En1b0101 Ge51r1105d
En1b0101 Ge51r1105d
CONTROLLER
HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION INSTRUCTIONS
EN1B-0101GE51 R1105D 2
EXCEL 50 INSTALLATION INSTRUCTIONS
CONTENTS
Revision Overview........................................................................................................................................................................ 5
General .......................................................................................................................................................................................... 5
Safety Instructions .................................................................................................... 5
Hardware Overview .................................................................................................. 6
Version Overview...................................................................................................... 6
Dimensions ............................................................................................................... 7
Mounting ....................................................................................................................................................................................... 8
Housing .................................................................................................................... 8
Front Door ............................................................................................................ 8
Inside Cabinet without MMI .................................................................................. 9
Inside Cabinet with MMI ..................................................................................... 10
Application Module ................................................................................................. 10
Installation .................................................................................................................................................................................. 10
Terminal Details...................................................................................................... 11
Block A ............................................................................................................... 11
Block B ............................................................................................................... 11
Cabling ................................................................................................................... 11
Cable Routing .................................................................................................... 11
Shielding ............................................................................................................ 11
Cable Lengths and Cross Sectional Areas ......................................................... 12
Analog Inputs.......................................................................................................... 12
Technical Description ......................................................................................... 12
Technical Specification....................................................................................... 12
Pull-Up Resistor Handling .................................................................................. 13
Sensors and Transducers .................................................................................. 14
Digital Inputs ........................................................................................................... 15
Technical Description ......................................................................................... 15
Technical Specification....................................................................................... 15
Connection Examples ........................................................................................ 15
Analog Outputs ....................................................................................................... 15
Technical Description ......................................................................................... 15
Technical Specification....................................................................................... 15
Relay Modules.................................................................................................... 15
Digital Outputs ........................................................................................................ 16
Technical Description ......................................................................................... 16
Technical Specification....................................................................................... 16
Connection Examples ........................................................................................ 17
Power Supply.......................................................................................................... 17
CRT-Series ........................................................................................................ 17
1450 Series ........................................................................................................ 17
Standard Transformers ...................................................................................... 18
Screw Terminal Block Installation ........................................................................... 18
Adjusting the MMI Display Contrast ........................................................................ 19
Front Door Mounted with MMI ............................................................................ 19
DIN Rail Mounted with MMI................................................................................ 19
Communication .......................................................................................................................................................................... 19
C-Bus...................................................................................................................... 20
C-Bus Termination ............................................................................................. 20
Cable Specification............................................................................................. 20
C-Bus Extension by Using Repeaters ................................................................ 20
C-Bus Connection Procedure............................................................................. 21
LONWORKS Network Interface ................................................................................. 21
LONWORKS Bus Termination............................................................................... 21
LONWORKS Service LED Diagnostics ...................................................................... 22
Controller Serial Port .............................................................................................. 24
3 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
MMI Connection..................................................................................................24
Cable Specifications............................................................................................24
Modem or ISDN Terminal Adapter Connections .................................................24
Changing Between MMI and Modem Connection ...............................................24
EN1B-0101GE51 R1105D 4
EXCEL 50 INSTALLATION INSTRUCTIONS
REVISION OVERVIEW
On the following pages, changes have been made compared to the previous release of this document:
Page: Change:
13 Section "Pull-Up Resistor Handling" has been modified.
34 Section "LON-Bus (i.e. LonWorks Network)" has been modified.
GENERAL
Safety Instructions
• When performing any work (installation, mounting,
start-up), all instructions given by the manufacturer and
in particular the safety instructions provided in these In- CAUTION
stallation Instructions are to be observed. Disconnect the power supply before you start to in-
• The Excel 50 Controller may be installed and mounted stall the Excel 50 Controller. Do not reconnect the
only by authorized and trained personnel. power supply until you have completed installation.
• If the unit is modified in any way, except by the manu- IMPORTANT
facturer, all warranties concerning operation and safety To comply with CE requirements, devices with a
are invalidated. voltage in the range of 50 to 1000 Vac or 75 to
• Make sure that certain local standards and regulations 1500 Vdc which are not provided with a supply
are observed at all times. Examples of such regulations cord and a plug or with other means for discon-
are VDE 0800 and VDE 0100. nection from the supply having a contact
• Use only accessory equipment coming from or approved separation of at least 3 mm in all poles, must have
by Honeywell. the means for disconnection incorporated in the
fixed wiring.
• Before the system is dismantled, disconnect the power
supply. Do this by removing the terminal block or by in-
stalling an additional 3rd-party switch onto the DIN rail
close to the controller; see the following caution and
CAUTION
note. Disconnect the power supply before removing or
plugging in the application module.
5 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
Hardware Overview
M+ M- M+ M- M+ M-
M-Bus
On Short Slave
5 4 3 2 1
9 8 7 6
PW3
Power RS232C
V+ V- RX TX
Version Overview
*Version can be upgraded by firmware. Firmware with
Housing:
integrated modem communication is available for down-
With Man-Machine-Interface (MMI) loading to the controller.
Without MMI
Mounting:
Application Module: Front door
Standalone (EPROM) Cabinet, front side facing DIN rail
Standalone (Flash-EPROM)* Cabinet, back side facing DIN rail
C-Bus (Flash-EPROM)*
C-Bus/serial port for Meter-Bus (Flash-EPROM)* Terminals:
LONWORKS network (Flash-EPROM)* Screw Terminal blocks
C-Bus/LONWORKS network (Flash-EPROM)*
EN1B-0101GE51 R1105D 6
EXCEL 50 INSTALLATION INSTRUCTIONS
Dimensions
0000042a
7.79 in. (198 mm)
LCD DISPLAY
5.90 in. (150 mm)
STANDARD DIN-CUTOUT
CUTOUT
7.32 in. (186 mm)
(34 mm)
1.34 in.
1.34 in.
PORT FOR
APPLICATION
MODULE
DIN-RAIL DIN-RAIL
1 MOUNTING
CLIP
MOUNTING
CLIP
2
5.43 in. (138 mm)
CUTOUT
PORT A PORT B
SERIAL -PORT
Fig. 7. Dimensions
7 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
MOUNTING
If the Excel 50 Controller has an MMI, the housing is mounted
either in the front door of a cabinet or on a DIN rail with the
back facing to the DIN rail.
The controller without an MMI is mounted on a DIN rail with
the front facing to the DIN rail.
Table 1. Mounting versions
where
MMI version necessary accessory*
mounted
XL 50 ACC3 - rubber
cutout in
front door sealing ring and front door
front door
mounting clamps
yes
inside cabinet DIN rail DIN rail mounting clips
no inside cabinet DIN rail DIN rail mounting clips
*The DIN rail mounting clips are part of the delivery. The
Accessory kit XL 50 ACC3 for front door mounting must be
ordered separately.
Housing
Front Door
1. Choose the position of the controller in the front door.
Observe the min. and max. distances to other devices in
Fig. 9. Inserting sealing ring
the front door.
2. Cut a rectangle measuring 7-21/64 in. x 5-7/16 in. 4. Insert the controller into the cutout in the front door.
(186 mm x 138 mm) out of the front door (standard DIN
cutout).
EN1B-0101GE51 R1105D 8
EXCEL 50 INSTALLATION INSTRUCTIONS
9 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
INSTALLATION
Direct wiring of the Excel 50 is performed using screw
terminal blocks. For proper installation, follow these
instructions. Read all of section "Installation" carefully.
BLOCK A BLOCK B
Fig. 13. Cabinet mounting with MMI The two screw terminal blocks are attached directly to the
controller housing.
EN1B-0101GE51 R1105D 10
EXCEL 50 INSTALLATION INSTRUCTIONS
IMPORTANT
Avoid joining sensor cables.
Shielding
Block B
00000046
15
A01
16
17
A02
18
19
A03
20
21
A04
22
23
DI1
24 GND
25
DI2
26
DI3
27 Fig. 18. Sensor shielding
28
29
DI4
30
Shielding of sensor and actuator cables with low protective
+10V/5mA REF. 31 voltages is not necessary if the general guidelines on cable
DI-POWER 32 routing are observed (see "Cable Routing", page 11). If these
33
AI1
34
guidelines cannot be observed, shielded cable must always
35 be used. The shielded cable must be grounded as shown in
AI2
36 Fig. 18.
37
AI3
38
IMPORTANT
39
AI4 Shielding of I/O cables that are connected to
40 AGND
AI5
41 peripherals such as sensors and actuators must be
42 grounded at the control cabinet side, only; this is in
43
AI6
44 order to avoid ground loops.
