(6&
'5,9(
˚ '$7$
偅ࡼᓣ $'9
5(6(7
$'9 (17(5 $'9
* 3,'ࠊ
* * ড作ϻ༅Ẕߎᯊ䯈 ড作ϻ༅Ẕߎᯊ䯈
E VHF E VHF E VHF
0(18 (6&
(6&
48,&.
ㅔᯧᑣᓣ
*
* * '$7$
˚ (17(5
0(18 5(6(7 $'9 $'9
$'9
䕀ⶽᵕ䰤 ℷ䕀⬉ࡼ䕀ⶽᵕ䰤 ℷ䕀⬉ࡼ䕀ⶽᵕ䰤
/ / /
(6& (6&
˚ '$7$
5(6(7 (17(5
$'9 $'9 $'9
䕀ⶽᵕ䰤 ড䕀⫳ݡ䕀ⶽᵕ䰤 ড䕀⫳ݡ䕀ⶽᵕ䰤
/ / /
(6&
(6&
$ %
3-10
Modes
“ 写入完毕 ” is displayed for 1.0 s after the data setting has been confirmed
11
with the DATA/ENTER Key.
3-11
External Fault Setting Procedure
Examples of the Digital Operator displays that appear when setting an eternal error for a multi-function con-
tact input in Advanced Programming Mode are shown in the following diagram.
$ %
'$7$ '$7$
(17(5 (17(5
'$7$ ˚
(17(5 5(6(7
$'9 $'9 $'9 $'9
催㑻ᑣᓣ ᭄ᄫ䕧ܹ ッᄤ6ࡳ㛑䆒ᅮ $ᐌᯊ㞾⬅䖤㸠
* *
* + + +
(6& (6& (6&
0(18
˚
5(6(7 $'9
$'9 $'9
9(5,)< ッᄤ6䆒ᅮ
᭄ᄫ䕧ܹ %ᐌᯊ㞾⬅䖤㸠
᷵偠ᓣ
*
+ + +
* * (6&
0(18 ˚
5(6(7 $'9
$'9 $'9
$781(
᭄ᄫ䕧ܹ ッᄤ6䆒ᅮ $䖤㸠Ё㞾⬅䖤㸠
㞾ᄺдᓣ + + +
* (6&
* *
0(18
$'9
%䖤㸠Ё㞾⬅䖤㸠
'5,9( $'9
+
偅ࡼᓣ ᭄ᄫ䕧ߎ
* +
* *
0(18
$'9
48,&.
㛝ކ䕧ܹ䕧ߎ䆒ᅮ
ㅔᯧᑣᓣ
* +
* * $'9
0(18
%䖤㸠Ёা䄺
$ % + )
3-12
Modes
Verify Mode
Verify mode is used to display any constants that have been changed from their default settings in a program-
ming mode or by autotuning. “ 无变更 ” will be displayed if no settings have been changed.
Of the environment mode settings, only A1-02 will be displayed if it has been changed. Other environment
modes settings will not be displayed even if they have been changed from their default settings.
Even in verify mode, the same procedures can be used to change settings as are used in the programming
modes. Use the Increment, Decrement, and Shift/RESET Keys to change the frequency. The user constant will
be written and the monitor display will be returned to when the DATA/ENTER Key is pressed after changing
the setting.
Example Operations
An example of key operations is given below for when the following settings have been changed from their
default settings: b1-01 (Reference Selection), C1-01 (Acceleration Time 1), E1-01 (Input Voltage Setting), and
E2-01 (Motor Rated Current).
$'9
催㑻ᑣᓣ
***
$ %
0(18
'$7$
(17(5 '$7$
9(5,)< 9(5,)< (17(5 9(5,)<
᷵偠ᓣ 乥⥛ᣛҸ䗝ᢽ
᪡఼
* E
* *
E
(6&
(6&
0(18
'$7$
9(5,)< (17(5 9(5,)<
䕧ܹ⬉य़ 䕧ܹ⬉य़
3-13
Autotuning Mode
Autotuning automatically tunes and sets the required motor constants when operating in the vector control
methods. Always perform autotuning before starting operation.
When V/f control has been selected, stationary autotuning for only line-to-line resistance can be selected.
When the motor cannot be disconnected from the load, perform stationary autotuning. Contact your Yaskawa
representatives to set motor constants by calculation.
The Inverter's autotuning function automatically determines the motor constants, while a servo system's auto-
tuning function determines the size of a load, so these autotuning functions are fundamentally different. The
default setting of the Inverter is for open-loop vector 1 control.
Example of Operation
Set the motor output power (in kW), rated voltage, rated current, rated frequency, rated speed, and number of
poles specified on the nameplate on the motor and then press the RUN Key. The motor is automatically run
and the motor constants measured based on these settings and autotuning will be set.
Always set the above items. Autotuning cannot be started otherwise, e.g., it cannot be started from the motor
rated voltage display.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET Keys to
change the frequency. The user constant will be written and the monitor display will be returned to when the
DATA/ENTER Key is pressed after changing the setting.
The following example shows autotuning for open-loop vector control while operating the motor without
switching to motor 2.
3-14
Modes
9(5,)<
᷵偠ᓣ
***
$
0(18
'$7$
(17(5 '$7$
$781( $781( (17(5 $781(
㞾ᄺдᓣ 䗝ᢽ㞾ᄺдᓣ ᮟ䕀ᔶ㞾ᄺд
* *
* 7 7
(6& (6&
0(18
'$7$
$781( (17(5 $781(
'5,9(
⬉ᴎᴀ乥⥛ ⬉ᴎᴀ乥⥛
偅ࡼᓣ 7 +] 7 +]
* *
* (6&
'$7$
0(18 $781( (17(5 $781(
⬉ᴎᵕ᭄ ⬉ᴎᵕ᭄
7
48,&.
(6&
ㅔᯧᑣᓣ
$'9 6723
催㑻ᑣᓣ The display will
$ automatically
* *
* change depending
$781(
㞾ᄺдЁℶ
$781(
㞾ᄺдᅠ↩
0(18 on the status of 䕧ܹњ 6723 䬂
autotuning.
* TUn10 will be displayed during rotational autotuning and TUn11 will be displayed during stationary autotuning. The DRIVE indicator will light when
autotuning starts.
The setting displays in for autotuning depend on the control method (V/f, V/f with PG, or open-loop vector). If
a fault occurs during autotuning, refer to Chapter 7 Troubleshooting.
IMPORTANT
3-15
Trial Operation
This chapter describes the procedures for trial operation of the Inverter and provides an example
of trial operation.
START
Installation
Wiring
Turn ON power.
Confirm status.
Select
Basic settings
operating
(Quick programming mode)
method.
Vector (A1-02=2, 3, or 4)*5
V/f control?
V/f YES V/f with PG
(Default: A1-02=0) (A1-02=1)
PG?
YES NO
NO Stationary autotuning for *4 Rotational Stationary Stationary
line-to-line resistance only autotuning autotuning 1 *6 autotuning 2 *6
Application settings
(Advanced programming mode)
*1 Set for 400 V Class Inverter for 55 kW or more.
No-load operation
*2 If there is a reduction gear between the motor and PG, set
the reduction ratio in F1-12 and F1-13 in advanced
Loaded operation programming mode.
Check/record constants. *4 If the motor cable changes to 50 m or longer for the actual
installation, perform stationary autotuning for the line-to-line
resistance only on-site.
END
*5 The default control mode is open-loop vector control 2
(A1-02 =2).
4-2
Trial Operation Procedures
Power tap
Power ON
Confirm all of the following items and then turn ON the power supply.
• Check that the power supply is of the correct voltage.
200 V Class: 3-phase 200 to 240 VDC, 50/60 Hz
400 V Class: 3-phase 380 to 480 VDC, 50/60 Hz
• Make sure that the motor output terminals (U, V, W) and the motor are connected correctly.
• Make sure that the Inverter control circuit terminal and the control device are wired correctly.
• Set all Inverter control circuit terminals to OFF.
• When using a PG Speed Control Board, make sure that it is wired correctly.
• Make sure that the motor is not connected to the mechanical system (no-load status)
4-3
Checking the Display Status
If the Digital Operator's display at the time the power is connected is normal, it will read as follows:
'5,9( 5G\
Display for normal operation 乥⥛ᣛҸ The frequency reference monitor is dis-
played in the data display section.
8 +]
When an fault has occurred, the details of the fault will be displayed instead of the above display. In that case,
refer to Chapter 7 Troubleshooting. The following display is an example of a display for faulty operation.
'5,9(
The display will differ depending on the
Display for fault operation 89 type of fault.
Џಲ䏃⬉य़ A low voltage alarm is shown at left.
4-4
Trial Operation Procedures
Basic Settings
Switch to the quick programming mode (“QUICK” will be displayed on the LCD screen) and then set the fol-
lowing user constants. Refer to Chapter 3 Digital Operator and Modes for Digital Operator operating proce-
dures and to Chapter 5 User Constants and Chapter 6 Constant Settings by Function for details on the user
constants.
Constants that must be set are listed in Table 4.1 and those that are set according to the application are listed in
Table 4.2.
Table 4.1 Constants that Must Be Set
Con-
Setting Factory
stant Name Description Page
Range Setting
Number
Set the control method for the Inverter.
0: V/f control
Control method 1: V/f control with PG
A1-02 0 to 4 2 5-8
selection 2: Open-loop vector 1 control
3: Flux vector
4: Open-loop vector 2 control
Set the frequency reference input method.
0: Digital Operator 5-10
Reference selec- 1: Control circuit terminal (analog input) 6-2
b1-01 0 to 4 1
tion 2: MEMOBUS communications 6-76
3: Option board 6-94
4: Pulse train input
Set the Run Command input method.
5-10
0: Digital Operator
Operation 6-10
b1-02 1: Control circuit terminal (sequence input) 0 to 3 1
method selection 6-76
2: MEMOBUS communications
6-94
3: Option board
Acceleration time Set the acceleration time in seconds for the output 5-21
C1-01 0.0 to 6000.0 10.0 s
1 frequency to climb from 0% to 100%. 6-18
Deceleration time Set the deceleration time in seconds for the output 5-21
C1-02 0.0 to 6000.0 10.0 s
1 frequency to fall from 100% to 0%. 6-18
200 V
155 to 255 V (200 V
Set the Inverter's nominal input voltage in volts.
Input voltage set- (200 V Class) Class) 5-33
E1-01 This setting is used as a reference value in protec-
ting 310 to 510 V 400 V 6-120
tion functions.
(400 V Class) (400 V
Class)
Setting for
general-
10% to 200% purpose 5-34
Motor rated cur-
E2-01 Set the motor rated current. of Inverter's motor of 6-57
rent
rated current same 6-117
capacity
as Inverter
Set to enable or disable the motor overload protec-
tion function using the electronic thermal relay.
Motor protection 0: Disabled 5-57
L1-01 0 to 3 1
selection 1: General motor protection 6-57
2: Inverter motor protection
3: Vector motor protection
4-5
Table 4.2 Constants that Are Set as Required
Con-
Setting Factory
stant Name Description Page
Range Setting
Number
Select stopping method when Stop Command is
sent.
Stopping method 0: Deceleration to stop 5-10
b1-03 0 to 3 0
selection 1: Coast to stop 6-12
2: DC braking stop
3: Coast to stop with timer
Depends
on capac-
Carrier fre- ity, volt-
C6-02 1 to F 5-26
quency selection age, and
The carrier frequency is set low if the motor cable control
is 50 m or longer or to reduce radio noise or leak- method.
age current.
Carrier fre-
Depends
quency selection
C6-11 1 to 4 on kVA 5-26
for open-loop
setting.
vector 2 control
d1-01 to
Frequency refer-
d1-01 to d1-04:
ences 1 to 4 and Set the required speed references for multi-step
d1-04 and 0 to 400.00 Hz 0.00 Hz 5-27
jog frequency ref- speed operation or jogging.
d1-17 d1-17:
erence
6.00 Hz
Set the voltage level gain for the multi-function H4-02:
H4-02
FM and AM ter- analog output 1 (H4-02) and 2 (H4-05). 1.00
and H4- 0.00 to 2.50 5-53
minal output gain Set the number of multiples of 10 V to be output as H4-05:
05
the 100% output for the monitor item. 0.50
0: Disabled (Deceleration as set. If deceleration
time is too short, a main circuit overvoltage
may result.)
1: Enabled (Deceleration is stopped when the
main circuit voltage exceeds the overvoltage
level. Deceleration restarts when voltage is
Stall prevention returned.)
5-60
L3-04 selection during 2: Intelligent deceleration mode (Deceleration 0 to 3 1
6-25
deceleration rate is automatically adjusted so that the
Inverter can decelerate in the shortest possible
time. Set deceleration time is disregarded.)
3: Enabled (with Braking Resistor Unit)
When a braking option (Braking Resistor, Braking
Resistor Unit, Braking Unit) is used, always set to
0 or 3.
4-6
Trial Operation Procedures
Overview of Settings
Make the required settings in quick programming mode and autotuning mode according to the following flow-
chart.
START
NO
Vector control (A1-02 = 2, 3, or 4)*3
V/f control?
YES 㧔A1-02=0 or 1)
V/f
Control mode selection
PG?
YES
NO 㧔A1-02=1㧕
(Default:
A1-02=0)
Set E1-03. Set E1-03, E2-04, and F1-01. *2
V/f default: 200V/50Hz(400V/50Hz) V/f default: 200V/50Hz(400V/50Hz)
NO YES
END
Note If the motor cable changes to 50 m or longer for the actual installation, perform stationary autotuning for the line-to-line resistance only on-site.
* 1. Use rotational autotuning to increase autotuning accuracy whenever it is okay for the motor to be operated. Always perform rotational autotuning when
using open-loop vector 2 control.
* 2. If there is a reduction gear between the motor and PG, set the reduction ratio in F1-12 and F1-13.
* 3. The default setting of the Inverter is for open-loop vector 1 control (A1-02 = 2).
* 4. If the maximum output frequency is different from the base frequency, set the maximum output frequency (E1-04) after autotuning.
Fig 4.3 Settings According to the Control Method
4-7
Setting the Control Method
Any of the following five control methods can be set.
Constant Set-
Control Method Basic Control Main Applications
ting
Variable speed control, particularly
control of multiple motors with one
V/f control A1-02 = 0 Voltage/frequency ratio fixed control
Inverter and replacing existing Invert-
ers
Applications requiring high-precision
Voltage/frequency ratio fixed control
V/f control with PG A1-02 = 1 speed control using a PG on the
with speed compensation using a PG
machine side
Variable speed control, applications
Open-loop vector 1 A1-02 = 2
Current vector control without a PG requiring speed and torque accuracy
control (factory setting)
using vector control without a PG
Very high-performance control with a
PG (simple servo drives, high-preci-
Flux vector control A1-02 = 3 Flux vector control
sion speed control, torque control, and
torque limiting)
Very high-performance control with-
Current vector control without a PG
out a PG (torque control without a PG,
Open-loop vector 2 with an ASR (speed controller)
A1-02 = 4 torque limiting, applications requiring
control (Always perform rotational autotun-
a 1:200 speed control range without a
ing.)
PG)
Note With vector control, the motor and Inverter must be connected 1:1. The motor capacity for which stable control is possible is 50% to 100% of the capac-
ity of the Inverter.
4-8
Trial Operation Procedures
• Perform stationary autotuning for the line-to-line resistance only if the motor cable is 50 m or longer for
the actual installation or the load is heavy enough to produce stalling. Refer to the following section on
Autotuning for details on stationary autotuning.
Autotuning
Use the following procedure to perform autotuning to automatically set motor constants when using the vector
control method, when the cable length is long, etc.
If the control method was changed after autotuning, be sure to perform autotuning again.
One of the following four autotuning modes can be set.
• Rotational autotuning
• Stationary autotuning 1
• Stationary autotuning for line-to-line resistance only
• Stationary autotuning 2
4-9
• If the wiring between the Inverter and motor changes by 50 m or more between autotuning and motor
installation, perform stationary autotuning for line-to-line resistance only.
• If the motor cable is long (50 m or longer), perform stationary autotuning for line-to-line resistance only
even when using V/f control.
• The status of the multi-function inputs and multi-function outputs will be as shown in the following table
during autotuning. When performing autotuning with the motor connected to a load, be sure that the hold-
ing brake is not applied during autotuning, especially for conveyor systems or similar equipment.
• To cancel autotuning, always use the STOP Key on the Digital Operator.
• Power will be supplied to the motor when stationary autotuning is performed even though the motor will
not turn. Do not touch the motor until autotuning has been completed.
1. Always disconnect the motor from the machine and confirm that it is safe to operate the motor before
performing rotational autotuning.
2. If the motor cannot be operated by itself, perform stationary autotuning, but always use rotational
IMPORTANT autotuning whenever it is possible to operate the motor by itself to increase performance.
4-10
Trial Operation Procedures
3. After stopping the motor, check the values of E2-02 and E2-03 again in verify mode or advanced program-
ming mode. If the values of E2-02 and E2-03 differ from the ones before the first operation was carried
out, the settings have been successfully completed. Next, check if the values are suitable or not.
If the values of E2-02 and E2-03 differed greatly from the reference data of the motor in the test report or the
instruction manual, hunting, motor vibrations, insufficient motor torque, or an overcurrent may occur because
the motor is operated although the aforementioned conditions have not been fulfilled after stationary
autotuning1. For elevators, failure to observe this caution may result in the cage falling or injury. If so, per-
form stationary autotuning1 again and run the motor using the aforementioned procedure under the recom-
mended conditions or perform stationary autotuning 2 or rotational autotuning.
Usually the standard setting for E2-02 is 1 Hz to 3 Hz, and that for E2-03 is 30% to 65% of the rated current
for a general-purpose motor. Generally, the larger the motor capacity is, the smaller the rated slip and the ratio
of the no-load current to the rated current become. Use the data given in Factory Settings that Change with the
Inverter Capacity (o2-04) of Chapter 5 User Constants as a reference.
1. Power will be supplied to the motor when stationary autotuning 1 is performed even though the motor
will not turn. Do not touch the motor until autotuning has been completed.
2. When performing stationary autotuning 1 connected to a conveyor or other machine, ensure that the
IMPORTANT holding brake is not activated during autotuning.
1. Power will be supplied to the motor when stationary autotuning for line-to-line resistance is performed
even though the motor will not turn. Do not touch the motor until autotuning has been completed.
2. When performing stationary autotuning connected to a conveyor or other machine, ensure that the
IMPORTANT holding brake is not activated during autotuning.
1. Power will be supplied to the motor when stationary autotuning 2 is performed even though the motor
will not turn. Do not touch the motor until autotuning has been completed.
2. When performing stationary autotuning 2 connected to a conveyor or other machine, ensure that the
IMPORTANT holding brake is not activated during autotuning.
4-11
Precautions for Rotational and Stationary Autotuning
Lower the base voltage based on Fig 4.4 to prevent saturation of the Inverter’s output voltage when the rated
voltage of the motor is higher than the voltage of the power supply to the Inverter. Use the following proce-
dure to perform autotuning.
1. Input the voltage of the input power supply to T1-03 (Motor rated voltage).
2. Input the results of the following formula to T1-05 (Motor base frequency):
(Base frequency from the motor’s nameplate × setting of T1-03)/(Rated voltage from motor’s nameplate)
3. Perform autotuning.
After having completed autotuning, set E1-04 (Max. output frequency) to the base frequency shown on the
motor nameplate.
Output voltage
Output frequency
0 Base frequency
Base frequency from motor nameplate
from motor nameplate ×T1-03
Fig 4.4 Motor Base Frequency and Inverter Input Voltage Setting
1. When speed precision is required at high speeds (i.e., 90% of the rated speed or higher), set T1-03 (Motor
rated voltage) to the input power supply voltage × 0.9.
2. When operating at high speeds (i.e., 90% of the rated speed or higher), the output current will increase as
IMPORTANT the input power supply voltage is reduced. Be sure to provide sufficient margin in the Inverter current.
4-12
Trial Operation Procedures
If the values of E2-02 and E2-03 differed greatly from the reference data of the motor in the test report or the
instruction manual, hunting, motor vibrations, insufficient motor torque, or an overcurrent may occur because
the motor is operated although the aforementioned conditions have not been fulfilled after stationary autotun-
ing 1. For elevators, failure to observe this caution may result in the cage falling or injury. If so, perform sta-
tionary autotuning 1 again and run the motor using the aforementioned procedure under the recommended
conditions or perform stationary autotuning 2 or rotational autotuning.
Usually the standard setting for E2-02 is 1 Hz to 3 Hz, and that for E2-03 is 30% to 65% of the rated current
for a general-purpose motor. Generally, the larger the motor capacity is, the smaller the rated slip and the ratio
of the no-load current to the rated current become. Use the data given in Factory Settings that Change with the
Inverter Capacity (o2-04) of Chapter 5 User Constants as a reference.
4-13
Constant Settings for Autotuning
The following constants must be set before autotuning.
Motor out-
put power
Set the output power of the 0.00 to 0.40 kW
T1-02 Yes Yes Yes Yes Yes
motor in kilowatts.*5 *7 650.00 kW *2
电机额定功
率
Motor 0.0 to
rated volt- 255.0 V 200.0 V
age (200 V (200 V
Set the rated voltage of the Class) Class)
T1-03 - - Yes Yes Yes
motor in volts.*5 *6 0.0 to 400.0 V
电机额定电 510.0 V (400 V
压
(400 V Class)
Class)
Motor
rated cur-
Set the rated current of the 0.32 to
T1-04 rent 1.90 A*2 Yes Yes Yes Yes Yes
motor in amps.*5 *7 6.40 A*3
电机额定电
流
Motor base
frequency Set the base frequency of the 0.0 to
T1-05 50.0 Hz - - Yes Yes Yes
电机基本频 motor in hertz.*5 *6 400.0 Hz
率
Number of
motor
poles
2 to 48
T1-06 Set the number of motor poles. 4 poles - - Yes Yes Yes
poles
电机极数
4-14
Trial Operation Procedures
Motor base
speed
Set the base speed of the motor 1450
T1-07 0 to 24000 - - Yes Yes Yes
in min−1.*5 min−1
电机额定速
度
Number of
PG pulses
when turn- Set the number of pulses for the
ing PG (pulse generator or
T1-08 encoder). Set the number of 0 to 60000 600 - Yes - Yes -
pulses per motor revolution
PG 脉冲数 without a multiplication factor.
4-15
Application Settings
User constants are set as required in advanced programming mode (“ADV” will be displayed on the LCD
screen). All the constants that can be set in quick programming mode can also be displayed and set in
advanced programming mode.
Setting Examples
The following are examples of settings for applications.
• When using an Inverter-mounted braking resistor (ERF), set L8-01 to 1 to enable ERF braking resistor
overheating protection.
• To prevent the machine from being operated in reverse, set b1-04 to 1 to disable reverse operation.
• To increase the speed of a 50 Hz motor by 10%, set E1-04 to 55.0 Hz.
• To use a 0 to 10-V analog signal for a 50 Hz motor for variable-speed operation between 0 and 45.0 Hz
(0% to 90% speed deduction), set H3-02 to 90.0%.
• To control speed between 20% and 80% to ensure smooth gear operation and limit the maximum speed of
the machine, set d2-01 to 80.0% and set d2-02 to 20.0%.
No-load Operation
To being no-load operation (without connecting the machine and the motor), press the LOCAL/REMOTE Key
on the Digital Operator to change to LOCAL mode (the SEQ and REF indicators on the Digital Operator
should be OFF).
Always confirm safety around the motor and machine before starting Inverter operation from the Digital
Operator. Confirm that the motor works normally and that no errors are displayed at the Inverter.
Jog Frequency Reference (d1-17, default: 6.00 Hz) can be started and stopped by pressing and releasing the
JOG Key on the Digital Operator. If the external sequence prevent operation from the Digital Operator, con-
firm that emergency stop circuits and machine safety mechanisms are functioning, and then start operation in
REMOTE mode (i.e., with a signal from the control signal terminals). The safety precautions must always be
taken before starting the Inverter with the motor connected to the machine.
Both a Run Command (forward or reverse) and a frequency reference (or multi-step speed reference) must
be provided to start Inverter operation.
Input these commands and reference regardless of the operation method (i.e., LOCAL of REMOTE).
INFO
Loaded Operation
Connect the machine to the motor and then start operation as described for no-load operation (i.e., from the
Digital Operator or by using control circuit terminal signals).
4-16
Trial Operation Procedures
4-17
Adjustment Suggestions
If hunting, vibration, or other problems originating in the control system occur during trial operation,
adjust the constants listed in the following table according to the control method. This table lists only the
most commonly used user constants.
4-18
Adjustment Suggestions
4-19
Table 4.4 Adjusted User Constants (Continued)
Recom-
Control Name (Constant Factory
Performance mended Adjustment Method
Method Number) Setting
Setting
Set the output frequency at
Switching the ASR which to change the ASR
proportional gain and 0.0 to max. proportional gain and inte-
ASR switching fre-
integral time accord- 0.0 Hz output fre- gral time when the same val-
quency (C5-07)
ing to the output fre- quency ues cannot be used for both
quency high-speed and low-speed
operation.
Increase the setting if
0.04 to machine rigidity is low and
0.010 s
0.020 s the system vibrates easily.
ASR primary delay • Controlling hunting
(Enabled in the range 0 to
time (C5-06) and vibration
0.010 to 35 Hz. Refer to Procedure
0.035 s for Increasing the Speed
0.035 s
Response below.)
Increase the setting if
machine rigidity is low and
ASR primary delay • Controlling hunting 0.010 to the system vibrates easily.
0.010 s
time 2 (C5-10) and vibration 0.035 s (Enabled above 35 Hz. Refer
to Procedure for Increasing
the Speed Response below.)
(Enabled below the N4-11
Open-loop setting.)
vector 2 • Reduce the setting if speed
control response is slow. (Typi-
• Speed response
(A1-02 = 4) Integral time of speed • Controlling hunting 0.030 ms
0.015 to cally, reduce in intervals of
estimator (N4-07) 0.060 ms 0.05. Refer to Procedure
and vibration
for Increasing the Speed
Response below.)
• Increase the setting if hunt-
ing or vibration occurs.
(Enabled below the N4-11
setting.)
• Increase the setting if
speed response is slow.
High-speed propor- • Speed response (Typically, increase in
tional gain of speed • Controlling hunting 15 10 to 60 intervals of 5. Refer to
estimator (N4-10) and vibration Procedure for Increasing
the Speed Response
below.)
• Reduce the setting if hunt-
ing or vibration occurs.
• Increase the setting if
• Reducing motor motor magnetic noise is
magnetic noise Depends high.
Carrier frequency Default
• Controlling hunting on the • Reduce the setting if hunt-
selection (C6-11) value
and vibration at low capacity. ing or vibration occurs at
speeds (3 Hz or less) low to middle-range
speeds.
* 1. The setting is given for 200 V Class Inverters. Double the voltage for 400 V Class Inverters.
* 2. The factory setting for 400V 132kW and 220kW flax vector control (A1-02 = 3) is 1.5 kHz, for software version VSG123032 or later.
4-20
Adjustment Suggestions
No
C5-01 ≥ 30.0 Increase the setting for the ASR proportional gain (C5-01).
(Typically, increase in intervals of 5.)
Yes
No Reduce the setting for the ASR primary delay time (C5-06).
C5-06 ≤ 0.01
(Typically, reduce in intervals of 0.01.)
Yes
Speed ≥ N4-11
Is the speed response to be Increase the setting for the high-speed proportional gain of
increased for low-speed
operation or high-speed
speed estimator (N4-10). (Typically, increase in intervals
operation? of 5.)
• Do not change the Torque Compensation Gain (C4-01) from its default setting of 1.00 when using open-
loop vector 1 control.
• If speeds are inaccurate during regeneration in open-loop vector 1 control, enable Slip Compensation Dur-
ing Regeneration (C3-04 = 1).
• Use slip compensation to improve speed control during V/f control (A1-02 = 0).
Set the Motor Rated Current (E2-01), Motor Rated Slip (E2-02), and Motor No-load Current (E2-03), and
then adjust the Slip Compensation Gain (C3-01) to between 0.5 and 1.5. The default setting for V/f control
is C3-01 = 0.0 (slip compensation disabled).
• To improve speed response and stability in V/f control with a PG (A1-02 = 1), set the ASR constants (C5-
01 to C5-05) to between 0.5 and 1.5 times the default. (It is not normally necessary to adjust this setting.)
ASR for V/f control with a PG will only control the output frequency; a high gain, such as is possible for
open-loop vector 2 control or flux vector control, cannot be set.
The following user constants will also indirectly affect the control system.
4-21
Table 4.5 Constants Indirectly Affecting Control and Applications (Continued)
Name (Constant Number) Application
Set the maximum torque during vector control. If a setting is increased,
Torque limits (L7-01 to L7-04, L7-06, L7-07) use a motor with higher capacity than the Inverter. If a setting is reduced,
stalling can occur under heavy loads.
Used to increase response for acceleration/deceleration or to reduce over-
shooting when there is low machine rigidity and the gain of the speed
Feed forward control (N5-01 to N5-03) controller (ASR) cannot be increased. The inertia ratio between the load
and motor and the acceleration time of the motor running alone must be
set.
4-22
User Constants
This chapter describes all user constants that can be set in the Inverter.
5-2
Digital Operation Display Functions and Levels
5-3
User Constants Settable in Quick Programming Mode
The minimum user constants required for Inverter operation can be monitored and set in quick programming
mode. The user constants displayed in quick programming mode are listed in the following table. These, and
all other user constants, are also displayed in advanced programming mode.
Refer to the overview of modes on page 3-5 for an overview of quick programming mode.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f -loop Flux Loop BUS
stant Description Range Setting Opera-
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Control
Set the control method for the Inverter.
method 0: V/f control
selection
1: V/f control with PG
A1-02 0 to 4 2 No Q Q Q Q Q 102H
2: Open-loop vector 1 control
控制模式选 3: Flux vector control
择 4: Open-loop vector 2 control
Stopping
Select stopping method when Stop
methodCommand is sent.
selection
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than 0 to 3
b1-03 0 No Q Q Q Q Q 182H
coast to stop, without regenerative *10
停止方法选 operation.)
择 3: Coast to stop with timer (Run
Commands are disregarded during
deceleration time.)
Accelera- Set the acceleration time in seconds
C1-01 tion time 1 for the output frequency to climb from Yes Q Q Q Q Q 200H
加速时间 1 0% to 100%. 0.0 to
6000.0 10.0 s
Decelera- Set the deceleration time in seconds *1
C1-02 tion time 1 for the output frequency to fall from Yes Q Q Q Q Q 201H
减速时间 1 100% to 0%.
Carrier fre-
quency Select carrier wave fixed pattern.
selection 1 to F 6 No
C6-02 Select F to enable detailed settings No Q Q Q Q 224H
*11 *2 *13
载波频率选
using constants C6-03 to C6-07.
择
5-4
Digital Operation Display Functions and Levels
Jog
Frequency reference when Jog Fre-
frequency
quency Selection, FJOG command, or
reference
d1-17 6.00 Hz Yes Q Q Q Q Q 292H
RJOG command is ON for a multi-
点动频率上 function input (unit: Set in o1-03).
限
V/f pattern
selection 0 to E: Select from 15 preset patterns.
E1-03 F: Custom user-set patterns (Applica- 0 to F F No Q Q No No No 302H
V/F 曲线设 ble for setting E1-04 to E1-10).
定
5-5
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f -loop Flux Loop BUS
stant Description Range Setting Opera-
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Max.
output
frequency 40.0 to
50.0 Hz
E1-04 (FMAX) 400.0 No Q Q Q Q Q 303H
*4
*7
最高输出频 Output voltage (V)
VMAX
率 (E1-05)
(V BASE)
(E1-13)
Max.
voltage
VC
(E1-08) 0.0 to 200.0
E1-05 (VMAX) VMIN 255.0 V No Q Q Q Q Q 304H
(E1-10) *3 *3*4
FMIN FB FA FMAX
最大电压 (E1-09) (E1-07) (E1-06) (E1-04)
Frequency (Hz)
Base fre-
quency To set V/f characteristics in a straight 0.0 to
50.0 Hz
E1-06 (FA) line, set the same values for E1-07 and 400.0 No Q Q Q Q Q 305H
*4
E1-09. In this case, the setting for E1- *7
基本频率 08 will be disregarded.
Min. out- Always ensure that the four frequen-
put fre- cies are set in the following manner:
quency E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 0.0 to
(FB) ≥ E1-09 (FMIN) 0.5 Hz
E1-09 (FMIN) 400.0 No Q Q Q A Q 308H
*4
*7
最低输出频
率
Number of
motor Set the number of motor poles. The
E2-04 poles value is set automatically during auto- 2 to 48 4 poles No No Q No Q Q 311H
tuning.
电机极数
Motor
rated Set the output of the motor in units of
output 0.00 to 0.40
E2-11 0.01kW. This constant is automatically No Q Q Q Q Q 318H
650.00 *8
电机额定功
set during autotuning.
率
5-6
Digital Operation Display Functions and Levels
Stall pre-
0: Disabled (Deceleration as set. If
vention deceleration time is too short, a
selection main circuit overvoltage may
during result.)
decelera-
1: Enabled (Deceleration is stopped
tion when the main circuit voltage
exceeds the overvoltage level.
Deceleration restarts when voltage
is returned.)
2: Intelligent deceleration mode 0 to 3
L3-04 1 No Q Q Q Q Q 492H
(Deceleration rate is automatically *9
adjusted so that the Inverter can
减速防止失
decelerate in the shortest possible
速选择 time. Set deceleration time is
disregarded.)
3: Enabled (with Braking Resistor
Unit)
When a braking option (Braking
Resistor, Braking Resistor Unit, Brak-
ing Unit) is used, always set to 0 or 3.
* 1. The setting range for acceleration/deceleration times depends on the setting of C1-10 (Acceleration/deceleration Time Setting Unit). If C1-10 is set to 0,
the setting range is 0.00 to 600.00 (s).
* 2. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter for 0.4 kW are given.
* 3. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 4. The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
* 5. E1-13 is set to the same value as E1-05 by autotuning.
* 6. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 7. The setting range for open-loop vector 2 control is 0 to 132.0.
* 8. The same capacity as that of the Inverter will be set if the constants are initialized.
* 9. The setting range for flux vector and open-loop vector 2 control is 0 to 2.
* 10.0 or 1 for flux vector control and open-loop vector 2 control.
* 11.The setting range depends on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 12.Displayed in Quick Programming Mode when motor 2 is set for a multi-function input.
* 13.The CH1 output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the H4-05 or H4-06 setting is displayed in quick, Advance, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
5-7
User Constant Tables
A: Setup Settings
The following settings are made with the environment constants (A constants): Language displayed on the
Digital Operator, access level, control method, initialization of constants.
Initialize Mode: A1
User constants for the environment modes are shown in the following table.
Name Control Methods
Change
Con- Open Open MEMO-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Language Used to select the language
selection for displayed on the Digital
Digital Operator (LCD).
Operator 0: English
display 1: Japanese
2: German
A1-00 3: French 0 to 7 7 Yes A A A A A 100H -
4: Italian
5: Spanish
语言选择 6: Portuguese
7: Chinese
This constant is not initialized
by the initialize operation.
Constant
Used to set the constant
access level
access level (set/read.)
0: Monitoring only
(Monitoring drive mode
and setting A1-01 and A1-
04.)
1: Used to select user
constant
4-17
A1-01 (Only constants set in A2- 0 to 2 2 Yes A A A A A 101H 6-156
参数的访问级 01 to A2-32 can be read
and set.)
2: Advanced
(Constants can be read
and set in both quick
programming mode and
advanced programming
(A) mode.)
5-8
User Constant Tables
User-set Constants: A2
The constants set by the user are listed in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
User setting Used to set the constant num-
constants bers that can be set/read.
Maximum 32.
A2-01 Effective when the Constant b1-01 106H
to Access Level (A1-01) is set to to - No A A A A A to 6-157
A2-32 用户参数 User Program (1). Constants o3-02 125H
set in constants A2-01 to A2-
32 can be set/read in pro-
gramming mode.
5-9
b: Application Constants
The following settings are made with the application constants (B constants): Operation method selection, DC
injection braking, speed searching, timer functions, dwell functions, droop control, energy saving control, and
zero-servo control.
Prohibition
of reverse
operation 0: Reverse enabled
b1-04 0 or 1 0 No A A A A A 183H 6-62
1: Reverse disabled
反转禁止选
择
5-10
User Constant Tables
5-11
DC Injection Braking: b2
User constants for injection braking are shown in the following table.
DC injection
braking cur- Sets the DC injection braking
0 to 6-12
b2-02 rent current as a percentage of the 50% No A A A No No 18AH
100 6-16
Inverter rated current.
直流制动电流
5-12
User Constant Tables
Speed Search: b3
User constants for the speed search are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Speed Enables/disables the speed
search search function for the Run
selection Command and sets the speed
(current search method.
detection or 0: Disabled, speed calculation
speed calcu- 1: Enabled, speed calculation
lation) 2: Disabled, current detection
3: Enabled, current detection
Speed Calculation:
When the search is started, the
motor speed is calculated and
b3-01 acceleration/deceleration is 0 to 3 2* No A A A No A 191H 6-65
performed from the calculated
speed to the specified
起动速度搜
frequency (motor direction is
索 also searched).
Current Detection:
The speed search is started
from the frequency when
power was momentarily lost
and the maximum frequency,
and the speed is detected at
the search current level.
Speed Sets the speed search operation
search oper- current as a percentage, taking
ating current the Inverter rated current as
(current 100%. 0 to
b3-02
detection) Not usually necessary to set. 200 100%* No A No A No A 192H 6-65
When restarting is not possible
速度搜索电 with the factory settings,
流 reduce the value.
Speed
search Sets the output frequency
decelera- deceleration time during speed
tion time search in 1-second units.
0.1 to
b3-03 (current Set the time for deceleration 2.0 s No A No A No No 193H 6-65
10.0
detection) from the maximum output fre-
quency to the minimum output
搜索减速时 frequency.
间
5-13
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Speed Operation restarts at a speed
search obtained by multiplying the
detection speed from the speed search by
compensa- the compensation gain (excita-
tion gain tion search only.) 1.00 to
b3-10 1.10 No A No A No A 19AH 6-65
(speed cal- Increase this setting if over- 1.20
culation) voltages occur when a speed
search is performed after a
搜索速度补 long baseblock, for example, in
偿增益 searches at startup.
Rotation
direction 0: Disabled (operates with
search specified rotation direction)
b3-14 selection 1: Enabled (operates with 0 or 1 1 No A A A No A 19EH 6-66
rotation direction found by
旋转方向搜 search)
索选择
Speed
search Sets the current level to retry a
retrial cur- speed search as a percentage, 0 to
b3-17 rent level 150% No A No A No A 1F0H 6-66
taking the Inverter rated cur- 200
rent as 100%.
搜索重试 I
值
Speed
search
retrial detec- Sets the time for detection in a 0.00 to
b3-18 tion time speed search retrial in units of 0.10 s No A No A No A 1F1H 6-66
1.00
seconds.
速度搜索检
出时间
Number of
speed search
retrials Sets the number of times that a
b3-19 0 to 10 0 No A No A No A 1F2H 6-66
speed search can be retried.
速度搜索重
试次数
* The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
5-14
User Constant Tables
Timer Function: b4
User constants for timer functions are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Timer func- Sets the timer function out-
tion ON- put ON-delay time (dead
delay time band) for the timer function
0.0 to
b4-01 input, in 1-second units. 0.0 s No A A A A A 1A3H 6-105
300.0
Enabled when a timer func-
ON 延迟时间 tion is set in H1- or H2-
.
Timer func- Sets the timer function out-
tion OFF- put OFF-delay time (dead
delay time band) for the timer function
0.0 to
b4-02 input, in 1-second units. 0.0 s No A A A A A 1A4H 6-105
300.0
Enabled when a timer func-
OFF 延迟时间 tion is set in H1- or H2-
.
PID Control: b5
User constants for PID control are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
PID control 0: Disabled
method 1: Enabled (Deviation is D-
selection controlled.)
2: Enabled (Feedback value
is D-controlled.)
3: PID control enabled
b5-01 (frequency reference + 0 to 4 0 No A A A A A 1A5H 6-107
PID output, D control of
PID 控制选择 deviation)
4: PID control enabled
(frequency reference +
PID output, D control of
feedback value).
Proportional Sets P-control proportional
0.00
gain (P) gain as a percentage.
b5-02 to 1.00 Yes A A A A A 1A6H 6-107
P-control is not performed
PID 增益 25.00
when the setting is 0.00.
5-15
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
PID upper Sets the upper limit after PID-
limit 0.0 to
b5-06 control as a percentage of the 100.0% Yes A A A A A 1AAH 6-107
100.0
PID 上限 maximum output frequency.
PID feed-
back com-
mand loss
detection Sets the PID feedback loss 0.0 to
b5-14 1.0 s No A A A A A 1B2H 6-108
time detection level in s units. 25.5
反馈丧失检出
时间
5-16
User Constant Tables
暂停动作值
PID sleep
operation Set the delay time until the
delay time 0.0 to
b5-16 PID sleep function starts in 0.0 s No A A A A A 1B4H 6-108
25.5
暂停动作延迟
seconds.
时间
Accel/decel
time for PID
reference Set the accel/decel time for 0.0 to
b5-17 0.0 s No A A A A A 1B5H 6-108
PID reference in seconds. 25.5
PID 加减速
时间
Dwell Functions: b6
User constants for dwell functions are shown in the following table.
Name Control Methods
Con- Change Open Open MEMO-
Fac-
stant Setting during BUS
Num-
Description Range
tory
Opera-
V/f Loop Flux Loop Page
Display Setting V/f with Vec- Vec- Vec- Regis-
ber tion PG tor tor tor ter
1 2
Dwell fre-
quency at
0.0 to 4-21
b6-01 start 0.0 Hz No A A A A A 1B6H
400.0 6-22
起动暂停频
率
5-17
Droop Control: b7
User constants for droop functions are shown in the following table.
5-18
User Constant Tables
Energy Saving: b8
User constants for energy-saving control functions are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Energy-sav- Select whether to enable or
ing mode disable energy-saving con-
b8-01 selection trol. 0 or 1 0 No A A A A A 1CCH 6-115
0: Disable
节能模式设定 1: Enable
Energy-sav-
ing filter time Set the energy-saving filter 0.00 to 0.50 s
b8-03 constant time constant with the open- Yes No No A A A 1CEH 6-115
10.0 *2
loop vector control method.
节能滤波时间
5-19
Zero-servo: b9
User constants for dwell functions are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Zero-servo Adjust the strength of the
gain zero-servo lock.
Enabled when the “zero-servo
command” is set for the
multi-function input. When
the zero-servo command has
been input and the frequency
0 to
b9-01 reference drop below excita- 5 No No No No A No 1DAH 6-145
100
零伺服增益 tion level (b2-01), a position
control loop is created and the
motor stops. Increasing the
zero-servo gain in turn
increases the strength of the
lock. Increasing it by too
much will cause oscillation.
5-20
User Constant Tables
C: Autotuning Constants
The following settings are made with the autotuning constants (C constants): Acceleration/deceleration times,
s-curve characteristics, slip compensation, torque compensation, speed control, and carrier frequency func-
tions.
Acceleration/Deceleration: C1
User constants for acceleration and deceleration times are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Accelera- Sets the acceleration time to
4-5
tion time 1 accelerate from 0 to the maxi-
C1-01 Yes Q Q Q Q Q 200H 4-21
mum output frequency, in 1-
加速时间 1 6-18
second units.
5-21
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Accel/decel
time setting
unit 0: 0.01-second units 4-21
C1-10 0 or 1 1 No A A A A A 209H
1: 0.1-second units 6-18
加减速时间
单位
S-curve Acceleration/Deceleration: C2
User constants for S-curve characteristics are shown in the following table.
Name Control Methods
Con- Change Open Open MEMO-
Fac-
stant Setting during BUS
Num-
Description Range
tory
Opera-
V/f Loop Flux Loop Page
Display Setting V/f with Vec- Vec- Vec- Regis-
ber tion PG tor tor tor ter
1 2
S-curve
characteris-
tic time at
0.00 to 4-21
C2-01 accelera- 0.20 s No A A A A A 20BH
tion start 2.50 6-19
加速开始 S
字
S-curve
characteris- All sections of the S-curve characteris-
tic time at tic time are set in seconds units. 0.00 to 4-21
C2-02 accelera- When the S-curve characteristic time is 0.20 s No A A A A A 20CH
tion end 2.50 6-19
set, the accel/decel times will increase
加速结束 S by only half of the S-curve characteris-
字 tic times at start and end.
S-curve
characteris-
tic time at
0.00 to 4-21
C2-04 decelera- 0.00 s No A A A A A 20EH
tion end 2.50 6-19
减速结束 S
字
5-22
User Constant Tables
5-23
Torque Compensation: C4
User constants for torque compensation are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Torque com- Sets torque compensation
pensation gain as a ratio.
gain Usually setting is not neces-
sary.
Adjust in the following cir-
cumstances:
• When the cable is long;
increase the set value.
• When the motor capacity is
smaller than the Inverter
capacity (Max. applicable
motor capacity), increase
the set values. 0.00 to 4-18
C4-01 1.00 Yes A A A No No 215H
• When the motor is oscillat- 2.50 6-39
转矩补偿增 ing, decrease the set val-
益 ues.
Adjust the output current
range at minimum speed rota-
tion so that it does not exceed
the Inverter rated output cur-
rent.
Do not alter the torque com-
pensation gain from its
default (1.00) when using the
open-loop vector 1 control
method.
Forward
starting Sets the forward starting
torque 0.0 to
C4-03 torque as a percentage of the 0.0% No No No A No No 217H -
200.0
motor rated torque.
正转起动
转矩量
Reverse
starting Sets the reverse starting
torque -200.0
C4-04 torque as a percentage of the 0.0% No No No A No No 218H -
to 0.0
motor rated torque.
反转起动
转矩量
Starting
torque time Sets the delay time in ms for
constant starting torque. The filter is 0 to
C4-05 10 ms No No No A No No 219H -
disabled if the time is set to 0 200
起动转矩时 to 4 ms.
间
* The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
5-24
User Constant Tables
ASR pro-
portional 0.00 to
Sets the proportional gain of the speed 20.00 4-19
C5-01 (P) gain 1 300.00 Yes No A No A A 21BH
loop (ASR.) *1 6-136
*2
比例增益 1
ASR inte-
gral (I) 0.000 0.500
Sets the integral time of the speed loop 4-19
C5-02 time 1 to s Yes No A No A A 21CH
(ASR) in 1-second units. 6-136
10.000 *1
积分时间 1
ASR pro-
portional Usually setting is not necessary. 0.00 to
20.00 4-19
C5-03 (P) gain 2 Set to change the rotational speed gain. 300.00 *1
Yes No A No A A 21DH
6-136
2
P, I *
比例增益 2 P=C5-01
I=C5-02
ASR inte-
P=C5-03
gral (I) 0.000 0.500
I=C5-04 4-19
C5-04 time 2 to s Yes No A No A A 21EH
0 E1-04 Motor speed (Hz) 6-136
10.000 *1
积分时间 2
ASR inte-
gral (I) Set to a small value to prevent any rad-
0 to
C5-08 limit ical load change. Set to 100% of the 400% No No No No A A 222H 6-137
400
maximum output frequency.
积分极限
5-25
Carrier Frequency: C6
User constants for the carrier frequency are shown in the following table.
Name Control Methods
Con- Change MEMO-
Fac- Open Open
stant Setting during BUS
Num-
Description Range
tory
Opera-
V/f Loop Flux Loop
Regis-
Page
Display Setting V/f with Vec- Vec- Vec-
ber tion PG tor tor tor ter
1 2
Carrier fre-
quency Select carrier wave fixed pattern. 4-6
1 to F 6 No
C6-02 selection Select F to enable detailed settings No Q Q Q Q 224H 4-18
*2 *1 *4
载波频率选
using constants C6-03 to C6-07. 6-42
择
Carrier fre-
quency
Output frequency x (C6-05) x K
propor-
Output
tional gain frequency
C6-05
(Max. output frequency)
00 to
00 No A A No No No 227H 6-42
*3
K is a coefficient that depends on the 99
载波频率比 setting of C6-03.
例增益 C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
Carrier fre-
quency
selection Select the carrier frequency when open-
for open- loop vector 2 control is used.
4-6
loop vec- 1: 2 kHz 1 No No No No
C6-11 1 to 4 No Q 22DH 4-20
tor 2 con- 2: 4 kHz *1 *4 *4 *4 *4
6-42
trol 3: 6 kHz
4: 8 kHz
无 PG 矢量
2 载波
* 1. The factory settings depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 2. The setting ranges depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 3. This constant can be monitored or set only when F is set for C6-02.
* 4. Displayed in Quick Programming Mode when motor 2 is set for a multi-function input.
* 5. The maximum output frequency depends on the setting for the carrier frequency (refer to page 6-43).
* 6. The factory setting for 400V 132kW and 220kW flax vector control (A1-02 = 3) is 1.5 kHz, for software version VSG123032 or later.
5-26
User Constant Tables
d: Reference Constants
The following settings are made with the reference constants (d constants): Frequency references.
Preset Reference: d1
User constants for frequency references are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Frequency
reference 1 Sets the frequency reference 4-6
d1-01 0.00 Hz Yes Q Q Q Q Q 280H
in the units used in o1-03. 6-5
频率指令 1
5-27
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Frequency The frequency reference
reference 12 when multi-step speed refer-
d1-12 0.00 Hz Yes A A A A A 28DH -
ences 1, 2, and 4 are ON for
频率指令 12 multi-function inputs.
Reference Limits: d2
User constants for frequency reference limits are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Frequency Set the output frequency
reference upper limit as a percent, tak- 0.0 to 6-34
d2-01 upper limit 100.0% No A A A A A 289H
ing the max. output frequency 110.0 6-79
频率指令上限 to be 100%.
5-28
User Constant Tables
Jump Frequencies: d3
User constants for jump frequencies are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Jump fre- Set the center values of the
quency 1 jump frequencies in Hz. 4-21
d3-01 0.0 Hz No A A A A A 294H
This function is disabled by 6-31
禁止频率 1
setting the jump frequency to
Jump fre- 0 Hz. Always ensure that the
quency 2 following applies: 0.0 to 4-21
d3-02 0.0 Hz No A A A A A 295H
d3-01 ≥ d3-02 ≥ d3-03 400.0 6-31
禁止频率 2 Operation in the jump fre-
quency range is prohibited
Jump fre-
but during acceleration and 4-21
d3-03 quency 3 0.0 Hz No A A A A A 296H
deceleration, speed changes 6-31
禁止频率 3 smoothly without jump.
5-29
Torque Control: d5
User constants for the torque control are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Torque con- 0: Speed control (C5-01 to
trol selection C5-07)
1: Torque control
This function is only avail-
able in flux vector control
d5-01 method. To use the function 0 or 1 0 No No No No A A 29AH 6-127
转矩控制选择 for switching between speed
and torque control, set to 0
and set the multi-function
input to “speed/torque control
change.”
5-30
User Constant Tables
Field Weakening: d6
User constants for the field weakening command are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Field weak- Set the Inverter output volt-
ening level age when the field weakening
command is input.
It is enabled when the field
0 to
d6-01 weakening command is set 80% No A A No No No 2A0H -
100
弱励磁值 for a multi-function input.
Set the level as a percentage
taking the voltage set in the
V/f pattern as 100%.
5-31
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Field forcing
function Set the field forcing function.
d6-03 selection 0: Disabled 0 or 1 0 No No No A A A 2A2H -
1: Enabled
励磁增强功能
5-32
User Constant Tables
V/f Pattern: E1
User constants for V/f characteristics are shown in the following table.
Name Control Methods
Con- Change Open Open MEMO-
stant Setting Factory during BUS
Num-
Description Range Setting Opera-
V/f Loop Flux Loop
Regis-
Page
Display V/f with Vec- Vec- Vec-
ber tion PG tor tor tor ter
1 2
Max.
output 40.0 to 50.0
E1-04 frequency 400.0 Hz No Q Q Q Q Q 303H 6-120
*5 *2
最高输出频
率
Min. output
frequency 0.0 to
voltage 2.4 V 4-18
E1-10 255.0 No A A A No No 309H
*1 *2 6-120
*1
最低输出电
压
5-33
Name Control Methods
Con- Change Open Open MEMO-
stant Setting Factory during BUS
Num-
Description Range Setting Opera-
V/f Loop Flux Loop Page
Display V/f with Vec- Vec- Vec- Regis-
ber tion PG tor tor tor ter
1 2
Mid. output
frequency Set only to fine-adjust V/f for the 0.0 to
0.0 V
E1-12 voltage 2 output range. Normally, this setting 255.0 No A A A A A 30BH 6-120
*3
is not required. *1
中间电压 2
Base 0.0 to
voltage 0.0 V
E1-13 255.0 No A A Q Q Q 30CH 6-120
*4
*1
基本电压
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. E1-13 is set to the same value as E1-05 by autotuning.
* 5. The setting range for open-loop vector 2 control is 0 to 132.0.
Motor Setup: E2
User constants for motor 1 are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Motor rated Sets the motor rated current in
current 1 A units.
These set values will become
0.32 to 4-5
the reference values for motor 1.90 A
E2-01 6.40 No Q Q Q Q Q 30EH 6-57
protection, torque limits and *1
电机额定电流 *2 6-117
torque control.
This constant is automatically
set during autotuning.
Motor rated Sets the motor rated slip in
slip Hz units.
These set values will become
0.00 to 2.90 Hz 6-115
E2-02 the reference values for slip No A A A A A 30FH 6-117
20.00 *1
电机额定滑差 compensation.
This constant is automatically
set during autotuning.
Motor no- Sets the motor no-load cur-
0.00 to
load current rent in 1 A units. 1.20 A
E2-03 1.89 No A A A A A 310H 6-117
This constant is automatically *1
空载电流 *3
set during autotuning.
Number of Sets the number of motor
motor poles poles.
E2-04 2 to 48 4 poles No No Q No Q Q 311H 6-117
This constant is automatically
电机极数
set during autotuning.
Motor line- Sets the motor phase-to-phase
to-line resis- 0.000 9.842
resistance in Ω units.
E2-05 tance to Ω No A A A A A 312H 6-117
This constant is automatically
65.000 *1
线间电阻 set during autotuning.
Motor leak Sets the voltage drop due to
inductance motor leakage inductance as a
percentage of the motor rated 0.0 to 18.2%
E2-06 No No No A A A 313H 6-117
voltage. 40.0 *1
电机漏电感
This constant is automatically
set during autotuning.
5-34
User Constant Tables
铁损
Motor rated Set the rated output of the
output motor in units of 0.01 kW. 0.00 to 0.40
E2-11 No Q Q Q Q Q 318H 6-115
This constant is automatically 650.00 *4
电机额定功率
set during autotuning.
Motor iron Sets the motor iron saturation
saturation coefficient at 130% of mag-
1.30 to
E2-12 coefficient 3 netic flux. 1.30 No No No A A A 328H 6-118
1.60
This constant is automatically
饱和系数 3
set during autotuning.
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 3. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given. The upper limit depends on the setting of
E2-01.
* 4. The same capacity as that of the Inverter will be set if the constants are initialized.
5-35
Motor 2 V/f Pattern: E3
User constants for motor 2 V/f characteristics are shown in the following table.
Name Control Methods
Con- Change Open Open MEMO-
stant Setting Factory during BUS
Num-
Description Range Setting Opera-
V/f Loop Flux Loop Page
Display V/f with Vec- Vec- Vec- Regis-
ber tion PG tor tor tor ter
1 2
Motor 2
max. out-
put fre- 40.0 to
50.0
E3-02 quency 400.0 No A A A A A 31AH -
Hz
(FMAX) *3
最高频率
Motor 2
max. volt- 0.0 to 200.0
E3-03 age 255.0 V No A A A A A 31BH -
(VMAX) *1 *2
最大电压
Motor 2
max. volt-
age fre- 0.0 to 50.0
E3-04 quency No A A A A A 31CH -
Output voltage (V) 400.0 Hz
(FA) VMAX
E3-03
基本频率
Motor 2 VC
mid. out- E3-06
Motor 2
mid. out- To set V/f characteristics in a
put fre- straight line, set the same values for
E3-05 and E3-07. 0.0 to
quency 13.2 V
E3-06 In this case, the setting for E3-06 255.0 No A A A No No 31EH -
voltage 1 *1
*1
(VC) will be disregarded.
Always ensure that the four frequen-
中间电压 cies are set in the following manner:
E3-02 (FMAX) ≥ E3-04 (FA) > E3-
Motor 2
05 (FB) > E3-07 (FMIN)
min. out-
put fre-
quency 0.0 to 0.5 Hz
E3-07 No A A A A A 31FH -
(FMIN) 400.0 *2
最低输出频
率
Motor 2
min. out-
put fre-
quency 0.0 to
2.4 V
E3-08 voltage 255.0 No A A A No No 320H -
*1
*1
(VMIN)
最低输出电
压
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
* 3. The setting range for open-loop vector 2 control is 0 to 132.0.
5-36
User Constant Tables
Motor 2 Setup: E4
User constants for motor 2 are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Motor 2 rated Sets the motor rated current in
current 1 A units.
These set values will become
0.32
the reference values for motor 1.90 A
E4-01 to 6.40 No A A A A A 321H 6-57
protection, torque limits and *1
*2
电机额定电流 torque control.
This constant is automatically
set during autotuning.
Motor 2 num-
ber of poles Sets the number of motor
(number of poles.
E4-04 2 to 48 4 poles No No A No A A 324H -
poles) This constant is automatically
set during autotuning.
电机 2 极数
Motor 2 line-
to-line resis- Sets the motor phase-to-phase
0.000 9.842
tance resistance in Ω units.
E4-05 to Ω No A A A A A 325H -
This constant is automatically
电机 2 线间电
65.000 *1
set during autotuning.
阻
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
* 3. If a multi-function input is set for motor 2 (H1- = 16), the setting range will depend upon the Inverter capacity. The value for a 200 V Class Inverter
of 0.4 kW is given. The upper limit depends on the setting of E4-01.
* 4. The same capacity as that of the Inverter will be set if the constants are initialized.
5-37
F: Option Constants
The following settings are made with the option constants (F constants): Settings for option boards
5-38
User Constant Tables
Overspeed
detection Sets the overspeed detection
0 to
F1-08 level method. 115% No No A No A A 387H 6-159
120
Frequencies above that set for
过速检出值 F1-08 (set as a percentage of
the maximum output fre-
Overspeed
detection quency) that continue to
exceed this frequency for the 0.0 to 0.0 s
F1-09 delay time No No A No A A 388H 6-159
time set in F1-09 are detected 2.0 *
OS 过速检出 as overspeed faults.
时间
Excessive
Sets the speed deviation
speed devia-
detection method.
F1-10 tion detec- 0 to 50 10% No No A No A A 389H 6-159
Any speed deviation above
tion level
the F1-10 set level (set as a
DEV 检出值 l percentage of the maximum
output frequency) that contin-
Excessive ues for the time set in F1-11 is
speed devia- detected as a speed deviation.
tion detec- Speed deviation is the differ- 0.0 to
F1-11 tion delay ence between actual motor 0.5 s No No A No A A 38AH 6-159
10.0
time speed and the reference com-
mand speed.
DEV 检出时间
5-39
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Number of Sets the number of teeth on
PG gear teeth the gears if there are gears
F1-12 1 between the PG and the 0 No No A No No No 38BH 6-159
motor.
PG 齿轮齿数 1
0 to
Input pulses from PG 60 F1-13
Number of 1000
F1-01 F1-12
PG gear teeth
F1-13 2 A gear ratio of 1 will be used 0 No No A No No No 38CH 6-159
if either of these constants is
PG 齿轮齿数 2 set to 0.
5-40
User Constant Tables
5-41
Analog Monitor Boards: F4
User constants for the Analog Monitor Board are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Channel 1 Effective when the Analog
monitor Monitor Board is used.
F4-01 selection Monitor selection: 1 to 50 2 No A A A A A 391H 6-89
Set the number of the monitor
CH1 输出监视
item to be output. (U1-)
Channel 1 Gain:
gain Set the multiple of 10 V for 0.00 to
F4-02 1.00 Yes A A A A A 392H 6-89
outputting monitor items. 2.50
CH1 输出增益 4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
Channel 2
are not used. When the AO-
monitor
F4-03 12 Analog Monitor Board is 1 to 50 3 No A A A A A 393H 6-89
selection
used, outputs of ± 10 V are
CH2 输出监视 possible. To output ± 10 V, set
F4-07 or F4-08 to 1. When
Channel 2 the AO-08 Analog Monitor
gain Board is used, only outputs of 0.00 to
F4-04 0 to +10 V are possible. 0.50 Yes A A A A A 394H 6-89
2.50
CH2 输出增益 A meter calibration function
is available.
Channel 1
output moni- Sets the channel 1 item bias
-10.0 to
F4-05 tor bias to 100%/10 V when the Ana- 0.0 Yes A A A A A 395H 6-89
10.0
log Monitor Board is used.
AO CH1 偏置
Channel 2
output moni- Sets the channel 2 item bias
-10.0 to
F4-06 tor bias to 100%/10 V when the Ana- 0.0 Yes A A A A A 396H 6-89
10.0
log Monitor Board is used.
AO CH2 偏置
Analog out-
put signal
level for 0: 0 to 10 V
F4-07 0 or 1 0 No A A A A A 397H 6-89
channel 1 1: -10 to +10 V
CH1 信号电平
Analog out-
put signal
level for 0: 0 to 10 V
F4-08 0 or 1 0 No A A A A A 398H 6-89
channel 2 1: -10 to +10 V
CH2 信号电平
5-42
User Constant Tables
5-43
Communications Option Boards: F6
User constants for a Communications Option Board are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Operation Set the stopping method for
selection after communications errors.
communica- 0: Deceleration stop using
tions error deceleration time in C1-
02
F6-01 0 to 3 1 No A A A A A 3A2H -
1: Coast to stop
2: Emergency stop using
BUS 检出动作 deceleration time in C1-
09
3: Continue operation
Input level of
external fault
from Com- 0: Always detect
F6-02 munications 0 or 1 0 No A A A A A 3A3H -
1: Detect during operation
Option Board
EF0 检出选择
Torque refer-
ence/torque 0: Torque reference/torque
limit selec- limit from transmission
tion from disabled.
F6-06 0 or 1 0 No No No No A A 3A7H -
optical option 1: Torque reference/torque
limit from transmission
转矩指令及 enabled.
极限
SI-T BUS
5-44
User Constant Tables
Terminal S4
function selec- Multi-function contact input
H1-02 tion 0 to 79 14 No A A A A A 401H -
2
端子 S4 设定
Terminal S5
function selec- Multi-function contact input
H1-03 tion 3
0 to 79 3 (0)* No A A A A A 402H -
端子 S5 设定
Terminal S6
function selec- Multi-function contact input
H1-04 tion 4
0 to 79 4 (3)* No A A A A A 403H -
端子 S6 设定
Terminal S7
function selec- Multi-function contact input
H1-05 tion 5
0 to 79 6 (4)* No A A A A A 404H -
端子 S7 设定
Terminal S8
function selec- Multi-function contact input
H1-06 tion 6
0 to 79 8 (6)* No A A A A A 405H -
端子 S8 设定
Terminal S9
function selec- Multi-function contact input
H1-07 tion 0 to 79 5 No A A A A A 406H -
7
端子 S9 设定
Terminal S10
function selec- Multi-function contact input
H1-08 tion 0 to 79 32 No A A A A A 407H -
8
端子 S10 设定
Terminal S11
function selec- Multi-function contact input
H1-09 tion 0 to 79 7 No A A A A A 408H -
9
端子 S11 设定
5-45
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Terminal S12
function selec- Multi-function contact input
H1-10 tion 0 to 79 15 No A A A A A 409H -
10
端子 S12 设定
1 Local/Remote selection (ON: Local, OFF: Remote) Yes Yes Yes Yes Yes 6-76
6-83
2 Option/Inverter selection (ON: Option board) Yes Yes Yes Yes Yes
6-164
6 Jog frequency command (higher priority than multi-step speed reference) Yes Yes Yes Yes Yes 6-5
8 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes Yes Yes 6-77
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes Yes 6-77
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, fre-
A Yes Yes Yes Yes Yes 6-78
quency on hold)
B OH2 alarm signal input (ON: OH2 will be displayed) Yes Yes Yes Yes Yes -
C Multi-function analog input selection (ON: Enable) Yes Yes Yes Yes Yes -
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f con-
D No Yes No No No 6-137
trol)
E Speed control integral reset (ON: Integral control disabled) No Yes No Yes Yes 6-137
10 Up command (Always set with the down command) Yes Yes Yes Yes Yes 6-79
11 Down command (Always set with the up command) Yes Yes Yes Yes Yes 6-79
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
14 Fault reset (Reset when turned ON) Yes Yes Yes Yes Yes 7-2
19 PID control disable (ON: PID control disabled) Yes Yes Yes Yes Yes 6-109
5-46
User Constant Tables
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop Page
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
1A Accel/Decel time 2 Yes Yes Yes Yes Yes 6-19
Constants write enable (ON: All constants can be written-in. OFF: All constants 6-156
1B Yes Yes Yes Yes Yes
other than frequency monitor are write protected.) 7-24
Trim control increase (ON: d4-02 frequency is added to analog frequency refer-
1C Yes Yes Yes Yes Yes 6-82
ence.)
Trim control decrease (ON: d4-02 frequency is subtracted from analog frequency
1D Yes Yes Yes Yes Yes 6-82
reference.)
1E Analog frequency reference sample/hold Yes Yes Yes Yes Yes 6-83
PID control integral reset (reset when reset command is input or when stopped
30 Yes Yes Yes Yes Yes 6-109
during PID control)
31 PID control integral hold (ON: Hold) Yes Yes Yes Yes Yes 6-109
34 PID soft starter ON/OFF Yes Yes Yes Yes Yes 6-109
35 PID input characteristics switch Yes Yes Yes Yes Yes 6-109
60 DC injection braking command (ON: Performs DC injection braking) Yes Yes Yes Yes Yes 6-16
61 External search command 1 (ON: Speed search from maximum output frequency) Yes No Yes No Yes 6-67
62 External search command 2 (ON: Speed search from set frequency) Yes No Yes No Yes 6-67
Field weakening command (ON: Field weakening control set for d6-01 and d6-
63 Yes Yes No No No -
02)
64 External speed search command 3 (NC contact) Yes Yes Yes Yes Yes -
65 KEB (deceleration at momentary power loss) command (NC contact) Yes Yes Yes Yes Yes -
66 KEB (deceleration at momentary power loss) command (NO contact) Yes Yes Yes Yes Yes -
Communications test mode (“Pass” is displayed when the communications test is
67 Yes Yes Yes Yes Yes 6-104
passed.)
6-129
71 Speed/torque control change (ON: Torque control) No No No Yes Yes
6-135
77 Speed control (ASR) proportional gain switch (ON: C5-03) No No No Yes Yes 6-137
78 Polarity reversing command for external torque reference No No No Yes Yes 6-129
* If the multi-function input is set to 79 and the input value is “closed,” operation will be performed with a speed specification of 0.
5-47
Multi-function Contact Outputs: H2
User constants for multi-function outputs are shown in the following tables.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Terminal M1-
M2 function
selection
H2-01 (contact) Multi-function contact output 0 to 3D 0 No A A A A A 40BH -
端子 M1M2
设定
Terminal P1
function
selection Multi-function contact output
H2-02 (open collec- 0 to 3D 1 No A A A A A 40CH -
1
tor)
端子 P1 设定
Terminal P2
function
selection Multi-function contact output
H2-03 (open collec- 0 to 3D 2 No A A A A A 40DH -
2
tor)
端子 P2 设定
Terminal P3
function
selection Multi-function contact output
H2-04 (open collec- 0 to 3D 6 No A A A A A 40EH -
3
tor)
端子 P3 设定
Terminal P4
function
selection Multi-function contact output
H2-05 (open collec- 0 to 3D 10 No A A A A A 40FH -
4
tor)
端子 P4 设定
5-48
User Constant Tables
2 Frequency agree 1 (L4-02 used.) Yes Yes Yes Yes Yes 6-51
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and dur-
3 Yes Yes Yes Yes Yes 6-51
ing frequency agree)
7 During DC bus undervoltage (UV) detection Yes Yes Yes Yes Yes -
8 During baseblock (ON: during baseblock) Yes Yes Yes Yes Yes -
9 Frequency reference selection (ON: Frequency reference from Operator) Yes Yes Yes Yes Yes -
A Run Command selection status (ON: Run Command from Operator) Yes Yes Yes Yes Yes -
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque
B Yes Yes Yes Yes Yes 6-54
detection at ON)
C Loss of frequency reference (Effective when 1 is set for L4-05) Yes Yes Yes Yes Yes 6-71
D Braking resistor fault (ON: Resistor overheat or braking transistor fault) Yes Yes Yes Yes Yes 6-74
Fault (ON: Digital Operator communications error or fault other than CPF00 and
E Yes Yes Yes Yes Yes -
CPF01 has occurred.)
F Not used. (Set when the terminals are not used.) - - - - - -
10 Minor fault (ON: Alarm displayed) Yes Yes Yes Yes Yes -
13 Frequency agree 2 (L4-04 used) Yes Yes Yes Yes Yes 6-51
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and dur-
14 Yes Yes Yes Yes Yes 6-51
ing frequency agree)
15 Frequency detection 3 (ON: Output frequency ≤ -L4-03, L4-04 used) Yes Yes Yes Yes Yes 6-51
16 Frequency detection 4 (ON: Output frequency ≥ -L4-03, L4-04 used) Yes Yes Yes Yes Yes 6-51
17 Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes 6-54
18 Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at ON) Yes Yes Yes Yes Yes 6-54
19 Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes 6-54
1A During reverse run (ON: During reverse run) Yes Yes Yes Yes Yes -
1B During baseblock 2 (OFF: During baseblock) Yes Yes Yes Yes Yes -
1E Restart enabled (ON: Restart enabled) Yes Yes Yes Yes Yes 6-72
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detec- 6-58
1F Yes Yes Yes Yes Yes
tion level) 6-87
20 Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting) Yes Yes Yes Yes Yes 6-87
5-49
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop Page
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
Maintenance Time
2F ON: The operation time of either the electrolytic capacitors or the cooling fan has Yes Yes Yes Yes Yes -
reached the specified maintenance time.
30 During torque limit (current limit) (ON: During torque limit) No No Yes Yes Yes -
Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected (internal
32 No No No Yes Yes 6-129
torque reference < external torque reference).
Output when the motor is rotating at the speed limit.
6-87
33 Zero-servo end (ON: Zero-servo function completed) No No No Yes No
6-146
During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, ini-
37 Yes Yes Yes Yes Yes 6-86
tial excitation, operation stop)
3D Inverter's Cooling Fan Fault detected Yes Yes Yes Yes Yes 6-73
Analog Inputs: H3
User constants for analog inputs are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Signal level
selection (ter- 0: 0 to 10 V
minal A1) 1: -10V to 10 V
H3-01 0 or 1 0 No A A A A A 410H 6-28
[11-bit + polarity (posi-
端子 A1 信号 tive/negative) input]
选择
Signal level
selection (ter- 0: 0 to 10 V
minal A3) 1: -10 V to 10 V 6-28
H3-04 0 or 1 0 No A A A A A 413H
[11-bit + polarity (posi- 6-128
端子 A3 信号 tive/negative) input]
电平
Multi-func-
tion analog
input (termi- Select multi-function analog 6-28
H3-05 nal A3) func- input function for terminal 0 to 1F 2 No A A A A A 414H
6-128
tion selection A3. Refer to the next page.
端子 A3 设定
5-50
User Constant Tables
Multi-func-
tion analog
input (termi- Select multi-function analog 6-28
H3-09 nal A2) func- input function for terminal 0 to 1F 0 No A A A A A 418H
6-128
tion selection A2. Refer to the next table.
端子 A2 设定
5-51
H3-05,H3-09 Settings
Control Methods
Set- Open Open
ting Function Contents (100%) V/f Loop Flux Loop Page
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
6-30
0 Add to terminal A1 Maximum output frequency Yes Yes Yes Yes Yes
6-129
6 DC injection braking current Inverter rated output current Yes Yes Yes No No 6-17
Overtorque/undertorque detection Motor rated torque for vector control
7 Yes Yes Yes Yes Yes 6-56
level Inverter rated output current for V/f control
8 Stall prevention level during run Inverter rated output current Yes Yes No No No 6-50
Frequency reference lower limit
9 Maximum output frequency Yes Yes Yes Yes Yes 6-35
level
A Jump frequency Maximum output frequency Yes Yes Yes Yes Yes 6-32
B PID feedback Maximum output frequency Yes Yes Yes Yes Yes 6-109
C PID target value Maximum output frequency Yes Yes Yes Yes Yes 6-109
D Frequency bias 2 Maximum output frequency Yes Yes Yes Yes Yes 6-31
E Motor temperature input 10 V = 100% Yes Yes Yes Yes Yes 6-61
10 Positive torque limit Motor's rated torque No No Yes Yes Yes 6-47
11 Negative torque limit Motor's rated torque No No Yes Yes Yes 6-47
12 Regenerative torque limit Motor's rated torque No No Yes Yes Yes 6-47
15 Positive/negative torque limit Motor's rated torque No No Yes Yes Yes 6-47
1F Analog input not used. - Yes Yes Yes Yes Yes 6-6
16 to 1E Not used - - - - - - -
5-52
User Constant Tables
Gain (ter-
Sets the multi-function analog
minal FM)output 1 voltage level gain.
Sets whether the monitor item
output will be output in multi- 0.00 to 4-6
H4-02 ples of 10 V. 1.00 Yes Q Q Q Q Q 41EH
2.50 6-88
端子 FM 增益 The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.*
Gain (ter-
Set the voltage level gain for
minal AM)multi-function analog output 2.
Set the number of multiples of
10 V to be output as the 100% 0.00 to 4-6
H4-05 output for the monitor items. 0.50 Yes Q Q Q Q Q 421H
2.50 6-88
端子 AM 增益 The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.*
5-53
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Analog out-
put 2 signal Sets the signal output level for
level selec- multi-function output 2 (termi-
H4-08 tion nal AM) 0 or 1 0 No A A A A A 424H -
0: 0 to +10 V output
AO2 信号电 1: 0 to ±10 V output
平
* The CH1 output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
MEMOBUS Communications: H5
User constants for MEMOBUS communications are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Slave
address 0 to 20
H5-01 Set the Inverter's slave address. 1F No A A A A A 425H 6-94
*
从站地址
Send wait
time Set the time from the Inverter
H5-06 receiving data to when the 5 to 65 5 ms No A A A A A 42AH 6-94
通信等待时 Inverter starts to send.
间
5-54
User Constant Tables
5-55
Pulse Train I/O: H6
User constants for pulse I/O are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Pulse train
input func-
tion selec- 0: Frequency reference 6-2
H6-01 tion 1: PID feedback value 0 to 2 0 No A A A A A 42CH 6-33
2: PID target value 6-108
脉冲输入选
择
Pulse train
input scal- Set the number of pulses in
ing 1000 to 1440 6-2
H6-02 hertz, taking the reference to be Yes A A A A A 42DH
32000 Hz 6-33
脉冲输入比
100%.
例
Pulse train
input gain Set the input gain level as a per-
0.0 to
H6-03 cent when the pulse train set in 100.0% Yes A A A A A 42EH 6-33
脉冲输入增
1000.0
H6-02 is input.
益
Pulse train
input bias -100.0
Set the input bias when the
H6-04 to 0.0% Yes A A A A A 42FH 6-33
脉冲输入偏
pulse train is 0.
100.0
置
Pulse train
input filter Set the pulse train input pri-
time 0.00 to 0.10
H6-05 mary delay filter time constant Yes A A A A A 430H 6-33
2.00 s
脉冲输入滤
in seconds.
波时间
5-56
User Constant Tables
Motor Overload: L1
User constants for motor overloads are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Motor pro- Sets whether the motor over-
tection load function is enabled or dis-
selection abled at electric thermal
overload relay.
0: Disabled
1: General-purpose motor
protection
2: Inverter motor protection
3: Vector motor protection
In some applications when the 4-5
L1-01 0 to 3 1 No Q Q Q Q Q 480H
Inverter power supply is 6-57
电机保护功 turned off, the thermal value is
能选择 reset, so even if this constant is
set to 1, protection may not be
effective.
When several motors are con-
nected to one Inverter, set to 0
and ensure that each motor is
installed with a protection
device.
5-57
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Motor over- Set H3-09 to E and select the
heating operation when the motor tem-
operation perature (thermistor) input
selection exceeds the operation detec-
tion level (2.34 V).
L1-04 0 to 2 1 No A A A A A 483H 6-60
0: Decelerate to stop using the
OH4 检出动
deceleration time in C1-02.
作 1: Coast to stop
2: Emergency stop using the
deceleration time in C1-09.
Motor tem-
perature
input filter Set H3-09 to E and set the pri-
time con- mary delay time constant for 0.00 to
L1-05 0.20 s No A A A A A 484H 6-60
stant motor temperature (thermistor) 10.00
inputs in seconds.
OH4 检出动
作
瞬时停电补
of seconds.
偿时间
5-58
User Constant Tables
Momentary
recovery Set in seconds the time to
time accelerate to the set speed after 0.0 to 0.0 s
L2-07 No A A A A A 48BH -
recovery from a momentary 25.5 *3
瞬时停电恢 power loss.
复时间
5-59
Stall Prevention: L3
User constants for the stall prevention function are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Stall pre- 0: Disabled (Acceleration as
vention set. With a heavy load, the
selection motor may stall.)
during accel 1: Enabled (Acceleration
stopped when L3-02 level is
exceeded. Acceleration
starts again when the 4-21
L3-01 0 to 2 1 No A A A No No 48FH
current is returned.) 6-23
加速防止失
2: Intelligent acceleration
速选择 mode (Using the L3-02
level as a basis, acceleration
is automatically adjusted.
Set acceleration time is
disregarded.)
5-60
User Constant Tables
Reference Detection: L4
User constants for the reference detection function are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Speed agree Effective when “Desired fre-
detection quency (ref/setting) agree 1,”
level “Frequency detection 1,” or
0.0 to
L4-01 “Frequency detection 2" is set 0.0 Hz No A A A A A 499H 6-50
400.0
for a multi-function output.
频率检出值 Frequencies to be detected are
set in Hz units.
5-61
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Speed agree Effective when “Frequency
detection (speed) agree 1,” “Desired fre-
width quency (speed) agree 1,” or
“Frequency (FOUT) detection
0.0 to
L4-02 1,” Frequency (FOUT) detec- 2.0 Hz No A A A A A 49AH 6-50
20.0
tion 2 is set for a multi-function
频率检出幅
度 output.
Sets the frequency detection
width in Hz units.
Speed agree Effective when “Desired fre-
detection quency (speed) agree 2,” “Fre-
level (+/-) quency (FOUT) detection 3,”
-400.0
or “Frequency (FOUT) detec-
L4-03 to 0.0 Hz No A A A A A 49BH 6-51
tion 4" is set for a multi-func-
+400.0
频率检出值 tion output.
+- Frequency that should be
detected is set in Hz units.
Fault Restart: L5
User constants for restarting faults are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Number of Sets the number of auto restart
auto restart attempts.
L5-01 attempts Automatically restarts after a 0 to 10 0 No A A A A A 49EH 6-72
故障重试次
fault and conducts a speed
数 search from the run frequency.
5-62
User Constant Tables
Torque Detection: L6
User constants for the torque detection function are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Overtorque/ 0: Overtorque/undertorque
Under- detection disabled.
torque 1: Overtorque detection only
detection with speed agreement;
selection 1 operation continues after
overtorque (warning).
2: Overtorque detected
continuously during
operation; operation
continues after overtorque
(warning).
3: Overtorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
4: Overtorque detected
continuously during
operation; output stopped
upon detection (protected
L6-01 0 to 8 0 No A A A A A 4A1H 6-53
operation).
5: Undertorque detection only
转矩检出 1 with speed agreement;
动作 operation continues after
overtorque (warning).
6: Undertorque detected
continuously during
operation; operation
continues after overtorque
(warning).
7: Undertorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
8: Undertorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
Overtorque/
Under- Open-loop vector control:
torque Motor rated torque is set as
detection 0 to
L6-02 100%. 150% No A A A A A 4A2H 6-53
level 1 300
V/f control: Inverter rated cur-
转矩检出 1
rent is set as 100%.
值
Overtorque/
Under-
torque Sets the overtorque/under-
detection 0.0 to
L6-03 torque detection time in 1-sec- 0.1 s No A A A A A 4A3H 6-54
time 1 10.0
ond units.
转矩检出 1
时间
5-63
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Overtorque/
Under-
torque
L6-04 detection 0 to 8 0 No A A A A A 4A4H 6-54
selection 2
转矩检出 2
动作 Multi-function output for over-
torque detection 1 is output to
Overtorque/ multi-function contact output
Under- when overtorque detection 1
torque NO or overtorque detection 1
detection 0 to
L6-05 NC is selected. Multi-function 150% No A A A A A 4A5H 6-54
level 2 300
output for overtorque detection
2 is output to multi-function
转矩检出 2
值 contact output when overtorque
detection 2 NO or overtorque
Overtorque/ detection 2 NC is selected.
Under-
torque
detection 0.0 to
L6-06 0.1 s No A A A A A 4A6H 6-54
time 2 10.0
转矩检出 2
时间
Torque Limits: L7
User constants for torque limits are shown in the following table.
Control Methods
Con- Change Open Open MEMO-
Fac-
stant Setting during BUS
Num-
Name Description Range
tory
Opera-
V/f Loop Flux Loop Page
Setting V/f with Vec- Vec- Vec- Regis-
ber tion PG tor tor tor ter
1 2
Forward
drive
torque 0 to 4-21
L7-01 limit 200% No No No A A A 4A7H
300 6-46
正转电动转
矩极限
Reverse
Sets the torque limit value as a per-
drive
centage of the motor rated torque.
torque 0 to 4-21
L7-02 limit Four individual regions can be set. 200% No No No A A A 4A8H
300 6-46
反转电动转 Output torque
矩极限 Positive torque
Forward No. of
Regenerative motor
regenera- Reverse state rotations
tive torque Regenerative Forward 0 to 4-21
L7-03 limit state 200% No No No A A A 4A9H
300 6-46
Negative torque
正转再生转
矩极限
Reverse
regenera-
tive torque 0 to 4AA 4-21
L7-04 limit 200% No No No A A A
300 H 6-46
反转再生转
矩极限
5-64
User Constant Tables
Control Methods
Con- Change Open Open MEMO-
Fac-
stant Setting during BUS
Num-
Name Description Range
tory
Opera-
V/f Loop Flux Loop Page
Setting V/f with Vec- Vec- Vec- Regis-
ber tion PG tor tor tor ter
1 2
Integral
time set-Set the integral time for the torque
ting for limit. When integral control is set for
5 to 200 4-21
L7-06 torque the torque limit, reduce this setting to No No No A No No 4ACH
limit 10,000 ms 6-46
increase the change in frequency for
转矩限制时
the torque limit.
间
Control
method
selection Select the control method for the
for torque torque limit during acceleration and
limit dur- deceleration.
0: Proportional control (integral con- 4-21
L7-07 ing accel- 0, 1 0 No No No A No No 4C9H
eration and trol during constant speed) 6-46
decelera- 1: Integral control
tion Normally, this constant does not need
to be set.
转矩极限控
制选择
Hardware Protection: L8
User constants for hardware protection functions are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Protect selec-
tion for inter- 0: Disabled (no overheating
nal DB protection)
L8-01 resistor (Type 0 or 1 0 No A A A A A 4ADH 6-74
1: Enabled (overheating
ERF) protection)
制动电阻保护
5-65
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Input open- 0: Disabled
phase protec- 1: Enabled (Detects if input
tion selection current open-phase, power
supply voltage imbalance
or main circuit
L8-05 electrostatic capacitor 0 or 1 0 No A A A A A 4B1H -
deterioration occurs.)
输入缺相保护 This fault is detected if a load
is greater than approximately
80% of the maximum motor
capacity.
Ground pro-
tection selec-
tion 0: Disabled
L8-09 0 or 1 1 No A A A A A 4B5H -
1: Enabled
接地短路保护
选择
Cooling fan
control delay Set the time in seconds to
time delay turning OFF the cooling 0 to
L8-11 60 s No A A A A A 4B7H -
fan after the cooling fan OFF 300
风扇控制延迟 command is received.
时间
Soft Current
Limitation 0: Disable (gain = 0)
L8-18 0 or 1 1 No A A A A A 4BEH -
1: Enable
软件 CLA
OH1 detec-
tion of 0: Disabled (FAN minor
Inverter’ s fault detection)
L8-32 0 or 1 1 No A A A A A 4E2H 6-73
cooling fan 1: Enabled (OH1 major fault
detection)
OH1 检出选择
5-66
User Constant Tables
Reduced
carrier 0, 4 to 2.0 kHz
Sets the reduced carrier fre-
L8-39 frequency 2.0 *1 *2 No A A A No No 4F0H -
quency.
*3
降低载波频率
5-67
N: Special Adjustments
The following settings are made with the special adjustments constants (N constants): Hunting prevention,
speed feedback detection control, high-slip braking, speed estimation, and feed forward control.
Hunting-pre-
vention time Set the hunting-prevention
0 to
N1-03 constant primary delay time in units of
500 10 ms * No A A No No No 582H 6-40
ms.
防止失调时间
* The factory setting depends upon the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
5-68
User Constant Tables
Speed feed-
back detec- Set the time constant to
tion control decide the rate of change in 0 to
N2-02 (AFR) time 50 ms No No No A No No 585H 6-41
the speed feedback detection 2000
constant control.
AFR 时间
Speed feed-
back detec- Increase the setting if over-
tion control voltage (OV) failures occur at
0 to
N2-03 (AFR) time the completion of accelera- 750 ms No No No A No No 586H 6-41
2000
constant 2 tion or when the load changes
radically.
AFR 时间 2
High-slip Braking: N3
User constants for high-slip braking are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
High-slip
braking Sets the frequency width for
deceleration deceleration during high-slip
N3-01 frequency braking as a percent, taking 1 to 20 5% No A A No No No 588H -
width the Maximum Frequency
(E1-04) as 100%.
HSB 频率幅度
5-69
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
High-slip Set in seconds the dwell time
braking stop for the output frequency for
dwell time FMIN (1.5 Hz) during V/f 0.0 to
N3-03 1.0 s No A A No No No 58AH -
control. 10.0
HSB 暂停时间 Effective only during deceler-
ation for high-slip braking.
High-slip Set the OL time when the out-
braking OLput frequency does not
30 to
N3-04 time change for some reason dur- 40 s No A A No No No 58BH -
1200
ing deceleration for high-slip
HSOL 检出时间 braking.
Speed Estimation: N4
User constants for speed estimation are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Integral time
of speed esti- Set the integral time of the 0.000
mator 0.030
N4-07 speed estimator for PI con- to No No No No No A 59AH 4-20
ms
trol. 9.999
速度推定积分
时间
Proportional
gain of speed Set the proportional gain of
estimator 0 to
N4-08 the speed estimator for PI 15 No No No No No A 59BH -
1000
control.
速度推定比例
增益
High-speed
proportional
gain of speed Set the high-speed propor-
0 to
N4-10 estimator tional gain of the speed esti- 15.0 No No No No No A 59DH 4-20
1000.0
mator for PI control.
推定高速积分
时间
Speed estima-
tor switching Set the switching frequency
frequency of high-speed/low-speed 40 to 7-33
N4-11 70 Hz No No No No No A 59EH
operation for the speed esti- 70 10-4
速度推定切换 mator.
频率
Torque
adjustment Set the torque adjustment 0.0 to
N4-17 gain 0.8 No No No No No A 5A4H 7-33
gain for low-speed power. 5.0
转矩调整增益
5-70
User Constant Tables
Speed estima-
tor gain fluc- Set ratio for fluctuating the
tuation rate speed estimator’s low-speed 0.0 to
N4-34 200.0% No No No No No A 5B9H 7-32
proportional gain (PI control). 200.0
速度推定增益 Set the value as a percentage.
变化
Feed Forward: N5
User constants for the feed forward control are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Feed forward Select the feed forward con-
control selec- trol. 0 4-21
N5-01 tion 0 or 1 No No No No A A 5B0H
0: Disabled *1 6-142
FF 控制选择 1: Enabled
5-71
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Motor accel- Set the time required to
eration time accelerate the motor at the
rated torque (T100) to the
rated speed (Nr).
J: GD2/4, P: Motor rated out- 0.001
put 0.178 s 4-21
N5-02 to No No No No A A 5B1H
*2 6-142
电机加速时间 ta =
2π x J [kgm2] x Nr [min-1]
[s]
10.000
60 x T100 [N x m]
However,
60 P [kW]
T100 = x × 103 [N x m]
2π Nr [min-1]
* 1. When the control method is changed, the factory setting will change. The flux vector factory setting is given.
* 2. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
Monitor Select: o1
User constants for Digital Operator Displays are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Monitor Set the number of the monitor
selection item to be displayed in the
earliest 4 monitor items. (U1-
o1-01 ) 4 to 99 6 Yes A A A A A 500H -
The output monitor voltage
显示项目选择 (factory setting) can be
changed.
5-72
User Constant Tables
5-73
Multi-function Selections: o2
User constants for Digital Operator key functions are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
LOCAL/ Sets the Digital Operator
REMOTE Local/Remote Key
key enable/ 0: Disabled
o2-01 disable 1: Enabled (Switches 0 or 1 1 No A A A A A 505H 6-148
between the Digital
L/R 键功能
Operator and the constant
settings.)
kVA selection
o2-04
变频器容量
Do not set. 0 to FF 0* No A A A A A 508H -
选择
Cumulative
operation Sets the cumulative operation
time setting time in hour units. 0 to
o2-07 0 hr No A A A A A 50BH 6-149
Operation time is calculated 65535
累积运行时间 from the set values.
设定
5-74
User Constant Tables
Copy Function: o3
User constants for the copy function are shown in the following table.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Copy func- 0: Normal operation
tion selection 1: READ (Inverter to
Operator)
o3-01 0 to 3 0 No A A A A A 515H 6-151
2: COPY (Operator to
拷贝功能选择 Inverter)
3: Verify (compare)
Read permit-
ted selection 0: Read prohibited
o3-02 0 or 1 0 No A A A A A 516H 6-151
1: Read permitted
读出许可选择
5-75
T: Motor Autotuning
The following settings are made with the motor autotuning constants (T constants): Settings for autotuning.
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Page
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Motor 1/2 Set the location where the
selection autotuned motor constants are
T1-00 to be stored. 1 or 2 1 No Yes Yes Yes Yes Yes 700H 4-14
1: Motor 1
选择电机
2: Motor 2
Motor output
power Set the output power of the 0.00 to 0.40
T1-02 motor in kilowatts. 650.00 kW No Yes Yes Yes Yes Yes 702H 4-14
*3
电机额定功率
Motor rated
voltage Set the rated voltage of the 0.0 to 200.0 V
T1-03 No No No Yes Yes Yes 703H 4-14
motor in volts. 255.5*2 *2
电机额定电压
Motor rated
current Set the rated current of the 0.32 to 1.90 A
T1-04 No Yes Yes Yes Yes Yes 704H 4-14
motor in amps. 6.40 *4 *3
电机额定电流
Motor base
frequency Set the base frequency of the 0.0 to
T1-05 motor in hertz. 400.0 50.0 Hz No No No Yes Yes Yes 705H 4-14
电机基本频率
Number of
motor poles Set the number of motor 2 to 48
T1-06 poles. poles 4 poles No No No Yes Yes Yes 706H 4-14
电机极数
Motor base
speed Set the base speed of the 0 to 1450
T1-07 No No No Yes Yes Yes 707H 4-15
motor in min−1. 24000 min−1
电机额定速度
5-76
User Constant Tables
U: Monitor Constants
The following settings are made with the monitor constants (U constants): Setting constants for monitoring in
drive mode.
Output fre-
quency Monitors the output fre- 10 V: Max. frequency 0.01
U1-02 A A A A A 41H
quency.* (-10 to 10 V possible) Hz
输出频率
DC bus volt-
age Monitors the main DC 10 V: 400 VDC (800 VDC)
U1-07 1V A A A A A 46H
主回路直流电
voltage in the Inverter. (0 to +10 V output)
压
* The unit is set in o1-03 (frequency units of reference setting and monitor).
5-77
Name Control Methods
Con- Output Signal Level Open Open MEMO-
Min. V/f Loop Flux Loop BUS
stant Description During Multi-Function Unit
Number Display V/f with Vec- Vec- Vec- Regis-
Analog Output PG tor tor tor ter
1 2
Input termi- Shows input ON/OFF status.
nal status U1-10= 00000000
1: FWD command
(S1) is ON.
1: REV command
(S2) is ON.
1: Multi input 1
(S3) is ON.
1: Multi input 2
(S4) is ON.
1: Multi input 3
(S5) is ON.
1: Multi input 4
(S6) is ON.
1: Multi input 5
(S7) is ON.
1:Multi input 6
U1-10 (S8) is ON. (Cannot be output.) - A A A A A 49H
输入端子状
The ON/OFF status of the fol-
态
lowing input terminals can be
checked by displaying U1-10
and pressing the Enter Key.
(Press the Enter Key again to
return to the original dis-
play.)
U1-10= 0000
1: Multi input 7
(S9) is ON.
1: Multi input 8
(S10) is ON.
1: Multi input 9
(S11) is ON.
1: Multi input 10
(S12) is ON.
1: Major fault
5-78
User Constant Tables
软件编号
5-79
Name Control Methods
Con- Output Signal Level Open Open MEMO-
Min. V/f Loop Flux Loop BUS
stant Description During Multi-Function Unit
Number Display V/f with Vec- Vec- Vec- Regis-
Analog Output PG tor tor tor ter
1 2
DI-16H2 Monitors the reference value
input status from a DI-16H2 Digital Refer-
ence Board.
U1-25 (Cannot be output.) - A A A A A 58H
DI16 指令状
The value will be displayed in
态 binary or BCD depending on
user constant F3-01.
Output volt-
age refer- Monitors the Inverter internal
ence (Vq) 10 V: 200 VAC (400 VAC) 0.1
U1-26 voltage reference for motor No No A A A 59H
(-10 to 10 V possible) V
输出电压
secondary current control.
(Vq)
Output volt-
age refer- Monitors the Inverter internal
ence (Vd) 10 V: 200 VAC (400 VAC) 0.1
U1-27 voltage reference for motor No No A A A 5AH
(-10 to 10 V possible) V
输出电压
excitation current control.
(Vd)
Software
No. (CPU) (Manufacturer’s CPU software
U1-28 (Cannot be output.) - A A A A A 5BH
CPU 软件编
No.)
号
ACR out-
put of q axis Monitors the current control 10 V: 100% 0.1
U1-32 output value for the motor sec- No No A A A 5FH
Q 轴 ACR 输
(-10 to 10 V possible) %
ondary current.
出
ACR out-
put of d axis Monitors the current control 10 V: 100% 0.1
U1-33 output value for the motor No No A A A 60H
D 轴 ACR 输
(-10 to 10 V possible) %
excitation current.
出
OPE fault
constant Shows the first constant num-
U1-34 ber where an OPE fault was - A A A A A 61H
OPE 故障参 detected.
数
PID input
volume PID feedback volume
10 V: Max. frequency 0.01
U1-36 Given as maximum frequency/ A A A A A 63H
PID 的输入
(-10 to 10 V possible) %
100%
量
5-80
User Constant Tables
Cooling fan
operating Monitors the total operating
time 1
U1-40 time of the cooling fan. The (Cannot be output.) A A A A A 68H
hr
风扇运行时
time can be set in 02-10.
间
Motor flux
current Monitors motor flux current
compensa- 10 V: Rated secondary cur-
compensation value. 100% is 0.1
U1-43 tion rent of motor No No No No A 6AH
displayed for the rated second- %
(-10 V to 10 V)
励磁电流补
ary current of the motor.
偿
ASR out-
put without Monitors the output from the
filter speed control loop (i.e., the 10 V: Rated secondary cur-
0.01
U1-44 primary filter input value). rent of motor No No No A A 6BH
%
反馈控制输
100% is displayed for rated (-10 V to 10 V)
出 secondary current of the
motor.
Stable
speed for Monitors the minimum speed
regenera- for which the speed will not
0.01
U1-48 tion exceed the speed reference in a 0.00 to 20.00 No No No No A 6FH
Hz
steady state during 100% load
再生时稳定 regeneration.
速度
5-81
Name Control Methods
Con- Output Signal Level Open Open MEMO-
Min. V/f Loop Flux Loop BUS
stant Description During Multi-Function Unit
Number Display V/f with Vec- Vec- Vec- Regis-
Analog Output PG tor tor tor ter
1 2
CF error Monitors the CF error code.
code 00: No deceleration for 3 s
after Stop Command
01: Magnetic flux calculation
error
02: Startup status fault
U1-50 04: Speed estimator gain 0 to FFFF H No No No No A 71H
CF 故障报警 adjustment fault
代码 08: Low-speed regeneration
fault
10: Zero-speed fault
20: Rotation direction limit
fault
Peak hold Displays the peak value of the 10V: Inverter rated output
current 0.01
current during run. “Peak current
U1-83 A A A A A A 7CFH
峰值保持电
Hold” refers to the moment (-10 to 10 V absolute value
*1
流 that the peak value is saved. output)
Output
frequency
during Displays the frequency value 0.01
10V: Max frequency
U1-84 peak hold when the output current Hz A A A A A 7DOH
(-10 to 10 V)
reached its peak value. *2
峰值保持输
出频率
* 1. The minimum unit differs depending on the Inverter capacity. (0.01 A for Inverter of 0.4 kW to 7.5 kW, and 0.1 A for Inverter of 11 kW or more)
* 2. The setting unit can be selected in o1-03.
5-82
User Constant Tables
Fault Trace: U2
User constants for error tracing are shown in the following table.
Name Control Methods
Output Signal
Con- Open Open MEMO-
Level During Min. V/f Loop Flux Loop BUS
stant Description
Number Display Multi-Function Unit V/f with Vec- Vec- Vec- Regis-
PG tor tor tor ter
Analog Output
1 2
Current fault
U2-01 The contents of the current fault. - A A A A A 80H
当前故障
Output fre-
quency at The output frequency when the 0.01
U2-04 fault A A A A A 83H
previous fault occurred. Hz
输出频率
Output cur-
rent at fault The output current when the pre-
U2-05 0.1 A A A A A A 84H
vious fault occurred.
输出电流
Output volt-
age reference The output reference voltage
U2-07 at fault 0.1 V A A A A A 86H
when the previous fault occurred.
故障输出电压
DC bus volt-
age at fault The main current DC voltage
U2-08 1V A A A A A 87H
主回路直流电
when the previous fault occurred.
压
Output power
at fault The output power when the pre- 0.1
U2-09 A A A A A 88H
vious fault occurred. kW
输出功率
5-83
Name Control Methods
Output Signal
Con- Open Open MEMO-
Level During Min. V/f Loop Flux Loop BUS
stant Description Unit
Number Display Multi-Function V/f with Vec- Vec- Vec- Regis-
PG tor tor tor ter
Analog Output
1 2
Input termi- The input terminal status when
nal status at the previous fault occurred.
U2-11 fault - A A A A A 8AH
The format is the same as for U1-
输入端子状态
10.
Output termi-
nal status at The output terminal status when
U2-12 fault the previous fault occurred. The - A A A A A 8BH
format is the same as for U1-11.
输出端子状态
Cumulative
operation (Cannot be output.)
The operating time when the pre- 1
U2-14 time at fault A A A A A 8DH
vious fault occurred. hr
累积时间
Peak hold
current at Displays the peak hold current 0.01
U2-21 fault A A A A A 7E6H
when the last fault occurred. A*
峰值保持电流
Peak hold
output Displays the frequency value at
frequency at the moment the current reached 0.01
U2-22 fault A A A A A 7E7H
its peak value when the last fault Hz
峰值保持输出
occurred.
频率
Note 1. The following errors are not included in the error trace: CPF00, 01, 02, 03, UV1, and UV2.
2. If the PUF fault is already indicated in U2- or U3-, even if the PUF fault is detected again, the fault trace is not updated.
* The minimum unit differs depending on the Inverter capacity. (0.01 A for Inverter of 0.4 kW to 7.5 kW, and 0.1 A for Inverter of 11 kW or more)
5-84
User Constant Tables
Fault History: U3
User constants for the error log are shown in the following table.
Name Control Methods
Con- Output Signal Level Open Open MEMO-
Min. V/f Loop Flux -loop BUS
stant Description During Multi-Function Unit
Number Display V/f with Vec- Vec- Vec- Regis-
Analog Output PG tor tor tor ter
1 2
Most recent
fault The error contents of 1st
U3-01 - A A A A A 90H
previous fault.
1 次前故障
Second most
recent fault The error contents of 2nd
U3-02 - A A A A A 91H
previous fault.
2 次前故障
Third most
recent fault The error contents of 3rd
U3-03 - A A A A A 92H
previous fault.
3 次前故障
Fourth/oldest
fault The error contents of 4th
U3-04 - A A A A A 93H
previous fault.
4 次前故障
Cumulative
operation The total operating time
time at fault 1
U3-05 when the 1st previous fault A A A A A 94H
hr
故障累积时间
occurred. (Cannot be output.)
1
Accumulated
time of sec- The total operating time
ond fault 1
U3-06 when the 2nd previous fault A A A A A 95H
hr
故障累积时间
occurred.
2
Accumulated
time of third The total operating time
fault 1
U3-07 when the 3rd previous fault A A A A A 96H
hr
故障累积时间
occurred.
3
Accumulated
time of
fourth/oldest The total operating time
1
U3-08 fault when the 4th previous fault A A A A A 97H
hr
occurred.
故障累积时间
4
Note The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.
5-85
Factory Settings that Change with the Control Method (A1-02)
The factory settings of the following user constants will change if the control method (A1-02) is changed.
Name Factory Setting
Con- Open- Open
stant Setting Range Unit V/f V/f with loop Flux Loop
Number Display Control PG Vector Vector Vector
1 2
Speed search selection
b3-01 0 to 3 1 2 3 2 - 2
起动速度搜索
Energy-saving gain
b8-02 0.0 to 10.0 0.1 - - 0.7 1.0 0.7
节能增益
5-86
User Constant Tables
E1-08 Mid. output frequency voltage (VC)*2 0.0 to 255.0 15.0 15.0
0.1 V 13.2 0.0 0.0
E3-06 (0.0 to 510.0) *3 *3
中间电压
E1-10 Min. output frequency voltage (VMIN)*2 0.0 to 255.0 9.0 9.0
0.1 V 2.4 - -
E3-08 (0.0 to 510.0) *3 *3
最低输出电压
* 1. The settings will be 0.05 (Flux vector)/1.00 (open-loop vector) for Inverters of 45kW or larger.
* 2. The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
* 3. Settings vary as shown in the following tables depending on the Inverter capacity and E1-03.
* 4. The setting range for open-loop vector 2 control is 0 to 132.0.
* 5. 1000 ms for Inverters of 200 V Class 30 to 110 kW and 400 V Class 55 to 300 kW.
* 6. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 7. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 50.0 50.0 50.0 50.0
E1-05
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
*
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 50.0 50.0 50.0 0.0
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5 3.0 3.0 0.0
E1-08
V 15.0 15.0 15.0 15.0 35.0 50.0 35.0 50.0 19.0 24.0 19.0 24.0 15.0 15.0 15.0 15.0 13.2 15.9 0.0
*
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.2 0.5 0.3 0.0
E1-10
V 9.0 9.0 9.0 9.0 8.0 9.0 8.0 9.0 11.0 13.0 11.0 15.0 9.0 9.0 9.0 9.0 2.4 1.5 0.0
*
* The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 50.0 50.0 50.0 50.0
E1-05
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
*
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 50.0 50.0 50.0 0.0
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5 3.0 3.0 0.0
E1-08
V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0 14.0 13.2 15.9 0.0
*
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.2 0.5 0.3 0.0
5-87
Con- Open Open
stant
Num-
Unit Factory Setting Loop
Vector
Loop
Vector
Flux
Vector
Con- Con- Con-
ber trol trol trol
E1-03 - 0 1 2 3 4 5 6 7 8 9 A B C D E F 1 2
E1-10
V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0 2.4 1.5 0.0
*
* The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 50.0 50.0 50.0 50.0
E1-05
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
*
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 50.0 50.0 50.0 0.0
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5 3.0 3.0 0.0
E1-08
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0 12.0 13.2 15.9 0.0
*
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.2 0.5 0.3 0.0
E1-10
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.0 2.4 1.5 0.0
*
* The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
5-88
User Constant Tables
b8-04 Energy-saving coefficient - 288.20 223.70 169.40 156.80 122.90 94.75 72.69 70.44 63.13
E2-01
Motor rated current A 1.90 3.30 6.20 8.50 14.00 19.60 26.60 39.7 53.0
(E4-01)
E2-02
Motor rated slip Hz 2.90 2.50 2.60 2.90 2.73 1.50 1.30 1.70 1.60
(E4-02)
E2-03
Motor no-load current A 1.20 1.80 2.80 3.00 4.50 5.10 8.00 11.2 15.2
(E4-03)
E2-06
Motor leak inductance % 18.2 13.8 18.5 18.4 19.6 18.2 15.5 19.5 17.2
(E4-06)
L2-04 Voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.6
L8-39 Reduced carrier frequency kHz 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Hunting-prevention time
N1-03 ms 10 10 10 10 10 10 10 10 10
constant
N5-02 Motor acceleration time s 0.178 0.142 0.166 0.145 0.154 0.168 0.175 0.265 0.244
5-89
Con-
stant Name Unit Factory Setting
Number
- Inverter Capacity
E2-11 Motor Rated Capacity
kW 18.5 22 30 37 45 55 75 90 110
2nd Motor Rated
E4-07
Capacity
o2-04 kVA selection - 9 A B C D E F 10 11
Energy-saving filter time
b8-03 s 0.50 (Open-loop vector control) 2.00 (Open-loop vector control)
constant
b8-04 Energy-saving coefficient - 57.87 51.79 46.27 38.16 35.78 31.35 23.10 20.65 18.12
C6-02 Carrier frequency selection - 6 4 4 4 4 4 4 1 1
E2-01
Motor rated current A 65.8 77.2 105.0 131.0 160.0 190.0 260.0 260.0 260.0
(E4-01)
E2-02
Motor rated slip Hz 1.67 1.70 1.80 1.33 1.60 1.43 1.39 1.39 1.39
(E4-02)
E2-03
Motor no-load current A 15.7 18.5 21.9 38.2 44.0 45.6 72.0 72.0 72.0
(E4-03)
E2-06
Motor leak inductance % 20.1 19.5 20.8 18.8 20.2 20.5 20.0 20.0 20.0
(E4-06)
L2-04 Voltage recovery time s 0.6 0.6 0.6 0.6 1.0 1.0 1.0 1.0 1.0
L8-02 Overheat pre-alarm level °C 90 90 95 100 100 110 100 110 110
L8-39 Reduced carrier frequency kHz 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Hunting-prevention time
N1-03 ms 10 10 10 10 10 10 10 100 100
constant
N5-02 Motor acceleration time s 0.317 0.355 0.323 0.320 0.387 0.317 0.533 0.592 0.646
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V Class
Inverters with outputs of 0.4 to 7.5 kW.
* 1. The initial settings for C6-02 are as follows: 0: Low noise PWM, 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, and 6: 15.0 kHz. If the
carrier frequency is set higher than the factory setting for Inverters with outputs of 5.5 kW or more, the Inverter rated current will need to be reduced.
* 2. The initial settings for C6-11 are as follows: 1: 2.0 kHz, 2: 4.0 kHz, 3: 6.0 kHz, 4: 8.0 kHz.
5-90
User Constant Tables
Con-
stant
Name Unit Factory Setting
Num-
ber
- Inverter Capacity
Motor Rated
E2-11
Capacity kW 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15
2nd Motor Rated
E4-07
Capacity
o2-04 kVA selection - 20 21 22 23 24 25 26 27 28 29
Energy-saving filter time
b8-03 s 0.50 (Open-loop vector control)
constant
b8-04 Energy-saving coefficient - 576.40 447.40 338.80 313.60 245.80 236.44 189.50 145.38 140.88 126.26
Carrier frequency selec-
C6-02 - 3 3 3 3 3 3 3 3 3 3
tion*1
Carrier frequency selec-
C6-11 tion for open-loop vector - 1 1 1 1 1 1 1 1 1 1
2 control*2
E2-02
Motor rated slip Hz 2.90 2.60 2.50 3.00 2.70 2.70 1.50 1.30 1.70 1.60
(E4-02)
E2-03
Motor no-load current A 0.60 0.80 1.40 1.50 2.30 2.30 2.60 4.00 5.6 7.6
(E4-03)
E2-05 Motor line-to-line resis-
Ω 38.198 22.459 10.100 6.495 3.333 3.333 1.595 1.152 0.922 0.550
(E4-05) tance
E2-06
Motor leak inductance % 18.2 14.3 18.3 18.7 19.3 19.3 18.2 15.5 19.6 17.2
(E4-06)
L2-03 Min. baseblock (BB) time s 0.2 0.3 0.4 0.5 0.6 0.6 0.7 0.8 0.9 1.0
L2-04 Voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.6
Reduced carrier
L8-39 kHz 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
frequency
Hunting-prevention time
N1-03 ms 10 10 10 10 10 10 10 10 10 10
constant
N5-02 Motor acceleration time s 0.178 0.142 0.166 0.145 0.154 0.154 0.168 0.175 0.265 0.244
5-91
Con-
stant Name Unit Factory Setting
Number
- Inverter Capacity
Motor Rated
E2-11
Capacity kW 18.5 22 30 37 45 55 75 90 110 132 160 185 220 300
2nd Motor Rated
E4-07
Capacity
o2-04 kVA selection - 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 36 37
Energy-saving filter
b8-03 s 0.50 (Open-loop vector control) 2.00 (Open-loop vector control)
time constant
Energy-saving coeffi-
b8-04 - 115.74 103.58 92.54 76.32 71.56 67.20 46.20 38.91 36.23 32.79 30.13 30.57 27.13 21.76
cient
Carrier frequency
C6-02 - 3 3 3 3 3 2 2 F F F*3 1 1 F*3 1
selection*1
Carrier frequency
C6-11 selection for open- - 1 1 1 1 1 1 1 1 1 1 1 1 1 1
loop vector 2 control*2
Carrier frequency
- - 3 3 3 3 3 2 2 3.0 3.0 1 1 1 1 1
selection upper limit
E2-01
Motor rated current A 32.9 38.6 52.3 65.6 79.7 95.0 130.0 156.0 190.0 223.0 270.0 310.0 370.0 500.0
(E4-01)
E2-02
Motor rated slip Hz 1.67 1.70 1.80 1.33 1.60 1.46 1.39 1.40 1.40 1.38 1.35 1.30 1.30 1.25
(E4-02)
E2-03
Motor no-load current A 7.8 9.2 10.9 19.1 22.0 24.0 36.0 40.0 49.0 58.0 70.0 81.0 96.0 130.0
(E4-03)
E2-06
Motor leak inductance % 20.1 23.5 20.7 18.8 19.9 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
(E4-06)
L2-04 Voltage recovery time s 0.6 0.6 0.6 0.6 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Overheat pre-alarm
L8-02 °C 95 95 95 95 95 100 105 105 120 110 115 100 110 115
level
Reduced carrier
L8-39 kHz 2.0 2.0 2.0 2.0 2.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
frequency
Hunting-prevention
N1-03 ms 10 10 10 10 10 30 30 30 30 30 30 100 100 100
time constant
Motor acceleration
N5-02 s 0.317 0.355 0.323 0.320 0.387 0.317 0.533 0.592 0.646 0.673 0.777 0.864 0.910 1.392
time
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 400 V Class Inverters
with outputs of 0.4 to 7.5 kW.
* 1. The initial settings for C6-02 are as follows: 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz, and F: optional setting (initial value for
Inverters of 90 or 110 kW: 3.0 kHz).
* 2. The initial settings for C6-11 are as follows: 1: 2.0 kHz, 2: 4.0 kHz, 3: 6.0 kHz, 4: 8.0 kHz.
* 3. The factory setting for 400V 132kW and 220kW flax vector control (A1-02 = 3) is 1.5 kHz, for software version VSG123032 or later.
5-92
Constant Settings by
Function
Frequency Reference ..................................................6-2
Run Command...........................................................6-10
Stopping Methods ......................................................6-12
Acceleration and Deceleration Characteristics ..........6-18
Adjusting Frequency References...............................6-28
Speed Limit (Frequency Reference Limit Function)...6-34
Improved Operating Efficiency...................................6-36
Machine Protection ....................................................6-42
Continuing Operation.................................................6-63
Inverter Protection .....................................................6-74
Input Terminal Functions............................................6-76
Output Terminal Functions.........................................6-86
Monitor Constants......................................................6-88
Individual Functions ...................................................6-92
Digital Operator Functions .......................................6-148
Options ....................................................................6-158
Using Inverters for Elevating Machines ...................6-170
Current Alarm Function............................................6-181
Peak Hold Current Monitoring Function...................6-182
Maintenance Timer Display Function.......................6-183
Frequency Reference
This section explains how to input the frequency reference.
Related Constants
Pulse train
input func-
tion selec- 0: Frequency reference
H6-01 tion 1: PID feedback value 0 to 2 0 No A A A A A 42CH
2: PID target value
脉冲输入选
择
Pulse train
input scal- 1000
ing Set the number of pulses in hertz, tak- 1440
H6-02 to Yes A A A A A 42DH
ing the reference to be 100%. Hz
脉冲输入比
32000
例
'5,9( 5G\
乥⥛ᣛҸ
8 +]
Fig 6.1 Frequency Setting Display
6-2
Frequency Reference
Inputting the Frequency Reference Using Control Circuit Terminal (Analog Setting)
When b1-01 is set to 1, you can input the frequency reference from control circuit terminal A1 (voltage input),
or control circuit terminal A2 (voltage or current input).
Inverter
+V Power supply: 15 V,
20 mA
2 kΩ A1 Master speed frequency
reference
(voltage input)
A2 Master speed frequency
reference
(current input)
A3 Auxiliary speed frequency
reference 1
AC Analog common
Inverter
+V Power supply: 15 V,
20 mA
Master speed frequency
A1
reference
4 to 20-mA input (voltage input)
A2 Master speed frequency
reference
(current input)
A3 Auxiliary speed frequency
reference 1
AC Analog common
1
DIP switch
2 S1
V I
Turn ON pin 2 of DIP switch S1 (toward I), the voltage/current switch, when inputting a current to terminal A2.
Turn OFF pin 2 of DIP switch S1 (toward V), the voltage/current switch, when inputting a voltage to terminal
A2. Set H3-08 to the correct setting for the type of input signal being used.
IMPORTANT
6-3
When switching between the master and auxiliary speeds, set H3-05 (Multi-function analog input terminal
A3) to 2 (auxiliary frequency reference, 2nd step analog) and set on of the multi-function input terminals to
multi-step speed reference 1.
When inputting a current to terminal A2 for the master speed frequency reference, set H3-08 (Multi-function
analog input terminal A2 signal level selection) to 2 (current input), and set H3-09 (Multi-function analog
input terminal A2 function selection) to 0 (add to terminal A1).
Inverter
S5 Multi-step speed
reference 1
+V Power supply: 15 V,
20 mA
Master speed
2 kΩ A1 frequency reference
(voltage input)
Master speed
4 to 20 mA
A2 frequency reference
(current input)
2 kΩ A3 Auxiliary speed
frequency reference 1
AC Analog common
6-4
Frequency Reference
Related Constants
To switch frequency references, set multi-step speed references 1 to 3 and the jog reference selection in the
multi-function contact inputs. Setting examples are shown below.
Multi-step speed reference 2 [Also used for auxiliary frequency reference 2 when multi-
S6 H1-04 4
function analog input H3-09 is set to 3 (auxiliary frequency reference 2).]
S7 H1-05 6 Jog frequency selection (given priority over multi-step speed reference)
* Terminal S7's jog frequency selection is given priority over multi-step speed references.
6-5
Setting Precautions
Refer to the following to set step 1 to step 3 to analog inputs.
• Step 1
When setting terminal A1's analog input to step 1, set b1-01 to 1, and when setting d1-01 (Frequency Ref-
erence 1) to step 1, set b1-01 to 0.
• Step 2
When setting terminal A3's analog input to step 2, set H3-05 to 2 (auxiliary frequency reference 1). When
setting d1-02 (Frequency Reference 2) to step 2, set H3-05 to 1F (Analog input not used).
• Step 3
When setting terminal A2's analog input to step 3, set H3-09 to 3 (auxiliary frequency reference 2). When
setting d1-03(Frequency Reference 3) to step 3, set H3-05 to 1F (Analog input not used).
When inputting 0 to 10 V to terminal A2’s analog input, set H3-08 to 0, and turn OFF pin 2 to DIP switch
S1 on the control circuit terminal board. (Refer to page 2-26.)
Inverter
S1 Forward/stop
S2 Reverse/stop
S3 External fault
S4 Fault reset
S7 Jog frequency
SC Sequence common
6-6
Frequency Reference
Frequency
reference 8
Frequency
reference 7
Frequency
reference 6
Frequency
reference 5
Frequency
reference 4
Frequency
Frequency reference 3:
reference Frequency ref- Auxiliary
erence 2: Auxil- speed fre-
iary speed quency 2
frequency 1
Frequency Jog frequency
reference 1:
Master speed
frequency
Forward/stop
Multi-step speed
reference 1
Multi-step speed
reference 2
Multi-step speed
reference 3
Jog frequency
selection
6-7
6-8
B1-01
*
*
Primary #
delay filter *
8 8
*
* *
*
Primary
delay filter * $
≠
8 8
*
* 2 is current input.
*
*
*
Primary
*
%
delay filter
8 8 ≠
*
6-9
Run Command
This section explains input methods for the Run Command.
Related Constants
Inverter
Forward/stop
Reverse/stop
Sequence common
6-10
Run Command
50 ms min.
Motor speed
1. Use a sequence that turns ON terminal S1 for 50 ms or longer for the Run Command. This will make the
Run Command self-holding in the Inverter.
2. When the 3-wire sequence is set, do not make the wiring for the control circuit unless the multi-function
input terminal constant is set. Failure to observe this warning may result in injury.
INFO
6-11
Stopping Methods
This section explains methods of stopping the Inverter.
Related Constants
Zero-speed
level (DC Used to set the frequency which starts
injection DC injection braking in units of Hz
braking when deceleration to stop is selected. 0.0 to
b2-01 starting fre- 0.5 Hz No A A A A A 189H
When b2-01 is less than E1-09, E1-09 10.0
quency) becomes the DC injection braking
直流制动开
starting frequency.
始频率
DC injec-
tion brak- Sets the DC injection braking current
ing current 0 to
b2-02 as a percentage of the Inverter rated 50% No A A A No No 18AH
100
直流制动电
current.
流
6-12
Stopping Methods
Deceleration to Stop
If the Stop Command is input (i.e., the Run Command is turned OFF) when b1-03 is set to 0, the motor decel-
erates to a stop according to the deceleration time that has been set. (Factory setting: C1-02 (Deceleration
Time 1))
If the output frequency when decelerating to a stop falls below b2-01, the DC injection brake will be applied
using the DC current set in b2-02 only for the time set in b2-04.
For deceleration time settings, refer to page 6-18 Setting Acceleration and Deceleration Times.
Run command
ON OFF
Output frequency
Decelerates to stop at
deceleration time
DC injection brake
6-13
The operation after stopping depends on the setting of b1-05 when flux vector control is selected (A1-02 = 3).
Frequency reference
via analog input E1-09
Baseblock Baseblock
b2-03 b2-04
Run Command turns OFF
b1-05=3 and zero-speed control start
(Zero-speed) Injection brake when motor speed drops to b2-01.
time at start Zero speed control
Setting Precautions
• When using flux vector control, the zero-speed control starts when motor speed drops to b2-01 during
deceleration. Also, the setting b2-01 < E1-09 is possible.
• The current level during injection brake time at start is the value of E2-03 (motor no-load current). Accord-
ingly, b2-02 is invalid in flux vector control.
Coast to Stop
If the Stop Command is input (i.e., the Run Command is turned OFF) when b1-03 is set to 1, the Inverter out-
put voltage is interrupted. The motor coasts to a stop at the deceleration rate that counterbalances damage to
the machine and inertia including the load.
Run Command
ON OFF
Output frequency
6-14
Stopping Methods
After the Stop Command is input, Run Commands are ignored until the Minimum Baseblock Time (L2-03) has
elapsed.
INFO
DC injection brake
b2-04
Minimum baseblock DC injection brake time
time (L2-03) Output frequency at
Stop Command input
10 100% (maximum output frequency)
Lengthen the Minimum Baseblock Time (L2-03) when an overcurrent (OC) occurs during stopping.
INFO
6-15
Using the DC Injection Brake
Set constant b2-03 to apply the DC injection braking current to the motor while it is coasting to a stop, to stop
the motor and then restart it.
Set b2-03 to 0 to disable the DC injection brake at start.
Set the DC injection brake current using b2-02. DC injection braking is used at startup for flux vector control
with the current set in E2-03 (Motor no-load current).
Related Constants
FRUN
Output frequency
6-16
Stopping Methods
Related Parameters
6-17
Acceleration and Deceleration Characteristics
This section explains the acceleration and deceleration characteristics of the Inverter.
Related Parameters
Accel/decel
time setting
unit 0: 0.01-second units
C1-10 0 or 1 1 No A A A A A 209H
1: 0.1-second units
加减速时间
单位
6-18
Acceleration and Deceleration Characteristics
S-curve char-
acteristic time
at accelera- 0.00 to
C2-01 0.20 s No A A A A A 20BH
tion start 2.50
加速开始 S 字
All sections of the S-curve charac-
S-curve char- teristic time are set in seconds units.
acteristic time When the S-curve characteristic
at accelera- time is set, the accel/decel times 0.00 to
C2-02 0.20 s No A A A A A 20CH
tion end will increase by only half of the S- 2.50
curve characteristic times at start
加速结束 S 字
and end.
S-curve char- Run Command
OFF
acteristic time Output ON
at decelera- frequency 0.00 to
C2-03 C2-02 C2-03 0.20 s No A A A A A 20DH
tion start 2.50
C2-01 C2-04
减速开始 S 字
Time
S-curve char-
acteristic time
at decelera- 0.00 to
C2-04 0.00 s No A A A A A 20EH
tion end 2.50
减速结束 S 字
* The setting range for acceleration/deceleration times depends on the setting of C1-10 (Acceleration/deceleration Time Setting Unit). If C1-10 is set to 0,
the setting range is 0.00 to 600.00 (s).
6-19
Acceleration/Decelera- Acceleration/Decelera-
tion Time Selection 1 Ter- tion Time Selection 2 Ter- Acceleration Time Deceleration Time
minal minal
ON OFF C1-03 C1-04
OFF ON C1-05 C1-06
ON ON C1-07 C1-08
Output frequency
Acceleration/
deceleration time
switching frequency
(C1-11)
6-20
Acceleration and Deceleration Characteristics
Setting Example
The S-curve characteristic when switching operation (forward/reverse) is shown in the following diagram.
Forward
Reverse
Output frequency
C2-01
C2-04
C2-01
C2-02 C2-03
6-21
Accelerating and Decelerating Heavy Loads (Dwell Function)
The dwell function stores the output frequency when starting or stopping heavy loads. By temporarily storing
the output frequency, you can prevent the motor from stalling. When using the dwell function, you must select
a deceleration stop. Set b1-03 (Stopping Method Selection) to 0.
Related Parameters
6-22
Acceleration and Deceleration Characteristics
Related Parameters
6-23
Time Chart
The following figure shows the frequency characteristics when L3-01 is set to 1.
Output current
Time
Output frequency
Time
Setting Precautions
• If the motor capacity is small compared to the Inverter capacity, or if the motor is operated using the fac-
tory settings, resulting in the motor stalling, lower the set value of L3-02.
• If using the motor in the constant output range, L3-02 will be automatically lowered to prevent stalling.
L3-03 is the limit value to prevent the stall prevention level in the constant output range from being
reduced more than necessary.
• Set the constants as a percent taking the Inverter rated voltage to be 100%.
Output frequency
E1-06
Base Frequency (FA)
6-24
Acceleration and Deceleration Characteristics
Related Constants
6-25
Setting Example
An example of stall prevention during deceleration when L3-04 is set to 1 as shown below.
Time
Deceleration time
(set value)
Setting Precautions
• The stall prevention level during deceleration differs depending on the Inverter capacity. Refer to the fol-
lowing table for details.
Inverter Capacity Stall Prevention Level during Deceleration (V)
200 V Class 380
E1-01 ≥ 400 V 760
400 V Class
E1-01 < 400 V 660
• When using the braking option (braking resistor, Braking Resistor Units, and Braking Units), be sure to set
constant L3-04 to 0 or 3.
• To decelerate at a shorter time than the deceleration time set when L3-04 is set to 0 with the braking option
enabled, set L3-04 to 3.
• The setting of L3-04 is ignored for flux vector control or open-loop vector 2 control.
6-26
Acceleration and Deceleration Characteristics
Related Constants
Setting Precautions
When this function is enabled, if the main circuit voltage rises, the regenerative torque limit will decrease to a
value less than its set value and so the motor will not rotate at the speed specified by the speed reference.
Therefore, in applications where it is necessary to rotate the motor at the speed specified by the speed refer-
ence, disable this function and use a converter, a dynamic braking resistor, or a power regenerative unit to sup-
press rises in the main circuit voltage.
6-27
Adjusting Frequency References
This section explains methods of adjusting frequency references.
Related Constants
Signal level 0: 0 to 10 V
selection (ter- 1: -10 to 10 V
H3-04 minal A3) 0 or 1 0 No A A A A A 413H
[11-bit + polarity (positive/
端子 A3 信号电平 negative) input]
Multi-function
analog input
(terminal A3) Select multi-function analog input
H3-05 function selec- 0 to 1F 2 No A A A A A 414H
function for terminal A3.
tion
端子 A3 设定
Signal level0: 0 to 10 V
selection 1: -10 to 10 V
(terminal A2)
2: 4 to 20 mA (9-bit input).
H3-08 0 to 2 2 No A A A A A 417H
Switch current and voltage input
端子 A2 信号选择 using the switch on the control
panel.
Multi-function
analog input
(terminal A2) Select multi-function analog input
H3-09 function selec- 0 to 1F 0 No A A A A A 418H
function for terminal A2.
tion
端子 A2 设定
6-28
Adjusting Frequency References
Analog input
filter time con- Sets primary delay filter time con-
stant stant in seconds for the analog 0.00 to 0.03
H3-12 No A A A A A 41BH
input terminal. 2.00 s
模拟量滤波 Effective for noise control etc.
时间
(H3-06)
6-29
Adjusting Frequency Gain Using an Analog Input
When H3-09 or H3-05 is set to 1 (frequency gain), you can adjust the frequency gain using the analog input
terminal A2 or A3.
Frequency gain
The frequency gain for terminal A1 is the product of H3-02 and terminal A2 gain. For example, when H3-02
is set to 100% and terminal A2 is set to 5 V, the terminal A1 frequency reference will be 50%.
Frequency reference
100% H3-02
Frequency bias
For example, if H3-02 is 100%, H3-03 is 0%, and terminal A2 is set to 1 V, the frequency reference from
terminal A1 when 0 V is input to A1 will be 10%.
6-30
Adjusting Frequency References
Frequency reference
H3-02
10%
Bias
Terminal A1 input voltage
0V 10 V
When constant H3-09 or H3-05 is set to D (frequency bias 2), the frequency equivalent to the terminal A2 or
A3 input voltage is added to A1 as a bias.
Related Constants
The relationship between the output frequency and the jump frequency reference is as follows:
6-31
Output frequency
Frequency
reference
ascending
Jump
frequency
Jump width d3-04
frequency
width d3-04
Jump frequency
Setting Precautions
• Set the jump frequency according to the following formula: d3-01 ≥ d3-02 ≥ d3-03 > Analog input.
• When constants d3-01 to d3-03 are set to 0 Hz, the jump frequency function is disabled.
6-32
Adjusting Frequency References
Related Constants
Pulse train
input filter time Set the pulse train input primary 0.00 to 0.10
H6-05 delay filter time constant in sec- Yes A A A A A 430H
脉冲输入滤波时 onds.
2.00 s
间
The following diagram shows the method for adjusting the frequency reference using pulse inputs.
6-33
Speed Limit (Frequency Reference Limit Func-
tion)
This section explains how to limit the motor speed.
Related Constants
Related Constants
6-34
Speed Limit (Frequency Reference Limit Function)
Fig 6.32 Output Frequency Lower Level for Multi-function Analog Input
If constant d2-02 and terminal A2 output frequency lower level have been set at the same time, the larger set
value will become the frequency lower limit.
INFO
6-35
Improved Operating Efficiency
This section explains functions for improving motor operating efficiency.
Related Constants
6-36
Improved Operating Efficiency
Set C3-01 to 1.0 to compensate the rated slip set using the rated torque output status.
Adjust the slip compensation gain using the following procedure.
1. Set E2-02 (Motor Rated Slip) and E2-03 (Motor No-load Current) correctly.
You can calculate the motor rated slip from the values on the motor nameplate using the following for-
mula.
Amount of motor rated slip (Hz) = Motor rated frequency (Hz) - No. of rated rotations (min−1.) × No. of
motor poles / 120
Set the values for rated voltage, rated frequency, and no-load current in the motor unladen current. The
motor rated slip is set automatically in the vector control using autotuning.
2. In V/f control, set C3-01 to 1.0. Setting this constant to 0.0 disables slip compensation.
3. Apply a load, and measure the speed to adjust the slip compensation gain. Adjust the slip compensation
gain by 0.1 at a time. If the speed is less than the target value, increase the slip compensation gain, and if
the speed is greater than the target value, reduce the slip compensation gain.
For flux vector control, the slip compensation gain is used as the motor temperature compensation gain. When
the motor temperate increases, the motor’s internal constant increases, resulting in an increase in slip. If C3-01
is set, the amount of slip is adjusted as the temperature rises. Set C3-01 if the amount of torque varies with the
temperature when using torque control or a torque limit. The larger the value of C3-01, the larger the compen-
sation.
6-37
Slip compensation limit
Output frequency
Setting Precautions
• If using the device at medium to low speed only, if the power supply voltage is 10% or more higher than
the motor rated voltage, or if the torque control accuracy at high speeds is insufficient, it is not necessary to
change the output voltage limit operation.
• If the power supply voltage is too low compared with the motor rated voltage, torque control accuracy may
be lost even if the output voltage limit operation is enabled.
6-38
Improved Operating Efficiency
Related Constants
转矩补偿延迟时
increase the set values.
间 • When the responsiveness of the
motor is low, decrease the set
values.
* The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
6-39
Normally, there is no need to make this setting. Adjust the constant as shown below.
• If the motor is vibrating, increase the set value.
• If the motor response is low, decrease the set value.
Hunting-prevention Function
The hunting-prevention function suppresses hunting when the motor is operating with a light load. This func-
tion can be used in V/f and V/f with PG.
Related Constants
Hunting-pre-
vention time Set the hunting-prevention pri- 0 to
N1-03 constant mary delay time in units of ms. 500 10 ms* No A A No No No 582H
防止失调时间
* The factory setting depends upon the Inverter capacity. The value for a 200 v Class Inverter of 0.4 kW is given.
6-40
Improved Operating Efficiency
Related Constants
Speed feed-
back detection Set the time constant to decide the
control (AFR) 0 to
N2-02 rate of change in the speed feed- 50 ms No No No A No No 585H
time constant 2000
back detection control.
AFR 时间
Speed feed-
back detection Increase the setting if overvoltage
control (AFR) (OV) failures occur at the comple- 0 to 750
N2-03 No No No A No No 586H
time constant 2 tion of acceleration or when the 2000 ms
load changes radically.
AFR 时间 2
6-41
Machine Protection
This section explains functions for protecting the machine.
Related Constants
Name Control Methods
Change Open MEMO
Con- Open
Setting Factory during V/f Flux Loop BUS
stant Description Range Setting Opera- Loop
Number Display V/f with Vec- Vec- Regis-
tion Vector ter
PG tor tor
1
2
Carrier fre-
quency Select carrier wave fixed pattern.
selection 1 to F 6 No
C6-02 Select F to enable detailed settings using No Q Q Q Q 224H
*2 *1 *4
constants C6-03 to C6-07.
载波频率选
择
Carrier fre-
quency Select the carrier frequency when open-
selection loop vector 2 control is used.
for open- 1: 2 kHz 1 No No No No
C6-11 loop vector 1 to 4 No Q 22DH
2: 4 kHz *1 *4 *4 *4 *4
2 control 3: 6 kHz
无 PG 矢量 2
4: 8 kHz
载波
* 1. The factory settings depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 2. The setting ranges depend on the capacity of the Inverter. The values for a 200 V Class Inverter for 0.4 kW are given.
* 3. This constant can be monitored or set only when F is set for C6-02.
* 4. Displayed in Quick Programming Mode when motor 2 is set for a multi-function input.
* 5. The maximum output frequency depends on the setting for the carrier frequency (refer to page 6-43).
6-42
Machine Protection
* The upper limit of the carrier frequency depends on the Inverter capacity.
If speed and torque are inconsistent at low speeds: Set the carrier frequency low.
If leakage current from the Inverter is large: Set the carrier frequency low.
If metallic noise from the motor is large: Set the carrier frequency high.
• When using V/f control or V/f control with PG, you can vary the carrier frequency according to the output
frequency, as shown in the following diagram, by setting C6-03 (Carrier Frequency Upper Limit), C6-04
(Carrier Frequency Lower Limit), and C6-05 (Carrier Frequency Proportional Gain).
6-43
Carrier Frequency
C6-03
Output frequency
* K is the coefficient determined by the set E1-04
value in C6-03. Max. Output Frequency
C6-03 ≥ 10.0 kHz: K=3
10.0 kHz > C6-03 ≥ 5.0 kHz: K=2
5.0 kHz < C6-03: K=1
Fig 6.34
• With vector control, the carrier frequency is fixed to the Carrier Frequency Upper Limit in C6-03 if user-
set or by the carrier frequency set in C6-02.
• To fix the carrier frequency, set C6-03 and C6-04 to the same value, or set C6-05 to 0.
• If the settings are as shown below, OPE11 (Constant setting error) will occur.
If Carrier Frequency Proportional Gain (C6-05) > 6 and C6-03 < C6-04.
• The Inverter overload current level can be reduced by the carrier frequency setting, and an OL2 (Inverter
overload) may be detected even if the overload current is smaller than 150%. The reduction levels of the
Inverter overload current are shown in the following figures.
100%
80%
200 V Class,
22 kW
50%
Carrier frequency
0 10 kHz 15 kHz
Fig 6.35 Reduction Levels for V/f, V/f with PG, Open-loop Vector 1, and Flux Vector Control
6-44
Machine Protection
100%
87%
200 V Class,
30 to 75 kW
50%
Carrier frequency
0 4 kHz 8 kHz
Fig 6.36 Reduction Levels for Open-loop Vector 2 Control
For 400 V Class Inverters, the following limitations apply to the maximum output frequency that can be set
for the carrier frequency settings.
Carrier Frequency 0.4 kHz 1 kHz 1.5 kHz* 2 kHz 3 kHz 5 kHz 8 kHz
Maximum output frequency setting 33 Hz 83 Hz 120 Hz 166 Hz 250 Hz 400 Hz 400 Hz
Applicable Inverter capacity 40P4 to 40P4 to 40P4 to
40P4 to 4300
CIMR-G7B 4110 4075 4045
* The factory setting for 400V 132kW and 220kW flax vector control (A1-02 = 3) is 1.5 kHz, for software version VSG123032 or later.
6-45
Limiting Motor Torque (Torque Limit Function)
The motor torque limit function is enabled with flux vector control and open-loop vector control.
In the open-loop vector control and flux vector control, the user-set value is applied to the torque limit by cal-
culating internally the torque output by the motor. Enable this function if you do not want a torque above a
specified amount to be applied to the load, or if you do not want a regeneration value above a specified
amount to occur.
Related Constants
Reverse
Sets the torque limit value as a percent-
drive
age of the motor rated torque. 0 to
L7-02 torque limit 200% No No No A A A 4A8H
Four individual regions can be set. 300
反转电动转
矩极限 Output torque
Positive torque
Forward
regenera- No. of
Regenerative motor
tive torque Reverse state rotations 0 to
L7-03 limit Forward 200% No No No A A A 4A9H
Regenerative
state
300
正转再生转
矩极限 Negative torque
Reverse
regenera-
tive torque 0 to
L7-04 limit 200% No No No A A A 4AAH
300
反转再生转
矩极限
Integral
time set- Set the integral time for the torque limit.
ting for When integral control is set for the
5 to 200
L7-06 torque limit torque limit, reduce this setting to No No No A No No 4ACH
10,000 ms
increase the change in frequency for the
转矩限制时 torque limit.
间
Control
method
selection Select the control method for the torque
for torque limit during acceleration and decelera-
limit during tion.
accelera- 0: Proportional control (integral control
L7-07 0, 1 0 No No No A No No 4C9H
tion and during constant speed)
decelera- 1: Integral control
tion Normally, this constant does not need to
be set.
转矩极限控
制选择
6-46
Machine Protection
Control Methods
Set- Open Open
ting Function Contents (100%) V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
10 Positive torque limit Motor's rated torque No No Yes Yes Yes
Output torque
Positive
Positive/negative torque limits
Forward torque limit
6-47
Setting Torque Limits Using Constants and an Analog Input
The following block diagram shows the relationship between torque limit using constants and torque limit
using an analog input.
Selecting the Control Method for Torque Limit during Acceleration and Deceleration
L7-07 is used to select the control method for the torque limit during acceleration and deceleration. The selec-
tions are proportional control and integral control. For applications, such as presses, in which the torque limit
will be reached during acceleration and deceleration, torque control can be given priority by selecting integral
control. To increase the change in frequency for the torque limit when integral control is selected, decrease the
value set for L7-06 (Integral Time Setting for Torque Limit).
Setting Precautions
• When the torque limit function is operating, control and compensation of the motor speed is disabled
because torque control is given priority. Therefore, the acceleration and deceleration times may increase or
the number of motor rotations may decrease.
• When using the torque limit to raise and lower loads, do not carelessly lower the torque limit value, as this
may result in the motor falling or slipping.
• Torque limits using an analog input are the upper limit value (during 10 V or 20 mA input) of 100% of the
motor rated torque. To make the torque limit value during 10 V or 20 mA input 150% of the rated torque,
set the input terminal gain to 150.0 (%). Adjust the gain for multi-function analog input terminal A2 using
H3-10 and for multi-function analog input terminal A3 using H3-06.
• The torque limit accuracy is ±5% at the output frequency of 10 Hz or above. When output frequency is less
than 10 Hz, accuracy is lowered.
• When the torque is limited while L7-07 is set to 1 (integral control), the acceleration and deceleration
times may increase or the motor speed may not agree with the speed reference value.
6-48
Machine Protection
Related Constants
6-49
Changing Stall Prevention Level during Operation Using an Analog Input
If you set H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-05 (Multi-function
Analog Input Terminal A3 Function Selection) to 8 (stall prevention level during run), you can change the stall
level during operation by setting H3-10 (Gain (Terminal A2)) and H3-11 (Bias (Terminal A2)) or H3-06 (Gain
(Terminal A3)) and H3-07 (Bias (Terminal A3).
The stall prevention level during operation enabled is the multi-function analog input terminal A2 or A3 input
level or the set value in constant L3-06, whichever is the smaller.
Fig 6.39 Stall Prevention Level during Operation Using an Analog Input
If the motor capacity is smaller than the Inverter capacity or the motor stalls when operating at the factory set-
tings, lower the stall prevention level during operation.
INFO
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Speed agree Set the speed that you want to
detection level detect in Hz.
0.0 to
L4-01 The set speed is an absolute value, 0.0 Hz No A A A A A 499H
400.0
频率检出值 so the speed is detected in forward
or reverse.
Speed agree
detection width Set the speed detection range in 0.0 to
L4-02 2.0 Hz No A A A A A 49AH
Hz. 20.0
频率检出幅度
Speed agree
detection level Set the speed that you want to
−400.0
(+/−) detect in Hz.
L4-03 to 0.0 Hz No A A A A A 49BH
Set positive values for forward,
频率检出值
+400.0
negative values for reverse.
+-
6-50
Machine Protection
Set the corresponding setting in the multi-function output (H2-01 to H2-05) to output the desired Fref/Fout
Agree signal, Fref/Set Agree signal, or Frequency Detection signal.
Function Setting
Fref/Fout Agree 1 2
Fref/Set Agree 1 3
Frequency Detection 1 4
Frequency Detection 2 5
Fref/Fout Agree 2 13
Fref/Set Agree 2 14
Frequency Detection 3 15
Frequency Detection 4 16
Frequency Detection 5 36
6-51
Timing Chart for Frequency Detection Operation
Related L4-01: Speed Agree Level L4-03: Speed Agree Level +/−
constant L4-02: Speed Agree Width L4-04: Speed Agree Width +/−
Fref/Fout Agree 1 Fref/Fout Agree 2
Agree
L4-02
L4-01 L4-03
Fref/Set tput frequency
Output frequency
or motor speed
Agree motor speed
L4-01
L4-02
L4-01 L4-03
L4-01
L4-02
L4-01 L4-03
Detection
L4-01
L4-02
L4-01
Output frequency
or motor speed
L4-01
L4-02
6-52
Machine Protection
Related Constants
6-53
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Torque detec-
tion time 1 Sets the overtorque/undertorque 0.0 to
L6-03 0.1 s No A A A A A 4A3H
detection time in 1-second units. 10.0
转矩检出 1
时间
Torque detec-
tion selection 2 Multi-function output for over-
L6-04 0 to 8 0 No A A A A A 4A4H
转矩检出 2 torque detection 1 is output to
动作 multi-function contact output
when overtorque detection 1 NO
Torque detec- or overtorque detection 1 NC is
tion level 2 0 to
L6-05 selected. Multi-function output 150% No A A A A A 4A5H
300
转矩检出 2 值 for overtorque detection 2 is out-
put to multi-function contact out-
Torque detec- put when overtorque detection 2
tion time 2 NO or overtorque detection 2 NC 0.0 to
L6-06 is selected. 0.1 s No A A A A A 4A6H
10.0
转矩检出 2
时间
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detec-
B Yes Yes Yes Yes Yes
tion at ON)
6-54
Machine Protection
Setting Example
The following diagram shows the time chart for overtorque and undertorque detection.
• Overtorque Detection
* *
L6-02 or L6-05
* Overtorque detection disabled band is approximately 10% of the Inverter rated output
current (or motor rated torque).
6-55
• Undertorque Detection
*
L6-02 or L6-05
L6-03 L6-03
Undertorque detection 1 NO or or
or Undertorque detection 2 NO L6-06 ON L6-06 ON
* The undertorque detection disabled margin is approximately 10% of the Inverter rated output
current (or motor rated torque)
Detection level
Control Methods
Set- Open Open
ting Function Contents (100%) V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
Overtorque/undertorque detection Motor rated torque for vector control
7 Yes Yes Yes Yes Yes
level Inverter rated output current for V/f control
6-56
Machine Protection
Related Constants
6-57
Multi-Function Outputs (H2-01 to H2-05)
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection
1F Yes Yes Yes Yes Yes
level)
6-58
Machine Protection
Torque (%)
This motor yields a
cooling effect even
Vector motor Operates continuously at
3 Continuous
when operating at
(1:100) 0.6 to 60 Hz.
Frame number
Max. speed of
200 LJ min. extremely low speeds
Frame number Max. speed (approx. 0.6 Hz).
of 160 MJ to 180 LJ
Frame number Max.
speed of 132 MJ
Cold start
Hot start
Setting Precautions
• If multiple motors are connected to one Inverter, set constant L1-01 to 0 (disabled). To protect the motor,
install a thermal relay in the motor power cable, and perform overload protection on each motor.
• With applications where the power supply is often turned ON and OFF, there is a risk that the circuit cannot be pro-
tected even if this constant has been set to 1 (enabled), because the thermal value will be reset.
• To detect overloads in good time, set the set value in constant L1-02 to a low setting.
• When using a general-purpose motor (standard motor), the cooling ability will be lowered by f1/4 (fre-
quency). Consequently, the frequency may cause motor overload protection (OL1) to occur, even below
the rated current. If operating using the rated current at a low frequency, use a special motor.
6-59
Setting the Motor Overload Pre-Alarm
If the motor overload protection function is enabled (i.e., L1-01 is set to other than 0) and you set H2-01 to
H2-05 (multi-function output terminals M1-M2, P1-PC, P2-PC, P3-C3, and P4-C4 function selection) to 1F
(motor overload OL1 pre-alarm), the motor overload pre-alarm will be enabled. If the electronic thermal value
reaches minimum 90% of the overload detection level, the output terminal that has been set will be turned ON.
Related Constants
6-60
Machine Protection
Class F Class H
Resistance (ohms) 180°C
150°C
1330
Temperature
Tr
Tr 5 Tr Tr+5
Inverter
Multi-function Multi-function
contact input contact output
Fault contact
output
Branch resistance
18 kΩ
A2, A3
(0-10 V)
* When using terminal A2, set DIP switch S1-2 to OFF (0 to 10 V).
6-61
Limiting Motor Rotation Direction
If you set motor reverse rotation prohibited, a Reverse Run Command will not be accepted even if it is input.
Use this setting for applications in which reverse motor rotation can cause problems (e.g., fans, pumps, etc.)
Related Constants
6-62
Continuing Operation
Continuing Operation
This section explains functions for continuing or automatically restarting Inverter operation using speed
search even if an error occurs.
Related Constants
Momentary
power loss ride- Ridethrough time, when Momen-
thru time 0 to 0.1 s
L2-02 tary Power Loss Selection (L2- No A A A A A 486H
25.5 *1
瞬时停电补偿时
01) is set to 1, in units of seconds.
间
6-63
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Voltage recov- Sets the time required to return
ery time the Inverter output voltage to nor-
mal voltage at the completion of a
speed search, in units of one sec- 0.0 to 0.3 s
L2-04 No A A A A A 488H
ond. 5.0 *1
电压恢复时间 Sets the time required to recover
from 0 V to the maximum volt-
age.
Undervoltage Sets the main circuit undervoltage
detection level (UV) detection level (main circuit
DC voltage) in V units.
150 to
Usually setting is not necessary. 190 V
L2-05 210 No A A A A A 489H
Insert an AC reactor in the *2
*2
PUV 检出值 Inverter input side to lower the
main circuit undervoltage detec-
tion level.
Note Attach a Backup Capacitor Unit for Momentary Power Loss if compensation for power interruptions of up to 2.0 seconds is required for 200 V/400 V
Class Inverters with outputs of 0.4 to 7.5 kW.
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. These values are for a 200 V Class Inverter. For a 400 V Class Inverter, double the values.
Setting Precautions
• Error output signals are not output during momentary power loss recovery.
• To continue Inverter operation after power has been restored, make settings so that Run Commands from
the control main circuit terminal are stored even while power is suspended.
• If the momentary power loss operation selection is set to 0 (Disabled), when the momentary power loss
exceeds 15 ms during operation, alarm UV1 (main circuit undervoltage) will be detected.
Speed Search
The speed search function finds the actual speed of the motor that is rotating using inertia, and then starts
smoothly from that speed. When restoring power after a temporary power loss, the speed search function
switches connection from the commercial power supply, and then restarts the fan that is rotating using inertia.
6-64
Continuing Operation
Related Constants
Speed Calculation:
When the search is started, the
motor speed is calculated and
acceleration/deceleration is 2
b3-01 0 to 3 No A A A No A 191H
performed from the calculated *1
speed to the specified frequency
起动速度搜索 (motor direction is also
searched).
Current Detection:
The speed search is started from
the frequency when power was
momentarily lost and the
maximum frequency, and the
speed is detected at the search
current level.
Speed search Sets the speed search operation
operating cur- current as a percentage, taking the
rent (current Inverter rated current as 100%.
0 to 100%
b3-02 detection) Not usually necessary to set. No A No A No A 192H
200 *1
When restarting is not possible
速度搜索电流 with the factory settings, reduce
the value.
6-65
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Proportional Sets the proportional gain (PI con-
gain of the trol) of the speed estimator during
speed estimator speed search taking the setting of
during speed N4-08 to be equivalent to a setting
search of 1.0. 0.1 to
b3-13 1.0% No No No No No A 19DH
Usually, there is no need to 2.0
change this setting. If, however,
速度推定比例增 the load inertia is large and over-
益 voltages occur during the search,
reduce this setting.
Rotation direc-
tion search 0: Disabled (operates with speci-
selection fied rotation direction)
b3-14 0 or 1 1 No A A A No A 19EH
1: Enabled (operates with rota-
旋转方向搜索选 tion direction found by search)
择
Speed search
retrial detec- Sets the time for detection in a
tion time 0.00 to
b3-18 speed search retrial in units of 0.10 s No A No A No A 1F1H
1.00
速度搜索检出时
seconds.
间
Number of
speed search
retrials Sets the number of times that a
b3-19 0 to 10 0 No A No A No A 1F2H
speed search can be retried.
速度搜索重试次
数
* 1. The factory setting will change when the control method is changed. The open-loop vector 1 control factory settings are given.
* 2. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
6-66
Continuing Operation
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
61 External search command 1 (ON: Speed search from maximum output frequency) Yes No Yes No Yes
62 External search command 2 (ON: Speed search from set frequency) Yes No Yes No Yes
Setting Precautions
• When both external search commands 1 and 2 are set for the multi-function contact terminals, an OPE03
(invalid multi-function input selection) operation error may occur. Set either external search command 1 or
external search command 2.
• If speed search during startup is selected when using V/f control with PG, the Unit will start from the fre-
quency detected by PG.
• If performing speed search using external search commands, add an external sequence so that the period
when the Run Command and external search command are both ON is at the very least the Minimum
Baseblock Time (L2-03).
• If the Inverter output is equipped with a contact, set the contact operation delay time in the Speed Search
Wait Time (b3-05). The factory setting is 0.2 s. When not using the contact, you can reduce the search time
by making the setting 0.0 s. After waiting for the speed search wait time, the Inverter starts the speed
search.
• Constant b3-02 is a current detection speed search (current detection level for search completion). When
the current falls below the detection level, the speed search is viewed as completed, and the motor acceler-
ates or decelerates to the set frequency. If a motor overload (OL1) or an Inverter overload (OL2) occurs
and the motor cannot restart, lower the set value.
• If an overcurrent (OC) is detected when using speed search after recovery following a power loss, lengthen
the Minimum Baseblock Time (L2-03).
• If a main circuit over voltage (OV) is detected when using a current detection speed search after a momen-
tary power loss, lengthen the Speed search detection time (b3-03).
The motor will not operate when stationary autotuning or stationary autotuning for line-to-line
resistance only is performed.
IMPORTANT
6-67
Speed Search Selection
Set whether to enable or disable speed search at startup, and set the type of speed search (estimated speed or
current detection) using setting b3-01. To perform speed search when inputting the Run Command, set b3-01
to 1 or 3.
OFF ON
Run Command Set frequency
reference
Start using
speed detected
Output frequency
b3-02
Output current
1.0 s
* Lower limit set using Speed Search Wait Time (b3-05).
Note: If the stopping method is set to coast to stop, and the Run Command turns ON in a short time,
the operation may be the same as the search in case 2.
6-68
Continuing Operation
Speed Search after Short Baseblock (during Power Loss Recovery, etc.) (b3-01 = 0)
The time chart when the Inverter operation is restarted after power has been restored is shown below.
• Loss Time Shorter Than the Minimum Baseblock Time (L2-03)
Output frequency
Output current
10 ms
Fig 6.45 Speed Search after Baseblock (When Estimated Speed: Loss Time Is Set in L2-03)
Output current
10 ms
Fig 6.46 Speed Search After Baseblock (Estimated Speed: Loss Time > L2-03)
6-69
Current Detection Speed Search (b3-01 = 2 or 3)
The time charts for current detection speed search is shown below.
Output current
* * Lower limit is set using Speed Search Time (b3-05).
Minimum baseblock time
(L2-03)
Output current
*1 Baseblock time may be reduced by the output frequency
immediately before baseblock.
Minimum baseblock time (L2-03) *1 *2 After AC power supply recovery, motor waits for the minimum
Speed Search Wait Time (b2-03).
*2
Fig 6.48 Speed Search After Baseblock (Current Detection: Loss Time < L2-03)
Output current
Speed search wait time (b3-05)
Fig 6.49 Speed Search After Baseblock (Current Detection: Loss Time > L2-03)
6-70
Continuing Operation
Related Constants
6-71
Restarting Operation After Transient Fault (Auto Restart Function)
If an Inverter fault occurs during operation, the Inverter will perform self-diagnosis. If no fault is detected, the
Inverter will automatically restart using the speed search function (b3-01). This is called the auto restart func-
tion.
Set the number of auto restarts in constant L5-01. A fault reset is attempted every 5 ms after a fault occurs and
minimum baseblock time has passed. The number of auto restarts is counted when the Inverter attempts a fault
reset and restarts operation. The protection function will operate if a fault continues to occur after auto restart-
ing the number of times set in L5-01.
The auto restart function can be applied to the following faults. If a fault not listed below occurs, the protec-
tion function will operate and the auto restart function will not.
• OC (Overcurrent) • RH (Braking resistor overheated)
• GF (Ground fault) • RR (Braking transistor error)
• PUF (Fuse blown) • OL1 (Motor overload)
• OV (Main circuit overvoltage) • OL2 (Inverter overload)
• UV1 (Main Circuit Undervoltage, Main Circuit Magnetic Contactor Operation • OH1 (Motor overheat)
Failure)*
• PF (Main circuit voltage fault) • OL3 (Overtorque)
• LF (Output phase failure) • OL4 (Overtorque)
* When L2-01 is set to 1 or 2 (continue operation during momentary power loss)
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Number of auto Sets the number of auto restart
restart attempts attempts.
L5-01 Automatically restarts after a fault 0 to 10 0 No A A A A A 49EH
故障重试次数
and conducts a speed search from
the run frequency.
Auto restart Sets whether a fault contact out-
operation selec- put is activated during fault
tion restart.
L5-02 0: Not output (Fault contact is 0 or 1 0 No A A A A A 49FH
not activated.)
故障重试接点动
作 1: Output (Fault contact is
activated.)
Application Precautions
• The number of auto restarts count is reset under the following conditions:
After auto restart, normal operation has continued for 10 minutes.
After the protection operation has been performed, and the fault has been verified, and an fault reset
has been input.
After the power supply is turned OFF, and then ON again.
• Do not use the auto restart function with variable loads.
6-72
Continuing Operation
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
OH1 detection 0: Disabled (FAN minor fault
of Inverter’ s detection)
L8-32 cooling fan 0 or 1 1 No A A A A A 4E2H
1: Enabled (OH1 major fault
OH1 检出选择 detection)
The following table describes the operation of the motor and the display of the Digital Operator in accordance
with the settings of the L8-32 if a cooling fan fault occurred.
Setting Multi-function Con-
Fault Digital Operator Motor Operation
Value tact Output
Cooling Fin Overheating OH1 (lit) Coast to a stop Fault
0
Inverter’s Cooling Fan Fault FAN (blink) Continue operation* Minor fault
If L8-32 is set to 0, be sure to set H2-01 to H2-03 multi-function contact outputs to 10 (minor fault) or to 3D
(Inverter’s cooling fan fault.) If a cooling fan fault occurs, stop the Inverter immediately and replace the cool-
ing fan. If the Inverter continues to run while a cooling fan fault occurs, the Inverter’s cooling ability will be
IMPORTANT affected and the Inverter’s internal temperature will increase and shorten the Inverter’s life.
During a cooling fan fault, the cooling fan stops for about 3 seconds every minute (interval operation.)
6-73
Inverter Protection
This section explains the functions for protecting the Inverter and the braking resistor.
Related Constants
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
D Braking resistor fault (ON: Resistor overheat or braking transistor fault) Yes Yes Yes Yes Yes
The most likely causes of RH (Mounted braking resistor overheating) being detected are that the deceleration
time is too short or that the motor regeneration energy is too large. In these cases, lengthen the deceleration
time or replace the Braking Resistor Unit with one with a higher breaking capacity.
INFO
6-74
Inverter Protection
Related Constants
6-75
Input Terminal Functions
This section explains input terminal functions, which set operating methods by switching functions for the
multi-function contact input terminals (S3 to S12).
Related Constants
You can also perform local/remote switching using the LOCAL/REMOTE Key on the Digital Operator. When
the local/remote function has been set in the external terminals, the LOCAL/REMOTE Key function on the
Digital Operator will be disabled.
INFO
6-76
Input Terminal Functions
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
8 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes Yes Yes
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes Yes
Time Chart
The time chart when using baseblock commands is shown below.
Forward operation/Stop
Input Cleared
Baseblock command
Frequency reference
Output frequency
Hold
If using baseblock commands with a variable load, do not frequently input baseblock commands during oper-
ation, as this may cause the motor to suddenly start coasting, and may result in the motor falling or slipping.
IMPORTANT
6-77
Stopping Acceleration and Deceleration (Acceleration/Deceleration
Ramp Hold)
The acceleration/deceleration ramp hold function stops acceleration and deceleration, stores the output fre-
quency at that point in time, and then continues operation.
Set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selection)
to A (acceleration/deceleration ramp hold) to stop acceleration and deceleration when the terminal is turned
ON and to store the output frequency at that point in time. Acceleration and deceleration will restart when the
terminal is turned OFF.
If d4-01 is set to 1 and the Acceleration/Deceleration Ramp Hold command is input, the output frequency is
still stored even after the power supply is turned OFF.
Related Constants
Time Chart
The time chart when using Acceleration/Deceleration Ramp Hold commands is given below.
Power supply
Forward/Stop
Acceleration/Deceleration
Ramp Hold
Frequency reference
Output frequency
Hold Hold
6-78
Input Terminal Functions
Application Precautions
• When d4-01 is set to 1, the output frequency on hold is stored even after the power supply is turned OFF. If
performing operations using this frequency after the Inverter has also been turned OFF, input the Run
Command with the Acceleration/Deceleration Ramp Hold turned ON.
• When d4-01 is set to 0 and a Run Command is input while the Acceleration/Deceleration Ramp Hold is
turned ON, the output frequency will be set to zero.
• If you input an Acceleration/Deceleration Ramp Hold command by error when decelerating during posi-
tioning, deceleration may be canceled.
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Frequency ref-
erence upper Set the output frequency upper
0.0 to 100.0
d2-01 limit limit as a percent, taking the max. No A A A A A 289H
110.0 %
output frequency to be 100%.
频率指令上限
Frequency ref-
erence lower Sets the output frequency lower
0.0 to
d2-02 limit limit as a percentage of the maxi- 0.0% No A A A A A 28AH
110.0
mum output frequency.
频率指令下限
Precautions
When setting and using UP and DOWN commands, observe the following precautions.
Setting Precautions
If multi-function input terminals S3 to S12 are set as follows, operation error OPE03 (Invalid multi-function
input selection) will occur:
• Only either the UP command or DOWN command has been set.
• UP/DOWN commands and Acceleration/Deceleration Ramp Hold have been allocated at the same time.
6-79
Application Precautions
• Frequency outputs using UP/DOWN commands are limited by the frequency reference upper and lower
limits set in constants d2-01 to d2-03. Here, frequency references from analog frequency reference termi-
nal A1 becomes the frequency reference lower limit. If using a combination of the frequency reference
from terminal A1 and the frequency reference lower limit set in either constant d2-02 or d2-03, the larger
lower limit will become the frequency reference lower limit.
• If inputting the Run Command when using UP/DOWN commands, the output frequency accelerates to the
frequency reference lower limit.
• When using UP/DOWN commands, multi-step operations are disabled.
• When d4-01 (Frequency Reference Hold Function Selection) is set to 1, the frequency reference held using
the UP/DOWN functions is stored even after the power supply is turned OFF. When the power supply is
turned ON and the Run Command is input, the motor accelerates to the frequency reference that has been
stored. To reset (i.e., to 0 Hz) the stored frequency reference, turn ON the UP or DOWN command while
the Run Command is OFF.
Inverter
Forward
operation/Stop
Reverse
operation/Stop
Up command
Down command
Sequence
0 to 10 V analog common
signal Frequency
reference lower limit
6-80
Input Terminal Functions
Output frequency
Upper limit
Accelerates to
lower limit Same
frequency
Lower limit
Forward operation/stop
UP command
Reference
frequency reset
DOWN command
Frequency
matching signal*
Power supply
* The frequency matching signal turns ON when the motor is not accelerating/
decelerating while the Run Command is ON.
6-81
Accelerating and Decelerating Constant Frequencies in the Analog Refer-
ences (+/- Speed)
The +/- speed function increments or decrements the frequency set in analog frequency reference d4-02 (+/-
Speed Limit) using two contact signal inputs.
To use this function, set One of the constants H1-01 to H1-10 (multi-function contact terminal inputs S3 to
S12 function selection) to 1C (Trim Control Increase command) and 1D (Trim Control Decrease command).
Be sure to allocate two terminals so that the Trim Control Increase command and Trim Control Decrease com-
mand can be used as a pair.
Related Constants
Application Precautions
• Trim Control Increase/Decrease command is enabled when speed reference > 0 and the speed reference is
from an analog input.
• When the analog frequency reference value - d4-02 < 0, the frequency reference is set to 0.
• If only the Trim Control Increase command or Trim Control Decrease command has been set for a multi-
function contact input terminal S3 to S12, operation error OPE03 (invalid multi-function input selected)
will occur.
6-82
Input Terminal Functions
The analog value 100 ms after the command is turned ON is used as the frequency reference.
Sample/hold
command
Analog input
Frequency reference
Precautions
When setting and executing sample and hold for analog frequency references, observe the following precau-
tions.
Setting Precautions
When using sample/hold of analog frequency reference, you cannot use the following commands at the same
time. If these commands are used at the same time, operation error OPE03 (invalid multi-function input selec-
tion) will occur.
• Acceleration/Deceleration Ramp Hold command
• UP/DOWN command
• Trim Control Increase/Decrease command
Application Precautions
• When performing sample/hold of analog frequency references, be sure to store references of 100 ms mini-
mum. If the reference time is less than 100 ms, the frequency reference will not be held.
• The analog frequency reference that is held will be deleted when the power supply is turned OFF.
6-83
Setting Precautions
To switch command inputs between the Communications Option Board and the control circuit terminals, set
the following constants.
• Set b1-01 (Reference Selection) to 1 [Control circuit terminal (analog input)]
• Set b1-02 (Operation Method Selection to 1 [Control circuit terminal (sequence inputs)]
• Set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selec-
tion) to 2 (Option/Inverter selection).
Terminal Status Frequency Reference and Run Command Selection
Inverter
OFF (Can be operated from frequency reference or control circuit terminal from analog input termi-
nal.)
Communications Option Board
ON
(Frequency reference and Run Command are enabled from Communications Option Board.)
Related Constants
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes Yes
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes Yes
Application Precautions
• Jog frequencies using FJOG and RJOG commands are given priority over other frequency references.
• When both FJOG command and RJOG commands are ON for 500 ms or longer at the same time, the
Inverter stops according to the setting in b1-03 (stopping method selection).
6-84
Input Terminal Functions
6-85
Output Terminal Functions
The output terminal function, which sets the output methods by switching the functions of the multi-func-
tion output terminals (M1-M2, P1-PC, P2-PC, P3-C3, and P4-C4), is described here.
Output frequency
OFF ON
During run 2 output
Zero-speed (Setting: 1)
The output frequency is greater than the minimum output frequency (E1-09).
OFF
(With flux vector control, is greater than the zero-speed level (b2-01).)
The output frequency is less than the minimum output frequency (E1-09).
ON
(With flux vector control, is less than the zero-speed level (b2-01).)
OFF ON
Zero-speed output
6-86
Output Terminal Functions
• This output function is valid when the motor overload protection function is enabled (L1-01 =1).
• This output can be used to warn of overheating before the protection function itself operates.
• This output function indicates that the temperature of the cooling fins reaches the temperature set in L8-02
(the Inverter overheating alarm detection level).
• This output function indicates that zero-servo position control has been completed.
• The output is turned ON after the zero-servo command is input and the difference between the zero-servo
operation starting position and the current position is within the zero-servo completion width (b9-02).
6-87
Monitor Constants
This section explains the analog monitor and pulse monitor constants.
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Monitor selec- Sets the number of the monitor
tion (terminal item to be output (U1-) from
FM) terminal FM.
H4-01 1 to 45 2 No A A A A A 41DH
4, 10 to 14, 25, 28, 34, 39, 40 can-
端子 FM 设定 not be set. 29 to 31 and 41 are not
used.
6-88
Monitor Constants
Channel 1 out-
put monitor Sets the channel 1 item bias to
-10.0
F4-05 bias 100%/10 V when the Analog 0.0 Yes A A A A A 395H
to 10.0
Monitor Board is used.
AO CH1 偏置
Channel 2 out-
put monitor Sets the channel 2 item bias to
-10.0
F4-06 bias 100%/10 V when the Analog 0.0 Yes A A A A A 396H
to 10.0
Monitor Board is used.
AO CH2 偏置
Analog output
signal level for 0: 0 to 10 V
F4-07 channel 1 0 or 1 0 No A A A A A 397H
1: -10 to +10 V
CH1 信号电平
Analog output
signal level for 0: 0 to 10 V
F4-08 channel 2 0 or 1 0 No A A A A A 398H
1: -10 to +10 V
CH2 信号电平
6-89
Adjusting the Meter
The output voltage for terminals FM-AC and AM-AC and output channels 1 and 2 of the AO option board can
be adjusted while the Inverter is stopped. For example, just pressing the Enter Key and displaying the data set-
ting display for H4-02 or H4-03 will cause the following voltage to be output by the FM-AC terminals.
10 V/100% monitor output × output gain (H4-02) + output bias (H4-03)
Just pressing the Enter Key and displaying the data setting display for F4-02 or F4-05 will cause the following
voltage to be output to channel 1 of the AO option board.
10 V/100% monitor output × output gain (H4-02) + output bias (H4-05)
Output voltage
Gain x 10 V
Bias x 10/100 V
Monitor item
You can select the signal levels separately for multi-function analog output terminals and analog output option
terminals.
INFO
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Pulse train Select the pulse train monitor out-
monitor selec- put items (value of the part 1, 2, 5,
tion of U1-).
H6-06 20, 24, 2 Yes A A A A A 431H
There are two types of monitor
items: Speed-related items and 36
脉冲监视选择
PID-related items.
6-90
Monitor Constants
Application Precautions
When using a pulse monitor constant, connect a peripheral device according to the following load conditions.
If the load conditions are different, there is a risk of characteristic insufficiency or damage to the machinery.
AC
6-91
Individual Functions
This section explains the individual functions used in special applications.
MEMOCON-series PLC
RS-485 connections
example
Communications Specifications
The MEMOBUS communications specifications are shown in the following table.
Item Specifications
Interface RS-422, RS-485
Communications Cycle Asynchronous (Start-stop synchronization)
Baud rate: Select from 1,200, 2,400, 4,800, 9,600, and 19,200 bps.
Data length: 8 bits fixed
Communications Parameters
Parity: Select from even, odd, or none.
Stop bits: 1 bit fixed
Communications Protocol MEMOBUS (RTU mode only)
Number of Connectable Units 31 units max. (when using RS-485)
6-92
Individual Functions
S+ +
-
S- S1 Terminating
O OFF ON resistance
RS-422A 1
or RS-485 R+ F
F 2
Switch
R- 1
1. Separate the communication cables from the main circuit cables and other wiring and power cables.
2. Use shielded cables for the communication cables, connect the shield cover to the Inverter earth terminal,
and arrange the terminals so that the other end is not connected to prevent operating errors due to noise.
IMPORTANT 3. When using RS-485 communications, connect S+ to R+, and S- to R-, on the Inverter exterior.
R+ R S+ S
Set the timer on the master to monitor response time from the slave. Set the master so that if the slave does
not respond to the master within the set time, the same command message will be sent from the master
again.
INFO
6-93
Related Constants
6-94
Individual Functions
MEMOBUS communications can perform the following operations regardless of the settings in b1-01 and b1-
02.
• Monitoring operation status from the PLC
• Setting and reading constants
• Resetting errors
• Inputting multi-function commands
An OR operation is performed between the multi-function commands input from the PLC and commands
input from multi-function contact input terminals S3 to S12.
Message Format
In MEMOBUS communications, the master sends commands to the slave, and the slave responds. The mes-
sage format is configured for both sending and receiving as shown below, and the length of data packets is
changed by the command (function) contents.
Slave address
Function code
Data
Error check
The space between messages must support the following.
Slave Address
Set the Inverter address from 0 to 20 Hex. If you set 0, commands from the master will be broadcast (i.e., the
Inverter will not return responses).
6-95
Function Code
The function code specifies commands. There are three function codes, as shown below.
Command Message Response Message
Function Code
Function Min. Max. Min. Max.
(Hexadecimal)
(Bytes) (Bytes) (Bytes) (Bytes)
03H Read storage register contents 8 8 7 37
08H Loopback test 8 8 8 8
10H Write multiple storage registers 11 41 8 8
Data
Configure consecutive data by combining the storage register address (test code for a loopback address) and
the data the register contains. The data length changes depending on the command details.
Error Check
Errors are detected during communications using CRC-16. Perform calculations using the following method.
1. The factory setting for CRC-16 communications is usually 0, but when using the MEMOBUS system, set
the factory setting to 1 (i.e., set all 16 bits to 1).
2. Calculate CRC-16 using MSB as slave address LSB, and LSB as the MSB of the final data.
3. Also calculate CRC-16 for response messages from the slaves, and compare them to the CRC-16 in the
response messages.
6-96
Individual Functions
6-97
Loopback Test
The loopback test returns command messages directly as response messages without changing the contents to
check the communications between the master and slave. You can set user-defined test code and data values.
The following table shows a message example when performing a loopback test with the slave 1 Inverter.
Response Message Response Message
Command Message
(During Normal Operation) (During Error)
Slave address 01H Slave address 01H Slave address 01H
Function code 08H Function code 08H Function code 89H
Higher Higher
00H 00H Error Code 01H
place place
Test Code Test Code
Lower Lower Higher
00H 00H 86H
place place place
CRC-16
Higher Higher Lower
A5H A5H 50H
place place place
Data Data
Lower Lower
37H 37H
place place
Higher Higher
DAH DAH
place place
CRC-16 CRC-16
Lower Lower
8DH 8DH
place place
6-98
Individual Functions
Set the number of data specified using command messages as quantity of specified messages x 2. Handle
response messages in the same way.
INFO
Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcast
data.
Reference Data
The reference data table is shown below. You can both read and write reference data.
Register No. Contents
0000H Not used
Frequency reference
Bit 0 Forward Run/Stop Command 1: Forward run 0: Stop
Bit 1 Reverse Run/Stop Command 1: Reverse run 0: Stop
Bit 2 External fault 1: Error (EFO)
Bit 3 Fault reset 1: Reset command
Bit 4 ComNet
Bit 5 ComCtrl
Bit 6 Multi-function input command 3
0001H Bit 7 Multi-function input command 4
Bit 8 Multi-function input command 5
Bit 9 Multi-function input command 6
Bit A Multi-function input command 7
Bit B Multi-function input command 8
Bit C Multi-function input command 9
Bit D Multi-function input command 10
Bit E Multi-function input command 11
Bit F Multi-function input command 12
0002H Frequency reference (Set units using constant o1-03)
0003H Not used
0004H Not used
0005H Not used
0006H PID target value
0007H Analog output 1 setting (-11 V/-1540 to 11 V/1540)
0008H Analog output 2 setting (-11 V/-1540 to 11 V/1540)
Multi-function contact output setting
Bit 0 Contact output (Terminal M1-M2) 1: ON 0: OFF
Bit 1 PHC1(Contact P1-PC) 1: ON 0: OFF
Bit 2 PHC2(Contact P2-PC) 1: ON 0: OFF
Bit 3 PHC3(Contact P3-C3) 1: ON 0: OFF
0009H
Bit 4 PHC4(Contact P4-C4) 1: ON 0: OFF
Bit 5 Not used
Bit 6 Set error contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Bit 7 Error contact (terminal MA-MC) 1: ON 0: OFF
Bits 8 to F Not used
000AH to 000EH Not used
6-99
Register No. Contents
Reference selection settings
Bit 0 Not used
Bit 1 Use MEMOBUS 0006H PID target value 1: Enabled 0: Disabled
Bits 2 to B Not used
000FH
C Broadcast data terminal S5 input 1: Enabled 0: Disabled
D Broadcast data terminal S6 input 1: Enabled 0: Disabled
E Broadcast data terminal S7 input 1: Enabled 0: Disabled
F Broadcast data terminal S8 input 1: Enabled 0: Disabled
Note Write 0 to all unused bits. Also, do not write data to reserved registers.
Monitor Data
The following table shows the monitor data. Monitor data can only be read.
Register No. Contents
Inverter status
Bit 0 Operation 1: Operating 0: Stopped
Bit 1 Reverse operation 1: Reverse operation 0: Forward operation
Bit 2 Inverter startup complete 1: Completed 2: Not completed
Bit 3 Error 1: Error
Bit 4 Data setting error 1: Error
0020H
Bit 5 Multi-function contact output (terminal M1 - M2) 1: ON 0: OFF
Bit 6 Multi-function PHC output 1 (terminal P1 - PC) 1: ON 0: OFF
Bit 7 Multi-function PHC output 2 (terminal P2 - PC) 1: ON 0: OFF
Bit 8 Multi-function PHC output 3 (terminal P3 - C3) 1: ON 0: OFF
Bit 9 Multi-function PHC output 4 (terminal P4 - C4) 1: ON 0: OFF
Bits A and B Not used
Error details
Bit 0 Overcurrent (OC) Ground fault (GF)
Bit 1 Main circuit overvoltage (OV)
Bit 2 Inverter overload (OL2)
Bit 3 Inverter overheat (OH1, OH2)
Bit 4 Injection brake transistor resistance overheat (rr, rH)
Bit 5 Fuse blown (PUF)
Bit 6 PID feedback reference lost (FbL)
Bit 7 External fault (EF, EFO)
0021H Bit 8 Hardware error (CPF)
Motor overload (OL1), overtorque 1 (OL3) detected, or overtorque 2 (OL4)
Bit 9
detected
Bit A PG broken wire detected (PGO), Overspeed (OS), Speed deviation (DEV)
Bit B Main circuit undervoltage (UV) detected
Main circuit undervoltage (UV1), control power supply error (UV2), inrush preven-
Bit C
tion circuit error (UV3), power loss
Bit D Main Circuit Voltage Fault (PF), Output Open-phase (LF)
Bit E MEMOBUS communications error (CE)
Bit F Operator disconnected (OPR)
Data link status
Bit 0 Writing data
Bit 1 Not used
0022H Bit 2 Not used
Bit 3 Upper and lower limit errors
Bit 4 Data integrity error
Bits 5 to F Not used
0023H Frequency reference (U1-01)
0024H Output frequency (U1-02)
0025H Output voltage reference (U1-06)
0026H Output current (U1-03) (Unit: 1/0.1A)
0027H Output power (U1-08)
6-100
Individual Functions
6-101
Register No. Contents
Communications error details
Bit 0 CRC error
Bit 1 Invalid data length
Bit 2 Not used
003DH Bit 3 Parity error
Bit 4 Overrun error
Bit 5 Framing error
Bit 6 Time-out
Bits 7 to F Not used
003EH kVA setting
003FH Control method
Note Communications error details are stored until an fault reset is input (you can also reset while the Unit is operating).
Broadcast Data
The following table shows the broadcast data. You can also write this data.
Register
Contents
Address
Operation signal
Bit 0 Run Command 1: Operating 0: Stopped
Bit 1 Reverse operation command 1: Reverse 0: Forward
Bits 2 and 3 Not used
Bit 4 External fault 1: Error (set using H1-01)
0001H Bit 5 Fault reset 1: Reset command (set using H1-02)
Bits 6 to B Not used
Bit C Multi-function contact input terminal S5 input
Bit D Multi-function contact input terminal S6 input
Bit E Multi-function contact input terminal S7 input
Bit F Multi-function contact input terminal S8 input
Frequency ref-
0002H 30000/100%
erence
Note Bit signals not defined in the broadcast operation signals use local node data signals continuously.
ENTER Command
When writing constants to the Inverter from the PLC using MEMOBUS communications, the constants are
temporarily stored in the constant data area in the Inverter. To enable these constants in the constant data area,
use the ENTER command.
There are two types of ENTER commands: ENTER commands that enable constant data in RAM, and
ENTER commands that write data to EEPROM (non-volatile memory) in the Inverter at the same time as
enabling data in RAM.
The following table shows the ENTER command data. ENTER command data can only be written.
The ENTER command is enabled by writing 0 to register number 0900H or 0901H.
Register No. Contents
0900H Write constant data to EEPROM
0910H Constant data is not written to EEPROM, but refreshed in RAM only.
The maximum number of times you can write to EEPROM using the Inverter is 100 thousand. Do not fre-
quently execute ENTER commands (0900H) written to EEPROM.
The ENTER command registers are write-only. Consequently, if reading these registers, the register address
will become invalid (Error code: 02H).
INFO
6-102
Individual Functions
Error Codes
The following table shows MEMOBUS communications error codes.
Error Code Contents
Function code error
01H
A function code other than 03H, 08H, or 10H has been set by the PLC.
Invalid register number error
02H • The register address you are attempting to access is not recorded anywhere.
• With broadcast sending, a start address other than 0000H, 0001H, or 0002H has been set.
Invalid quantity error
03H • The number of data packets being read or written is outside the range 1 to 16.
• In write mode, the number of data packets in the message is not No. of packets x 2.
Data setting error
• A simple upper limit or lower limit error has occurred in the control data or when writing con-
21H
stants.
• When writing constants, the constant setting is invalid.
Write mode error
• Attempting to write constants from the PLC during operation.
• Attempting to write via ENTER commands from the PLC during operation.
22H
• Attempting to write constants other than A1-00 to A1-05, E1-03, or 02-04 when warning alarm
CPF03 (defective EEPROM) has occurred.
• Attempting to write read-only data.
Writing during main circuit undervoltage (UV) error
23H • Writing constants from the PLC during UV (main circuit undervoltage) alarm.
• Writing via ENTER commands from the PLC during UV (main circuit undervoltage) alarm.
Writing error during constants processing
24H
Attempting to write constants from the PLC while processing constants in the Inverter.
Application Precautions
Set a timer in the master to monitor response time from the slaves. Make the setting so that if no response is
sent to the master from the slave within the set time, the same command message is sent again from the mas-
ter.
6-103
Self-Diagnosis
The Inverter has a built-in function for self-diagnosing the operations of serial communications interface cir-
cuits. This function is called the self-diagnosis function. The self-diagnosis function connects the communica-
tions parts of the send and receive terminals, receives the data sent by the Inverter, and checks if
communications are being performed normally.
Perform the self-diagnosis function using the following procedure.
1. Turn ON the power supply to the Inverter, and set 67 (communications test mode) in constant H1-05 (Ter-
minal S7 Function Selection).
2. Turn OFF the power supply to the Inverter.
3. Perform wiring according to the following diagram while the power supply is turned OFF.
4. Turn ON the terminating resistance. (Turn ON pin 1 on DIP switch 1.)
5. Turn ON the power supply to the Inverter again.
6-104
Individual Functions
Related Constants
Setting Example
When the timer function input ON time is longer than the value set in b4-01, the timer output function is
turned ON. When the timer function input OFF time is longer than the value set in b4-02, the timer output
function is turned OFF. An example of timer function operation is given in the following diagram.
6-105
Using PID Control
PID control is a method of making the feedback value (detection value) match the set target value. By combin-
ing proportional control (P), integral control (I), and derivative control (D), you can even control targets
(machinery) with play time.
The characteristics of the PID control operations are given below.
P control Outputs the amount of operation proportional to the deviation. You cannot, however, set the
deviation to zero using P control alone.
I control Outputs the amount of operation that integrates the deviation. Used for matching feedback
value to the target value. I control is not suited, however, to rapid variations.
D control Outputs the amount of operation derived from the deviation. Can respond promptly to rapid
variations.
Deviation
Time
PID control
Amount of operation I control
D control
P control
Time
6-106
Individual Functions
Related Constants
6-107
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Selection of 0: No detection of loss of PID
PID feedback feedback.
command loss 1: Detection of loss of PID
detection feedback.
Operation continues during
detection, with the
b5-12 malfunctioning contact not 0 to 2 0 No A A A A A 1B0H
operating.
反馈丧失检出 2: Detection of loss of PID
feedback.
Coasts to stop during
detection, and fault contact
operates.
PID feedback
command loss Sets the PID feedback loss detec-
detection level tion level as a percent units, with 0 to
b5-13 0% No A A A A A 1B1H
the maximum output frequency at 100
反馈丧失 100%.
检出值
PID feedback
command loss
detection time Sets the PID feedback loss detec- 0.0 to
b5-14 1.0 s No A A A A A 1B2H
tion level in s units. 25.5
反馈丧失检出时
间
Accel/decel
time for PID
reference Set the accel/decel time for PID 0.0 to
b5-17 0.0 s No A A A A A 1B5H
reference in seconds. 25.5
PID 加减速
时间
Pulse train
input function 0: Frequency reference
H6-01 selection 1: PID feedback value 0 to 2 0 No A A A A A 42CH
2: PID target value
脉冲输入选择
Monitor Functions
6-108
Individual Functions
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
19 PID control disable (ON: PID control disabled) Yes Yes Yes Yes Yes
PID control integral reset (reset when reset command is input or when stopped during
30 Yes Yes Yes Yes Yes
PID control)
31 PID control integral hold (ON: Hold) Yes Yes Yes Yes Yes
Control Methods
Set- Open Open
ting Function Contents (100%) V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
B PID feedback Maximum output frequency Yes Yes Yes Yes Yes
C PID target value Maximum output frequency Yes Yes Yes Yes Yes
6-109
PID Input Methods
Enable PID control using constant b5-01, and set the PID target value and PID feedback value.
Set H3-05 or H3-09 to C (PID target value). Also, be sure to set H6-01 (pulse train input
Multi-Function Analog Ter-
function selection) to 1 (PID feedback value).
minal A2, or A3 Input
The negative inputs cannot be used for target values.
Set MEMOBUS bit 1 in register address 000FH to 1 (enable/disable PID target value
MEMOBUS register 0006H
from communications) to be able to use register number 0006H as the PID target value.
Pulse train input Set H6-01 to 2 (PID target value).
Adjust PID target value and PID feedback value using the following items.
• Analog input: Adjust using the analog input terminal gain and bias.
• Pulse train input: Adjust using pulse train scaling, pulse train input gain, and pulse train input bias.
INFO
6-110
Individual Functions
Suppressing Overshoot
If overshoot occurs, reduce derivative time (D), and increase integral time (I).
After adjustment
Time
Response
Before adjustment
After adjustment
Time
After adjustment
Time
6-111
Suppressing Short Cycle Vibration
If vibration occurs when the vibration cycle is short, and the cycle is almost identical to the derivative time (D)
set value, the differential operation is too strong. Shorten the derivative time (D) to suppress the vibration.
If vibration continues even when the derivative time (D) is set to 0.00 (D control disabled), reduce the propor-
tional gain (P), or increase the PID primary delay time constant.
After adjustment
Time
Setting Precautions
• In PID control, the b5-04 constant is used to prevent the calculated integral control value from exceeding a
specified amount. If the load changes rapidly, the machine may be damaged or the motor may stall because
of unpredictable response from the Inverter. In this case, reduce the set value.
• The b5-06 constant is used to prevent the arithmetic operation following the PID control calculation from
exceeding a specified amount. Set taking the maximum output frequency to be 100%.
• The b5-07 constant is used to adjust PID control offset. Set in increments of 0.1%, taking the maximum
output frequency to be 100%.
• Set the low pass filter time constant for the PID control output in b5-08. Enable this constant to prevent
machinery resonance from occurring when machinery adhesive abrasion is great, or rigidity is poor. In this
case, set the constant to be greater than the resonance frequency cycle. Increase this time constant to
reduce Inverter responsiveness.
• Using b5-09, you can invert the PID output polarity. Consequently, if you increase the PID target value,
you can apply this constant to applications to lower the Inverter output frequency.
• Using b5-10, you can apply gain to the PID control output. Enable this constant to adjust the amount of
compensation if adding PID control output to the frequency reference as compensation.
• When PID control output is negative, you can use constant b5-11 to invert the Inverter. When b1-04 (Pro-
hibition of Reverse Operation) is set to 1 (enabled), however, PID output limit is 0.
• With the Inverter, by setting an independent acceleration/deceleration time in constant b5-17, you can
increase or decrease the PID target value using the acceleration/deceleration time. The acceleration/
deceleration function (constant C1) used normally, however, is allocated after PID control, so depending
on the settings, resonance with PID control and hunting in the machinery may occur. If this happens,
reduce constant C1 until hunting does not occur, and maintain the acceleration/deceleration time using b5-
17. Also, you can disable the set value in b5-17 from the external terminals during operation using multi-
function input set value 34 (PID soft starter ON/OFF).
6-112
b1-01
Option Card 3
Frequency reference
using multi-step command
Serial Com b5-01=0 Enable/disable reverse operation
2 Frequency reference when PI output is negative
b5-01=3,4 Upper limit
(U1-01)
1 Fmax x109%
Terminal A1 PID OFF +
1 b5-11=0
Output frequency
b5-17 (U1-02)
PID Control Block
+
0 b5-01=1,2
d1-01 Lower limit 0
0 PID ON b5-11=1
PID SFS Cancel Multi-function input PID control cancel
signal is ON. PID is OFF under the Upper limit
d1-02 Fmax x109%
following conditions:
b5-01 = 0
During JOG command input
Lower limit
d1-16 -(Fmaxx109%)
feedback H3-05 or
H3-09=B
Pulse input terminal RP PID input volume PID output
H6-01=1 (U1-36) gain (b5-10)
+
+ Store integral using Integral rset using
P multi-function inputs multi-function inputs
+
b5-01=2,4 Proportional -1 Integral Integral (I)
+ time PID first order lag
gain (P) (I) time
b5-05 b5-04 time constant 0
b5-02 b5-03 PID Limit
Derivative (D) + b5-08 1
time + + + + +
Z -1 1 1
b5-01=1,3 T T
Select multi-function inputs
+ + + -1 +
PID input characteristics
PID feed-back Z -1 1
Z -1 PID upper
value (U1-24) limit PID offset
b5-01=1,3 b5-06 adjustment (b5-07)
+
b5-05 Select PID output
characteristics selection
Z-1 Derivative (b5-09)
b5-01=2,4
time
Individual Functions
6-113
PID Feedback Loss Detection
When performing PID control, be sure to use the PID feedback loss detection function. If PID feedback is lost,
the Inverter output frequency may accelerate to the maximum output frequency.
When setting b5-12 to 1 and the status of the PID feedback value detection level in b5-13 is insufficient and
continues for the time set in b5-14, an FbL (PID feedback reference lost) alarm will be displayed on the Digi-
tal Operator and Inverter operation will continue.
When b5-12 is set to 2, an FbL (PID feedback reference lost) error alarm will be displayed on the Digital
Operator, the error contact will operate, and Inverter operation will be stopped.
The time chart for PID feedback loss detection (set b5-12 to 2) is shown below.
Loss detection
level
(b5-13)
Time
No FbL
detection
FbL detection
Loss detection time Loss detection time
(b5-14) (b5-14)
PID Sleep
The PID sleep function stops the Inverter when the PID sleep function delay time continues while the PID
control target value is at an insufficient level to operate the PID sleep function. When the PID sleep delay time
continues and the PID control target value is above the PID sleep function operation level, Inverter operation
will automatically resume.
When PID control is disabled, the PID sleep function is also disabled. When using the PID sleep function,
select decelerate to stop or coast to stop as the stopping method.
The PID sleep time chart is shown below.
6-114
Individual Functions
Energy-saving
To perform energy saving, set b8-01 (Energy Saving Mode Selection) to 1. Energy-saving control can be per-
formed using both V/f control and vector control. The constants to be adjusted are different for each. In V/f
control, adjust b8-04 to b8-06, and in vector control, adjust b8-02 and b8-03.
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Energy-saving Select whether to enable or dis-
mode selection able energy-saving control.
b8-01 0 or 1 0 No A A A A A 1CCH
0: Disable
节能模式设定 1: Enable
Energy-saving
filter time con- Set the energy-saving filter time
0.00 to 0.50 s
b8-03 stant constant with the open-loop vec- Yes No No A A A 1CEH
10.0 *2
tor control method.
节能滤波时间
Power detection
filter time con-
stant Set the time constant for output 0 to
b8-05 20 ms No A A No No No 1D0H
power detection. 2000
电力检出滤波时
间
6-115
Adjusting Energy-saving Control
The method of adjustment during energy-saving control operations differs depending on the control method.
Refer to the following when making adjustments.
V/f Control
In V/f control method, the voltage for optimum motor efficiency is calculated and becomes the output voltage
reference.
• b8-04 (Energy-saving Coefficient) is set at the factory for motor use applied to the Inverter. If the motor
capacity differs from the motor applied to the Inverter, set the motor capacity in E2-11 (Motor Rated Out-
put). Also, adjust the output voltage in steps of 5 until it reaches minimum. The larger the energy-saving
coefficient, the greater the output voltage.
• To improve response when the load fluctuates, reduce the power detection filter time constant b8-05. If b8-
05 is set too small, however, motor rotations when the load is light may become unstable.
• Motor efficiency varies due to temperature fluctuations and differences in motor characteristics. Conse-
quently, control motor efficiency online to optimize efficiency by causing minute variations in voltage
using the search operation. Constant b8-06 (Search Operation Voltage Limiter) controls the range that con-
trol the voltage using the search operation. For 200 V Class Inverters, set the range to 100%/200 V, and for
400 V Class Inverters, set the range to 100%/400 V. Set to 0 to disable the search operation.
Vector Control
In vector control method, control the slip frequency so that motor efficiency is maximized.
• Taking the motor rated slip for the base frequency as optimum slip, calculate the optimum slip for motor
efficiency for each frequency. In vector control, be sure to perform autotuning, and set the motor rated slip.
• If the motor performs hunting when using energy-saving control in vector control, reduce the set value in
b8-02 (Energy-saving Gain), or increase the set value in b8-03 (Energy-saving Filter Time Constant).
6-116
Individual Functions
Related Constants
铁损
6-117
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Motor iron sat- Sets the motor iron saturation
uration coeffi- coefficient at 130% of magnetic
1.30 to
E2-12 cient 3 flux. 1.30 No No No A A A 328H
1.60
This constant is automatically set
饱和系数 3 during rotational autotuning.
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
For the motor no-load current, set E2-03 to a value less than that of E2-01.
* 3. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given. The upper limit depends on the setting of
E2-01.
Amount of motor rated slip = Motor rated frequency (Hz) - No. of rated rotations (min−1) x No. of motor
poles/120.
6-118
Individual Functions
6-119
Setting the V/f Pattern
In V/f control method, you can set the Inverter input voltage and the V/f pattern as the need arises.
Related Constants
Mid. output
frequency Frequency (Hz) 0.0 to 3.0 Hz
E1-07 No A A A No No 306H
400.0 *2
中间频率 To set V/f characteristics in a
straight line, set the same values for
Mid. output
E1-07 and E1-09. In this case, the 0.0 to
frequency 13.2 V
E1-08 setting for E1-08 will be disre- 255.0 No A A A No No 307H
voltage *1 *2
garded. *1
中间电压 Always ensure that the four fre-
quencies are set in the following
Min. output manner: 0.0 to
frequency 0.5 Hz
E1-09 E1-04 (FMAX) ≥ E1-06 (FA) > E1- 400.0 No Q Q Q A Q 308H
*2
最低输出频率 07 (FB) ≥ E1-09 (FMIN) *5
Min. output
frequency 0.0 to
2.4 V
E1-10 voltage 255.0 No A A A No No 309H
*1 *2
*1
最低输出电压
Mid. output
Set only to fine-adjust V/f for the
frequency 0.0 to
output range. Normally, this setting 0.0 V
E1-12 voltage 2 255.0 No A A A A A 30BH
is not required. *1
*3
中间电压 2
6-120
Individual Functions
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. E1-13 is set to the same value as E1-05 by autotuning.
* 5. The setting range for open-loop vector 2 control is 0 to 132.0.
If selecting a fixed V/f pattern (E1-03 = 0 to E) in V/f control the values of the max. voltage (E1-05), the mid.
Output frequency voltage (E1-08), and the min. output frequency voltage (E1-10) will change if the value for
the input voltage setting (E1-01) is changed.
6-121
Setting V/f Pattern
Set the V/f pattern in E1-03 when using V/f control (with or without a PG). There are two methods of setting
the V/f pattern: Select one of the 15 pattern types (set value: 0 to E) that have been set beforehand, or set a
user-defined V/f pattern (set value: F).
The factory setting for E1-03 is F. The contents of E1-03 when factory-set to F are the same as when E1-03 is
set to 1.
To select one of the existing patterns, refer to the following table.
Set
Characteristic Application Specifications
Value
0 (F) 50 Hz specifications
When you select these patterns, the values of constants E1-04 to E1-10 are changed automatically. There are
three types of values for E1-04 to E1-10, depending on the Inverter capacity.
• 0.4 to 1.5 kW V/f pattern
• 2.2 to 45 kW V/f pattern
• 55 to 300 kW V/f pattern
The characteristics diagrams for each are shown in the following pages.
6-122
Individual Functions
(1.2)
6-123
2.2 to 45 kW V/f Pattern
The diagrams show characteristics for a 200-V class motor. For a 400-V class motor, multiply all voltages by 2.
• Constant Torque Characteristics (Set Value: 0 to 3)
(1.2)
6-124
Individual Functions
(1.2)
6-125
When E1-03 is set to F (User-defined V/f pattern), you can set constants E1-04 to E1-10. If E1-03 is set to
anything other than F, you can only refer to constants E1-04 to E1-10. If the V/f characteristics are linear, set
E1-07 and E1-09 to the same value. In this case, E1-08 will be ignored.
E1-05
(VMAX)
E1-13
(V Base)
E1-08
(VC)
E1-10
(VMIN)
Frequency (Hz)
E1-09 E1-07 E1-06 E1-04
(FMIN) (FB) (FA) (FMAX)
Setting Precautions
When the setting is to user-defined V/f pattern, beware of the following points.
• When changing control method, constants E1-07 to E1-10 will change to the factory settings for that
control method.
• Be sure to set the four frequencies as follows:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
6-126
Individual Functions
Torque Control
With flux vector control or open-loop vector 2 control, the motor's output torque can be controlled by a torque
reference from an analog input. To control torque, set d5-01 to 1 or set multi-function contact inputs H1-
to 71 (Speed/Torque control) and turn ON the contact.
Related Constants
6-127
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Speed/torque Set the delay time from inputting
control the multi-function input “speed/
switching timer torque control change” (from ON
to OFF or OFF to ON) until the
control is actually changed in ms
units.
This function is enabled when the
0 to
d5-06 multi-function input “speed/ 0 No No No No A A 29FH
1000
torque control change” is set. In
控制切换时间 the speed/torque control switch-
ing timer, the analog inputs hold
the values of when the “speed/
torque control change” changes.
Always be sure to allow time for
this process to finish completely.
Rotation 0: Disabled
direction limit 1: Enabled
operation Usually, use a setting of 1
selection (enabled).
d5-07 0 or 1 1 No No No No No A 2A6H
Be sure to enable this setting
when rotating the motor in the
旋转方向限制
动作 same direction as the speed limit
(winding operation).
Signal level 0: 0 to 10V
selection (ter- 1: -10 to 10V
H3-04 minal A3) 0 or 1 0 No A A A A A 413H
[11-bit + polarity (positive/
端子 A3 信号电平 negative) input]
Multi-function
analog input
(terminal A3) Select multi-function analog input
H3-05 function selec- 0 to 1F 2 No A A A A A 414H
function for terminal A3.
tion
端子 A3 设定
端子 A2 设定
6-128
Individual Functions
Monitor Function
Name Control Methods
Con- Output Signal Level Open Open MEMO
Min. V/f Loop Flux Loop BUS
stant Description During Multi-Func- Unit Reg-
Number Display V/f with Vec- Vec- Vec-
tion Analog Output PG tor tor tor ister
1 2
Torque refer- Monitor in internal torque
ence 10 V: Motor rated torque 0.1
U1-09 reference value for vector No No A A A 48H
(-10 to 10 V possible) %
转矩指令 control.
6-129
Inputting Torque References and Torque Reference Directions
The torque reference can be changed according to an analog input by setting H3-09 (Multi-function analog
input terminal A2 selection) or H3-05 (Multi-function analog input terminal A3 selection) to 13 (torque refer-
ence) or 14 (torque compensation). The torque reference input methods are listed in the following table.
Application Precautions
If the analog signal input level is 0 to 10 V or 4 to 20 mA, a forward torque reference will not be applied. To
apply reverse torque, use an input level of -10 V to 10 V or switch the direction using a multi-function input
set to 78 (polarity Reverse Command for external torque reference).
6-130
Individual Functions
Torque compensation
from analog input
Speed limiter
Speed feedback
Application Precautions
There are two ways to set a speed limit: using an input from an analog input terminal and setting a speed limit
in d5-04. The inputs methods for a speed limit are listed in the following table.
Voltage input (-10 to 10 V) The value will be added to the value input
on A1 to determine the speed limit.
b1-01 = 0
Set H3-03 to 0 if the speed limit input on
Between A2 and AC H3-08 = 1
A2 is always to be positive.
H3-09 = 1
Turn OFF (V side) pin 2 of DIP switch S1
on the terminal board.
The value will be added to the value input
b1-01 = 0
on A1 to determine the speed limit.
Current input (4 to 20 mA) Between A2 and AC H3-08 = 2
Turn ON (I side) pin 2 of DIP switch S1
H3-09 = 1
on the terminal board.
If H3-09 is set to 0, the sum of the input
Option board (AI-4B) b1-01 = 3 between TC2 and TC4 will be added the
Between TC1 and TC4
(-10 to 10 V) F2-01 = 0 input between TC1 and TC4 to determine
the speed limit.
6-131
The direction in which speed is controlled is determined by the sign of the speed limit signal and the direction
of the Run Command.
• Positive voltage applied: The speed in the forward direction will be limited for forward operation.
IMPORTANT • Negative voltage applied: The speed in the reverse direction will be limited for reverse operation.
If the direction of motor rotation and the command direction are not the same, speed will be limited to 0 as
long as b5-05 is set to 0.
Forward torque
ΔN %
Winding Operation
In a winding operation, the line (speed) and torque generated by the motor are in the same direction. For the
winding operation, both the speed limit and the torque reference input are positive. The motor will accelerate
when the torque reference input is larger than the load and will decelerate when it is smaller than the load. If
the motor turns faster than the speed limit, a negative compensation value is output from the speed limiter cir-
cuit. When the speed then drops below the speed limit, a positive compensation value is output. The torque
compensation is proportional to the ASR proportional gain. When the sum of the torque reference and the
torque compensation output by the speed limiter is the same as the actual load, the motor will stop accelerating
and run at a constant speed.
6-132
Individual Functions
Rewinding Operation
In a rewinding operation, the line (speed) and torque generated by the motor are in the opposite directions. (In
this example, we’ll assume that the line speed is positive and the torque reference input is negative.) For the
rewinding operation, the speed limit is positive and the torque reference input is negative. If the motor turns
faster than the speed limit, a negative compensation value is output from the speed limiter circuit. If the motor
is rotating in reverse, a negative compensation value is output. If the speed is 0 or is below the speed limit, a 0
compensation value is output. In this way, the output from the speed limiter is used to maintain the motor
speed between 0 and the speed limit. When the sum of the torque reference and the torque compensation out-
put by the speed limiter is the same as the actual load, the motor will stop accelerating and run at a constant
speed.
Winding Operation Rewinding Operation
Line direction N T N T Line direction
T N T N
X X X X
Configuration
Normal Rotation
Forward Reverse Forward Reverse
Direction
Torque Reference
Polarity (TREF)
Speed Limit
Polarity (SLIM)
Torque Torque Torque
Torque Torque Torque
Torque Torque limit limit
limit ΔN limit
TREF
TREF
(d5-05) ΔN
(d5-05)
SLIM
SLIM
0 Speed
0 Speed
0 0 Speed SLIM
SLIM Speed ΔN
Generated Torque (d5-05) Torque (d5-05)
TREF TREF limit
Torque
Torque ǍN Torque
limit
limit limit
Rotation Direction Limit Operation Selection (Valid Only in Open-loop Vector 2 Con-
trol)
In applications where the machine is not rotated in the opposite direction to the sign of the speed limit (i.e., in
winding operation), use with d5-07 set to 1. If the sign of the calculated speed is the opposite to that of the
speed limit, a torque will be output to prevent the motor from accelerating in the opposite direction.
6-133
Setting the Torque Compensation
Set multi-function analog input A2 or A3 to torque compensation (setting 14). When the amount of torque loss
for mechanical loss or other factor at the load is input to one of these terminals, it is added to the torque refer-
ence to compensate for the loss. The direction of torque will be as follows:
• Positive voltage (current): Torque compensation reference for forward motor rotation (counterclockwise as
viewed from the motor output axis).
• Negative voltage: Torque compensation reference for reverse motor rotation (clockwise as viewed from
the motor output axis).
Since the polarity of the voltage input determines the direction, only forward torque compensation can be
input when the 0 to 10 V or 4 to 20 mA signal level has been selected. If you want to input reverse torque com-
pensation, be sure to select the -10 to 10 V signal level.
6-134
Individual Functions
Application Precautions
• The frequency reference (during speed control) is set in b1-01. The speed limit during torque control is set
in d5-03.
• If the torque reference has been assigned to a multi-function analog input, terminal A2, or terminal A3, the
input function changes when the control method is switched between torque control and speed control.
During speed control: The multi-function analog input terminal is used as the torque limit input.
During torque control: The multi-function analog input terminal is used as the torque reference input.
• When the Run Command turns OFF, the control method when stopped will be for speed control. Even
from the torque control method, the system will automatically change to speed control and decelerate to a
stop when the Run Command turns OFF.
• When A1-02 (control method selection) is set to 3 (flux vector control), the speed/torque change command
(a setting of 71) can be set for a multi-function input (H1-01 to H1-10) to switch between speed and torque
control during operation. An example is shown below.
CLOSED CLOSED
OPEN OPEN
Speed/torque change signal
(terminal S8 input)
Run
6-135
Speed Control (ASR) Structure
Speed control (ASR) during vector control adjusts the torque reference so that the deviation between the
speed reference and the estimated speed (PG feedback or speed estimator) is 0. Speed control (ASR) during V/
f control with a PG adjusts the output frequency so that the deviation between the speed reference and the esti-
mated speed (PG feedback or speed estimator) is 0. The following block diagram shows the structure of the
speed control for vector or V/f control with a PG.
Torque limits
C5-01, C5-03
+ + Torque reference
Frequency Primary
P filter
reference
− I +
I limit
C5-06
(C5-10) L7-01 to L7-04
Detected speed
C5-02, C5-04 C5-08
Estimated speed
Speed Control Block Diagram for Vector Control
+ Output frequency
Frequency
reference
+
Limit
+ +
− Change
Detected speed
rate
P
+
limiter
I
C5-01
C5-05
C5-03
C5-02, C5-04
Related Constants
ASR inte-
gral (I) time 0.000 0.500
Sets the integral time of the speed loop
C5-02 1 to Yes No A No A A 21CH
(ASR) in 1-second units.
10.000 s*1
积分时间 1
ASR propor-
tional (P) Usually setting is not necessary. 0.00 to
20.00
C5-03 gain 2 Set to change the rotational speed gain. 300.00 Yes No A No A A 21DH
*1
P, I *2
比例增益 2 P=C5-01
I=C5-02
ASR inte-
P=C5-03 0.000
gral (I) time I=C5-04 0.500
C5-04 2 to Yes No A No A A 21EH
0 E1-04 Motor speed (Hz) 10.000 s*1
积分时间 2
6-136
Individual Functions
ASR switch-
Set the frequency for switching between
ing fre-
Proportion Gain 1, 2 and Integral Time 1,
quency 2 in Hz units. 0.0 to
C5-07 0.0 Hz No No No No A A 221H
Speed control (ASR) proportional gain 400.0
增益切换频率 switching for a multi-function input takes
priority.
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
Speed control disable setting for V/f control with PG
D OFF: Use speed control V/f control with PG No Yes No No No
ON: Do not use speed control for V/f control with PG
Speed control integral reset
E No No No Yes Yes
Enables switching between PI and P control for the speed control loop.
Speed control (ASR) proportional gain switch (switching between C5-01 and C5-03)
77 OFF: Use proportional gain in C5-01 No No No Yes Yes
ON: Use proportional gain in C5-03
6-137
Speed Control (ASR) Gain Adjustment for Vector Control
Use the following procedure to adjust C5-01 and C5-03 with the mechanical system and actual load con-
nected.
NO
Fine Adjustments
When you want even finer gain adjustment, adjust the gain while observing the speed waveform. Constant set-
tings like those shown in the following table will be necessary to monitor the speed waveform.
Constant
Name Setting Explanation
No.
H4-01 Multi-function analog output 1 terminal FM monitor selection 2
Settings that allow multi-func-
H4-02 Multi-function analog output 1 terminal FM output gain 1.00 tion analog output 1 to be used
to monitor the output frequency.
H4-03 Multi-function analog output 1 terminal FM bias 0.0
H4-04 Multi-function analog output 2 terminal AM monitor selection 5
Settings that allow multi-func-
H4-05 Multi-function analog output 2 terminal AM output gain 1.00 tion analog output 2 to be used
to monitor the motor speed.
H4-06 Multi-function analog output 2 terminal AM bias selection 0.00
H4-07 Multi-function analog output 1 terminal signal level selection 1 Settings that allow a -10 to 10 V
H4-08 Multi-function analog output 2 terminal signal level selection 1 signal range to be monitored.
The multi-function analog outputs have the following functions with these constant settings.
• Multi-function analog output 1 (terminal FM): Outputs Inverter's output frequency (-10 to 10 V).
• Multi-function analog output 2 (terminal AM): Outputs actual motor speed (-10 to 10 V).
Terminal AC is the multi-function analog output common.
We recommend monitoring both the output frequency and the motor speed to monitor the response delay or
deviations from the reference value, as shown in the following diagram.
6-138
Individual Functions
Motor speed
Time
Motor speed
Time
6-139
Different Gain Settings for Low-speed and High-speed
Switch between low-speed and high-speed gain when oscillation occurs because of resonance with the
mechanical system at low speed or high speed. The proportional gain P and integral time I can be switched
according to the motor speed, as shown below.
P = C5-01
P, I
I = C5-02
P = C5-03
I = C5-04 (Low speed)
ON
ASR Gain Switch signal
(a multi-function input)
OFF
Proportional gain
Proportional gain (P)
determined
by motor speed.
C5-02 C5-02
6-140
Individual Functions
P and I setting
P = C5-01
I = C5-02
P = C5-03
I = C5-04
Fig 6.76 Speed Control Gain Integral Time Adjustment for V/f Control with PG
Fine Adjustments
When you want even finer gain adjustment, adjust the gain while observing the speed waveform. The adjust-
ment method is the same as that for vector control.
Enable integral operation during acceleration and deceleration (by setting F1-07 to 1) when you want the
motor speed to closely follow the frequency reference during acceleration and deceleration. Reduce the setting
of C5-01 if overshooting occurs during acceleration, and reduce the setting of C5-03 and increase the setting
of C5-04 if undershooting occurs when stopping. If overshooting and undershooting cannot be eliminated by
adjusting only the gain, reduce the value of C5-05 speed control and reduce the limit of the frequency refer-
ence compensation value.
6-141
Increasing the Speed Reference Response (Feed Forward Control)
Use feed forward control to increase the responsiveness to speed references. This function is effective for
machines for which the ASR gain cannot be increased to a large value because doing so would result in vibra-
tions. There is also the additional effect of making the system less prone to overshoot. This function is valid
only in flux vector and open-loop vector 2 controls.
Overshooting when acceleration completed
is being suppressed
Overshooting
Rotation Rotation
speed speed
(min-1) (min-1)
Time(s) Time(s)
Feed forward control Conventional speed control
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Feed forward
control selec- Select the feed forward control.
0
N5-01 tion 0: Disabled 0 or 1 No No No No A A 5B0H
*1
1: Enabled
FF 控制选择
6-142
Individual Functions
Feed
Frequency Secondary
forward Torque limit
reference U1-44 current
controller
reference
Primary
Speed controller (ASR)
filter
C5-06
L7-01 to L7-04
(C5-10)
U1-05
Detected speed
(Calculated speed)
Fig 6.78 Structure of Speed Controller (ASR) and Feed Forward Control
Setting Precautions
• When N5-02 (Motor acceleration time) is not properly set, the acceleration time may not increase. The fac-
tory setting of N5-02 depends on the Inverter capacity. When the Inverter capacity is different from the
motor capacity, calculate an appropriate acceleration time using the equation given in N5-02 of Chapter 5
User Constants or set the time that corresponds to the motor capacity referring to Factory Settings that
Change with the Control Method (A1-02) (Page 5-86)
• When setting the feed forward proportional gain (N5-03), take the inertia of the motor to be equivalent to
1. If the speed reference response is slow, increase the feed forward proportional gain (N5-03). If over-
shoot occurs with the actual speed, or if a negative torque reference is output when acceleration is com-
pleted, reduce the feed forward proportional gain (N5-03).
• When using the droop control function (i.e., if b7-01 is not set to 0.0), disable feed forward control (i.e., set
N5-01 to 0).
The balance of the load is very different with different amounts of slip.
TA TA
Load torque Load torque
TB TB
6-143
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Droop control Sets the slip as a percentage of
gain maximum frequency when the
maximum output frequency is
specified and the rated torque 0.0 to
b7-01 0.0 Yes No No No A A 1CAH
occurs. 100.0
DROOP 增益 Droop-control is not performed
when the setting is 0.0.
Setting Precautions
• Droop control is disabled if b7-01 is set to 0.0.
• Set b7-01 to the amount of slip as the percentage of slip when the maximum output frequency is input and
the rated torque is generated.
• Constant b7-02 is used to adjust the responsiveness of droop control. Increase this setting if oscillation or
hunting occur.
• Disable the feed forward control (N5-01 = 0) when using the droop control function.
Torque
b7-01
100%
Speed
0 Speed reference
6-144
Individual Functions
Zero-servo Function
The zero-servo function holds the motor when the motor is stopped in what is call a zero-servo status. This
function can be used to stop the motor even with an external force acts on the motor or the analog reference
input is offset.
The zero-servo function is enabled when one of the multi-function inputs (H1-01 to H1-10) is set to 72 (zero-
servo command). If the zero-servo command is ON when the frequency (speed) reference falls below the zero-
speed level, a zero-servo status is implemented.
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Zero-speed Used to set the frequency which
level (DC injec- starts DC injection braking in
tion braking units of Hz when deceleration to
starting fre- stop is selected.
0.0 to
b2-01 quency) When b2-01 is less than E1-09, 0.5 Hz No A A A A A 189H
10.0
E1-09 becomes the DC injection
直流制动开始频
braking starting frequency.
率 (For flux vector control, zero-
speed control from B2-01)
Zero-servo gain Adjust the strength of the zero-
servo lock.
Enabled when the zero-servo
command is set for a multi-func-
tion input. When the zero-servo
command has been input and the
frequency reference drop below 0 to
b9-01 5 No No No No A No 1DAH
零伺服增益 excitation level (b2-01), a posi- 100
tion control loop is created and
the motor stops. Increasing the
zero-servo gain in turn increases
the strength of the lock. Increas-
ing it by too much will cause
oscillation.
6-145
Multi-function Contact Input Functions (H1-01 to H1-10)
Control Methods
Set- Open Open
ting Function V/f Loop Flux Loop
V/f with Vec- Vec- Vec-
Value PG tor tor tor
1 2
72 Zero-servo command (ON: Zero-servo) No No No Yes No
To output the zero-servo status externally, assign the Zero-servo End signal (setting 33) to one of the multi-
function outputs (H2-01 to H2-05).
Monitor Function
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Zero-servo (Can-
movement Shows the number of PG pulses
not be
U1-35 pulses times 4 for the movement range 1 No No No A No 62H
out-
when stopped at zero.
零伺服移动脉冲 put.)
Time Chart
A time chart for the zero-servo function is given in Time Chart for Zero-servo.
ON OFF
Run Command
Excitation level
b2-01
Motor speed
6-146
Individual Functions
Application Precautions
• Be sure to leave the Run Command input ON. If the Run Command is turned OFF, the output will be inter-
rupted and the zero-servo function will become ineffective.
• The holding force of the zero-servo is adjusted in b9-01. The holding force will increase if the value of the
setting is increased, but oscillation and hunting will occur if the setting is too large. Adjust b9-01 after
adjusting the speed control gain.
• The zero-servo detection width is set as the allowable position offset from the zero-servo start position. Set
4 times the number of pulses from the PG.
• The Zero-servo End signal will go OFF when the zero-servo command is turned OFF.
Do not lock the servo for extended periods of time at 100% when using the zero-servo function. Inverter
errors may result. Extended periods of servo lock can be achieved by ensuring that the current during the ser-
volock is 50% or less or by increasing the Inverter capacity.
IMPORTANT
6-147
Digital Operator Functions
This section explains the Digital Operator functions.
Related Constants
6-148
Digital Operator Functions
Cumulative
operation time Sets the cumulative operation
setting time in hour units. 0 to
o2-07 0 hr No A A A A A 50BH
Operation time is calculated from 65535
累积运行时间设 the set values.
定
6-149
Setting Precautions
If selecting monitor constants other than U1-01 (Frequency Reference), U1-02 (Output Frequency), and U1-
03 (Output Current), first select the monitor items to be displayed in o1-01, and then set o1-02 to 4.
Setting the Frequency Reference using the UP and DOWN Keys without Using the
Enter Key
Use this function when inputting frequency references from the Digital Operator. When o2-05 is set to 1, you
can increment and decrement the frequency reference using the UP and DOWN Keys without using the Enter
Key.
For example, enter the Run Command using a 0 Hz reference, and then continuously press the UP Key to
increment the frequency reference by 0.01 Hz only for the first 0.5 s, and then by 0.01 Hz every 80 ms for 3 s
thereafter. Press and hold down the UP Key for 3 s minimum to reach the maximum output frequency 10 s
after that. The frequency reference that has been set will be stored in memory 5 s after the UP or DOWN Keys
are released.
6-150
Digital Operator Functions
Copying Constants
The Digital Operator can perform the following three functions using the built-in EEPROM (non-volatile
memory).
• Store Inverter constant set values in the Digital Operator (READ)
• Write constant set values stored in the Digital Operator to the Inverter (COPY)
• Compare constant set values stored in the Digital Operator with Inverter constants (VERIFY)
Related Constants
Read permitted
selection 0: Read prohibited
o3-02 0 or 1 0 No A A A A A 516H
1: Read permitted
读出许可选择
6-151
Storing Inverter Set Values in the Digital Operator (READ)
To store Inverter set values in the Digital Operator, make the settings using the following method.
Set 03-02 (Read permitted selection) to 1 (read permitted).
2 Press the DATA/ENTER Key, and select the constants monitor display.
Display o3-01 (Copy Function Selection) using the Increment Key and Decrement
3
Key.
4 Press the DATA/ENTER Key, and select the constants setting display.
6 Set the changed data using the DATA/ENTER Key. The READ function will start.
7 If the READ function ends normally, End is displayed on the Digital Operator.
An error may occur while saving to memory. If an error is displayed, press any key to cancel the error display
and return to the o3-01 display.
Error displays and their meanings are shown below. (Refer to Chapter 7 Errors when Using the Digital Oper-
ator Copy Function.)
Error Display Meaning
6-152
Digital Operator Functions
Tried to write constants to EEPROM on the Digital Operator, but unable to perform write
operation.
Writing Constant Set Values Stored in the Digital Operator to the Inverter (COPY)
To write constant set values stored in the Digital Operator to the Inverter, make the settings using the follow-
ing method.
2 Press the DATA/ENTER Key, and select the constants monitor display.
Display o3-01 (Copy Function Selection) using the Increment Key and Decrement
3
Key.
4 Press the DATA/ENTER Key, and select the constants setting display.
6 Set the changed data using the DATA/ENTER Key. The COPY function will start.
7 If the COPY function ends normally, End is displayed on the Digital Operator.
6-153
Table 6.2 COPY Function Procedure(Continued)
Step
Digital Operator Display Explanation
No.
During the copy operation, errors may occur. If an error is displayed, press any key to cancel the error display
and return to the 03-01 display.
Error displays and their meanings are shown below. (Refer to Chapter 7 Errors when Using Digital Operator
Copy Function.)
Error Display Meaning
Inverter capacity with which you are trying to copy, and the Inverter capacity stored in
the Digital Operator are different.
The Inverter control method in which you are trying to copy, and the Inverter control
method stored in the Digital Operator are different.
Comparison between the constant written to the Inverter and the constant in the Digital
Operator shows they are different.
After copying has ended, comparison between the sum value of the Inverter constant area
and the sum value of the Digital Operator constant area shows they are different.
Comparing Inverter Constants and Digital Operator Constant Set Values (VERIFY)
To compare Inverter constants and Digital Operator constant set values, make the settings using the following
method.
2 Press the DATA/ENTER Key, and select the constants monitor display.
6-154
Digital Operator Functions
Display o3-01 (Copy Function Selection) using the Increment Key and Decrement
3
Key.
4 Press the DATA/ENTER Key, and select the function setting display.
Set the changed data using the DATA/ENTER Key. The VERIFY function will
6
start.
7 If the VERIFY function ends normally, End is displayed on the Digital Operator.
An error may occur during the comparison. If an error is displayed, press any key to cancel the error display
and return to the o3-01 display. Error displays and their meanings are shown below. (Refer to Chapter 7
Errors when Using Digital Operator Copy Function.)
Error Display Meaning
Verify error (Settings in the Digital Operator and the Inverter do not match).
Application Precautions
• When using the copy function, check that the following settings are the same between the Inverter and the
Digital Operator.
• Inverter product and type • Inverter capacity and voltage
• Software number • Control method
• Use the copy function off-line or with a communications option board removed.
• A CPF03 fault (EEPROM error) can occur if the power is shut down while the Inverter constants are being
copied. Do not shut down the power while copying the constants.
6-155
Prohibiting Writing Constants from the Digital Operator
If you set A1-01 to 0, you can refer to and set the A1 and A2 constant groups, and refer to drive mode, using
the Digital Operator.
If you set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selec-
tion) to 1B (write constants permitted), you can write constants from the digital operator when the terminal
that has been set is ON. When the set terminal is OFF, writing constants other than the frequency reference is
prohibited. You can, however, reference constants.
Setting a Password
When a password is set in A1-05, if the set values in A1-04 and A1-05 do not match, you cannot refer to or
change the settings of constants A1-01 to A1-03, or A2-01 to A2-32.
You can prohibit the setting and referencing of all constants except A1-00 by using the password function in
combination with setting A1-01 to 0 (Monitor only).
Related Constants
6-156
Digital Operator Functions
Setting Precautions
Constant A1-05 cannot be displayed using normal key operations. To display A1-05, hold down the RESET
Key and press the MENU Key while A1-04 is displayed.
Related Constants
6-157
Options
This section explains the Inverter option functions.
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
PG constant Sets the number of PG (pulse gen-
erator or encoder) pulses. 0 to
F1-01 600 No No Q No Q No 380H
PG 脉冲数 Sets the number of pulses per 60000
motor revolution.
6-158
Options
Overspeed
detection level Sets the overspeed detection 0 to
F1-08 115% No No A No A A 387H
method. 120
过速检出值 Frequencies above that set for F1-
Overspeed 08 (set as a percentage of the
maximum output frequency) that
detection delay
continue to exceed this frequency 0.0 to
F1-09 time 0.0 s* No No A No A A 388H
for the time set in F1-09 are 2.0
OS 过速检出 detected as overspeed faults.
时间
* When the control method is changed, the factory setting will change. The flux vector factory setting is given.
6-159
Using PG Speed Control Board
There are four types of PG Speed Control Board that can be used in V/f control with PG.
• PG-A2: A-phase (single) pulse input, compatible with open collector or complimentary outputs.
• PG-B2: A/B-phase pulse input, compatible with complimentary outputs.
• PG-D2: A-phase (single) pulse input, compatible with line drivers.
• PG-X2: A/B/Z-phase pulse input, compatible with line drivers.
There are two types of PG Speed Control Boards that can be used for flux vector control.
• PG-B2: A/B phase pulse inputs, complementary outputs
• PG-X2: A/B/Z phase pulse inputs, line driver outputs
For the connection diagram, refer to page 2-35 to 2-37.
Inverter
Motor PG (encoder)
Forward
Command
Pulse output
A-phase driven when set value = 0 B-phase driven when set value = 1
A-phase A-phase
B-phase B-phase
Example: Forward rotation of standard Yaskawa motor (PG used: Samtack (KK))
Yaskawa standard PG used is A-phase driven (CCW) when motor rotation is forward.
Generally, PG is A-phase driven when rotation is clockwise (CW) see from the input axis. Also, motor rota-
tion is counter-clockwise (CCW) seen from the output side when Forward Commands are output. Conse-
quently, when motor rotation is forward, PG is normally A-phase driven when a load is applied, and B-phase
driven when a load is not applied.
6-160
Options
Speed of motor rotations (min−1.) = No. of input pulses from PG × 60 / F1-01 × F1-13 (No. of gear teeth on
load side) / F1-12 (No. of gear teeth on motor side)
If F1-07 is set to 1, overshoot or undershoot may occur easily immediately after acceleration and decelera-
tion. To minimize the possibility of overshoot or undershoot occurring, set F1-07 to 0.
IMPORTANT
The dividing ratio can be set within the following range: 1/32 ≤ F1-06 ≤ 1. For example, if the dividing ratio is
1/2 (set value 2), half of the number of pulses from the PG are monitor outputs.
6-161
Using Digital Output Boards
There are two types of Inverter digital output boards:
• DO-02C
Relay contact output (DPDT contact)
• DO-08
6 photocoupler output channels (shared commons)
2 (independent) relay contact output channels (NC contact)
Photocoupler TD5
CH1 Photocoupler
+24 V TD6
Inverter CH2
TD
1 control TD7
Inverter panel 3CN 3CN CH3
control NC NO 2
CH1
panel 3CN 3 TD8 CH4
3CN
4 TD9 CH5
NC NO 5
CH2 TD10 CH6
6 TD11 COM (0 V common)
TD1
Relay contact TD2 CH7
TD3 Relay contact
DO-02C Digital Output Card TD4 CH8
Related Constants
6-162
Options
F5-09 Set to 0
Terminal
Set Value Output Details
Number
TD5-TD11 Overcurrent (SC, OC, GF)
TD6-TD11 Overvoltage (OV)
TD7-TD11 Inverter overload (OL2)
6-163
F5-09 Set to 1
Terminal
Set Value Output Details
Number
TD5-TD11 bit 0
F5-09 Set to 2
Output depends on the settings in F5-01 to F5-08.
6-164
Options
Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Bi-polar or uni- Sets the functions for channel 1 to
polar input 3 that are effective when the AI-
selection 14B Analog Reference Board is
used.
0: 3-channel individual (Chan-
nel 1: terminal A1, Channel 2:
terminal A2, Channel 3: termi-
F2-01 nal A3) 0 or 1 0 No A A A A A 38FH
1: 3-channel addition (Addition
AI14 动作选择 values are the frequency refer-
ence)
When set to 0, select 1 for b1-01.
In this case the multi-function
input “Option/Inverter selection”
cannot be used.
Setting Precautions
Always set b1-01 (Reference selection) to 1 (control circuit terminal) when using the AI-14B for three chan-
nels of independent inputs. When this is done, H1-01 to H1-10 (multi-function contact inputs) cannot be set to
2 (Option/Inverter selection).
Related Constants
6-165
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Frequency units Sets the units that will be set and
of reference set- displayed for the frequency refer-
ting and moni- ence and frequency monitor.
tor 0: 0.01 Hz units
1: 0.01% units (Maximum
output frequency is 100%)
2 to 39:
min−1 units (Sets the motor
poles.)
40 to 39999:
User desired display
Set the desired values for setting 0 to
o1-03 0 No A A A A A 502H
and display for the max. output 39999
frequency.
频率指令单位
Selecting Input Terminal Functions for the DI-16H2 Digital Reference Board
The frequency reference from the DI-16H2 Board is determined by the setting of F3-01 and the 12/16-bit
switch on the option board. The possible settings are listed in the following table.
6-166
Options
12-bit Binary 16-bit Binary 3-digit BCD with 4-digit BCD with 5-digit BCD with-
with Sign with Sign Sign Sign out Sign
Terminal Pin No.
F3-01 = 7 F3-01 = 7 F3-01 = 0 to 5 F3-01 = 0 to 5 F3-01 = 6
S1: 12 bit S1: 16 bit S1: 12 bit S1: 16 bit S1: 16 bit
1 Bit 1 (20) Bit 1 (20) 1 1 2
BCD digit 1
2 Bit 1 (21) Bit 1 (21) 2 BCD digit 1 2 BCD digit 1 4
(0, 2, 4, 6, 8)
(0 to 9) (0 to 9)
3 Bit 1 (22) Bit 1 (22) 4 4 8
Application Precautions
• The maximum frequency (100% speed) reference will be used when the binary input is set (setting: 6 or 7)
and all bits are 1.
• Setting F3-01 to 6 is valid only when the D1-16H2 is used. Using this setting, a frequency from 0.00 to
399.8 Hz can be set in BCD. The sign bit is used as a data bit, so only positive (plus) data can be set. Also,
the digit starts from 0, so the minimum setting is 0.02 Hz.
Selecting the Input Terminal Function for a DI-08 Digital Reference Board
The frequency reference from a DI-08 Board is determined by the setting of F3-01, as shown in the following
table.
6-167
8-bit Binary with Sign 2-digit BCD with Sign
Terminal Pin No.
F3-01 = 7 F3-01 = 0 to 5
1 Bit 1 (20) 1
4 Bit 1 (23) 8
5 Bit 1 (24) 1
TC 6 Bit 1 (25) 2 BCD digit 2
7 6 4 (0 to 15)
Bit 1 (2 )
8 Bit 1 (27) 8
9 Sign signal
10 SET (read) signal
11 Reference common signal (0 V)
Application Precautions
The DI-08 will not function if F3-01 is set to 6
6-168
Options
6-169
Using Inverters for Elevating Machines
This section describes precautions to be observed when using the Varispeed G7 for elevating machines
such as elevators and cranes.
When performing trial operation, enable Current alarm function (L8-41 =1), and be sure to make adjustments
to the braking sequence by using Peak hold functions (refer to Current Alarm Function and Peak Hold Cur-
rent Monitoring Function in Chapter 6 ) so that the startup current is less than 150% of the Inverter rated cur-
IMPORTANT rent.
IMPORTANT
* 1. This example shows multi-function output terminals M1-M2 used for the holding brake ON/OFF signal.
Do not set H2-01 to 0 (During run).
* 2. This is the standard setting range for open-loop vector 1 control. For V/f control, set to approximately the motor rated slip frequency +0.5 Hz.
If the set value is too low, the motor torque is insufficient and the load may slip when the brake is applied. Be sure to set L4-01 to a value larger than that
of E1-09 (Min. output frequency) and larger than that of L4-02 shown in Figure 6.84. If the set value is too large, the motor may not run smoothly when
it starts running.
* 3. The hysteresis in frequency detection 2 can be adjusted (from 0.1 to 0.5 Hz) by L4-02 (speed agree detection width). Change the setting to approxi-
mately 0.1 Hz if there are drops while stopping.
* 4. When using frequency detection 2, set L4-01 before H2-01. If H2-01 is set before L4-01, the holding brake will engage while stopping. Normally, use
frequency detection 5 in which a holding brake signal is OFF when the Inverter is baseblocked.
L4-01
L4-02
Output frequency Time
ON OFF
Frequency detection 2
Fig 6.84
6-170
Using Inverters for Elevating Machines
Note Design the sequence so that the holding brake contact is open when the sequence operation conditions are satisfied and the contact between M1 and M2
is closed (ON).
Make sure that the holding brake contact is closed when the emergency stop signal or Inverter fault contact output signal is ON.
Fig 6.85 Brake ON/OFF Sequence Circuit Configuration
Time Chart
The brake ON/OFF sequence time charts are shown in Figs. 6.86 and 6.87.
OFF ON
S1-SC UP
Input
Time
DC injection braking
Frequency detection 2
ON OFF
M1-M2 (H2-01 = 05)
Holding brake
operation CLOSE OPEN CLOSE
OFF ON
S1-SC UP
Input
6-171
Stall Prevention during Deceleration
If connecting a braking resistor to discharge regenerative energy, be sure to set Stall prevention selection dur-
ing decel (L3-04) to 0 (Disabled).
If Stall prevention selection during decel (L3-04) is set to the initial value 1 (Enabled), the motor may not stop
within the specified decelerating time.
Stall prevention selection during accel (L3-01) and Stall prevention selection during running (L3-05) should be
IMPORTANT set to their initial values 1 (Enabled) to enable these functions.
Autotuning
Always perform autotuning with the motor before operating using vector control. Be sure to disconnect the
motor from the load before conducting autotuning. Conducting autotuning while the motor is connected to an
elevating machine system is dangerous because it automatically runs the motor for approximately one minute.
1. When the motor cannot be disconnected from the load, perform stationary autotuning (T1-01 = 1 or 4).
Stationary autotuning will apply current to the motor in its stopped condition and automatically measure the
motor data. In the initial running period after autotuning (T1-01 =1) (20% speed min., fixed speed for 1 s
IMPORTANT min.), the motor data measured by autotuning will automatically be corrected.
2. To improve low-speed torque characteristics using V/f control, conduct stationary autotuning for line to line
resistance only (T1-01 = 2).
3. When conducting autotuning on wound motor or other special types of motors, obtain a test report for the
motor in advance and confirm that the E2 motor constants after autotuning do not vary greatly from those
of the test report.
Torque Limit
The torque limit values (L7-01 to L7-04) are the motor's rated torque. When there is a possibility of insuffi-
cient torque at start-up or other time, increase the Inverter capacity and set the torque limit value to between
200% and 300% (factory setting is 200%).
6-172
Using Inverters for Elevating Machines
Acceleration/Deceleration Time
If the delay time for the holding brake’s mechanical operation is not taken into consideration and the accelera-
tion/deceleration time on the Inverter side is set to a time that is too short, and overcurrent or wear on the
brakes may occur at staring or the load will slip at stopping because the holding brake does not operate on
time. If so, use the dwell function at start described on page 6-176 or the dwell function at stop described on
page 6-177 to tune the timing for the holding brake.
6-173
Control-related Adjustments
The Varispeed G7 is designed to provide sufficient performance for elevating machines. However, if problems
related to controllability should occur, such as vibration or slipping, adjust the following constants in accor-
dance with the control method. Only constants that frequently require adjustment are listed in this table.
6-174
Using Inverters for Elevating Machines
6-175
3. Do not use Slip compensation gain (C3-01) during V/f control (A1-02 = 0). (It is not used with the factory setting.)
4. Use the ASR constants (C5-01 to C5-05) in their factory settings when using V/f control with PG (A1-02 = 1). Vibration may occur if these constants
are changed greatly from their factory settings.
5. The torque and speed response of high-resistance (high-slip) motors are insufficient. Use appropriate adjustments to improve them. On the contrary,
low-resistance (low-slip) motors are easily subject to hunting and vibration. Here too, use appropriate adjustments to improve them.
6. The current during startup may increase when C4-02 (Torque compensation primary delay time constant) is increased. Check the current during star-
tup while adjusting this constant.
(High speed)
C2-02 C2-03
Output frequency (Low speed)
C2-03
C2-01 C2-04
C2-04
1. The factory setting for C2-04 (S-curve characteristic time at deceleration end) is 0.00 second, while the fac-
tory setting for all other S-curve characteristic times is 0.20 second. Make appropriate settings for the
accel/decel times and S-curve characteristic times at each point. (S-curve characteristic time = Approxi-
IMPORTANT mately 0.2 to 1.0 second)
2. The accel/decel rate can be automatically switched during acceleration and deceleration by using C1-11
(Accel/decel time switching frequency). (Factory setting: Disabled)
Output frequency ≥ set frequency: C1-01, C1-02 accel/decel times
Output frequency < set frequency: C1-07, C1-08 accel/decel times
3. If the output frequency during the S-curve characteristic time for deceleration falls below the value set for
E1-09 (Min. output frequency), the S-curve characteristic will be cancelled, and the DC injection braking
(Zero-speed control) will be applied.
4. Do not use the S-curve characteristic for applications where a short run time is desired, such as in cranes
and hoists. (S-curve characteristic time = Approximately 0.0 to 0.2 second)
b6-02
(High speed)
(Dwell time at start)
Output frequency 0.1 to 0.3 sec
b6-01 (Dwell frequency at start) 0.1 to 3.0 Hz
Frequency detection t
2 or During run 2 OFF ON
Holding brake
CLOSE OPEN
operation
6-176
Using Inverters for Elevating Machines
If the mechanical operation of the holding brake is slow, use the dwell function at start to prevent brake wear,
and accelerate after the brake is completely open.
1. When using open-loop vector 1 control and V/f control, set b6-01 (Dwell frequency at start) higher than fre-
quency detection 2 (frequency when brakes open).
2. If the motor tends to have insufficient torque when started, use the DC injection braking function to allow
IMPORTANT sufficient motor current (torque) before starting.
• b2-03 (DC injection braking time at start): 0.2 to 0.5 s
• b2-02 (DC injection braking current): 50% to 80% (open-loop vector 1 control, V/f control only)
When the holding brake’s mechanical operation is slow, use DC injection braking (zero-speed control for flux
vector control) until the brakes are fully closed to prevent the brakes from slipping when stopping.
1. When the load cannot be maintained sufficiently using DC injection braking with open-loop vector 1 control
and V/f control, use the dwell functions at stop.
• b6-03 (Dwell frequency at stop): Min. output frequency to 3.0 Hz.
IMPORTANT The value must be less than the frequency when frequency detection 2 is OFF (L4-01 - L4-02).
• b6-04 (Dwell time at stop): 0.3 to 0.5 s
[b2-04 (DC injection braking at stop): 0.0 s]
2. If the Inverter and motor must be isolated while stopping using a magnetic contactor, for example in an ele-
vator, fully close the holding brakes and isolate the Inverter during baseblock (during baseblock signal: ON)
as stipulated by law in the EU.
During motor control or DC injection braking (zero-speed control), an Inverter error may occur due to surge
voltage. When a magnetic contactor is used between the Inverter and motor, set L8-07 (Output open-
phase protection) to 1 (enabled).
6-177
Sequence Circuit Configuration
The following diagram shows the sequence circuit configuration for torque compensation.
UP
S1 (Forward run)
DOWN
S2 (Reverse run)
HIGH/LOW
S6 (Multi-step speed reference 2)
SC
Time Chart
• Lifting
The analog signals corresponding to the load size are input as torque compensation signals from before the
Inverter starts until operation stops. (Factory setting: 10 V/100% torque)
Positive polarity is input for motor loads and negative polarity is input for regenerative loads.
The following diagram shows the time chart for lifting.
UP (Forward) OFF
ON
HIGH/LOW OFF
ON
Torque compensation
signal: 0 Analog signals corresponding to load size (Motor load: Inputs positive polarity.)
Same as above (Regenerative load: Inputs negative polarity.)
Output frequency
Zero-speed control
0 t
• Lowering
In the same way as for lifting, when the torque decreases, the analog signals corresponding to the load size are
input as torque compensation signals from before the Inverter starts until operation stops. (Factory setting: 10
V/100% torque)
Negative polarity is input for motor loads and positive polarity is input for regenerative loads.
The following diagram shows the time chart for lowering.
6-178
Using Inverters for Elevating Machines
0 t
Output frequency
1. For either increasing or decreasing torque, externally maintain the torque compensation signals during
operation to prevent them from fluctuating. Fluctuation in compensation signals during operation may result
in vibration.
IMPORTANT 2. If reverse run is used for lifting and forward run is used for lowering, the torque compensation signal polar-
ity must be reversed.
6-179
Overvoltage Inhibit Function
Leave L3-11 (Overvoltage inhibit function selection) set to 0 (disabled). This function is used to prevent over-
voltage tripping when the braking resistor is not used with a regenerative load. When this function is enabled,
the torque reference on the regenerative side is automatically inhibited in the Inverter during regeneration.
Using this function in elevating machines is dangerous because the elevator may slip and fall.
Contact your Yaskawa representative for details on applications such as high-speed elevators (speed: 2 m/s or higher),
direct-drive elevators, or Inverters designed for cranes.
6-180
Current Alarm Function
*To output a minor failure contact signal from a multi-function contact terminal, set H2- to 10 (Minor failure).
Use the peak hold current monitoring function (U1-83 and U1-84) when performing retuning to reduce
the Inverter output current to 150% of the rated output current. Refer to Chapter 4 Trial Operation for
details.
For applications where a high current flows because of frequent start and stop operations, such as cranes, set L8-41 to 1
(Enabled).
If a current alarm occurs frequently, take measures such as:
IMPORTANT
• Reducing the frequency of operation and loading.
• Adjusting open/close timing of holding brake.
• Increasing acceleration/deceleration time.
• Taking enough time to produce motor magnetic flux (As described below).
■Related Constants
Name Control Methods
Change MEMO
Con- Open Open
Setting Factory during V/f Flux BUS
stant Description Range Setting Opera- Loop Loop Regis-
Number Display V/f with
Vector
Vec-
Vector
tion PG tor ter
1 2
Allows or restricts an alarm from
Current alarm being triggered when the relative
output current rises above 150%.
L8-41 0 or 1 1 No A A A A A 4F2H
0: Disabled.
1: Enabled (alarm will be
电流警告
output).
If load is applied to an induction motor at startup before motor magnetic flux has been produced (as when
acceleration starts while the motor is locked by a brake mechanism or acceleration is too sudden), a high start-
ing current may flow.
In this case, use the following functions and constants to accelerate the motor after the magnetic flux is pro-
duced.
Startup current can be reduced by producing motor magnetic flux.
• Magnetic flux compensation function (See related constants b2-02 and b2-08)
• Dwell function (See related constants b6-01 and b6-02)
• Initial excitation function (See the setting 60 of the multi-function contact input H1)
For flux loop vector control, a multi-function input terminal can be used for initial excitation by setting
H1- to 60.
• Field forcing function (See related constant d6-03)
6-181
Peak Hold Current Monitoring Function
This function saves the peak value (effective value) of the Inverter output current and displays it on the
Digital Operator for monitoring (U1-83). The Inverter output frequency at the moment the peak current
value is saved can be also monitored (U1-84).
At trial operation, perform adjustments so that the Inverter output current is limited to 150% of the rated
current checking the constants U1-83 and U1-84 of this function.
The values of peak current and output frequency during peak hold will be cleared when the Inverter stops and then starts,
or when the power is turned OFF and then ON. They will be retained while being baseblocked (stopped).
IMPORTANT
Output
frequency
during Displays the frequency value 0.01
10V: Max frequency
U1-84 peak hold when the output current Hz A A A A A 7D0H
(-10V to 10V)
reached its peak value. *2
峰值保持输
出频率
* 1. The minimum unit differs depending on the Inverter capacity. (0.01 A for Inverter of 0.4 kW to 7.5 kW, and 0.1 A for Inverter of 11 kW or more)
* 2. The setting unit can be selected in o1-03.
Peak hold
output Displays the frequency value at
frequency at the moment the current reached 0.01
U2-22 fault (Cannot be output.) A A A A A 7E7H
its peak value when the last fault Hz
峰值保持输出
occurred.
频率
* The minimum unit differs depending on the Inverter capacity. (0.01 A for Inverter of 0.4 kW to 7.5 kW, and 0.1 A for Inverter of 11 kW or more)
6-182
Maintenance Timer Display Function
The maintenance time periods displayed in the monitors as a percentage to the total life are only an estimate, not an exact
prediction of actual performance life.
Use them as guidelines for replacement.
IMPORTANT
Refer to Multi-function Contact Outputs: H2 in Chapter 5 User Constants for information on multi-function
contact outputs.
6-183
Related Alarm Displays
When setting a multi-function contact output H2- to 2F, the alarm is displayed on the Digital Operator as
shown below.
Related Constants
Name Control Methods
Change Open Open MEMO-
Con-
Setting Factory during V/f Loop Flux Loop BUS
stant Description Range Setting Opera-
Number Display V/f with Vec- Vec- Vec- Regis-
tion PG tor tor tor ter
1 2
Fan opera- Set the initial value of the fan
tion time set- operation time using time
ting 0 to
o2-10 units. 0 hr No A A A A A 50EH
65535
The operation time accumu-
风扇累积运行
时间 lates from the set value.
6-184
Troubleshooting
This chapter describes the fault displays and countermeasure for the Inverter and motor prob-
lems and countermeasures.
Fault Detection
When the Inverter detects a fault, the fault contact output operates, and the Inverter output is shut OFF causing
the motor to coast to a stop. (The stopping method can be selected for some faults, and the selected stopping
method will be used with these faults.) A fault code is displayed on the Digital Operator.
When a fault has occurred, refer to the following table to identify and correct the cause of the fault.
Use one of the following methods to reset the fault before restarting the Inverter:
• Set a multi-function contact input (H1-01 to H1-05) to 14 (Fault Reset) and turn ON the fault reset signal.
• Press the RESET Key on the Digital Operator.
• Turn the main circuit power supply OFF and then ON again.
Power isn't being supplied to the PG. Supply power to the PG properly.
7-2
Protective and Diagnostic Functions
7-3
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions
• The wiring of the control power cir-
cuit is incorrect.
• A Backup Capacitor Unit for • Try turning the power supply
Momentary Power Loss is not off and on.
UV2 Control Power Fault
attached to a 200 V/400 V Class • Replace the Inverter if the fault
控制回路 The control power supply voltage
Inverter of 7.5 kW or less and the continues to occur.
欠电压 dropped.
value of the Momentary power loss • Attach a Backup Capacitor Unit
ridethru time (L2-02) factory setting for Momentary Power Loss.
has been changed to the larger
value.
7-4
Protective and Diagnostic Functions
7-5
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions
The load is too heavy. The accelera- Check the size of the load and the
tion time, deceleration time, and cycle length of the acceleration, deceler-
time are too short. ation, and cycle times.
The Motor Rated Current (E2-01) is Check the Motor Rated Current
incorrect. (E2-01).
7-6
Protective and Diagnostic Functions
7-7
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions
• Make sure that the settings in
Undertorque Detected 1 L6-02 and L6-03 are appropri-
UL3
There has been a current less than the ate.
欠转矩 -
setting in L6-02 for longer than the • Check the mechanical system
检出 1
setting in L6-03. and correct the cause of the
overtorque.
Overshooting/Undershooting are
Adjust the gain again.
occurring.
Overspeed
OS The speed has been greater than the Check the reference circuit and
The reference speed is too high.
电机过速 setting in F1-08 for longer than the reference gain.
setting in F1-09.
The settings in F1-08 and F1-09 aren't Check the settings in F1-08 and
appropriate. F1-09.
Control Fault
The torque limit was reached continu-
Motor constant settings are not cor- • Check the motor constants.
ously for 3 seconds or longer during a
rect. • Perform autotuning.
deceleration stop during open-loop
CF
vector 1 control.
控制故障
An error occurred in the speed estima-
tion calculation for open-loop vector 2 Refer to Corrective Actions for Control Faults (CF) on page 7-14.
control.
7-8
Protective and Diagnostic Functions
EF3
端子 S3 External Fault (Input Terminal 3)
故障
EF6 External Fault (Input Terminal 6) • Reset external fault inputs to the
An “external fault” was input from a multi-function inputs.
EF7 External Fault (Input Terminal 7) multi-function input terminal. • Remove the cause of the exter-
nal fault.
EF8 External Fault (Input Terminal 8)
7-9
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions
SI-F/G Communications Error
Detected
E-15 A communications error was detected
Check the communications sig-
SI-F/G when a Run Command or frequency -
nals.
故障 reference was set from an option
board and continuous operation was
set for the E-15 operation selection.
Digital Operator Communications The Digital Operator's connector isn't Disconnect the Digital Operator
Error 1 connected properly. and then connect it again.
Communications with the Digital
CPF00 Operator were not established within 5 The Inverter's control circuits are
seconds after the power was turned Replace the Inverter.
操作器 faulty.
故障 1 on.
Digital Operator Communications The Digital Operator isn't connected Disconnect the Digital Operator
Error 2 properly. and then connect it again.
CPF01 After communications were estab-
操作器 lished, there was a communications
故障 2 The Inverter's control circuits are
error with the Digital Operator for Replace the Inverter.
faulty.
more than 2 seconds.
7-10
Protective and Diagnostic Functions
The option board is not connected Turn off the power and insert the
CPF06 properly. board again.
选择卡连 Option Board Connection Error
接故障 Replace the option board or the
The Inverter or option board is faulty.
Inverter.
CPF10 ASIC Version Fault The Inverter control circuit is faulty Replace the Inverter.
ASIC 故障
The option board is not connected Turn off the power and insert the
CPF20 Communications Option Board A/ properly. board again.
选件卡 D Converter Error
故障 The option board's A/D converter is Replace the Communications
faulty. Option Board.
7-11
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions
Replace the main circuit capacitor.
A loss in capacity due to aging of the
(Consult your YASKAWA repre-
main circuit capacitor.
sentative.)
7-12
Protective and Diagnostic Functions
Table 7.2 Causes and Corrective Actions When the Digital Operator Goes Dark
Display Meaning Probable Causes Corrective Actions
• Make sure that incorrect wiring
has not been done.
• A short-circuit between +V, −V, and
• Check the resistance and wir-
AC terminals occurred.
ing for the frequency setting
• Overload in the control circuit ter-
potentiometer, etc. (Check that
minal.
the current for terminals +V and
–V is 20 mA or less.)
7-13
Corrective Actions for Control Faults (CF)
CF occurs
Yes
U1-50 = 01,02 Refer to Autotuning on page
Are the motor No Execute autotuning for the 4-9. Execute autotuning after
constants set
correctly? motor constants. the control method is
changed.
Yes
U1-50 = 00,01, Refer to Autotuning on page
Has autotuning been No 02,08 Execute autotuning for the 4-9. Execute autotuning
executed for line-to-line
resistance?
line-to-line resistance. after changing cables.
Yes
Increase the torque limit Refer to Torque Limits: L7
Are the torque limit settings (L7-01 Yes or torque reference until on page 5-64. In particular, if
to L7-04, analog input) or the torque
reference input too small? is it within the allowable the regenerative torque limit
range for the machine. has been reduced to prevent
No
overvoltages, set L3-11 to 1
U1-50 = 00 If deceleration stop is not and set the regenerative
Is the stopping No torque limit to a large value.
possible or unnecessary
method appropriate? for the machine, set b1-03
to 1 (coast to stop).
Yes
U1-50 = 02 · Input the operation reference Refer to Speed Search
Is an operation reference Yes after the motor stops. on page 6-64.
being input while the motor · Set b3-01 to 1 or 3 (speed
is coasting?
search enabled).
No
U1-50 = 04 Refer to Procedure for
Adjust the speed estimator's
What is the CF error integral time (N4-07) or Increasing the Speed
code (U1-50)?
proportional gain (N4-08). Response on page 4-21.
U1-50 = 08
If the machine rotates only in the
same direction as the sign of the
speed limit, set b1-10 to 1.
U1-50 = 20
· If the machine rotates in the Refer to Speed/Torque
opposite direction to the sign of Control Switching Function
the speed limit (rewinding on page 6-134.
operation), set d5-07 to 0.
· Start with speed control and then
switch to torque control when the
Use in open loop vector 1 control. frequency exceeds 3 Hz.
U1-50 Meaning
00 Stop error
10 Zero-speed fault
7-14
Protective and Diagnostic Functions
Alarm Detection
Alarms are detected as a type of Inverter protection function that do not operate the fault contact output. The
system will automatically returned to its original status once the cause of the alarm has been removed.
The Digital Operator display blinks and an alarm is sent from the multi-function outputs (H2-01 to H2-05) if
selected.
When an alarm occurs, take appropriate countermeasures according to the table below.
7-15
Table 7.3 Alarm Displays and Processing (Continued)
Display Meaning Probable causes Corrective Actions
Check the size of the load and the
length of the acceleration, decelera-
OH3 Motor Overheating tion, and cycle times.
(闪烁) E was set for H3-09 and the motor
The motor has overheated.
电机过 temperature thermistor input exceeded Check the V/f characteristics.
热警告 the alarm detection level.
Check the motor temperature input on
terminals A1 and A2.
Overshooting/undershooting are
Adjust the gain again.
occurring.
Overspeed
OS The speed has been greater than the Check the reference circuit and refer-
(闪烁) setting in F1-08 for longer than the The reference speed is too high.
ence gain.
过速 setting in F1-09.
The settings in F1-08 and F1-09 aren't
Check the settings in F1-08 and F1-09.
appropriate.
The acceleration time and decelera- Lengthen the acceleration time and
DEV tion time are too short. deceleration time.
Excessive Speed Deviation
(闪烁) The speed deviation has been greater The load is locked. Check the mechanical system.
电机速 than the setting in F1-10 for longer
度偏差 than the setting in F1-11. The settings in F1-10 and F1-11 aren't
过大 Check the settings in F1-10 and F1-11.
appropriate.
7-16
Protective and Diagnostic Functions
EF3
(闪烁) External Fault (Input Terminal S3)
端子 S3
故障
CALL
(闪烁) Communications on Standby Check the communications devices
SI-B Control data was not normally -
and signals.
通信 received when power was turned ON.
错误
7-17
Table 7.3 Alarm Displays and Processing (Continued)
Display Meaning Probable causes Corrective Actions
RUNC Reset during Run Command Input
(闪烁) Error Check that a Run Command is not
外部运 The reset signal was input during Run - being input from an external terminal
行输入 Command input from an external ter- or other source.
不能 minal or other source.
复位
SI-T Watchdog Error Detected
E5 A Watchdog error was detected when
Synchronization error between master Check the communications timing
(闪烁) the Run Command or a frequency ref- controller and Inverter for control
SI-T erence was set from an option board
data. such as communications cycle. *1
WDT and continuous operation was set for
the E5 operation selection.
HCA Current Alarm Either a specialized motor or an Verify the setting for the Inverter
(闪烁) The output current has exceeded the excessively large motor is being used. capacity.
电流 overcurrent alarm level (over 150% of
the rated current). Momentary losses in power or fault
警告 The current has risen too high while
restarts may occasionally trigger an
performing speed search either during
overcurrent alarm, and are not neces-
a momentary loss in power or during
sarily indicators of an overcurrent
a fault restart.
problem.
LT-C
(闪烁) Electrolytic Capacitor Maintenance The electrolytic capacitors have Reset constant o2-18 to “0%” after
电容 Timer reached their estimated maintenance
Monitor U1-61 has reached 100%. time period. replacing *2 the electrolytic capacitors.
维护
时期
LT-F
(闪烁) Cooling Fan Maintenance Timer The cooling fan has reached its esti- Replace the cooling fan *2 and set con-
冷却扇 Monitor U1-63 has reached 100%. mated maintenance time period. stant o2-10 to “0H”.
维护
时期
* 1. Refer to MECHATROLINK COMMUNICATIONS INTERFACE CARD INSTRUCTIONS (TOBPC73060008) for details.
* 2. For details on replacement, refer to Chapter 8 Maintenance and Inspection
7-18
Protective and Diagnostic Functions
Operation Errors
An operation error will occur if there is an invalid setting or a contradiction between two constant settings. It
won't be possible to start the Inverter until the constants have been set correctly. (The alarm output and fault
contact outputs will not operate either.)
When an operation error has occurred, refer to the following table to identify and correct the cause of the
errors.
OPE02 Constant Setting Range The constant setting is outside of the valid setting range. Press the ENTER Key on
参数设定 Error the Digital Operator to display OPE fault constant (U1-34).
故障 2
One of the following errors has been made in the multi-function input (H1-01 to H1-
10) settings:
• The same setting has been selected for two or more multi-function inputs.
• An up or down command was selected independently. (They must be used
together.)
OPE03 • The up/down commands (10 and 11) and Accel/Decel Ramp Hold (A) were
Multi-function Input
参数设定 selected at the same time.
Selection Error
故障 3 • Speed Search 1 (61, maximum output frequency) and Speed Search 2 (62. set fre-
quency) were selected at the same time.
• The up/down commands (10 and 11) were selected while PID Control Method
Selection (b5-01) was enabled.
• Positive and negative speed commands have not been set at the same time.
• The emergency Stop Command NO and NC have been set at the same time.
OPE05 Option Board Selection The option board was selected as the frequency reference source by setting b1-01 to
参数设定 Error 3, but an option board isn't connected (C option).
故障 5
OPE06 Control Method Selec- V/f control with PG feedback was selected by setting A1-02 to 1, but a PG Speed
参数设定 tion Error Control Board isn't connected.
故障 6
The same setting has been selected for the analog input selection and the PID func-
tion selection.
OPE07 Multi-function Analog • H3-09 = B and H6-01 = 1
参数设定 Input Selection Error • H3-09 = C and H6-01 = 2
故障 7 b1-01 (Reference Selection) is set to 4 (pulse input) and H6-01 (Pulse Train Input
Function Selection) is set to a value other than 0 (frequency reference).
OPE08 A setting has been made that is not required in the current control method. Ex.: A
Constant Selection
参数设定 function used only with open-loop vector control was selected for V/f control. Press
Error
故障 8 the ENTER Key on the Digital Operator to display OPE fault constant (U1-34).
OPE10 Constants E1-04, E1-06, E1-07, and E1-09 do not satisfy the following conditions:
参数设定 V/f Data Setting Error • E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
故障 10 • E3-02 (FMAX) ≥ E3-04 (FA) > E3-05 (FB) ≥ E3-07 (FMIN)
7-19
Table 7.4 Operation Error Displays and Incorrect Settings (Continued)
Display Meaning Incorrect settings
One of the following constant setting errors exists.
OPE11 • C6-05 (Carrier Frequency Gain) > 6, the Carrier Frequency Lower Limit (C6-04)
参数设定 Constant Setting Error > the Carrier Frequency Gain (C6-05)
故障 11 • Upper/lower limit error in C6-03 to 05.
• C6-02 is 7 to E.
7-20
Protective and Diagnostic Functions
7-21
Table 7.5 Errors During Autotuning (Continued)
Display Meaning Probable causes Corrective Actions
Motor core satura- The results of autotuning has exceeded • Check the input data.
tion error (detected the setting range for a user constant so a • Check motor wiring.
饱和系数故障 only for rotational temporary setting was made for the • If the motor is connected to the
autotuning)* motor core saturation coefficient. machine, disconnect it.
IFE The read data length does not agree. Repeat the read.
READ READ DATA Illegal read data Check the Digital Operator cable.
功能 ERROR The write data is incorrect. Replace the Digital Operator.
7-22
Protective and Diagnostic Functions
VYE
The Digital Operator and Inverter set-
VERIFY Verify error Retry the copy and verify again.
tings do not agree.
VERIFY ERROR
功能
CPE The Inverter product code or software Use the copy function for the same
ID not matched
ID UNMATCH number is different. product code and software number.
7-23
Troubleshooting
Due to constant setting errors, faulty wiring, and so on, the Inverter and motor may not operate as
expected when the system is started up. If that should occur, use this section as a reference and apply the
appropriate measures.
If the contents of the fault are displayed, refer to Protective and Diagnostic Functions.
The display does not change when the Increment and Decrement Keys are pressed.
The following causes are possible.
7-24
Troubleshooting
The motor does not operate when the RUN Key on the Digital Operator is pressed.
The following causes are possible.
If the Inverter is not in drive mode and the DRIVE indicator on the Digital Operator (JVOP-161) does not light
up, the Inverter will remain in ready status and will not start. Press the Menu Key to display the drive mode,
and enter the drive mode by pressing the DATA/ENTER Key. “-Rdy-” will be displayed when drive mode is
IMPORTANT entered.
The LOCAL/REMOTE Key is enabled by setting o2-01 to 1 and disabled by setting o2-01 to 2. It is enabled
when the drive mode is entered.
INFO
The motor does not operate when an external operation signal is input.
The following causes are possible.
7-25
The operation method selection is wrong.
If constant b1-02 (reference selection) is set to 0 (Digital Operator), the motor will not operate when an exter-
nal operation signal is input. Set b1-02 to 1 (control circuit terminal) and try again.
Similarly, the motor will also not operate if the LOCAL/REMOTE Key has been pressed to switch to Digital
Operator operation. In that case press the LOCAL/REMOTE Key* again to return to the original setting.
The LOCAL/REMOTE Key is enabled by setting o2-01 to 1 and disabled by setting o2-01 to 2. It is enabled
when the drive mode is entered.
INFO
7-26
Troubleshooting
7-27
The motor only rotates in one direction.
“Reverse run prohibited” is selected. If b1-04 (Prohibition of Reverse Operation) is set to 1 (reverse run pro-
hibited), the Inverter will not receive Reverse Run Commands. To use both forward and reverse operation, set
b1-04 to 0.
7-28
Troubleshooting
The analog frequency reference bias setting is wrong (the gain setting is wrong).
The frequency reference bias set in constant H3-03 is added to the frequency reference. Check to be sure that
the set value is suitable.
7-29
The torque limit has been reached.
When a torque limit has been set in constants L7-01 to L7-04, no torque will be output beyond that limit. This
can cause the deceleration time to be too long. Check to be sure that the value set for the torque limit is suit-
able.
If H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-05 (Multi-function Analog
Input Terminal A3 Function Selection) is set to 10, 11, 12 or 15 (positive and negative torque limit), check to
be sure that the analog input value is suitable.
7-30
Troubleshooting
There may be resonance between the mechanical system's characteristic frequency and the
carrier frequency.
If the motor is running with no problems and the machinery is oscillating with a high-pitched whine, it may
indicate that this is occurring. To prevent this type of resonance, adjust the carrier frequency with constants
C6-02 to C6-05.
There may be resonance between a machine's characteristic frequency and the output fre-
quency of the Inverter.
To prevent this from occurring, either use the jump frequency functions in constants d3-01 to d3-04 or install
rubber padding on the motor base to reduce oscillation.
7-31
Vector control will not perform if autotuning has not been performed. Perform autotuning separately for the
motor, or set the motor constants through calculations. Alternatively, change the control method selection (A1-
02) to V/f control (0 or 1).
7-32
Troubleshooting
7-33
• Reduce the setting for N4-11 to a value less than the factory setting. Reduce the setting in intervals of
approximately 5 Hz.
• If shock occurs during deceleration:
• Increase the deceleration time within the allowable range. Alternatively, reduce the torque limit.
• Reduce the setting for N4-28 to a value less than the factory setting. Reduce the setting in intervals of
approximately 5 Hz.
The factory settings for N4-11 (speed estimator switching frequency) and N4-28 (speed estimator switching
frequency 2) are 70 Hz and 50 Hz respectively. If the problem still occurs after making the above adjustments,
use open-loop vector 1 control (A1-02 = 2).
7-34
Troubleshooting
7-35
Maintenance and
Inspection
This chapter describes basic maintenance and inspection for the Inverter.
Outline of Warranty
The warranty period of the Inverter is as follows:
Warranty Period: This product is warranted for twelve months after being delivered to Yaskawa's customer or
if applicable eighteen months from the date of shipment from Yaskawa's factory whichever comes first.
Daily Inspection
Check the following items with the system in operation.
• The motor should not be vibrating or making unusual noises.
• There should be no abnormal heat generation.
• The ambient temperature should not be too high.
• The output current value shown on the monitor displays should not be higher than normal.
• The cooling fan on the bottom of the Inverter should be operating normally.
Periodic Inspection
Check the following items during periodic maintenance.
Always turn OFF the power supply before beginning inspection. Confirm that the LCD and LED indicators on
the front cover have all turned OFF, and then wait until at least five minutes has elapsed before beginning the
inspection. Be sure not to touch terminals right after the power has been turned off. Doing so can result in
electric shock.
Clean off any dirt and dust with an air gun using
Heatsinks Are the fins dirty or dusty? dry air at a pressure of 39.2 x 104 to 58.8 x 104 Pa
(4 to 6 kg•cm2).
Clean off any dirt and dust with an air gun using
Is there any conductive dirt or oil mist on dry air at a pressure of 39.2 x 104 to 58.8 x 104 Pa
PCBs
the PCBs? (4 to 6 kg•cm2).
Replace the boards if they cannot be made clean.
Is there any abnormal noise or vibration or
Cooling fan has the total operating time exceeded Replace the cooling fan.
20,000 hours?
Clean off any dirt and dust with an air gun using
Is there any conductive dirt or oil mist on
Power elements dry air at a pressure of 39.2 x 104 to 58.8 x 104 Pa
the elements?
(4 to 6 kg•cm2).
Are there any irregularities, such as dis-
Smoothing capacitor Replace the capacitor or Inverter.
coloration or odor?
8-2
Maintenance and Inspection
8-3
Step No. Digital Operator Display Description
1 Set o2-04 (kVA selection) to the capacity of the Inverter that you use.
Set A1-02 to the control method to be used. The value of the control method
2 should be set to the same value as when the constants were copied from the
Inverter to the Digital Operator.
If the mode is switched to the DRIVE after initialization has been completed,
the motor power setting display appears. Set T1-02 (Motor output power) to
4
the motor capacity of the connected motor.
This example is the setting for a 55 kW motor.
Press the Increment Key to view the shipping adjustment display. After con-
firming that the motor has been connected, press the RUN Key to start auto-
5 tuning.
Note: Do not touch the motor terminals. Although the motor does not rotate,
voltage is being supplied to the motor though the motor is not rotating.
After autotuning has been completed, use the copy function of the Operator to
copy the settings of the constants of the control board from the Operator to the
6 - Inverter before replacing the board.
If the copy function is not available, change the setting of the constants manu-
ally.
If the mode is switched to the DRIVE, the frequency setting display appears,
7
and the operation becomes enabled.
Press the Increment Key to view the motor rated power display. Set T1-02
2
(Motor output power) to the capacity of the connected motor.
Press the Increment Key to view the motor rated current display. Set T1-04
3
(Motor rated current) to the value of motor rated current.
8-4
Maintenance and Inspection
8-5
Cooling Fan Replacement Outline
Airflow direction
2
1
Fan cover
Fig 8.1 Cooling Fan Replacement (200 V Class Inverters of 3.7 kW)
8-6
Maintenance and Inspection
Airflow direction
Fig 8.2 Cooling Fan Replacement (200 V Class Inverters of 18.5 kW)
8-7
200 V Class Inverters of 22 kW, 45 kW, 55 kW and 400 V Class Inverters of 18.5 kW to 75 kW
Front cover
Terminal cover
Circulation fan
mounting screws
Fan cable pullout position
Circulation fan
Airflow direction
Fan support Fan support
mounting screws
Fan support
Airflow
direction
Cooling fans
Cooling fans
Fig 8.3 Cooling Fan Replacement (200 V Class Inverters of 45 kW and 55 kW)
8-8
Maintenance and Inspection
Fan cover
Bottom Inverter
Cooling fan
Top Inverter
Fig 8.4
Fig 8.5
3. Make sure that there is no gap between the fan cover and A. Then screw it in place with the three screws.
NG
A
A
Fig 8.6
8-9
200 V Class Inverters of 30 kW and 37 kW
Gate drive
board
Front cover
Panel
mounting
screws
Capacitor
Terminal cover
Terminal
board
Terminal cover mounting screws
Pay attention to
the protruding part Circulation fan
of the fan cable. Cooling fans
Airflow direction
Cooling fan
mounting screws
Fan cover
Fig 8.7 Cooling Fan Replacement (200 V Class Inverters of 30 kW and 37 kW)
8-10
Maintenance and Inspection
Front cover
Terminal cover
Fan cover
mounting screws
Fan power relay board Fan cover
Control board mounting panel
Control board mounting Circulation fan
mounting screws
panel
Cooling fan
Control circuit terminal board
Cooling fan
airflow direction
Finger guard
8-11
400 V Class Inverters of 90 kW and 110 kW
Front cover
Terminal cover
Circulation fan
Cooling fan power relay board
Fan cover mounting screws Airflow direction
Circulation fan
mounting screws
Circulation fan
Circulation fan
power connector
Fig 8.9 Cooling Fan Replacement (400 V Class Inverters of 90 kW and 110 kW)
8-12
Maintenance and Inspection
200 V Class Inverters of 90 kW and 110 kW/400 V Class Inverters of 132 kW and 160 kW
Front cover mounting screws Fan cover Fan cover mounting screws
Fan power
relay board
Gate drive
board
Front cover
Control board
Terminal
cover
Circulation fan
Circulation fan mounting screws
Circulation fan
Fan cover mounting screws airflow direction
Fan cover
Fan cover
Fan airflow
direction
8-13
400 V Class Inverters of 185 kW and 220 kW
Top front
cover
Terminal
Bottom cover
front
cover
Fan cable
Fan cover mounting screws Fan ground
cable
Enlarged view
Fan airflow
Fan cover mounting screws direction
Colling fan
Cooling fan mounting screws
Finger guard
Fig 8.11 Cooling Fan Replacement (400 V Class Inverters of 185 kW and 220 kW)
8-14
Maintenance and Inspection
Top front
cover
Bottom
front Terminal
cover cover
Fan units
Fan airflow
derection
Fig 8.12 Cooling Fan Replacement (400 V Class Inverters of 300 kW)
8-15
Circulation Fan Replacement Outline
With some capacities, there is a small fan installed inside the Inverter for the purpose of increasing circulation
in areas where heat has built up. These fans have built-in fan sensors that output an alarm when the rotation
rate of the fan drops to indicate that replacement is necessary.
200 V Class Inverters of 7.5 kW/400 V Class Inverters of 5.5 kW and 7.5 kW
The circulation fan is installed behind the control circuit terminal board inside the Inverter.
The circulation fan can be replaced by removing the control circuit terminal board.
Control Board
2
1
Airflow direction
Tabs (A)
Circulation fan
Fig 8.13 Circulation Fan Replacement (200 V Class Inverters of 7.5 kW/400 V Class Inverters of 5.5 kW and 7.5 kW)
8-16
Maintenance and Inspection
4
Circulation fan
2 1
Relay connector tab (A)
Fan tabs (B)
3
Airflow
direction
Fig 8.14 Circulation Fan Replacement (200 V Class Inverters of 15 kW/400 V Class Inverters of 11 kW and 15 kW)
8-17
2. Pull out the cables connected to the control circuit terminal board, the gate drive board, and the cooling fan
power relay board.
3. Remove the control board mounting panel.
4. Replace the circulation fan installed behind the control board mounting panel.
8-18
Maintenance and Inspection
Frame
Frame fixing screws
Fan airflow
direction
Enlarged view
Circulation fan
Fan airflow
direction
Enlarged view
Fan cable
Fig 8.15 Circulation Fan Replacement (400 V Class Inverters of 185 kW and 220 kW)
8-19
400 V Class Inverters of 300 kW
Two circulation fans are installed as described in the following sections.
Enlarged view
Circulation fan
Fan airflow
direction
Enlarged view
Fix the fan cable
with Insulok ties
Fan cable
Fig 8.16 Circulation Fan Replacement (400 V Class Inverters of 300 kW)
8-20
Maintenance and Inspection
Always confirm that the charge indicator is not lit before removing or mounting the control circuit terminal
board.
IMPORTANT
FE NC
8-21
Specifications
This chapter describes the basic specifications of the Inverter and specifications for options and
peripheral devices.
Specifications by Model
Specifications are given by model in the following tables.
200 V Class
Rated output current (A) 3.2 6 8 12 18 27 34 49 66 80 96 130 160 183 224 300 358 415
3-phase; 200, 208, 220, 230, or 240 VAC
Max. output voltage (V)
(Proportional to input voltage.)
Max. output frequency
Frequencies supported up to 400 Hz using constant setting
(Hz)
Rated voltage (V)
3-phase, 200/208/220/230/240 VAC, 50/60 Hz*2
Power supply characteristics
* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Inverter, be sure that the Inverter's
rated current is applicable for the motor's rated current.
* 2. The voltage of the cooling fan for 200 V Class Inverters of 30 kW is three-phase, 200, 208, or 220 V at 50 Hz or 200, 208, 220, or 230 V at 60 Hz.
* 3. A 3-wire transformer is required on the power supply for 12-phase rectification.
9-2
Standard Inverter Specifications
400 V Class
Table 9.2 400 V Class Inverters
Model Number CIMR-G7B 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018
Max. applicable motor output
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
(kW) *1
Rated input current (A) 2.2 4.1 5.8 7.4 10.8 18 25 32 40 46
Rated output capacity
1.4 2.6 3.7 4.7 6.9 11 16 21 26 32
Output ratings
(kVA)
Rated output current (A) 1.8 3.4 4.8 6.2 9 15 21 27 34 42
Max. output voltage (V) 3-phase; 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
Max. output frequency Frequencies supported up to 400 Hz using constant setting
(Hz)
Power supply characteristics
Model Number CIMR-G7B 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
Max. applicable motor output
22 30 37 45 55 75 90 110 132 160 185 220 300
(kW)*1
Rated input current (A) 57 72 88 107 141 182 215 264 297 332 407 495 666
Rated output capacity
40 50 61 74 98 130 150 180 210 230 280 340 460
Output ratings
(kVA)
Rated output current (A) 52 65 80 97 128 165 195 240 270 302 370 450 605
Max. output voltage (V) 3-phase, 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
Max. output frequency Frequencies supported up to 400 Hz using constant setting
(Hz)
* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Inverter, be sure that the Inverter's
rated current is applicable for the motor's rated current.
* 2. A 3-wire transformer (optional) is required on the power supply for 12-phase rectification.
9-3
Common Specifications
The following specifications apply to both 200 V and 400 V Class Inverters.
Overvoltage protection
400 Class Inverter: Stops when main-circuit DC voltage is approximately above 820 V.
200 Class Inverter: Stops when main-circuit DC voltage is approximately below 190 V.
Undervoltage protection
400 Class Inverter: Stops when main-circuit DC voltage is approximately below 380 V.
Momentary power loss Stops for 15 ms or more.
ridethrough *7 With a suitable constant setting, operation can be continued if power is restored within 2 s.
Cooling fin overheating Protection by thermistor.
Stall prevention Stall prevention during acceleration, deceleration, or running.
Grounding protection*6 Protection by electronic circuits. (Overcurrent level)
Charge indicator Lit when the main circuit DC voltage is approx. 50 V or more.
Ambient operating tem- -10°C to 40°C (Enclosed wall-mounted type)
perature 10°C to 45°C (Open chassis type)
Ambient operating humid-
95% max. (with no condensation)
ity
Storage temperature - 20°C to + 60°C (short-term temperature during transportation)
Environment
* 1. Rotational autotuning must be performed to ensure obtaining the specifications given for flux or open-loop vector 1/2 control.
9-4
Standard Inverter Specifications
* 2. When connecting a Braking Resistor or Braking Resistor Unit, set L3-04 (Stall prevention selection during deceleration) to 0 (disabled). Stopping may not be pos-
sible in the specified deceleration time if this function is not disabled.
* 3. The maximum output frequency for open-loop vector 2 control is 132 Hz.
* 4. The speed control accuracy depends on the installation conditions and type of motor used. Contact your Yaskawa representative for details.
* 5. Derating is required for applications that use repetitive loads. (Refer to page 10-6 for details.)
* 6. The ground fault here is one which occurs in the motor wiring while the motor is running. A ground fault may not be detected in the following cases.
y A ground fault with low resistance which occurs in motor cables or terminals.
y A ground fault occurs when the power is turned ON.
* 7. Attach a Backup Capacitor Unit for Momentary Power Loss if compensation for power interruptions of up to 2.0 seconds is required for 200 V/400 V Class
Inverters with outputs of 0.4 to 7.5 kW.
* 8. If running at a speed of 6 Hz or less, the overload protection function can operate even if running within 150% of rated output current per minute.
9-5
Specifications of Options and Peripheral Devices
The following options and peripheral devices can be used for the Inverter. Select them according to the
application.
(FIL001098)
Reduce the affects of Finemet zero- Input noise filter
phase reactor to Reduces noise from the line that sneaks into the Inverter input
radio and control device F11080GB
reduce radio power system. Insert as close to the Inverter as possible.
noise (FIL001097)
Can be use on both the input side and output side.
noise*2
F200160BP
(300-001-041) Inverter
Output Noise Fil- Reduces noise generated by the Inverter. Connect as close to
LF-
ter the Inverter as possible. Varispeed F7
* 1. Use a ground fault interrupter with a current sensitivity of 200 mA minimum and an operating time of 0.1 s minimum to prevent operating errors. The interrupter
must be suitable for high-frequency operation.
Example: NV series by Mitsubishi Electric Corporation (manufactured in or after 1988)
EG, SG series by Fuji Electric Co., Ltd. (manufactured in or after 1984)
* 2. The finement zero-phase reactor is manufactured by Hitachi Metals.
9-6
Specifications of Options and Peripheral Devices
2C-Relay
73600- Provides two multi-function outputs (DPDT relay contacts) in TOE-C736-
Output Board
D007X addition to those provided by the Inverter. 40.8
DO-02C
9-7
Table 9.5 Option Boards (Continued)
Code Num- Document
Type Name Function
ber Number
Used for V/f with PG control. Speed feedback is performed
using the PG attached to the motor to compensate for speed
fluctuations caused by slipping.
73600- • A-phase pulse (single pulse) input (voltage, complemen- TOE-C736-
PG-A2
A012X tary, open-collector input) 40.1
• Maximum input frequency: 32767 Hz
• Pulse monitor output: +12 V, 20 mA
(PG power supply output: +12 V, 200 mA max.)
9-8
Specifications of Options and Peripheral Devices
ProfiBus-DP
Communica-
73600-
tions Inter-
C022X
face Board Used to communicate with an Inverter from a host computer
SI-P using ProfiBus-DP communications to start/stop Inverter
-
ProfiBus-DP operation, read/set parameters, and read/set monitor constants
Communica- (output frequencies, output currents, etc.).
73600-
tions Inter-
C033X
face Board
SI-P1
InterBus-S
Used to communicate with an Inverter from a host computer
Communica-
using InterBus-S communications to start/stop Inverter opera-
tions Inter- * -
tion, read/set parameters, and read/set monitor constants (out-
face Board
put frequencies, output currents, etc.).
SI-R
CANopen
Used to communicate with an Inverter from a host computer
Communica-
using CANopen communications to start/stop Inverter opera-
tions Inter- * -
tion, read/set parameters, and read/set monitor constants (out-
Built-in Com- face Board
put frequencies, output currents, etc.).
SI-S1
(con- muni-
nected cations ControlNet
to con- Option Used to communicate with an Inverter from a host computer
Communica-
nector) Boards using ControlNet communications to start/stop Inverter opera-
tions Inter- * -
tion, read/set parameters, and read/set monitor constants (out-
face Board
put frequencies, output currents, etc.).
SI-U
CC-Link
Used to communicate with an Inverter from a host computer
Communica-
73600- using CC-Link communications to start/stop Inverter opera-
tions Inter- -
C032X tion, read/set parameters, and read/set monitor constants (out-
face Board
put frequencies, output currents, etc.).
SI-C
LONWORKS
Used to communicate with an Inverter from a host computer
Communica-
73600- using LONWORKS communications to start/stop Inverter
tions Inter- -
C035X operation, read/set parameters, and read/set monitor constants
face Board
(output frequencies, output currents, etc.).
SI-J
MECHA-
TROLINK- Used to communicate with an Inverter from a host computer
Communi- using MECHATROLINK communications to start/stop
cations Inter- 100-017-994 -
Inverter operation, read/set parameters, and read/set monitor
face Board constants (output frequencies, output currents, etc.).
SI-T
* Under development.
9-9
Appendix
This chapter provides precautions for the Inverter, motor, and peripheral devices and also pro-
vides lists of constants.
10
Varispeed G7 Control Methods
Details of the Varispeed G7-Series Inverter control methods and their features are provided in this section.
Current vector
Voltage/frequency control without a
fixed ratio control Current vector PG using a high-
Voltage/frequency Current vector
Basic Control with speed com- control without a performance mag-
fixed ratio control control with a PG
pensation using a PG netic flux and
PG speed estimator
(software)
Very high-perfor-
mance control
Variable speed
Very high-perfor- without a PG on
Variable speed control, applica-
mance control the motor side
control, particu- Applications tions requiring
with a PG on the (such as simple
larly for control of requiring high- high performance
motor side (sim- servodrives,
multiple motors precision speed without a PG on
Main Applications ple servodrives, torque control, and
with a single control using a PG the motor side,
high-precision torque limiting),
Inverter and for on the machine and for replacing
speed control, and function appli-
replacing existing side open-loop vector
torque control, and cations between
Inverters control of the pre-
torque limiting) flux vector and
vious VS-616G5.
open-loop vector 1
control.
Speed Control
±2 to 3% ±0.03% ±0.2% ±0.02% ±0.2%
Accuracy*2
Basic Speed
Perfor- Approx. 1 Hz Approx. 1 Hz 5 Hz 40 Hz 10 Hz
Response*3
mance
Maximum
Output Fre- 400 Hz 400 Hz 400 Hz 400 Hz 60 Hz, 120 Hz
quency
Starting
150%/3 Hz 150%/3 Hz 150%/1 Hz 150%/0 min−1 150%/0.3 Hz
Torque*4
10-2
Varispeed G7 Control Methods
Zero-servo
No No No Yes No
Control*8
Speed Estima-
tion (Detec- Yes (speed detec-
tion) Yes (speed and Yes (speed and Yes (speed and Yes (speed and
tion and rotation
Instantaneous rotation direction rotation direction rotation direction rotation direction
direction estima-
Speed estimation) estimation) detection) estimation)
tion)
Search*9
Automatic
Energy-sav- Yes Yes Yes Yes Yes
ing Control*10
10-3
Application Function Precautions
Observe the following precautions when using the application functions.
• Perform rotational autotuning during trial operation whenever it is possible to separate the motor and
machine. To achieve the characteristics of vector control described in Table 10.1, the control must be
adjusted within a range that the machine will not vibrate after rotational autotuning has been performed.
• With vector control, the motor and Inverter must be connected 1:1. Vector control is not possible when
multiple motors are connected to a single Inverter. Select an Inverter capacity so the rated motor current is
50% to 100% of the rated Inverter current.
• For estimated speed searching, the motor and Inverter must be connected 1:1. The speed search must be
performed at a frequency of 130 Hz or less and with a motor with the same number of frames as or one
frame less than the Inverter capacity.
• During high-slip braking, motor loss increases, so use a high-slip braking frequency of 5% ED or less, and
a braking time of 90 seconds or less. Once high-slip braking has started, the motor cannot be restarted until
it has stopped.
• Feed forward control is a function that improves the proportional gain of the motor speed in relation to the
change in the speed reference. Adjust the response to interference loads using the speed controller (ASR)
constants.
• The torque limit function will not operate during acceleration or deceleration (during soft start transition)
when using a control method such as open-loop vector 1 control. Even if the motor speed drops due to
torque limiting while set to a fixed speed, the speed will not fall below the minimum frequency and the
motor will not slip into reverse rotation. These conditions also apply to open-loop vector 2 control and
other application functions.
(Thermal relay)
Inverter M1
M2
M3
Fig 10.1
10-4
Varispeed G7 Control Methods
Conveyor
Inverter
PG
PG Speed Control Board
(PG-A2 or PG-D2)
Fig 10.2
Inverter M
Fig 10.3
Inverter M
PG
Fig 10.4
10
10-5
Inverter Application Precautions
This section provides precautions for selecting, installing, setting, and handling Inverters.
Selection
Observe the following precautions in selecting an Inverter.
Installing Reactors
A large peak current will flow in the power input circuit when the Inverter is connected to a large-capacity
power transformer (600 kVA or higher) or when switching a phase advancing capacitor. Excessive peak cur-
rent can destroy the convertor section. To prevent this, install a DC or AC reactor (optional) to improve the
power supply power factor.
DC reactors are built into 200 V Class Inverters of 18.5 to 110 kW and 400 V Class Inverters of 18.5 to 300
kW.
If a thyristor convertor, such as a DC drive, is connected in the same power supply system, connect a DC or
AC reactor regardless of the power supply conditions shown in the following diagram.
DC or AC reactor
Power supply Required
capacity (kVA)
DC or AC reactor
Not required
Fig 10.5
Inverter Capacity
When connecting special motors or multiple motors in parallel to an Inverter, select the Inverter capacity so
that the rated output current of the Inverter is 1.1 times the sum of all the motor rated currents.
Initial Torque
The startup and acceleration characteristics of the motor are restricted by the overload current ratings of the
Inverter that is driving the motor. The torque characteristics are generally less than those required when start-
ing using a normal commercial power supply. If a large initial torque is required, select an Inverter with a
somewhat larger capacity or increase the capacity of both the motor and the Inverter.
Emergency Stop
Although the Inverter's protective functions will stop operation when a fault occurs, the motor will not stop
immediately. Always provide mechanical stop and protection mechanisms on equipment requiring an emer-
gency stop.
10-6
Inverter Application Precautions
Options
Terminals B1, B2, , 1, 2, 3 are for connecting only the options specifically provided by Yaskawa.
Never connect any other devices to these terminals.
Installation
Observe the following precautions when installing an Inverter.
Installation in Enclosures
Either install the Inverter in a clean location not subject to oil mist, air-bourne matter, dust, and other contam-
inants, or install the Inverter in a completely enclosed panel. Provide cooling measures and sufficient panel
space so that the temperature surrounding the Inverter does not go beyond the allowable temperature. Do not
install the Inverter on wood or other combustible materials.
Installation Direction
Mount the Inverter vertically to a wall or other horizontal surface.
Settings
Observe the following precautions when making settings for an Inverter.
Upper Limits
The Digital Operator can be used to set high-speed operation up to a maximum of 400 Hz (depends on the car-
rier frequency). Incorrect settings can be dangerous. Use the maximum frequency setting functions to set
upper limits. (The maximum output frequency is factory-set to 60 Hz.)
Acceleration/Deceleration Times
The motor's acceleration and deceleration times are determined by the torque generated by the motor, the load 10
2
torque, and the load's inertial moment (GD /4). If the stall prevention functions are activated during accelera-
tion or deceleration, increase the acceleration or deceleration time. The stall prevention functions will increase
the acceleration or deceleration time by the amount of time the stall prevention function is active.
To reduce the acceleration or deceleration times, increase the capacity of the motor and Inverter.
10-7
Handling
Observe the following precautions when wiring or performing maintenance for an Inverter.
Wiring Check
The Inverter will be internally damaged if the power supply voltage is applied to output terminal U, V, or W.
Check wring for any mistakes before supplying power. Check all wiring and sequences carefully.
Setting the Power Supply Voltage Jumper (400 V Class Inverters of 55 kW or Higher)
If the jumper is inserted into a power tap that does not match the actual power supply voltage, the lifetime of
the transformer for the power supply or the wind capacity of the cooling fan may be reduced.
If the jumper is inserted and the voltage setting is too low for the actual power supply, a power surge may
occur on the transformer for the power supply and reduce the lifetime of the transformer.
If the jumper is inserted and the voltage setting is too high for the actual power supply, the wind capacity of
the cooling fan is reduced.
Insert the jumper into the power tap with the voltage setting nearest to the voltage of the actual power supply.
Refer to Chapter 4 Trial Operation for the procedure.
10-8
Motor Application Precautions
High-speed Operation
When using the motor at a speed higher than the rated speed, problems may arise in dynamic balance and
bearing durability. Contact your Yaskawa representative for details.
Torque Characteristics
The motor may require more acceleration torque when the motor is operated with the Inverter than when oper-
ated with a commercial power supply. Check the load torque characteristics of the machine to be used with the
motor to set a proper V/f pattern.
Vibration
The Inverter uses a high carrier PWM to reduce motor vibration. (A constant can be set to select low carrier,
PWM modulation control as well.) When the motor is operated with the Inverter, motor vibration is almost the
same as when operated with a commercial power supply.
Motor vibration may, however, become greater in the following cases.
Imbalanced Rotor
Take special care when the motor is operated at a speed higher than the rated speed.
Noise
Noise varies with the carrier frequency. At high carrier frequencies, the noise is almost the same when the
motor is operated with a commercial power supply. Motor noise, however, becomes louder when the motor is
operated at a speed higher than the rated speed.
10-9
Using the Inverter for Special Motors
Observe the following precautions when using a special motor.
Pole-changing Motor
The rated input current of pole-changing motors differs from that of standard motors. Select, therefore, an
appropriate Inverter according to the maximum input current of the motor to be used. Before changing the
number of poles, always make sure that the motor has stopped. Otherwise, the overvoltage protective or over-
current protective mechanism will be actuated, resulting in an error.
Submersible Motor
The rated input current of submersible motors is higher than that of standard motors. Therefore, always select
an Inverter by checking its rated output current. When the distance between the motor and Inverter is long, use
a cable thick enough to connect the motor and Inverter to prevent motor torque reduction.
Explosion-proof Motor
When an explosion-proof motor is to be used, it must be subject to an explosion-proof test in conjunction with
the Inverter. This is also applicable when an existing explosion-proof motor is to be operated with the Inverter.
Since the Inverter itself is, however, not explosion-proof, always install it in a safe place.
Gearmotor
The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
In particular, continuous operation of an oil-lubricated motor in the low speed range may result in burning. If
the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer.
Synchronous Motor
A synchronous motor is not suitable for Inverter control. If a group of synchronous motors is individually
turned ON and OFF, synchronism may be lost.
Single-phase Motor
Do not use an Inverter for a single-phase motor. The motor should be replaced with a 3-phase motor.
10-10
Conformance to UL Standard
Conformance to UL Standard
To comply with UL standard, follow the appropriate installation instructions.
Installation Site
Install the Inverter in a pollution degree 2 environment or equivalent.
10-11
Control Circuit Terminal
A UL Listed, Class 2 power supply must be used for the control circuits. See below table.
.
Interrupting Rating
Varispeed G7 is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical
amperes, 240 VAC maximum (200 V Class) and 480 VAC maximum (400 V Class).
Use a circuit breaker or fuses having an interrupting rating not less than 100,000 RMS symmetrical amperes,
600 VAC maximum.
10-12
Conformance to CE Markings
Conformance to CE Markings
Points regarding conformance to CE markings are given below.
CE Markings
CE markings indicate conformance to safety and environmental standards that apply to business transactions
(including production, imports, and sales) in Europe. There are unified European standards for mechanical
products (Machine Directive), electrical products (Low Voltage Directive), and electrical noise (EMC Direc-
tive). CE markings are required for business transactions in Europe (including production, imports, and sales).
The Varispeed G7-Series Inverters bear CE markings indicating conformance to the Low Voltage Directive
and the EMC Directive.
• Low Voltage Directive: 2006/95/EC
• EMC Directive: 2004/108/EC
Machinery and installations that incorporate the Inverter are also subject to CE markings. It is ultimately the
responsibility of customers making products incorporating the Inverter to attach CE markings to the finished
products. The customer must confirm that the finished products (machines or installations) conform to the
European Standards.
10-13
Wiring Example
This example shows wiring for conforming to undervoltage reference.
Thermal switch Thermal relay
contact trip contact
Braking Unit 3 4 1 2
(optional) + +0 P
Level
detector
-0 B
Motor
2MCCB Braking Resistor Unit
FU - (optional)
FU Cooling fan
FV
FW *1 FV IM
+1 +3 -
Noise FW
Fuse 1MCCB filter
MC
Inverter U
3-phase power R R/L1 U/T1
200 to 240 V S S/L2 V
CIMR-G7B2018 V/T2 IM
50/60 Hz
T W
T/L3 W/T3
Vm
ON
2MCCB THRX OFF MC
MC 4 Pulse B Wiring d
distance:
MA
Fault contact
reference 2 S6 30 m max.
Multi-step speed
Jog frequency
selection S7
External
Multi-function baseblock command S8 MP Pulse train output
contact inputs
Multi-step speed 0 to 32 kHz (2.2 kΩ)
Factory AC Default: Output
settings
reference 3 S9
frequency
Multi-step speed
reference 4 S10
Ammeter adjustment
Acc/dec time 1 S11 AM 20k Ω
Multi-function analog output 2
Emergency stop -10 to 10 V 2 mA
(NO) S12
- AM +
Default: Output current
0 to +10 V
CN5 (NPN setting) +24V 8mA
Ammeter adjustment
SC FM 20k Ω
Multi-function analog output 1
AC - + -10 to 10 V 2 mA
FM Default: Output frequency
+24V 0 to +10 V
R+
R- P3
MEMOBUS Open collector 3
communications S+ Factory setting:
RS-485/422 C3 Inverter operation
ready
S- P4
Open collector 4
Factory setting:
IG C4 minor fault
*3
* 1. The main circuit is separated from the terminal cover for safety reasons.
* 2. The contact output circuit is separated from the main circuit and the control circuit by reinforced insulation.
It can be connected to extra-low voltage circuits or circuits that are 250 VAC 1 A, 30 VDC 1 A or less.
* 3. The control circuit is an extra-low voltage circuit and separated from the main circuit and the contact output circuit by reinforced insulation. Always
connect it to extra-low voltage circuits.
Fig 10.6
10-14
Conformance to CE Markings
Input Fuses
In order to conform to the Low Voltage Directive, fuses must be provided for inputs. Use UL-compatible input
fuses with ratings higher than the voltages and currents, and fusing I2t specifications within the ranges shown
in the table below.
10-15
Table 10.4 Selection Requirements for Input Fuses with Examples (Continued)
Selection Requirements Input Fuse (Examples)
Inverter Model Fusing
Voltage
Number Voltage Current Fusing I2t
Class Model Number Manufacturer Ratings I 2t
CIMR-G7B (V) (A) (A2sec)
(A2sec)
600V
40P4 480 5 16 to 660 CR6L-20/UL FUJI 26
20A
600V
40P7 480 10 19 to 660 CR6L-20/UL FUJI 26
20A
600V
41P5 480 10 46 to 660 CR6L-30/UL FUJI 59
30A
600V
42P2 480 15 78 to 660 CR6L-50/UL FUJI 317
50A
600V
43P7 480 20 110 to 660 CR6L-50/UL FUJI 317
50A
600V
44P0 480 30 220 to 660 CR6L-50/UL FUJI 317
50A
600V
45P5 480 40 240 to 900 CR6L-50/UL FUJI 317
50A
600V
47P5 480 50 320 to 900 CR6L-75/UL FUJI 564
75A
600V
4011 480 50 1000 to 1800 CR6L-100/UL FUJI 1022
100A
600V
4015 480 60 1500 to 4100 CR6L-150/UL FUJI 3070
150A
600V
4018 480 70 530 to 5800 CR6L-150/UL FUJI 3070
150A
600V
4022 480 90 1130 to 5800 CR6L-150/UL FUJI 3070
400 V 150A
Class 600V
4030 480 110 1700 to 5800 CR6L-150/UL FUJI 3070
150A
600V
4037 480 140 2000 to 13000 CR6L-200/UL FUJI 5200
200A
600V
4045 480 160 3000 to 13000 CR6L-200/UL FUJI 5200
200A
600V
4055 480 220 6800 to 55000 CR6L-300/UL FUJI 17700
300A
600V
4075 480 280 9000 to 55000 CR6L-300/UL FUJI 17700
300A
700V
4090 480 330 12000 to 23000 A70P400-4 FERRAZ 19000
400A
700V
4110 480 400 18000 to 64000 A70P450-4 FERRAZ 24000
450A
700V
4132 480 450 28000 to 250000 A70P600-4 FERRAZ 43000
600A
700V
4160 480 540 40000 to 250000 A70P700-4 FERRAZ 59000
700A
700V
4185 480 620 43000 to 400000 A70P900-4 FERRAZ 97000
900A
700V
4220 480 750 63000 to 400000 A70P900-4 FERRAZ 97000
900A
700V
4300 480 1000 94000 to 920000 A70P1000-4 FERRAZ 120000
1000A
10-16
Conformance to CE Markings
EMC Directive
Varispeed G7-Series Inverters satisfy testing for conformance to the EMC Directive under the conditions
described in European Standard EN61800-3.
Installation Method
In order to ensure that the machinery or installation incorporating the Inverter conforms to the EMC Directive,
perform installation according to the method below.
• Install a noise filter that conforms to European Standards on the input side. (Refer to Table 10.5 EMC
Noise Filters).
• Use a shielded line or metal piping for wiring between the Inverter and Motor. Make the wiring as short as
possible.
• To suppress harmonics, install a DC reactor in CIMR-G7B20P4, 20P7, 40P4, and 40P7 models. (Refer to
Table 10.6 DC Reactors for Suppressing Harmonics.)
Inputs
Inverter
Filter
Wiring length:
40 cm max.
Metallic plate
Wiring length: 20 m max.
Remove the paint on the ground side.
IM
Fig 10.7 Installation Method for Filter and Inverter (CIMR-G7B20P4 to 2015, 40P4 to 4015) 10
10-17
R/L1, S/L2, T/L3 PE
Remove the paint on the ground side.
Inputs
Inverter
Filter
Outputs
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3
Wiring length:
40 cm max.
Metallic plate
Wiring length: 20 m max.
Remove the paint on the ground side.
IM
Fig 10.8 Installation Method for Filter and Inverter (CIMR-G7B2018 to 2110, 4018 to 4300)
10-18
Conformance to CE Markings
40P4
400 V Class UZDA-B YASKAWA 3.2 A 28 mH X010052
40P7
10-19
Wiring Examples
This section provides wiring examples to connect a Braking Unit and other peripheral devices to the main
circuits, examples of wiring a transformer to Inverter I/O, and other aspects of Inverter wiring.
Short-circuit bar
Fault contacts
10-20
Wiring Examples
Fault contacts
Forward Run/Stop
Forward Run Command (forward run when ON)
Reverse Run/Stop
Reverse Run Command (reverse run when ON)
Braking Unit
External fault
* 1. Remove the short-circuit bar (normally connected) from + 1 and + 2 when connecting a DC Reactor (Optional).
* 2. Disable stall prevention during deceleration by setting L3-04 when using a Braking Resistor Unit. The motor may not stop within the decel-
eration time if this setting is not changed.
Fig 10.10
10
10-21
Using Braking Units in Parallel
This example shows wiring for using two Braking Units in parallel.
There are connectors for selecting whether each Braking Unit is to be a Master or Slave. Select “Master” for
the first Braking Unit only, and select “Slave” for all other Braking Units (i.e., from the second Unit onwards).
detector
Level
Braking Unit 2
MCCB
Motor
R/L1 U/T1
3-phase power Inverter
200 to 220 V 50 Hz S/L2 V/T2
200 to 230 V 60 Hz
T/L3 W/T3
Cooling fan
* Disable stall prevention during deceleration by setting L3-04 to Resistor Unit. The motor may
not stop within the deceleration time if this setting is not changed.
Fig 10.11
10-22
Wiring Examples
detector
Level
Braking Unit
Thermal switch
MCCB
Motor
R/L1 U/T1
3-phase power Inverter
380 to 480 V S/L2 V/T2
50/60 Hz W/T3
T/L3
Cooling fan
Voltage
setting
External fault
* Disable stall prevention during deceleration by setting L3-04 to Resistor Unit. The motor may
not stop within the deceleration time if this setting is not changed.
Fig 10.12
10
10-23
Using a VS Operator
This example shows wiring for using a VS Operator. The VS Operator model number is JVOP-95• or
JVOP-96 •.
CIMR-G7B27P5 (200 V Class Inverters of 7.5 kW)
Short-circuit bar
(Standard)
MCCB
Motor
R/L1 U/T1
3-phase power
S/L2 Inverter V/T2
T/L3 W/T3
JVOP-95•, C-96• VS Operator
Sequence common (0 V)
Shield terminal
Multi-function contact
output (Default: Running
signal)
Fig 10.13
10-24
Wiring Examples
Using Transistors for Input Signals and a 0-V Common in Sinking Mode
with an Internal Power Supply
Set CN5 (shunt connector) on the control board to NPN as shown below for a sequence that uses an NPN tran-
sistor for an input signal (0-V command and sinking mode) and an internal +24-V power supply.
+1 +2 - B1 B2
MCCB
3-phase power
R R/L1 U/T1 Motor
S S/L2 V/T2 IM
T T/L3 Inverter W/T3
Ground
S1
Forward Run/Stop
S2
Reverse Run/Stop
S3
External fault
S4
Fault reset
Multi-function S5
contact inputs
Multi-step
Factory speed setting 1
settings
S12
Emergency stop CN5 (NPN setting) +24 V 8 mA
(NO contact)
SC
+24 V
E(G)
Shield wire
connection terminal
Fig 10.14
10-25
Using Transistors for Input Signals and a +24-V Common in Sourcing
Mode
Set CN5 (shunt connector) on the control board to PNP as shown below for a sequence that uses a PNP tran-
sistor for an input signal (+24-V common and sourcing mode) and an internal +24-V power supply.
+1 +2 - B1 B2
MCCB
3-phase power
R R/L1 U/T1 Motor
S S/L2 V/T2 IM
T T/L3 Inverter W/T3
Ground
S1
Forward Run/Stop
S2
Reverse Run/Stop
S3
External fault
S4
Fault reset
Multi-function S5
contact inputs
Multi-step
Factory speed setting 1
settings
S12
Emergency stop CN5 (PNP setting) +24 V 8 mA
(NO contact)
SC
+24 V
E(G)
Shield wire
connection terminal
Fig 10.15
10-26
Wiring Examples
Using Transistors for Input Signals and a 0-V Common in Sinking Mode
with an External Power Supply
Set CN5 (shunt connector) on the control board to EXT as shown below for a sequence that uses an NPN tran-
sistor for an input signal (0-V common and sinking mode) and an external +24-V power supply.
+1 +2 - B1 B2
MCCB
3-phase power
R R/L1 U/T1 Motor
S S/L2 V/T2 IM
T T/L3 Inverter W/T3
Ground
S1
Forward Run/Stop
S2
Reverse Run/Stop
S3
External fault
S4
Fault reset
Multi-function S5
contact inputs
Multi-step
Factory
settings speed setting 1
S12
Emergency stop CN5 (EXT setting) +24 V 8 mA
(NO contact) External
+24V
SC
+24 V
E(G) Shield wire
connection terminal
Note:
Set EXT as shown at the right even for
a PNP input signal transistor
sequence connection (+24-V S12
common/sourcing mode) with a +24-V
external power supply. +24 V 8 mA
CN5 (EXT setting)
External
+24V
SC
+24 V
Fig 10.16
10-27
Using Contact and Open Collector Outputs
This example shows wiring for contact outputs and open collector outputs.
The following example is for the CIMR-G7B25P5 (200 V Class Inverter for 5.5 kW).
+1 +2 - B1 B2
MCCB
R R/L1 U/T1 Motor
T T/L3 Inverter
W/T3
Ground
Surge
absorber
MA
M2
48 VDC max.
E(G) Flywheel
diode
P1
48 VDC max.
Open collector 1
Flywheel
(Default: zero speed)
diode
P2
Open collector 2
PC (Default: Freq agree)
Multi-function
open collector output
48 VDC 50 mA max.
Fig 10.17
10-28
User Constants
User Constants
Factory settings are given in the following table.
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
Language selection for Digital
A1-00
Operator display 7*1 b3-05 Speed search wait time 0.2
A1-05 Password setting 0 b3-18 Speed search retrial detection time 0.10
A2-01 to
User setting constants - b3-19 Number of speed search retrials 0
A2-32
b1-02 Operation method selection 1 b4-02 Timer function OFF-delay time 0.0
b1-06 Read sequence input twice 1 b5-04 Integral (I) limit 100.0
b1-10 Mode selection for zero-speed 0 b5-07 PID offset adjustment 0.0
b2-03 DC injection braking time at start 0.00 b5-10 PID output gain 1.0
b2-04 DC injection braking time at stop 0.50 b5-11 PID reverse output selection 0
b3-03 Speed search deceleration time 2.0 b5-15 PID sleep function operation level 0.0
10-29
Table 10.7 User Constants (Continued)
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
b5-16 PID sleep operation delay time 0.0 C1-10 Accel/decel time setting unit 1
b7-01 Droop control gain 0.0 C3-01 Slip compensation gain 1.0*2
288.20
b8-04 Energy-saving coefficient C4-01 Torque compensation gain 1.00
*5 *6
b8-06 Search operation voltage limiter 0 C4-03 Forward starting torque 0.0
C1-01 Acceleration time 1 10.0 C5-01 ASR proportional (P) gain 1 20.00*7
C1-02 Deceleration time 1 10.0 C5-02 ASR integral (I) time 1 0.500*7
C1-03 Acceleration time 2 10.0 C5-03 ASR proportional (P) gain 2 20.00*7
C1-04 Deceleration time 2 10.0 C5-04 ASR integral (I) time 2 0.500*7
C1-06 Deceleration time 3 10.0 C5-06 ASR primary delay time 0.004*7
C1-08 Deceleration time 4 10.0 C5-08 ASR integral (I) limit 400
C1-09 Emergency stop time 10.0 C5-10 ASR primary delay time 2 0.010
10-30
User Constants
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
C6-03*8 Carrier frequency upper limit 15.0*6 d3-02 Jump frequency 2 0.0
C6-04*8 Carrier frequency lower limit 15.0*6 d3-03 Jump frequency 3 0.0
d1-03 Frequency reference 3 0.00 d5-02 Torque reference delay time 0*7
d2-01 Frequency reference upper limit 100.0 E1-06 Base frequency 50.0*2
d2-02 Frequency reference lower limit 0.0 E1-07 Mid. output frequency 3.0*2
d2-03 Master speed reference lower limit 0.0 E1-08 Mid. output frequency voltage 13.2*2 *9
10-31
Table 10.7 User Constants (Continued)
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
E1-09 Min. output frequency 0.5*2 E4-01 Motor 2 rated current 1.90 *6
E1-10 Min. output frequency voltage 2.4*2 *9 E4-02 Motor 2 rated slip 2.90 *6
E1-11 Mid. output frequency 2 0.0*10 E4-03 Motor 2 no-load current 1.20 *6
E2-01 Motor rated current 1.90*6 E4-06 Motor 2 leak inductance 18.2*6
E2-02 Motor rated slip 2.90*6 E4-07 Motor 2 rated capacity 0.40*12
E2-11 Motor rated output 0.40*12 F1-09 Overspeed detection delay time 0.0*7
E3-03 Motor 2 max. voltage (VMAX) 200.0*2 F1-13 Number of PG gear teeth 2 0
10-32
User Constants
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
F4-05 Channel 1 output monitor bias 0.0 H1-05 Terminal S7 function selection 6 (4)*14
F4-06 Channel 2 output monitor bias 0.0 H1-06 Terminal S8 function selection 8 (6)*14
F5-09 DO-08 output mode selection 0 H3-02 Gain (terminal A1) 100.0
H1-02 Terminal S4 function selection 14 H3-12 Analog input filter time constant 0.03
10-33
Table 10.7 User Constants (Continued)
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
Alarm operation selection during
H4-01 Monitor selection (terminal FM) 2 L1-03 3
motor overheating
Motor overheating operation selec-
H4-02 Gain (terminal FM) 1.00 L1-04 1
tion
Motor temperature input filter time
H4-03 Bias (terminal FM) 0.0 L1-05 0.20
constant
H4-04 Monitor selection (terminal AM) 3 L2-01 Momentary power loss detection 0
H4-06 Bias (terminal AM) 0.0 L2-03 Min. baseblock time 0.2*6
H5-06 Send wait time 5 L3-03 Stall prevention limit during accel 50
H6-02 Pulse train input scaling 1440 L3-11 Overvoltage inhibit selection 0
H6-03 Pulse train input gain 100.0 L3-12 Overvoltage inhibit voltage level 380*9
H6-04 Pulse train input bias 0.0 L4-01 Speed agreement detection level 0.0
H6-05 Pulse train input filter time 0.10 L4-02 Speed agreement detection width 2.0
L1-02 Motor protection time constant 1.0 L5-01 Number of auto restart attempts 0
10-34
User Constants
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
OH1 detection of Inverter’s cool-
L5-02 Auto restart operation selection 0 L8-32 1
ing fan
Carrier frequency reduction selec-
L6-01 Torque detection selection 1 0 L8-38 tion 1*19
2.0
L6-02 Torque detection level 1 150 L8-39 Reduced carrier frequency
*6 *13
L6-06 Torque detection time 2 0.1 N1-03 Hunting-prevention time constant 10*6
Control method selection for N3-03 High-slip braking stop dwell time 1.0
L7-07 torque limit during acceleration 0
deceleration N3-04 High-slip braking OL time 40
L8-10 Cooling fan control selection 0 N4-17 Torque adjustment gain 0.8
L8-11 Cooling fan control delay time 60 N4-18 Feeder resistance adjustment gain 1.00
10-35
Table 10.7 User Constants (Continued)
Fac- Fac-
Set- Set-
No. Name tory No. Name tory
ting ting
Setting Setting
Speed estimator gain fluctuation Cumulative operation time selec-
N4-32 5.0 o2-08 0
frequency 1 tion
Speed estimator gain fluctuation
N4-33 20.0 o2-10 Fan operation time setting 0
frequency 2
Speed estimator gain fluctuation Fault trace/fault history clear func-
N4-34 200.0 o2-12 0
rate tion
Output power monitor clear selec-
N5-01 Feed forward control selection 0*7 o2-14
tion
0
N5-03 Feed forward proportional gain 1.0 o3-01 Copy function selection 0
10-36
Index
Index-1
Index
O undertorque 2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-16
undertorque detected 1 - - - - - - - - - - - - - - - - - - - - - - - - - - -7-8
open chassis type - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4
undertorque detected 2 - - - - - - - - - - - - - - - - - - - - - - - - - - -7-8
open-loop vector control - - - - - - - - - - - - - - - - - - - - - - - - - 4-9
user constant access levels - - - - - - - - - - - - - - - - - - - - - - - - 4-17
operation errors - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-19
option card communications error - - - - - - - - - - - - - - - - - - -7-17 V
option card connection error - - - - - - - - - - - - - - - - - - - - - - -7-11
V/f control - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4-8
option card selection error - - - - - - - - - - - - - - - - - - - - - - - -7-19
V/f control with PG - - - - - - - - - - - - - - - - - - - - - - - - - - - - -4-8
option communications error - - - - - - - - - - - - - - - - - - - - - - 7-9 V/f pattern - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-120, 6-122
output open-phase - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-4
verify mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-5, 3-13
overcurrent - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-2
VS operator - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10-24
overspeed - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-8, 7-16
overtorque 2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-16 W
overtorque detected 1 - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-7 watchdog timer fault - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-11
overtorque detected 2 - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-7 wire size - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-22
wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2-1
P
password - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-17, 6-156
periodic inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-2
periodic maintenance of parts - - - - - - - - - - - - - - - - - - - - - - 8-3
PG (encoder) pulses - - - - - - - - - - - - - - - - - - - - - - - - - - - -2-39
PG disconnection - - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-16
PG disconnection detected - - - - - - - - - - - - - - - - - - - - - - - - 7-8
PG pulse monitor output dividing ratio - - - - - - - - - - - - - - - 6-161
PG rotation direction - - - - - - - - - - - - - - - - - - - - - - - - - - 6-160
PG speed control card - - - - - - - - - - - - - - - - - - - - - - - - - 6-160
PG speed control cards - - - - - - - - - - - - - - - - - - - - - - - - - -2-31
PID control - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-106
PID control selection error - - - - - - - - - - - - - - - - - - - - - - - -7-19
PID feedback reference lost - - - - - - - - - - - - - - - - - - - 7-8, 7-17
power ON- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-3
Q
quick programming mode - - - - - - - - - - - - - - - - - - - - - 3-5, 3-8
R
radio interference - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2-20
rated current - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-58
RJOG - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-84
run command - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-10
S
S-curve characteristics - - - - - - - - - - - - - - - - - - - - - - - - - -6-21
setting speed limit bias - - - - - - - - - - - - - - - - - - - - - - - - - 6-132
slip compensation function - - - - - - - - - - - - - - - - - - - - - - -6-36
speed control with PG - - - - - - - - - - - - - - - - - - - - - - - - - 6-158
stabilizing speed - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-41
stall prevention function - - - - - - - - - - - - - - - - 6-23, 6-25, 6-50
standard connection diagrams - - - - - - - - - - - - - - - - - - - - - -2-15
standard inverter specifications - - - - - - - - - - - - - - - - - - - - - 9-2
stopping methods - - - - - - - - - - - - - - - - - - - - - - - - - - - - -6-12
straight solderless terminals - - - - - - - - - - - - - - - - - - -2-23, 2-38
surge absorber - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2-17
switching motors when the power supply is ON - - - - - - - - - - 6-149
T
terminal block - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-5
thermal overload relay - - - - - - - - - - - - - - - - - - - - - - - - - -2-19
tightening torque - - - - - - - - - - - - - - - - - - - - - - - - - - - - -2-38
timer function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-105
torque compensation - - - - - - - - - - - - - - - - - - - - - - - - - - -6-38
torque limit function - - - - - - - - - - - - - - - - - - - - - - - - - - -6-46
trial operation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-1
troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - 7-1, 7-24
U
undertorque 1 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -7-16
Index-2
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
Date of Rev.
Publication No. Section Revised Content
YASKAWA
In the event that the end user of this product is to be the military and said product is to be
employed in any weapons systems or the manufacture thereof, the export will fall under
the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant