BECAFZAR UPS+HMI Catalog
BECAFZAR UPS+HMI Catalog
1
FEATURES :
2
Standard Specification
Ac input
Supply phase & voltage: Three phase 400VAC/440VAC,3ph 4wire with protective earth
Supply voltage variation: +/-10%
Supply frequency: 50Hz with option for 60Hz
Supply frequency variation: +/-5%
UPS Output
Output voltage: 110VAC/220VAC, 380VAC single phase / three phase
Static voltage regulation: +/-2% for 0 -100% load variation
Dynamic voltage regulation: +/-7% for 100% load step,500ms recovery to within static limits
Overload capability: 150% for 1 m inute,125% for 10 m inutes,110% for 20 minutes
Short circuit capability: 2 x rated output current for 5 seconds
Waveform : Sinusoidal
Distortion: <3% with linear load <5% with non linear load
Crest Factor (Load Current): 3:1
Frequency: 50Hz with option for 60H z,+/-0.1% controlled
or synchronized to the bypass supply
Charger 90-95% at full load
Efficiency
Inverter 80-90% depends on model and rating
Mechanical
Protection Rating IP42 ( IP52 option)
Enclosure Finish RAL7032 / RAL 7035
Cooling power module assisted cooling dependant on rating
Audible Noise Level 50 - 65dBA dependant on rating and load
General
Operating temperature range: -10oC to +50°C
Storage temperature range: -20oC to +70°C
Operating altitude: 0 to 1000m
Operating humidity: 10% to 90% RH - non condensing
3
instrumentation & monitoring
HMI touch Screen Display The UPS user interface provides indication of measured UPS
operating values. The settings can be changed and operating mode
selected.
Measured values are displayed on the measurement page.
Main measured value including output voltage and current are
displayed on the main page.
The status of all parts of UPS comprising battery charger and Inverter
and static switch and manual bypass switch and position of input and
output switches and battery circuit breaker indicate on the HMI panel.
A password system protects the UPS configuration against
unauthorized changes.
measurements Rectifier input voltage, output voltage & current
Battery terminal voltage, current & charge state
UPS output voltage, current
Alarm s & Status Comprehensive set of UPS, rectifier, inverter, bypass and battery
alarms and status indications.
Event History The history log can hold up to 1000 events.
Graph The trends of Important parameters such as output current and voltage
and battery current and voltage and main input voltage are displayed
on the graph page.
Analog measurements:
Rectifier measurements Rectifier input voltage, and input current
Rectifier output voltage and current
Battery measurements Battery terminal voltage, current
4
Other Specification
Panel lighting
Remote alarm relay contacts (Rectifier fail - DC fail - Inverter fail- Bypass fail)
5
Standard Ups single line diagram