AI7
45 All Honeywell actuators are RFI suppressed in accordance
46
47
with VDE 0871/B and VDE 0875/N.
AI8
48
Lightning Protection
Please check with your local Honeywell representative for
Fig. 17. Screw Terminal Block B information on lightning protection.
NOTE: The output (18...30 Vdc) of terminal 32 in screw
terminal block B is not stabilized. If you wish to
connect terminal 32 to a digital input via a potential-
free relay, see Fig. 26 on page 15.
11 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
EN1B-0101GE51 R1105D 12
EXCEL 50 INSTALLATION INSTRUCTIONS
A A A
150 kΩ D 150 kΩ D 100 kΩ D
49.9 kΩ 49.9 kΩ 100 kΩ
13 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
Sensors and Transducers Analog Inputs Used as Digital Inputs (O.S. 2.04.xx or
higher)
00000061
0000062m
0 - 5 V 10 Vdc
4 33 31
A max. 5 mA 10 Vdc
3 34 32 31 max. 5 mA
2 31 1 33 32
I = 1 mA AI1
2 34 33
SAF25 AI1
SENSOR 35 34
AI2
0 - 10 V NTC 20 k 36
10 33 NOT CONNECTED 35
37 AI2
11 34 AI3 NORMALLY OPEN 36
B 38
12 31 37
I = 1 mA 39 L AI3
VMP ACTIVE AI4 230 Vac/ 50 Hz 38
SENSOR 40 AGND
41 120 Vac/ 60 Hz 39
AI5 AI4
0-10V 42 N 40 AGND
43 POWER 31 41
TRANSFORMER FOR AI6 10 Vac
ACTIVE SENSOR
44 42
C 45 43
AI7 31 AI6
46 44
0(4) to 47 NOT CONNECTED
R1 AI8 45
20 mA 48 NORMALLY CLOSED AI7
46
499
0.25% 47
L AI8
230 Vac/ 50 Hz 48
120 Vac/ 60 Hz
Fig. 22. Analog inputs, sensor connections
N
Analog Inputs Used as Digital Inputs (O.S. 2.03.xx or Fig. 24. Analog inputs used as digital inputs
lower)
Unconnected inputs have a default voltage of 0 V.
0000062a
10 Vdc
31 max. 10 mA
32 Table 6. Accuracy of analog inputs with NTC sensors
33
AI1
34
NOT CONNECTED 35 deviation / ± Kelvin
AI2
NORMALLY CLOSED 36 range (without sensor tolerance)
L AI3
37 NTC (20 kΩ)
230 Vac/ 50 Hz 38
120 Vac/ 60 Hz
AI4
39 -58 to <-40°F (-50 to <-40°C) ≤ 5.5 K
N 40 AGND
AI6
43 32 to <-4°F (-30 to <-20°C) ≤ 1.8 K
44
NOT CONNECTED
45 86 to <14°F (-20 to <-10°C) ≤ 1.1 K
NORMALLY OPEN AI7
46
47 158 to <32°F (-10 to <0°C) ≤ 0.8 K
L AI8
230 Vac/ 50 Hz 48
120 Vac/ 60 Hz
212 to <50°F (0 to <10°C) ≤ 0.6 K
N
266 to <122°F (10 to <50°C) ≤ 0.4 K
Fig. 23. Analog inputs used as digital inputs 266 to <158°F (50 to <70°C) ≤ 0.6 K
For normally-open contacts, a digital signal must be switched 266 to <194°F (70 to <90°C) ≤ 1.0 K
via the changeover contact of an additional relay. 266 to <212°F (90 to <100°C) ≤ 1.5 K
Unconnected analog inputs have a default voltage of 8.5 V.
This is interpreted by the controller as a logical 1. This means 266 to <248°F (100 to <120°C) ≤ 2.4 K
that, in general, no external relay is needed for normally-open 266 to <302°F (120 to <150°C) ≤ 5.3 K
contacts.
IMPORTANT
The relay contact must be suitable for switching low
voltage. In the case of long cable distances, the
analog input signal may be sensitive to interference.
In this case, an external relay may also be used for
normally-closed contacts.
EN1B-0101GE51 R1105D 14
EXCEL 50 INSTALLATION INSTRUCTIONS
pulse pause
frequency bounce time
duration interval
max. 15 Hz min. 20 ms min. 30 ms max. 5 ms
Connection Examples
15 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
MCE 3:
Relay terminal 16 controls the ON contact K3.
Relay terminal 17 controls the changeover contact K2.
Relay terminal 18 controls the changeover contact K1.
EN1B-0101GE51 R1105D 16
EXCEL 50 INSTALLATION INSTRUCTIONS
17 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
IMPORTANT
If there already are additional transformers, for
example supplying actuators or active sensors:
— Connect the 24 Vac (-) (secondary side) of the
Fig. 33. Connecting a cable to a screw terminal transformers together.
13. Attach the terminal blocks to the housing as shown in
IMPORTANT Fig. 35.
When installing a separate external transformer, do
not connect the cabinet ground to the controller
system ground.
5. If the distance between the controller and an actuator or
sensor with 24 Vac supply is greater than 550 ft
(170 m):
a) Choose a transformer from the transformers listed in
section "
Power Supply".
b) Connect the chosen transformer directly to the
actuator or sensor.
6. Connect sensors, transducers, etc. to the digital input
terminals.
7. Connect valves, actuators, relays, etc. to the analog
output terminals.
EN1B-0101GE51 R1105D 18
EXCEL 50 INSTALLATION INSTRUCTIONS
COMMUNICATION
The Excel 50 Controller has the capability to communicate
with the Excel Building Supervisor (XBS/XBSi, and Enterprise
Buildings Integrator) and other EXCEL 5000 devices via the
C-Bus. The Excel 50 Controller also has the capability to
communicate with devices on a LONWORKS network. A further
communication option is connection to a Meter-Bus. All
communications options are dependent upon the application
module, and not all options are available on one module (see
Table 16).
A modem/ISDN terminal adapter may be connected to Flash
EPROM versions with V2.01.00 software or newer to allow re-
mote communication with the controller.
Table 16. Application module versions
19 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
0000060c
LEDs
POWER, GRN Cable Specification
RESERVED
The max. cable length is 4,000 ft (1,200 m). There are
C-BUS TxD, YEL
C-BUS RxD, YEL
regional differences as to whether shielded or unshielded
RESERVED cable must/can be used.
C-BUS
IMPORTANT
TERMINATION In Europe, only shielded cable is permitted while in
SWITCH
the US, shielded or unshielded cable can be used.
4 5 6 Inside the cabinet: J-Y-(ST)Y 2 x 2 x 0.8
Outside the cabinet: A-Y-(ST) 2 x 2 x 0.8
C-BUS
In principle, data transmitting cables should be shielded in
SHIELD
C+
case of RFI.
C-
EN1B-0101GE51 R1105D 20
EXCEL 50 INSTALLATION INSTRUCTIONS
NOT USED
SHIELD
C-
A2
C+
specification for that cable type and bus type for each
repeater used. For example, adding repeaters for a
doubly-terminated bus using
JY (St) Y 2x2x0.8 cable increases the max. length
Fig. 39. LonWorks network connection 3,000 ft (900 m) for each repeater.
FTT devices can be wired in daisy chain, star, loop or any
combination thereof as long as the max. wire length re-
quirements given below are met. The recommended con-
LONWORKS Bus Termination
figuration is a daisy chain with two bus terminations. This One or two Termination Modules, part no. 209541B or part
layout allows for max. bus length, and its simple structure no. XAL-Term, are required for a LONWORKS Bus with FTT
presents the least number of possible problems, particularly devices on it, depending upon the configuration. See chapter
when adding on to an existing bus. "LonWorks System Engineering" of LonWorks Mechanisms –
21 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
Interface Description (Product Literature No.: EN0B- Table 22 describes each of the behaviors shown in the
0270GE51) for details. previous figure under different contexts. Again, this list is not
exhaustive and therefore does not provide explanations for
every possible service LED behavior.
LONWORKS Service LED Diagnostics
The LONWORKS service LED is used to diagnose the state of
the Excel 50 controller. In general:
— The controller is applicationless if the LED illuminates
continuously*.
— The controller has an application but, if the LED is
blinking, it is not configured.
— The controller is running normally if L2 is OFF.
The LONWORKS service LED is located on the application
module (see Fig. 39).
Pushing the LONWORKS service button will force a new
commissioning of the Excel 50. While commissioning, LED L2
continuously illuminates red for less than 1 minute and
afterwards return to the normal state (L2 = OFF).
A more detailed diagnosis can be carried out by observing the
duration of the ON and OFF states of the service LED in
connection with power ON / OFF. The following figure
illustrates the different service LED behaviors. These are the
most common behaviors, but others are possible since the
state of the service LED is under firmware control and can be
affected both by hardware and software anomalies.
EN1B-0101GE51 R1105D 22
EXCEL 50 INSTALLATION INSTRUCTIONS
23 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
MMI Connection
For direct communication the external operator interface
XI582 and the PC-based MMI XI584 can be connected to the
serial port.
When the cable from XI582 or XI584 is plugged in during
normal operation of an Excel 50 Controller with MMI, the EXCEL 50 (REAR VIEW)
SERIAL PORT
functionality of the Excel 50 MMI is disabled.
After unplugging the external MMI it takes up to 15 sec until
the local MMI activates again.
EN1B-0101GE51 R1105D 24
EXCEL 50 INSTALLATION INSTRUCTIONS
No Set-up for Standard Modem Behavior Set-up for In-house Telephone Systems
If no special modem behavior is required, there is no need to A common case of special modem behavior is when the
set up or initialize the modem/ISDN terminal adapter. The modem is connected to an in-house telephone network re-
Excel 50 Controller will automatically detect the device (MMI quiring a prefix to be dialed before the destination number to
or modem) attached to the serial port and set the appropriate provide access to the public telephone network. There are
communication speed. The controller will also automatically two important aspects of the special initialization of the
adapt to alphanumeric return codes used by the modem. This modem to consider:
automatic detection and adjustment can take up to 5
seconds. 1. Do not wait for the public network dial tone. Typically,
the init command ATX3 will trigger the modem to dial
NOTE: It is highly recommended to use a state-of-the-art without waiting for a public network dial tone. Save this
modem and leave it in its factory setting. modem set-up in the modem EEPROM with the com-
mand AT&W. Check the modem handbook to verify the
correct commands. Note that these commands are
Automatic Baudrate Synchronization executed automatically with the RESET MODEM com-
The default communication speed between the Excel 50 mand in the Excel 50 Controller Start-up Sequence.
Controller and the local modem/ISDN terminal adapter is 9.6 2. Add the prefix required for accessing the public tele-
Kbaud. phone network to the destination telephone number.
The communication speed between the Excel 50 and XBS Depending on the in-house telephone system, a certain
modems/ISDN terminal adapters is automatically syn- prefix may have to be added to the destination number
chronized by the two devices to the highest speed that both of in the XBS system configuration/site definition screen
the devices are capable of. This feature is called autobauding before sending the set-up to the remote Excel 50 con-
and is provided by all state-of-the-art modems / ISDN terminal troller.
adapters when left in their factory default settings.
The communication speed between the XBS and its modem /
ISDN terminal adapter is part of the modem set-up at the Set-up for Limited Communication Speed
XBS. The communication speed of the modem can be fixed to a
lower rate in case of data transmission errors due to tele-
phone line limitations. See section "Start-up Sequence" or
Auto / Manual Answer Detection see the Excel 50 User Guide, EN2B-0137GE51, for the
The Excel 50 Controller will automatically detect whether the procedure for fixing the baud rate.
modem/ISDN terminal adapter is initialized in auto-answer or
25 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
Troubleshooting
In case of any problems the handbook of the modem or ISDN
terminal adapter must be consulted.
A “Frequently Asked Questions and Troubleshooting”
document is available via the Honeywell Technical Assistance
Center (TAC) or, for Honeywell employees, on the HIVE
under:
Technical Assistance Center/Controllers/Excel 80 and 100
and 500 and 600/ technical literature/modemfaq.doc
or on the Honeywell DocuServer under:
http://web.ge51.honeywell.de/dep/mc/TAC_Tips/
Modem FAQ.doc
EN1B-0101GE51 R1105D 26
EXCEL 50 INSTALLATION INSTRUCTIONS
CAUTION
MOUNTING HOLES
TOP
BOTTOM
Use of the M20 Terminal on-board aircraft is for-
bidden. Use of a Cellular Engine in an aircraft, such
as for the purpose of wireless connection of an SIM CARD READER
aircraft-based HVAC system to an XBS central, can
endanger navigation, it interferes with the cellular net- OPERATING
STATUS LED
work, and it is illegal. Failure to comply with this pro-
hibition may lead to temporary suspension or per-
manent cancellation of Cellular Engine services for
the person who disregards this prohibition and/or to V.24 INTERFACE
POWER SUPPLY
AND AUDIO
FME ANTENNA
CONNECTOR
legal action against said person. SUB-D SOCKET INTERFACE
27 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
Serial Cable
For connecting the M20T to the Excel controller, a standard
RS232 cable (9-pin V24 sub-D sockets) is required.
EN1B-0101GE51 R1105D 28
EXCEL 50 INSTALLATION INSTRUCTIONS
29 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
EN1B-0101GE51 R1105D 30
EXCEL 50 INSTALLATION INSTRUCTIONS
INSERT
0000106a
METER-BUS CONNECTION (NOT METER-BUS
WIRES
AVAILABLE IN N. AMERICA)
The meter bus adapter PW3 is connected with the cable
XW586 to the RJ45 plug of the XD50-FCS-HE01-xx ("xx""
depends upon the language). The cable XW586 has a length
of 1.8 m.
Table 25. Cable XW586
3
CAUTION
Never connect V- of the PW3 to pin 2 of the Excel 50
1 Controller and V+ to pin 1. This could cause damage
to the Excel 50.
2
31 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
00000123
LEDs
POWER, GRN
METER BUS TxD, YEL
C-BUS TxD, YEL
C-BUS RxD, YEL
METER BUS RxD, YEL
C-BUS
TERMINATION
SWITCH
4 5 6
METER BUS
(RJ45 JACK)
Fig. 1. PW3 Meter Adapter power connections C-BUS
SHIELD
C+
Meter-Bus activity can by monitored using the LEDs on the
C-
HE01 application module (see Fig. 2).
device baud- mode energy vol. pwr. flow fwd. ret. temp. energy at ref.
rates temp. temp. diff. ref. day day
Siemens 300 1 X X X X X X X X
2WR4 2400 normal
300 2 X X X X X X
2400 fast
Schlumberger 300 1 X X X X X X X
CF50 2400 normal
300 2 X
2400 ref. day
Landis & Staefa 300 1 X X X X X X X X
Sonogyr WSD
Techem 300 1 X X X X X X
Delta-tech
Kompact and Split 2400
ABB / SVM 300 1 X X X X X X X
SVM 840 2400
Raab Karcher 300 1 X X X X X X X
Sensonic 2400
Kamstrup 300 1 X X X X X X X X
Multical 3 2400
Zenner Multidata S14 2400 1 X X X X X X X X1 X1
DZG Elektro 300 1 X
Baureihe S30 / 2400
DVS3016 9600
Relay 300 1 X2 X2
PadPuls M1C 2400
Relay 300 1 X2 X X3 X
PadPuls M4L 2400
1) Storage number 8.
2) PadPuls must be configured. Only one value can be counted.
3) Energy or volume at reference day depends on PadPuls configuration.
4) The Zenner meter requires twice as much power as other meters. Thus, only 1 Zenner meter can be connected to the PW3.
EN1B-0101GE51 R1105D 32
EXCEL 50 INSTALLATION INSTRUCTIONS
33 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
IMPORTANT
B-Port Config. The bus ID is a non-unique number (i.e. different
Excel 500 controllers can have the same bus ID in
Baudrate: !9600 common) between 0 and 99 (inclusive) which the
!BACK user can edit after a reset during the controller's
start-up sequence or by changing the configuration
property nciXL500BusSetup. The factory default is
Move the cursor with the arrow keys to the field to set baud "0", which enables C-Bus and Standard LONWORKS
rate for the B-Port. Use the '+' and '–' keys to edit the fields. communication. Assigning a bus ID other than "0" will
Confirm with ENTER. enable LONWORKS communication with Building
NOTE: Live CARE is now capable of autodetecting the con- Management functionality and disable C-Bus
troller baud rate setting, then switching it temporarily communication.
to 38.4 Kbaud. When Live CARE is disconnected,
the controller will switch back to the previous baud This screen displays the unique identification number for the
rate setting automatically within 15 seconds. Neuron chip in the controller.
Move the cursor to the 'BACK' field with the arrow keys. Move the cursor to the 'BACK' field with the arrow keys.
Confirm with ENTER. Confirm with ENTER.
C-Bus Meter-Bus
Select ‘C-Bus” and confirm with ENTER. The following screen Select ‘M-Bus” and confirm with ENTER. The following screen
appears: appears:
EN1B-0101GE51 R1105D 34
EXCEL 50 INSTALLATION INSTRUCTIONS
35 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
EN1B-0101GE51 R1105D 36
EXCEL 50 INSTALLATION INSTRUCTIONS
alarm buffer to see if they were detected by the con- Press ENTER to select the value. Change the value/state
troller. using the '+' or '–' keys. Confirm with ENTER.
Confirm with ENTER. Press CANCEL to return to the previous screen (list of user
If ‘Default Points’ has been selected, the following screen will addresses).
be displayed showing all default user addresses and their If ‘Alarm History’ has been selected, the following screen will
current values. be displayed showing all points in alarm as well as any
system alarms (max. 100 entries):
!<user addr.> <val>↑
!<user addr.> <val>1 !<user addr.> ↑
!<user addr.> <val> !<user addr.> 1
!<user addr.> <val>↓ !<user addr.>
!<user addr.> ↓
To manually set outputs, move the cursor to select the output
point from the list box using the arrow keys. Confirm with
NOTE: Alarms are generated for changes of state/value on
ENTER.
inputs, which allows shorting and opening the inputs
In the case of analog points, the following screen is displayed. at the switches and/or sensors and then checking the
alarm buffer to verify the wiring.
<user addr.> To view an alarm, move the cursor to select the default user
STATE/VALUE: address from the list box using the arrow keys. Confirm with
!0.00% ENTER. The following screen will appear:
<date.> <time>
Press ENTER to select the value. Change the value using the <user addr.>
'+' or '–' keys. Confirm with ENTER. In the case of digital <value>
points, the following screen is displayed. <alarm text>
37 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS
3
high fire risk.
Locate per UL 555S.
CAUTION
4 Locate separate from and below all building exhaust Equipment damage hazard.
fans and upstream of any prevailing winds. Failure to use listed/approved replacement parts can
damage the product, degrade operation, and result in
5 Exhaust to outside of building.
loss of safety function.
6 Locate airflow differential switch per CLEAFS405 and This product must be installed and operated within its
CLEAFS460 Airflow Differential Switches Installation environmental, mechanical, and electrical speci-
Instructions 95-6001. fications as contained in this document.
7 Locate UL-listed damper pressure / position indicator When servicing, use only listed/approved replace-
per damper installation instructions. ments parts ordered directly from the manufacturer.
8 Smoke control must be initiated by a listed fire alarm
control unit or in zone automatic alarm devices and
not devices located outside of the smoke control
zone interconnecting wiring must be within 20 feet (6
meters) and in conduit.
9 Refer to Smoke Control Fundamentals 77-1134.
10 Verify that the AC voltage source connected to inside
of main line voltage terminal block is from a UL 1481-
listed uninterruptible power supply. The main line
EN1B-0101GE51 R1105D 38
EXCEL 50 INSTALLATION INSTRUCTIONS
EN1B-0101GE51 R1105D 39
EXCEL 50 INSTALLATION INSTRUCTIONS
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: