0% found this document useful (0 votes)
41 views40 pages

En1b0101 Ge51r1105d

Uploaded by

iuryanskiy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views40 pages

En1b0101 Ge51r1105d

Uploaded by

iuryanskiy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

Excel 50

CONTROLLER
HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION INSTRUCTIONS

Copyright © 2005 Honeywell Inc. • All Rights Reserved


EN1B-0101GE51 R1105D
95-7568-10
EXCEL 50 INSTALLATION INSTRUCTIONS

Trademark Information Echelon, LON, LONMARK, LONWORKS, LonBuilder, NodeBuilder, LonManager,


LonTalk, LonUsers, LonPoint, Neuron, 3120, 3150, the Echelon logo, the LONMARK
logo, and the LonUsers logo are trademarks of Echelon Corporation registered in
the United States and other countries. LonLink, LonResponse, LonSupport, and
LonMaker are trademarks of Echelon Corporation.

EN1B-0101GE51 R1105D 2
EXCEL 50 INSTALLATION INSTRUCTIONS

CONTENTS

Revision Overview........................................................................................................................................................................ 5

General .......................................................................................................................................................................................... 5
Safety Instructions .................................................................................................... 5
Hardware Overview .................................................................................................. 6
Version Overview...................................................................................................... 6
Dimensions ............................................................................................................... 7

Mounting ....................................................................................................................................................................................... 8
Housing .................................................................................................................... 8
Front Door ............................................................................................................ 8
Inside Cabinet without MMI .................................................................................. 9
Inside Cabinet with MMI ..................................................................................... 10
Application Module ................................................................................................. 10

Installation .................................................................................................................................................................................. 10
Terminal Details...................................................................................................... 11
Block A ............................................................................................................... 11
Block B ............................................................................................................... 11
Cabling ................................................................................................................... 11
Cable Routing .................................................................................................... 11
Shielding ............................................................................................................ 11
Cable Lengths and Cross Sectional Areas ......................................................... 12
Analog Inputs.......................................................................................................... 12
Technical Description ......................................................................................... 12
Technical Specification....................................................................................... 12
Pull-Up Resistor Handling .................................................................................. 13
Sensors and Transducers .................................................................................. 14
Digital Inputs ........................................................................................................... 15
Technical Description ......................................................................................... 15
Technical Specification....................................................................................... 15
Connection Examples ........................................................................................ 15
Analog Outputs ....................................................................................................... 15
Technical Description ......................................................................................... 15
Technical Specification....................................................................................... 15
Relay Modules.................................................................................................... 15
Digital Outputs ........................................................................................................ 16
Technical Description ......................................................................................... 16
Technical Specification....................................................................................... 16
Connection Examples ........................................................................................ 17
Power Supply.......................................................................................................... 17
CRT-Series ........................................................................................................ 17
1450 Series ........................................................................................................ 17
Standard Transformers ...................................................................................... 18
Screw Terminal Block Installation ........................................................................... 18
Adjusting the MMI Display Contrast ........................................................................ 19
Front Door Mounted with MMI ............................................................................ 19
DIN Rail Mounted with MMI................................................................................ 19

Communication .......................................................................................................................................................................... 19
C-Bus...................................................................................................................... 20
C-Bus Termination ............................................................................................. 20
Cable Specification............................................................................................. 20
C-Bus Extension by Using Repeaters ................................................................ 20
C-Bus Connection Procedure............................................................................. 21
LONWORKS Network Interface ................................................................................. 21
LONWORKS Bus Termination............................................................................... 21
LONWORKS Service LED Diagnostics ...................................................................... 22
Controller Serial Port .............................................................................................. 24

3 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

MMI Connection..................................................................................................24
Cable Specifications............................................................................................24
Modem or ISDN Terminal Adapter Connections .................................................24
Changing Between MMI and Modem Connection ...............................................24

Remote Communications ...........................................................................................................................................................25


Modem Requirements .............................................................................................25
No Set-up for Standard Modem Behavior................................................................25
Automatic Baudrate Synchronization.......................................................................25
Auto / Manual Answer Detection .............................................................................25
Resetting the Modem ..............................................................................................25
Set-up for Special Modem Behavior ........................................................................25
Set-up for In-house Telephone Systems .................................................................25
Set-up for Limited Communication Speed ...............................................................25
Troubleshooting.......................................................................................................26
TCP/IP Dial-Up via TCP/IP Modem XM500.............................................................26

GSM Communication (Europe, only).........................................................................................................................................27


M20T Safety Precautions ........................................................................................27
Required Third-Party Equipment .............................................................................27
Serial Cable ........................................................................................................28
GSM Antenna Requirements ..............................................................................28
Antenna Examples ..............................................................................................28
GSM Antenna Installation........................................................................................29
M20 Terminal Set-up ...............................................................................................29

Meter-Bus Connection (not available in N. America) ...............................................................................................................31


Meter-Bus Connection Procedure .......................................................................31

Start-up Sequence ......................................................................................................................................................................33


Controller Setup.......................................................................................................33
B-Port..................................................................................................................34
C-Bus ..................................................................................................................34
LON-Bus (i.e. LonWorks Network) ......................................................................34
Meter-Bus ...........................................................................................................34
Modem Communication ......................................................................................34
Select Application ....................................................................................................35
Request Download ..................................................................................................36
Datapoint Wiring Check...........................................................................................36

Appendix 1: Smoke Control Mode .............................................................................................................................................38


Smoke Control Configuration...................................................................................38
Data File Set-Up ......................................................................................................38
Panel Reset .............................................................................................................38

EN1B-0101GE51 R1105D 4
EXCEL 50 INSTALLATION INSTRUCTIONS

REVISION OVERVIEW
On the following pages, changes have been made compared to the previous release of this document:

Page: Change:
13 Section "Pull-Up Resistor Handling" has been modified.
34 Section "LON-Bus (i.e. LonWorks Network)" has been modified.

GENERAL
Safety Instructions
• When performing any work (installation, mounting,
start-up), all instructions given by the manufacturer and
in particular the safety instructions provided in these In- CAUTION
stallation Instructions are to be observed. Disconnect the power supply before you start to in-
• The Excel 50 Controller may be installed and mounted stall the Excel 50 Controller. Do not reconnect the
only by authorized and trained personnel. power supply until you have completed installation.
• If the unit is modified in any way, except by the manu- IMPORTANT
facturer, all warranties concerning operation and safety To comply with CE requirements, devices with a
are invalidated. voltage in the range of 50 to 1000 Vac or 75 to
• Make sure that certain local standards and regulations 1500 Vdc which are not provided with a supply
are observed at all times. Examples of such regulations cord and a plug or with other means for discon-
are VDE 0800 and VDE 0100. nection from the supply having a contact
• Use only accessory equipment coming from or approved separation of at least 3 mm in all poles, must have
by Honeywell. the means for disconnection incorporated in the
fixed wiring.
• Before the system is dismantled, disconnect the power
supply. Do this by removing the terminal block or by in-
stalling an additional 3rd-party switch onto the DIN rail
close to the controller; see the following caution and
CAUTION
note. Disconnect the power supply before removing or
plugging in the application module.

5 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Hardware Overview

Fig. 3. Fuse, 4 A quick-acting (behind Terminal


Block A)

Fig. 4. Application module

M+ M- M+ M- M+ M-
M-Bus

On Short Slave

5 4 3 2 1
9 8 7 6
PW3

Power RS232C
V+ V- RX TX

Fig. 5. Meter-Bus adapter


Fig. 1. Excel 50 Controller housing

Fig. 6. Mounting accessories


Fig. 2. Screw terminal blocks

Version Overview
*Version can be upgraded by firmware. Firmware with
Housing:
integrated modem communication is available for down-
With Man-Machine-Interface (MMI) loading to the controller.
Without MMI
Mounting:
Application Module: Front door
Standalone (EPROM) Cabinet, front side facing DIN rail
Standalone (Flash-EPROM)* Cabinet, back side facing DIN rail
C-Bus (Flash-EPROM)*
C-Bus/serial port for Meter-Bus (Flash-EPROM)* Terminals:
LONWORKS network (Flash-EPROM)* Screw Terminal blocks
C-Bus/LONWORKS network (Flash-EPROM)*

EN1B-0101GE51 R1105D 6
EXCEL 50 INSTALLATION INSTRUCTIONS

Dimensions

0000042a
7.79 in. (198 mm)

LCD DISPLAY
5.90 in. (150 mm)

FAST ACCESS APPLICATION


KEYS MODULE

3.94 in. (100 mm)


BASIC FUNCTION KEYS

2.76 in. (70 mm) C-BUS PORT

3.19 in. (81 mm) 2.83 in. (72 mm)

STANDARD DIN-CUTOUT
CUTOUT
7.32 in. (186 mm)

4.17 in. (106 mm)


(34 mm)

(34 mm)
1.34 in.

1.34 in.
PORT FOR
APPLICATION
MODULE
DIN-RAIL DIN-RAIL
1 MOUNTING
CLIP
MOUNTING
CLIP
2
5.43 in. (138 mm)
CUTOUT

3.34 in. (85 mm)


3.34 in. (85 mm)

PORT A PORT B

FUSE HARDWARE ADJ. FOR


RESET LCD DISPLAY

SERIAL -PORT

3.82 in. (97 mm)

4.96 in. (126 mm)

1 = DIN-rail clip position when installed


without MMI (connectors to front).
2 = DIN-rail clip position when installed
with MMI (MMI to front).

Fig. 7. Dimensions

7 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

MOUNTING
If the Excel 50 Controller has an MMI, the housing is mounted
either in the front door of a cabinet or on a DIN rail with the
back facing to the DIN rail.
The controller without an MMI is mounted on a DIN rail with
the front facing to the DIN rail.
Table 1. Mounting versions

where
MMI version necessary accessory*
mounted
XL 50 ACC3 - rubber
cutout in
front door sealing ring and front door
front door
mounting clamps
yes
inside cabinet DIN rail DIN rail mounting clips
no inside cabinet DIN rail DIN rail mounting clips
*The DIN rail mounting clips are part of the delivery. The
Accessory kit XL 50 ACC3 for front door mounting must be
ordered separately.

Housing
Front Door
1. Choose the position of the controller in the front door.
Observe the min. and max. distances to other devices in
Fig. 9. Inserting sealing ring
the front door.
2. Cut a rectangle measuring 7-21/64 in. x 5-7/16 in. 4. Insert the controller into the cutout in the front door.
(186 mm x 138 mm) out of the front door (standard DIN
cutout).

Fig. 8. Front door cutout dimensions


Fig. 10. Inserting controller in front door cutout
3. Insert the rubber sealing ring into the gap around the
front plate of the Excel 50 Controller. 5. Attach Front Door Mounting clamps on both sides of the
controller and tighten the screws with a screwdriver as
shown in Fig. 11.

EN1B-0101GE51 R1105D 8
EXCEL 50 INSTALLATION INSTRUCTIONS

Inside Cabinet without MMI


1. Break plastic tabs covering the slots on the controller for
the DIN rail mounting clips using a screwdriver.
2. Attach the DIN rail mounting clips to the housing as
shown in Fig. 12.
3. Mount the controller on the DIN rail as shown in Fig. 12.

Fig. 12. Cabinet mounting without MMI

Fig. 11. Fixing controller with front door mounting


clamps

9 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Inside Cabinet with MMI Application Module


The screw terminal blocks and the switch for the bus ter-
mination cannot be accessed after the controller with MMI is
mounted on the DIN rail. CAUTION
Although the bus terminal socket can still be plugged in and Always plug in the application module before
unplugged, it is easier to do the complete installation before connecting the power supply.
mounting the controller on the DIN rail:
1. Plug in the application module as shown in Fig. 13.
2. Read the complete chapter "Installation" carefully. CAUTION
3. Follow the instructions in section "Screw Terminal Block Always disconnect the power supply before
Installation Procedure". unplugging the application module.
4. Optional: Connect the C-Bus to the application module — Plug in the application module until it snaps into the
as described in section "C-Bus Connection Procedure" controller housing.
and/or connect the application module serial port to the
Meter-Bus adapter as described in section “Meter-Bus
Connection Procedure”.
5. Break plastic tabs covering the slots on the controller for
the DIN rail mounting clips using a screwdriver.
6. Attach the DIN rail mounting clips at the housing as
shown in Fig. 13.
7. Mount the controller on the DIN rail.

Fig. 14. Plug-in of application module


NOTE: If the application module has been replaced or
plugged out and in again, please push the reset
button (behind I/O terminals) after power on.

INSTALLATION
Direct wiring of the Excel 50 is performed using screw
terminal blocks. For proper installation, follow these
instructions. Read all of section "Installation" carefully.

SCREW TERMINAL BLOCKS

BLOCK A BLOCK B

Fig. 15. Wiring options

Fig. 13. Cabinet mounting with MMI The two screw terminal blocks are attached directly to the
controller housing.

EN1B-0101GE51 R1105D 10
EXCEL 50 INSTALLATION INSTRUCTIONS

Table 2. Terminal blocks Cabling


name code no. of terminals Cable Routing
XS 50 Block A 14 All signal (input/output, low voltage) cables are communi-
screw terminal block cation circuits in accordance with VDE 0100, VDE 0800 and
XS 50 Block B 34
local regulations and should therefore be routed separately
from line voltage.
Terminal Details Table 3. Min. distances to line voltage
Block A cable type min. distance
unshielded cable 4 in. (100 mm)
shielded cable 3/8 in. (10 mm)

IMPORTANT
Avoid joining sensor cables.
Shielding

Fig. 16. Screw Terminal Block A

Block B
00000046

15
A01
16
17
A02
18
19
A03
20
21
A04
22
23
DI1
24 GND
25
DI2
26
DI3
27 Fig. 18. Sensor shielding
28
29
DI4
30
Shielding of sensor and actuator cables with low protective
+10V/5mA REF. 31 voltages is not necessary if the general guidelines on cable
DI-POWER 32 routing are observed (see "Cable Routing", page 11). If these
33
AI1
34
guidelines cannot be observed, shielded cable must always
35 be used. The shielded cable must be grounded as shown in
AI2
36 Fig. 18.
37
AI3
38
IMPORTANT
39
AI4 Shielding of I/O cables that are connected to
40 AGND

AI5
41 peripherals such as sensors and actuators must be
42 grounded at the control cabinet side, only; this is in
43
AI6
44 order to avoid ground loops.
AI7
45 All Honeywell actuators are RFI suppressed in accordance
46
47
with VDE 0871/B and VDE 0875/N.
AI8
48
Lightning Protection
Please check with your local Honeywell representative for
Fig. 17. Screw Terminal Block B information on lightning protection.
NOTE: The output (18...30 Vdc) of terminal 32 in screw
terminal block B is not stabilized. If you wish to
connect terminal 32 to a digital input via a potential-
free relay, see Fig. 26 on page 15.

11 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Cable Lengths and Cross Sectional Areas


Table 4. Signal types and cross-sectional areas Analog Inputs
cross-sectional area
Technical Description
type of signal The analog inputs convert data from passive sensors and
≤ 300 ft ≤ 550 ft ≤ 1,300 ft active sensors with voltage output. The analog inputs can be
(100 m) (170 m) (400 m) used as current inputs for active sensors, but then an external
Power supply ≤ 16 AWG ≤ 14 AWG resistor parallel to the sensor is necessary. It is also possible
- to feed digital signals to the analog inputs (see also section
(24 Vac) (≥ 1.5 mm2) 2
(≥ 2.5 mm )
"Sensors and Transducers" on page 14.
Low-current
≤ 20 AWG (≥ 0.5 mm2)
signals*
Technical Specification
*E.g. for 0...10 V sensors, totalizers, digital inputs, 0...10 V
signals for actuators. Number: Eight analog inputs

IMPORTANT Types of input signals:


The max. length of a signal cable with 24 Vac supply NTC 20 kΩ
is 550 ft (170 m). The max. length of a two-wire, 0 to +10 V (max. +11 V)
0...10 Vdc signal cable is 1,300 ft (400 m). The
0 (4) to 20 mA (with an external resistor of 499 Ω ±0.25%
secondary side of the transformer must not be
connected to earth ground. [see Fig. 22])
Each input is switched automatically via software either as
0000056b

input for NTC 20 kΩ (low impedance) or voltage source


PRIMARY 0...+10V (max. +11 V, high impedance).
VOLTAGE
2 24 V NTC 20k ohms: Range = -58 … +302 °F (-50 … +150 °C)
24 Vac Y
1 Voltage source: Range = 0...10 V
GND
TRANSFORMER
IMPORTANT
The analog inputs are protected against short circuit
MAX. 550 ft (170 m) and overvoltage up to 24 Vac and 40 Vdc. If any
MIN. 14 AWG (2.5 mm2) input is sourced with more than 40 Vdc or negative
voltage, the other inputs will be influenced. This
Fig. 19. Cabling of actuator with 24 Vac supply and max. could result in wrong values.
550 ft (170 m)
Passive sensors (NTC 20k ohms)
If the distance between the controller and actuator or sensor Room temperature sensor RF 20
with 24 Vac supply is greater than 550 ft (170 m), a separate Inlet temperature sensor VF 20A
external transformer for the actuator or sensor is necessary.
External temperature sensor AF 20
00000057d

MAX. 1300 ft (400 m)


MIN.20 AWG (0.5 mm2) Active sensors (0...10 V):
PRIMARY
VOLTAGE Duct Humidity Sensor H7011A1000
0 TO 10 Vdc
2 Duct Humidity Sensor H7012A1009
230 Vac 24 Vac
120 Vac GND
1 Active sensors (0 (4) to 20 mA):
TRANSFORMER
Immersion temperature sensor VF 100
230 Vac
Air duct temperature sensor LF 100
24 Vac
120 Vac
Wind sensor:
PRIMARY
VOLTAGE Wind sensor WS21
EXTERNAL
TRANSFORMER Further connections:
Temperature sensor terminal TF26
Fig. 20. Cabling of actuator with 24 Vac supply from Solar Sensor SAF 25
external transformer and max. 1,300 ft (400 m)
VMP Feedback Potentiometer
IMPORTANT The characteristic curves for other types of sensors can be
We recommend installing a fuse on the secondary entered manually in the data point description (see Excel 50
side of the transformer in order to protect the devices User Guide, EN2B-0137GE51).
against miswiring.

EN1B-0101GE51 R1105D 12
EXCEL 50 INSTALLATION INSTRUCTIONS

Pull-Up Resistor Handling


10 V Case 1 10 V Case 2 5V Case 3

24.9 kΩ 24.9 kΩ 18.2 kΩ


(pull-up) (pull-up) (pull-up)

A A A
150 kΩ D 150 kΩ D 100 kΩ D
49.9 kΩ 49.9 kΩ 100 kΩ

Fig. 21. Input circuit diagram

Table 5. Pull-up resistor handling

pull-up load-free voltage


input for voltage
circuit with NTC
device de- configured input or
configured activated diagram or low-
voltage hardware activated by DIP high-
by plug-in for DI on AI (Fig. 21) impedance
by @(8 switch impedance
input
input
XF521,
fixed NO YES case 2 8.89 V
XF521A NO
XF526 10 V fixed NO YES case 2 8.89 V 8.89 V
XFL521, (3 (6
YES config. case 1
XFL521A/B optional
YES 0V
Smart I/O switch-off
5V YES(4 NO YES(7 case 3 5V
XFC
XL20 fixed NO YES case 2 8.89 V
optional (2 (5
XL50 YES YES case 1 0V
switch-off
XL100, 10 V NO 8.89 V
fixed YES case 2 8.89 V
XL100A NO
XL100B optional YES configurable
case 1 0V
XL100C switch-off YES(1 NO YES(5
(1
controller firmware ≥ 2.03;
(2
controller firmware ≥ 2.02;
(3
controller firmware ≥ 2.03 (local/shared mode), CARE ≥ 5.00.01 (open mode);
(4
CARE ≥ 5.00.01;
(5
controller firmware < 2.04;
(6
controller firmware < 2.04 (local/shared mode), CARE ≥ 5.01.xx (open mode);
(7
CARE ≥ 5.01.xx;
(8
Assigning "@" as first digit of input characteristic name (e.g.: "@0-10V") in CARE text editor disables the pull-up resistor.

13 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Sensors and Transducers Analog Inputs Used as Digital Inputs (O.S. 2.04.xx or
higher)

00000061

0000062m
0 - 5 V 10 Vdc
4 33 31
A max. 5 mA 10 Vdc
3 34 32 31 max. 5 mA
2 31 1 33 32
I = 1 mA AI1
2 34 33
SAF25 AI1
SENSOR 35 34
AI2
0 - 10 V NTC 20 k 36
10 33 NOT CONNECTED 35
37 AI2
11 34 AI3 NORMALLY OPEN 36
B 38
12 31 37
I = 1 mA 39 L AI3
VMP ACTIVE AI4 230 Vac/ 50 Hz 38
SENSOR 40 AGND
41 120 Vac/ 60 Hz 39
AI5 AI4
0-10V 42 N 40 AGND
43 POWER 31 41
TRANSFORMER FOR AI6 10 Vac
ACTIVE SENSOR
44 42
C 45 43
AI7 31 AI6
46 44
0(4) to 47 NOT CONNECTED
R1 AI8 45
20 mA 48 NORMALLY CLOSED AI7
46
499
0.25% 47
L AI8
230 Vac/ 50 Hz 48
120 Vac/ 60 Hz
Fig. 22. Analog inputs, sensor connections
N

Analog Inputs Used as Digital Inputs (O.S. 2.03.xx or Fig. 24. Analog inputs used as digital inputs
lower)
Unconnected inputs have a default voltage of 0 V.
0000062a

10 Vdc
31 max. 10 mA
32 Table 6. Accuracy of analog inputs with NTC sensors
33
AI1
34
NOT CONNECTED 35 deviation / ± Kelvin
AI2
NORMALLY CLOSED 36 range (without sensor tolerance)
L AI3
37 NTC (20 kΩ)
230 Vac/ 50 Hz 38
120 Vac/ 60 Hz
AI4
39 -58 to <-40°F (-50 to <-40°C) ≤ 5.5 K
N 40 AGND

NORMALLY OPEN AI5


41 -40 to <-22°F (-40 to <-30°C) ≤ 3.0 K
42

AI6
43 32 to <-4°F (-30 to <-20°C) ≤ 1.8 K
44
NOT CONNECTED
45 86 to <14°F (-20 to <-10°C) ≤ 1.1 K
NORMALLY OPEN AI7
46
47 158 to <32°F (-10 to <0°C) ≤ 0.8 K
L AI8
230 Vac/ 50 Hz 48
120 Vac/ 60 Hz
212 to <50°F (0 to <10°C) ≤ 0.6 K
N
266 to <122°F (10 to <50°C) ≤ 0.4 K

Fig. 23. Analog inputs used as digital inputs 266 to <158°F (50 to <70°C) ≤ 0.6 K

For normally-open contacts, a digital signal must be switched 266 to <194°F (70 to <90°C) ≤ 1.0 K
via the changeover contact of an additional relay. 266 to <212°F (90 to <100°C) ≤ 1.5 K
Unconnected analog inputs have a default voltage of 8.5 V.
This is interpreted by the controller as a logical 1. This means 266 to <248°F (100 to <120°C) ≤ 2.4 K
that, in general, no external relay is needed for normally-open 266 to <302°F (120 to <150°C) ≤ 5.3 K
contacts.
IMPORTANT
The relay contact must be suitable for switching low
voltage. In the case of long cable distances, the
analog input signal may be sensitive to interference.
In this case, an external relay may also be used for
normally-closed contacts.

EN1B-0101GE51 R1105D 14
EXCEL 50 INSTALLATION INSTRUCTIONS

Digital Inputs Table 8. Dynamic parameters of digital inputs

Technical Description frequency


pulse pause
bounce time
duration interval
max. 0.4 Hz min. 1.25 s min. 1.25 s max. 50 ms

Table 9. Dynamic parameters of totalizers

pulse pause
frequency bounce time
duration interval
max. 15 Hz min. 20 ms min. 30 ms max. 5 ms

Connection Examples

Fig. 25. Input switching voltages


The digital inputs signals can be DC voltage signals. If an
input voltage is higher than 5 V, the digital signal switches to
logic "1" status. With a hysteresis of 2.5 V, the input signal
must fall below 2.5 V before the digital status switches to logic
"0".
Three out of four digital inputs can be used as totalizers.
With V2.04.00 and higher firmware, the online point attribute
"Normally Open / Normally Closed" (NO/NC) defines the
relation between the physical state (open/closed) and its
logical status. See Table 7.

Fig. 26. Digital inputs, connection examples


Technical Specification
Number: 4 digital inputs
Type of signals: DC signal (max. 24 Vdc)
Analog Outputs
Technical Description
Input resistance: 10k Ω
Analog outputs can be used, for example, to operate valve or
IMPORTANT damper actuators. The characteristic curves for these
The digital inputs are protected against short circuit actuators can be defined via MMI (see Excel 50 User Guide).
and overvoltage up to 24 Vac and 40 Vdc. Each analog output can also be used as a digital output.
Parameter requirements:
If the digital inputs are used for normal digital or analog Technical Specification
signals, the signals must meet the static and dynamic
requirements stated in Table 7 and Table 8. Number: Four analog outputs
If three out of four digital inputs are used as totalizers, the
signals at the totalizer inputs must fulfill the static and Analog output details:
dynamic requirements stated in Table 7 and Table 9 while the Table 10. Technical specifications of analog outputs
signal at the fourth input must meet only the static re-
quirements of Table 7. voltage current resolution min. step accuracy
Table 7. Static parameters of digital inputs 0...10 V, max. ±100 mV
8-Bit 0.043 mV
max. 11 V 1 mA ±1 digit
contact NO/NC
logical status input voltage
position attribute
Relay Modules
open NO 0 ≤ 2.5 V The relay modules facilitate the control of peripheral devices
closed NO 1 ≥5V with high load via the analog outputs of the controller. The
connection examples (for the relay modules MCD 3 and
open NC 1 ≤ 2.5 V MCE 3) are shown here.
closed NC 0 ≥5V IMPORTANT
The external supply of the relay modules must be
24 Vac, the same as of the supply of the controllers.

15 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

The analog outputs are protected against overvoltage


up to 24 Vac and 35 Vdc.
Digital Outputs
Supply:
Technical Description
Several relay modules can be connected in series via the The digital outputs are switched by a triac that can be
bridged terminal pair: connected directly to an external relay.
24 Vac: Terminals 11/12 of the relay
24 Vac (-): Terminals 13 to 16 of the relay Technical Specification
Number: Six digital outputs
Output stages:
Low signal 0V
High signal 24 Vac
Type Close, only
Load:
Per output min. 0.01 A
max. 0.8 A
Total max. 2.4 A
Cos ϕ 0.5 to 1
IMPORTANT
The digital outputs are protected against short circuit
current via internal fuse, but they are not protected
against overload. All digital outputs are protected via
only a single fuse; if any digital output is short-
Fig. 27. Analog outputs, connection of relay MCD 3 circuited, the fuse will be blown and will interrupt the
main power. In that case, the controller does not
MCD 3: work. If the CPU is running into the WATCHDOG as
Relay terminal 17 controls the changeover contact K3. a result of a software or hardware error, all digital
Relay terminal 18 controls the ON contacts K1, K2. outputs will be set to low signal, which means all
Ground can be looped through terminals 2/3. digital outputs are inactive.
Beginning with V2.04.00 firmware, the online point attribute
"Normally Open / Normally Closed" (NO/NC) defines the
relation between the physical state (relay ON/OFF) and its
logical status. See Table 11.
Table 11. Digital output parameters

relay ON/OFF NO/NC attribute logical status


ON NO 1
OFF NO 0
ON NC 0
OFF NC 1

Fig. 28. Analog outputs, connection of relay MCE 3

MCE 3:
Relay terminal 16 controls the ON contact K3.
Relay terminal 17 controls the changeover contact K2.
Relay terminal 18 controls the changeover contact K1.

EN1B-0101GE51 R1105D 16
EXCEL 50 INSTALLATION INSTRUCTIONS

Connection Examples CRT-Series


Table 12. No. of controllers connected to one transformer

transformer Excel 50 controller


CRT 2 1 (1.8 A max.)
CRT 6 2
CRT 12 4

Use quick-acting backup fuse 10 A (or automatic H16 or L16)


to protect the transformer primary side. On the primary side of
the CRT 2, there is a fusible output of type M 0.315 A (T)
250 V for the purpose of fine fusing.
Fig. 29. Digital outputs, connection of relay
Table 13. Overview of CRT Series AC/DC current

transformer max. AC current max. DC current


CRT 2 2A 0.5 A = 500 mA
CRT 6 6A 1.3 A = 1300 mA
CRT 12 12 A 2.5 A = 2500 mA

Fig. 30. Digital outputs, direct connection of 3-position


actuators Fig. 32. AC/DC current graphs

Power Supply 1450 Series


The Excel 50 Controller is powered by an external trans- Table 14. 1450 Series transformers
former.
part #
Transformer requirements for one Excel 50 Controller: primary side secondary side
1450 7287
Voltage 24 Vac ±20%
-001 120 Vac 24 Vac, 50 VA
Current 3 A, if fully equipped (6 DO's x 0.4 A)
2 A, if current of DO's does not exceed 1.8 A 2 x 24 Vac, 40 VA and 100 VA
-002 120 Vac
Power 72 VA, if fully equipped from separate transformer
The transformer, already installed in the cabinet, can be used 24 Vac, 100 VA and 24 Vdc
-003 120 Vac
to supply several controllers, communication devices or peri- 600 mA
pherals (actuators, etc.) if the transformer provides sufficient
-004 240/220 Vac 24 Vac, 50 VA
power.
2 x 24 Vac, 40 VA and 100 VA
-005 240/220 Vac
from separate transformer
24 Vac, 100 VA and 24 Vdc,
-006 240/220 Vac
600 mA

All transformers of the 1450 series are designed for 50/60 Hz


AC and have insulated accessory outputs. The transformers
Fig. 31. Transformer example include built-in fuses, line transient/surge protection and AC
convenience outlets and meet NEC class 2 requirements.

17 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Standard Transformers 8. Connect relays, actuators etc. to the digital output


terminals.
Standard commercially available transformers must fulfill the
following specifications: 9. Select one of the transformers of the CRT series or
1450 series (Table 13 or Table 14) or use a com-
Table 15. Requirements for standard transformers mercially available standard transformer fulfilling the
requirements in Table 15.
output voltage impedance AC current 10. Make sure that the application module is attached to the
24.5 Vac to 25.5 Vac ≤ 1.15 Ω max. 2 A controller housing.

24.5 Vac to 25.5 Vac ≤ 0.40 Ω max. 6 A


24.5 Vac to 25.5 Vac ≤ 0.17 Ω max. 12 A
WARNING
High Voltage
Screw Terminal Block Installation Risk of death or electrical shock.
1. Make sure that the power supply of the cabinet is — Do not connect line power supply directly to the
disconnected. terminals.
2. Make sure that the power supply of the cabinet is — Insulate devices with 120 Vac / 230 Vac by a
disconnected and that the application module is plugged transformer.
in the housing.
IMPORTANT
3. Choose the min. cross sectional areas for all cables to The transformer feeding the Excel 50 Controller must
and from sensors, actuators, valves, relays, etc. you be in the same cabinet. For the selection of the trans-
want to connect to the Excel 50 Controller from Table 4. former the max. DC current must be considered if
4. Connect sensors, transducers, etc. to the analog input field devices with DC load are used.
terminals. The secondary side of the transformer must not be
connected to earth ground.
11. Connect the 24 Vac (-) on the secondary side of the
transformer to terminal 1 on Screw Terminal block A.
12. Connect the 24 Vac on the secondary side of the
transformer to terminal 2 on Screw Terminal block A.

Fig. 34. Connecting the power supply

IMPORTANT
If there already are additional transformers, for
example supplying actuators or active sensors:
— Connect the 24 Vac (-) (secondary side) of the
Fig. 33. Connecting a cable to a screw terminal transformers together.
13. Attach the terminal blocks to the housing as shown in
IMPORTANT Fig. 35.
When installing a separate external transformer, do
not connect the cabinet ground to the controller
system ground.
5. If the distance between the controller and an actuator or
sensor with 24 Vac supply is greater than 550 ft
(170 m):
a) Choose a transformer from the transformers listed in
section "
Power Supply".
b) Connect the chosen transformer directly to the
actuator or sensor.
6. Connect sensors, transducers, etc. to the digital input
terminals.
7. Connect valves, actuators, relays, etc. to the analog
output terminals.

EN1B-0101GE51 R1105D 18
EXCEL 50 INSTALLATION INSTRUCTIONS

COMMUNICATION
The Excel 50 Controller has the capability to communicate
with the Excel Building Supervisor (XBS/XBSi, and Enterprise
Buildings Integrator) and other EXCEL 5000 devices via the
C-Bus. The Excel 50 Controller also has the capability to
communicate with devices on a LONWORKS network. A further
communication option is connection to a Meter-Bus. All
communications options are dependent upon the application
module, and not all options are available on one module (see
Table 16).
A modem/ISDN terminal adapter may be connected to Flash
EPROM versions with V2.01.00 software or newer to allow re-
mote communication with the controller.
Table 16. Application module versions

module model module type


XD50-E Standalone
Fig. 35. Attaching of screw terminal blocks
XD50-F Standalone/Flash EPROM
XD50-FC* C-Bus/Flash EPROM
Adjusting the MMI Display Contrast XD50-FCS C-Bus/Meter-Bus/Flash EPROM
Front Door Mounted with MMI XD50-FL* LONWORKS BUS/Flash EPROM
1. Unplug the screw terminal block B to Port B while the
XD50-FCL* C-Bus/LONWORKS BUS/Flash EPROM
controller is connected to the power supply.
2. Adjust the display contrast with a slotted screwdriver or XD52-FC C-Bus/Flash EPROM (Large RAM)
a cross-tip screwdriver. C-Bus/Flash EPROM (Large Ram), Meter-
XD52-FCS
Bus
*In the case of smoke control applications, use the "UUKL"
version of the Excel 50.

NOTE: EPROM versions can be upgraded by direct firmware


download via serial port or C-Bus.
IMPORTANT
Electrostatic discharge can damage the application
module. Always disconnect the power supply when
plugging in and unplugging the application module.

Fig. 36. Adjusting the display contrast

3. Attach screw terminal block B to Port B.


DIN Rail Mounted with MMI
1. Unmount the controller from the DIN rail.
2. Unplug the screw terminal block B to Port B while the
controller is connected to the power supply.
3. Adjust the display contrast with a slotted screwdriver or
a cross-tip screwdriver as shown in Fig. 36.
4. Attach screw terminal block B to Port B.
5. Mount the controller on the DIN rail again.

19 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

C-Bus The C-Bus may not work if the controllers with


termination are switched OFF.

0000060c
LEDs
POWER, GRN Cable Specification
RESERVED
The max. cable length is 4,000 ft (1,200 m). There are
C-BUS TxD, YEL
C-BUS RxD, YEL
regional differences as to whether shielded or unshielded
RESERVED cable must/can be used.

C-BUS
IMPORTANT
TERMINATION In Europe, only shielded cable is permitted while in
SWITCH
the US, shielded or unshielded cable can be used.
4 5 6 Inside the cabinet: J-Y-(ST)Y 2 x 2 x 0.8
Outside the cabinet: A-Y-(ST) 2 x 2 x 0.8
C-BUS
In principle, data transmitting cables should be shielded in
SHIELD
C+

case of RFI.
C-

Table 18 summarizes cable types and gives selection


guidance. Note that baud rate and max. bus length are
Fig. 37. C-Bus connection and LEDs related to each other.
Up to 30 controllers can communicate with one another and Table 18. C-Bus cable types
the Excel Building Supervisor PC (XBS) via the C-Bus.
Instead of an Excel 500/600 Controller, other C-Bus- cable type description recommended for
compatible components can also be connected (Excel IRC J-Y-(ST)Y shielded, Europe
Multicontroller; Excel EMC; Modem Device XM 100A). 2 x 2 x 0.8 twisted pair Inside cabinet
A-Y-(ST)Y shielded, Europe
C-Bus Termination 2 x 2 x 0.8 twisted pair Outside cabinet
unshielded, US
AK 3702
twisted pair not approved for Europe
US (low-cost)
AK 3740A shielded
not approved for Europe
Europe
Belden 9842 twisted pair
US also possible
Belden 9841 shielded US
unshielded, US
AK 3702
twisted pair not approved for Europe
US (low-cost)
AK 3740A shielded
Fig. 38. DIP Switch settings for C-bus not approved for Europe

The application module is equipped with a DIP switch for the


Each end of the shield on the C-Bus should be connected to
C-Bus to set the bus termination appropriate for the com-
the shield terminal of the respective device. Do not connect it
munication speed.
to the cabinet ground or any other ground points.
Table 17. DIP switch settings for C-bus termination

DIP switch communication controller compati- C-Bus Extension by Using Repeaters


setting speed (max.) location bility The C-Bus length can be extended by using repeaters. Each
repeater extends the bus length by 4,000 ft (1,200 m).
XD505A,
up 9.6 Kbaud - For the US the repeater is available either with or without
XL20XD
housing. In Europe, only the version with housing is allowed.
XD508,
middle 76.8 Kbaud middle of bus
XL20XD508 Table 19. Order no. for repeaters
beginning or XD508,
down 76.8 Kbaud description US order no. European order no.
end of bus XL20XD508
NOTE: Modules listed in Compatibility column are used in without housing 14507324-001 -
Excel 20/100B/500/600 Controllers. with housing 14507324-002 XD 509
NOTE: The controllers with the termination must be switched
ON prior to the controllers in the middle of the C-Bus.

EN1B-0101GE51 R1105D 20
EXCEL 50 INSTALLATION INSTRUCTIONS

C-Bus Connection Procedure NOTE: A doubly-terminated bus may have stubs of up to


10 ft (3 m) from the bus to each node.
1. Choose a suitable C-Bus cable from Table 18.
IMPORTANT Table 20. Doubly-terminated bus specifications
Make sure that all bus devices connected to the
cable type max. bus length
same C-Bus are set to the same baud rate;
otherwise, proper communication cannot be ensured. Belden 85102 2,700 m (8,900 ft)
2. Set the DIP switch according to Table 17.
Belden 8471 2,700 m (8,900 ft)
IMPORTANT
The C-Bus must be connected through the individual Level IV, 22 AWG 1,400 m (4,600 ft)
controllers (open ring). Star connection is not per-
JY (St) Y 2x2x0.8 900 m (3,000 ft)
mitted because uncontrollable line reflections could
occur. TIA568A Categ. 5 24AWG, twisted pair 900 m (3,000 ft)
3. Connect the cable shield to C-Bus terminal 4 (Fig. 37).
4. Connect the C+ cable to C-Bus terminal 5 (Fig. 37). NOTES:
5. Connect the C- cable to C-Bus terminal 6 (Fig. 37). The cable types listed above are as recommended by
6. If the max. C-Bus length for the chosen cable (Table 18) Echelon in their FTT-10A User Guide. The cable re-
is exceeded: commended by Honeywell is the level IV, 22 AWG, solid core,
— Use repeaters to extend to the max. C-Bus length nonshielded cable. Belden part numbers are 9H2201504
(see section " (plenum) and 9D220150 (non-plenum).
C-Bus Extension by Using Repeaters"). The FTT specification includes two components that must be
met for proper system operation. The distance from each
It may take up to two minutes to re-initialize the bus when
transceiver to all other transceivers and to the termination
adding or removing a controller to/from the C-Bus. During this
must not exceed the max. node-to-node distance. If multiple
time, communication on the C-Bus is lost.
paths exists, the max. total wire length is the total amount of
wire used.
LONWORKS Network Interface Table 21. Free topology (singly-terminated) specifications
Excel 50 Controllers may be equipped with an application
module (see Table 15) containing an FTT-10A Free Topology max. node-to- max. total wire
cable type
Twisted Pair Transceiver which allows communication with node distance length
other device on a LONWORKS network. FTT-10A transceivers Belden 85102 1,650 ft (500 m) 1,650 ft (500 m)
communicate at 78 Kbaud and provide transformer isolation
so that the bus wiring does not have a polarity; that is, it is not Belden 8471 1,300 ft (400 m) 1,650 ft (500 m)
important which of the two bus terminals are connected to Level IV, 22AWG 1,300 ft (400 m) 1,650 ft (500 m)
each wire of the twisted pair.
JY (St) Y 2x2x0.8 1,050 ft (320 m) 1,650 ft (500 m)
LON SERVICE BUTTON TIA568A Category 5
825 ft (250 m) 1,500 ft (450 m)
POWER, GRN
24AWG, twisted pair
LON SERVICE, RED
C-BUS TxD, YEL LEDs
C-BUS RxD, YEL IMPORTANT
RESERVED Do not use different wire types or gauges on the
same LONWORKS network segment. The step change
C-BUS in line impedance characteristics would cause
TERMINATION
SWITCH unpredictable reflections on the network.
NOTE: In the event that the limit on the total wire length is
1 2 3 4 5 6
exceeded, FTT physical layer repeaters (FTT 10A)
can be added to interconnect segments and increase
(optional)
LON
BUS
C-BUS the overall length by an amount equal to the original
00000124
A1

NOT USED

SHIELD

C-
A2

C+

specification for that cable type and bus type for each
repeater used. For example, adding repeaters for a
doubly-terminated bus using
JY (St) Y 2x2x0.8 cable increases the max. length
Fig. 39. LonWorks network connection 3,000 ft (900 m) for each repeater.
FTT devices can be wired in daisy chain, star, loop or any
combination thereof as long as the max. wire length re-
quirements given below are met. The recommended con-
LONWORKS Bus Termination
figuration is a daisy chain with two bus terminations. This One or two Termination Modules, part no. 209541B or part
layout allows for max. bus length, and its simple structure no. XAL-Term, are required for a LONWORKS Bus with FTT
presents the least number of possible problems, particularly devices on it, depending upon the configuration. See chapter
when adding on to an existing bus. "LonWorks System Engineering" of LonWorks Mechanisms –

21 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Interface Description (Product Literature No.: EN0B- Table 22 describes each of the behaviors shown in the
0270GE51) for details. previous figure under different contexts. Again, this list is not
exhaustive and therefore does not provide explanations for
every possible service LED behavior.
LONWORKS Service LED Diagnostics
The LONWORKS service LED is used to diagnose the state of
the Excel 50 controller. In general:
— The controller is applicationless if the LED illuminates
continuously*.
— The controller has an application but, if the LED is
blinking, it is not configured.
— The controller is running normally if L2 is OFF.
The LONWORKS service LED is located on the application
module (see Fig. 39).
Pushing the LONWORKS service button will force a new
commissioning of the Excel 50. While commissioning, LED L2
continuously illuminates red for less than 1 minute and
afterwards return to the normal state (L2 = OFF).
A more detailed diagnosis can be carried out by observing the
duration of the ON and OFF states of the service LED in
connection with power ON / OFF. The following figure
illustrates the different service LED behaviors. These are the
most common behaviors, but others are possible since the
state of the service LED is under firmware control and can be
affected both by hardware and software anomalies.

Fig. 40. LONWORKS Service LED behavior

EN1B-0101GE51 R1105D 22
EXCEL 50 INSTALLATION INSTRUCTIONS

Table 22. LONWORKS Service LED behavior descriptions

behavior context likely explanation


1 Power-up of the controller Controller hardware is defective.
2 Power-up of the controller Controller hardware is defective.
Power-up / reset of the The controller is applicationless. May be caused by the Neuron chip firmware
3
controller when a mismatch occurs on application checksums.
Possible corrupt EEPROM. Use a newly programmed PROM, or EEBLANK and
4 Anytime
follow bring-up procedure.
5 Anytime The controller is unconfigured.
The OFF duration is approx. 1 second. Service LED should then turn ON and
First power-up, Applicationless
6a stay ON, indicating an applicationless state. The controller is defective – return
firmware state exported
to factory.
The OFF duration is 1...15 seconds depending on the application size and
First power-up, Unconfigured
6b system clock. Service LED should then begin flashing as in behavior 5,
firmware state exported
indicating an unconfigured state.
The OFF duration is indefinite (1...15 seconds to load internal EEPROM; stays
First power-up, Configured
6c OFF, indicating configured state.) The controller is configured and running
firmware state exported
normally.
7 Anytime The controller is configured and running normally.

23 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Controller Serial Port


For connection to the XI584, a standard null modem cable
may be used.

Fig. 41. Serial port


The serial port has a 9-pin sub-D connector and has a default Fig. 42. MMI cable details
communication speed of 9.6 Kbaud.
Table 23. Signals of serial port Modem or ISDN Terminal Adapter Connections
For remote communications, a modem or ISDN terminal
signal type controller output controller input
adapter can be connected directly to the serial port of all
Signal ground Flash-EPROM versions of the Excel 50 Controller.
Transmit x NOTE: Remote communication via modem or ISDN terminal
adapter requires firmware version 2.01.00 or higher.
Receive x
Carrier detect x
Clear to send x
Data terminal ready x
5V x

MMI Connection
For direct communication the external operator interface
XI582 and the PC-based MMI XI584 can be connected to the
serial port.
When the cable from XI582 or XI584 is plugged in during
normal operation of an Excel 50 Controller with MMI, the EXCEL 50 (REAR VIEW)
SERIAL PORT
functionality of the Excel 50 MMI is disabled.
After unplugging the external MMI it takes up to 15 sec until
the local MMI activates again.

Fig. 43. Modem connection


Cable Specifications
The serial port of the Excel 50 controller accepts a standard
Ready-made cables with the shield already connected to the
modem cable with a female 9-pin connector. Use the cable
computer module plug end are available for the connection of
that is supplied with the modem/ISDN terminal adapter.
external MMIs.
The communication speed is 9.6 Kbaud by default but can be
Table 24. Cable specifications set as high as 38.4 Kbaud.
For more details, see section "Remote Communication".
MMI type cable length
XI582 (remote MMI) XW 582 17 ft (5 m)
Changing Between MMI and Modem Connection
XI584 (PC-based MMI) XW 585 17ft (5 m) The XL50 will detect when an MMI or modem/ISDN terminal
adapter is connected and will adjust the communication

EN1B-0101GE51 R1105D 24
EXCEL 50 INSTALLATION INSTRUCTIONS

speed automatically according to the preset values. This


automatic detection can take up to 5 seconds.
manual answer mode, and it will set the modem to the manual
REMOTE COMMUNICATIONS answer mode (S0=0).
Firmware version number 2.01.00 or later supports the direct
connection of modems or ISDN terminal adapters for
Resetting the Modem
communications to up to three remote XBS building super- For those cases where it is not clear if the modem to be used
visors. is in its factory setting, the modem can be reset to its factory
NOTE: XBSi building supervisors are not supported for setting by using the RESET MODEM command in the Start-
remote communication. up sequence or through the HW Config. part of the System
Info. sequence on the MMI. This will allow a quick and easy
NOTE: Communication via ISDN is applicable only for modem reset without having to run the modem set-up soft-
Europe. ware or the Windows™ terminal program.
The RESET MODEM command causes the following com-
Modem Requirements mands to be sent to the modem:
1. ATZ: Executes hardware reset on modem
• Modem must support Hayes compatible command set (not
V150 or V151 = Microsoft command set) 2. AT&FX3&W: Resets modem to factory configuration
settings, configures the modem to not wait for the public
• Modem must support alpha-numeric return codes phone system dial tone, and writes this to nonvolatile
• Modem must follow serial baud rate of the CPU memory.
• Modem must support auto-bauding (baud rate fall-back)
• When carrier detect (connect) is reported, the carrier must
be ON simultaneously at both modems (on CPU side and Set-up for Special Modem Behavior
on XBS side) ⇒ use same modem If special modem/ISDN terminal adapter behavior is required,
• After a switch-on of the DTR line by the CPU or XBS, the the communication device should be set up according to the
modem must accept a dial command after 3 seconds instructions provided with it. This typically involves running a
set-up program on a computer with the device connected to
• Modem must answer AT commands in less than 3 the computer serial port or using the Windows™ terminal
seconds program.

No Set-up for Standard Modem Behavior Set-up for In-house Telephone Systems
If no special modem behavior is required, there is no need to A common case of special modem behavior is when the
set up or initialize the modem/ISDN terminal adapter. The modem is connected to an in-house telephone network re-
Excel 50 Controller will automatically detect the device (MMI quiring a prefix to be dialed before the destination number to
or modem) attached to the serial port and set the appropriate provide access to the public telephone network. There are
communication speed. The controller will also automatically two important aspects of the special initialization of the
adapt to alphanumeric return codes used by the modem. This modem to consider:
automatic detection and adjustment can take up to 5
seconds. 1. Do not wait for the public network dial tone. Typically,
the init command ATX3 will trigger the modem to dial
NOTE: It is highly recommended to use a state-of-the-art without waiting for a public network dial tone. Save this
modem and leave it in its factory setting. modem set-up in the modem EEPROM with the com-
mand AT&W. Check the modem handbook to verify the
correct commands. Note that these commands are
Automatic Baudrate Synchronization executed automatically with the RESET MODEM com-
The default communication speed between the Excel 50 mand in the Excel 50 Controller Start-up Sequence.
Controller and the local modem/ISDN terminal adapter is 9.6 2. Add the prefix required for accessing the public tele-
Kbaud. phone network to the destination telephone number.
The communication speed between the Excel 50 and XBS Depending on the in-house telephone system, a certain
modems/ISDN terminal adapters is automatically syn- prefix may have to be added to the destination number
chronized by the two devices to the highest speed that both of in the XBS system configuration/site definition screen
the devices are capable of. This feature is called autobauding before sending the set-up to the remote Excel 50 con-
and is provided by all state-of-the-art modems / ISDN terminal troller.
adapters when left in their factory default settings.
The communication speed between the XBS and its modem /
ISDN terminal adapter is part of the modem set-up at the Set-up for Limited Communication Speed
XBS. The communication speed of the modem can be fixed to a
lower rate in case of data transmission errors due to tele-
phone line limitations. See section "Start-up Sequence" or
Auto / Manual Answer Detection see the Excel 50 User Guide, EN2B-0137GE51, for the
The Excel 50 Controller will automatically detect whether the procedure for fixing the baud rate.
modem/ISDN terminal adapter is initialized in auto-answer or

25 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Troubleshooting
In case of any problems the handbook of the modem or ISDN
terminal adapter must be consulted.
A “Frequently Asked Questions and Troubleshooting”
document is available via the Honeywell Technical Assistance
Center (TAC) or, for Honeywell employees, on the HIVE
under:
Technical Assistance Center/Controllers/Excel 80 and 100
and 500 and 600/ technical literature/modemfaq.doc
or on the Honeywell DocuServer under:
http://web.ge51.honeywell.de/dep/mc/TAC_Tips/
Modem FAQ.doc

TCP/IP Dial-Up via TCP/IP Modem XM500


The Honeywell TCP/IP modem XM500 allows use of a
TCP/IP network (e.g. Ethernet LAN/WAN networks) to
achieve a dial-up connection between an XBS building
supervisor and an Excel 50 controller. The set-up is identical
to that of a telephone modem connection, with the exception
of the additional need for definition of the Ethernet address.
Details can be obtained from the XM500 Product Data
Documentation on the Honeywell Intranet under:
http://web.ge51.honeywell.de/dep/mc/HVAC_Products/Autom
ation_and_Control/CentralPlantControls/Modem-
Interface/xm500/xm500_pd.zip

EN1B-0101GE51 R1105D 26
EXCEL 50 INSTALLATION INSTRUCTIONS

• Operation of the M20T can disrupt the operability


GSM COMMUNICATION (EUROPE, of inadequately protected medical devices. Please
ONLY) address all questions to a doctor or the manu-
facturer of the medical device.
For communication via the Global System for Mobile com- • The M20 Terminal shall not be used within wet
munications (GSM), a Siemens M20 Terminal (cellular environment, such as in public baths.
engine) is required and must be connected directly to the
• If your M20 Terminal, your SIM card, or both are
serial port of the Excel 50 controller. The M20T translates the
lost, notify your network operator immediately in
Excel CPU data received in transparent mode into the GSM
order to avoid misuse.
standard. The M20T behaves like a Hayes-compatible
modem connected to the Excel controller serial port, and it
then transmits via GSM like a cellular (mobile) phone.
Required Third-Party Equipment
NOTE: Communication via GSM requires firmware version
V2.3.0 or higher. The Siemens M20 Terminal (shown below) is required for
GSM communication. In addition, a 3 V Mini SIM card with
IMPORTANT personal identification number (PIN) is required for the M20T.
With the M20T, data communication is possible only The Mini SIM card, supplied by the GSM Network Provider,
in 900 MHz GSM networks. GSM networks operating must be released for data communication at 9.6 Kbaud. A
at 1800 MHz or 1900 MHz are not supported. separate telephone number is required for data com-
The max. communication speed is determined by the current munication having the same SIM card (one telephone number
GSM standard, which is 9.6 Kbaud. Due to a special trans- for voice communications and one for data).
mission mechanism, the effective communication throughput
is lower than 9.6 Kbaud – however this will be noticeable only
when high data volumes are transmitted, e.g. when HANDSET INTERFACE

application download is performed.

M20T Safety Precautions

CAUTION
MOUNTING HOLES
TOP
BOTTOM
Use of the M20 Terminal on-board aircraft is for-
bidden. Use of a Cellular Engine in an aircraft, such
as for the purpose of wireless connection of an SIM CARD READER
aircraft-based HVAC system to an XBS central, can
endanger navigation, it interferes with the cellular net- OPERATING
STATUS LED
work, and it is illegal. Failure to comply with this pro-
hibition may lead to temporary suspension or per-
manent cancellation of Cellular Engine services for
the person who disregards this prohibition and/or to V.24 INTERFACE
POWER SUPPLY
AND AUDIO
FME ANTENNA
CONNECTOR
legal action against said person. SUB-D SOCKET INTERFACE

Fig. 44. Siemens M20 terminal


CAUTION
Users are advised to NOT use the M20T in auto- Mechanical characteristics:
motive service stations. Weight 145 g
Users are reminded of the necessity of complying with Dimensions (max) LxWxH 107.0 x 63.5 x 31.3 mm
restrictions regarding the use of radio devices in fuel Temperature range -20°C to 55°C
depots, chemical plants, and locations where ex- Protection-class IP40
plosives are detonated.
Mechanical vibrations Amplitude 7.5 mm at
Additional precautions are as follows: 5 to 200 Hz sine
• When receiving calls on a public highway, such as Max. pulse-acceleration 30 g pulse with 18 ms
a cooling control system of a refrigeration truck duration
being called by an XBS central, the M20T is not
Air humidity 5–98%
permitted to use "warning" devices which permit
the vehicle’s horn to sound or the lights to flash. Electrical characteristics:
• Drivers are advised not to use the handheld micro- Operating voltage range 8 to 28.8 Vdc, +/- 5% ripple
phone or the telephone handset while their vehicle Undervoltage/overvoltage
is in motion, except in emergencies. Use the protection: 0 V / 45 V
hands-free facility to speak only if it does not divert
Power consumption at 12V <200 mA speech mode,
your attention from the traffic.
<14 mA idle mode

27 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

Max. line-in/out cable length 2 m (e.g. modified NOKIA


2110 for M20T)
Antenna Examples
Protection fuse 1 A, fast blow
Max. RF power 2 W at 900 MHz
Power supply connector 6-pin modular
CE conformity:
• 89/336/EC (EMC guideline)
• 73/23/EC (Low voltage guideline)
• 91/263/EC (Telecommunications devices guideline)
Standards:
• EMC: ETS 300 342-1
• Safety: EN 60950
• GSM network: TBR 19, TBR 20

Serial Cable
For connecting the M20T to the Excel controller, a standard
RS232 cable (9-pin V24 sub-D sockets) is required.

GSM Antenna Requirements


All major suppliers of GSM antennas can supply GSM900 Fig. 45. Round radiation antenna, magnetic base, 5 DBi
Antennas with FME plugs to connect with the M20 Terminal
for a variety of applications. Some antenna examples are
shown below. The antenna must satisfy the following
electrical requirements:
Antenna electrical requirements:
Frequency TX 890-915 MHz
Frequency RX 935-960 MHz
Impedance 50 Ω
VSWR TX: max. 1.7:1 installed
VSWR RX: max. 1.9:1 installed
Gain > 1.5 dB referenced to λ/2
dipole Fig. 46. Directional antenna (YAGI), 12 DBi
3dB width of cone vertical: 80°
horizontal: 360°
Max. power: 1 W (cw), 2 W peak; at
ambient temperature of 55 °C
Depending on the application and the RF field at the local
site, the GSM antenna may be mounted directly or via cable.
The max. antenna cable length is 8.0 m (including 20 cm M20
Terminal-cable)
NOTE: The max. number of push/pull cycles shall not
exceed 100.
The antenna interface connector of the M20 unit is an FME
connector (of type SMR nano (male)). Hence, the connector
on the GSM antenna or antenna cable has to be of type SMR
nano (female, or use a double female connector in between). Fig. 47. Round radiation antenna, 6.5 DBi

EN1B-0101GE51 R1105D 28
EXCEL 50 INSTALLATION INSTRUCTIONS

M20 Terminal Set-up


Prior to beginning the set-up, get the M20T manual (or CD-
ROM, if it was delivered with one). Everything is described in
it and you will need it.
IMPORTANT
It is absolutely mandatory to use a serial data line
monitor for the set-up of the M20T. Without such a
Fig. 48. Window Patch Antenna, 2 DBi device connected between the serial port of the PC
and the M20T, you will get no information on the set-
up process.
GSM Antenna Installation 1. Insert the SIM card into the M20T.
2. Connect the serial cable to the M20T and a PC or
The max. antenna cable length is 8.0 m (including the 20-cm laptop.
M20 Terminal cable). Use a cable that is specified by the
supplier of the GSM antenna. Improper cables with re- 3. Connect the antenna cable and antenna to the M20T
sistances that are too high will reduce the antenna's ampli- connector.
fication. 4. Start a terminal program, e.g., Windows™
• Ideally you should know in which direction the next GSM HyperTerminal
station is located in order to position of the antenna 5. Connect the power supply to the M20 Terminal and
accordingly. plug into mains.
• The easiest way to check the signal quality is to operate a The M20T LED will be blinking now.
cellular (mobile) phone at the very place where you want to 6. Set terminal program to 19200 baud.
place the antenna. 7. Verify the correct operation of the M20T serial interface
— The cellular phone must operate in the same GSM by entering: AT.
network as the M20T. The M20T will respond: OK.
8. Change the M20T’s baud rate from 19200 (factory
— Drop-outs in voice communication indicate that the default) to 9600: AT+IPR=9600.
reception is too weak. The data communication will
never work where you have drop-outs in voice com- 9. Set terminal program back to 9600 baud.
munication with the cellular phone. The preferred 10. Command the M20T to cut the line whenever the DTR
way is to set-up the M20T on a terminal program and signal is dropped (OFF) or toggled ON/OFF: AT&D2
check the reception with the SIEMENS AT com- 11. Store setting in nonvolatile memory: AT&W.
mands – see the M20T handbook. 12. You may now enter the PIN number or let the Excel
— An alternative way to verify the signal quality is to use CPU do this. If you want to enter the PIN number now,
the terminal program on the CD supplied with the enter the PIN with the command AT+CPIN=”xxxx”,
M20T. You will find a special button on it that allows where xxxx represents the PIN number.
checking on the signal quality. NOTE: Regarding the PIN entry, the M20T shows the same
• Dipole antennas (e.g. antennas with a magnetic foot) must behavior as a regular cellular phone, as it uses the
sit on metal ground to achieve the specified amplification. same type of SIM card. This means, for example,
The larger the metal ground, the better. that after three false PIN inputs, the SIM card will
lock and need to be released via the “PUK” Personal
• The antenna must be mounted vertically, NOT horizontally. Unlocking Key (Master PIN).
• Avoid barriers for the antenna signal. Ideally, within a Repeated (more than two times) input of the wrong
range of approx. 3 m, there should not be any vertical “PUK” will destroy the SIM card irrevocably.
barriers that would block the antenna signal, such as
13. Once the M20 has accepted the PIN it will log into the
doors, PCs, cupboards, etc.
GSM net.
• Select the most suitable antenna. Location and mounting The terminal window will show “OK”.
limitations may require that special antennas be used, The M20T LED will be ON continuously.
such as antennas with higher amplification or directional
14. Disconnect the serial cable from the PC/laptop and con-
antennas.
nect it to the Excel CPU.
• Avoid loose contacts. All connections from the M20T to the 15. Verify that the M20T dials out on the telephone number
antenna must be tight. for data communication, otherwise its call will not be
• Increase the distance between the antenna and Excel CPU recognized by the XBS. The M20T can be forced to do
if you experience electromagnetic interference of the so by adding the letter <i> to the telephone number,
antenna signal to the CPU. An indication of this might be e.g. <ATDi1234567891234>
that the functioning of the MMI of the CPU is disturbed or NOTE: As soon as the PIN is entered into the Excel con-
that the outputs behave abnormally. troller, the following mechanisms will take place auto-
matically:
— Cyclical check (once per minute) for existence
of the PIN number in the M20 (AT+CPIN?)

29 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

— Sending of PIN number to M20T, if it has lost it.


This guarantees that communication will re-
sume automatically after exchange of the SIM
card or after power to the M20T has been lost.
Deletion of the PIN number or resetting the controller
will stop the above mechanisms.

Verification of the PIN


You can verify the PIN without connecting a terminal program
by following these steps:
1. Connect the XI582AH MMI.
2. Enter PIN.
3. Disconnect the XI582AH MMI.
4. Connect the M20T.
5. Reconnect the XI582AH MMI.
6. View the “PIN” field.
7. If it shows “0”, the PIN was wrong.
8. If it shows “PIN”, the PIN was correct.
Additional information about the M20 terminal may be found
at the following website:
http://www.siemens.de/ic/products/cd/english/index/products/
cellular/m20t.html

EN1B-0101GE51 R1105D 30
EXCEL 50 INSTALLATION INSTRUCTIONS

INSERT

0000106a
METER-BUS CONNECTION (NOT METER-BUS
WIRES
AVAILABLE IN N. AMERICA)
The meter bus adapter PW3 is connected with the cable
XW586 to the RJ45 plug of the XD50-FCS-HE01-xx ("xx""
depends upon the language). The cable XW586 has a length
of 1.8 m.
Table 25. Cable XW586

RJ45 Plug, 9-Pin -Sub-D


RS232 function
Pin Number Connector Pin No.
1 DCD 1
XW586
2 RxD 2
3 TxD 3 INSERT POWER
SUPPLY WIRES
4 DTR 4
5 GND 5 Fig. 50. PW3 Meter-Bus adapter connections

6 DSR 6 3. Connect PW3 Meter-Bus Adapter to Excel 50 Controller


using XW586 cable.
7 RTS 7
8 CTS 8
Not used 9

Up to three meter-bus devices can communicate with


Excel 50 via the application card XD50-FCS-HE01-xx and the
connected meter bus adapter PW3.

Meter-Bus Connection Procedure


1. Install PW3 Meter-Bus Adapter on DIN rail. Insert a
screwdriver into the slot in the DIN rail clamp on the
underside of the PW3 and pry downward to loosen
clamp until the unit snaps onto the rail. See Fig. 49.
0000108a

Fig. 51. Connecting Excel 50 to Meter-Bus adapter


4. Connect 24 V power to the Meter-Bus Adapter
according to Fig. 1. Insert wires into the terminals on the
DIN RAIL underside of the PW3 and tighten the screws on the
front of the unit.

3
CAUTION
Never connect V- of the PW3 to pin 2 of the Excel 50
1 Controller and V+ to pin 1. This could cause damage
to the Excel 50.
2

Fig. 49. Mounting of PW3


2. Connect Meter-Bus devices to PW3 Meter-Bus Adapter.
See Table 26 for a list of supported devices. Insert wires
into the terminals on the top of the PW3 and tighten the
screws on the front of the unit.

31 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

00000123
LEDs
POWER, GRN
METER BUS TxD, YEL
C-BUS TxD, YEL
C-BUS RxD, YEL
METER BUS RxD, YEL

C-BUS
TERMINATION
SWITCH

4 5 6
METER BUS
(RJ45 JACK)
Fig. 1. PW3 Meter Adapter power connections C-BUS

SHIELD
C+
Meter-Bus activity can by monitored using the LEDs on the

C-
HE01 application module (see Fig. 2).

Fig. 2. XD50-FCS Application Module LEDs

Table 26. Meter bus devices supported

device baud- mode energy vol. pwr. flow fwd. ret. temp. energy at ref.
rates temp. temp. diff. ref. day day
Siemens 300 1 X X X X X X X X
2WR4 2400 normal
300 2 X X X X X X
2400 fast
Schlumberger 300 1 X X X X X X X
CF50 2400 normal
300 2 X
2400 ref. day
Landis & Staefa 300 1 X X X X X X X X
Sonogyr WSD
Techem 300 1 X X X X X X
Delta-tech
Kompact and Split 2400
ABB / SVM 300 1 X X X X X X X
SVM 840 2400
Raab Karcher 300 1 X X X X X X X
Sensonic 2400
Kamstrup 300 1 X X X X X X X X
Multical 3 2400
Zenner Multidata S14 2400 1 X X X X X X X X1 X1
DZG Elektro 300 1 X
Baureihe S30 / 2400
DVS3016 9600
Relay 300 1 X2 X2
PadPuls M1C 2400
Relay 300 1 X2 X X3 X
PadPuls M4L 2400
1) Storage number 8.
2) PadPuls must be configured. Only one value can be counted.
3) Energy or volume at reference day depends on PadPuls configuration.
4) The Zenner meter requires twice as much power as other meters. Thus, only 1 Zenner meter can be connected to the PW3.

EN1B-0101GE51 R1105D 32
EXCEL 50 INSTALLATION INSTRUCTIONS

If 'Ctr. No.' is selected:


START-UP SEQUENCE Set the controller number using the '+' or '–' keys. Confirm
After powering up the controller or after a RESET the initial with ENTER.
screen of the Start-up sequence appears. A RESET can be
achieved by pressing the 'DOWN' and '–' keys simul- IMPORTANT
taneously. If no controller number is set or if the number shown
is not reconfirmed, the controller will not go online on
NOTE: The screens of the Start-up sequence are always
the C-Bus after start-up.
displayed in English as they are a part of the
operating system. Move the cursor to the 'NEXT' field with the ARROW keys.
Confirm with ENTER.
NOTE: The sequence shown is for embedded applications.
The Start-up sequence for standard and custom
CARE applications is similar but does not include Modem Part:
entry of configuration codes. See the Excel 50 User <active/inactive>
Guide (EN2B-0137GE51), for more details.
Appl. Mem. Size
128 KB . !NEXT
Honeywell
XL 50 This screen provides information about whether modem com-
V 2.04.00 munication is enabled and about application memory size.
!NEXT Enabling modem communication and changing the value for
application memory are done in a later screen. NEXT is high-
lighted. Confirm with ENTER.
This is the first screen of the Start-up sequence. It shows the
version of the company name, the controller name and the
firmware version. Confirm with ENTER. !Contr. Setup
!Select Applic.
Date:!13.06.1998 !Requ. Download
Time:!17:35 !DP Wiring Check
Ctr No:!1
!NEXT Select:
— 'Contr. Setup’ to configure the controller-specific
Select: hardware interfaces.
— the 'Date' field to enter the current date. — 'Select Applic.' to choose the application manually.
— the 'Time' field to enter the current time. — 'Requ. Download' to download an application via the
XI584 PC MMI or the C-Bus.
— the 'Ctr. No' field to enter the controller number.
— 'DP Wiring Check’ to set up the test mode with default
Confirm with ENTER.
user addresses.
If 'Date' is selected: Confirm with ENTER.
Set the date using the '+' or '–' keys. Use the arrow keys to
move from field to field. Confirm with ENTER. Select BACK.
Confirm with ENTER to return to the previous screen. Controller Setup
NOTE: The date must be entered in the following format: If 'Contr. Setup' has been selected, the following screen will
DD. MM. YYYY; for example, the 23rd of July 1997 appear:
must be entered as 23. 07. 1997. Press the CANCEL HW-Interf. Cfg.
key to abort the operation or to cancel an incorrect !B-Port ↑
entry before ENTER has been pressed. The value
previously displayed will be restored.
C-Bus 1
LON-Bus ↓
If 'Time' is selected:
Set the time using the '+' or '–' keys. Use the arrow keys to The contents of this listbox will depend upon the exact hard-
move from field to field. Confirm with ENTER. Use the ware configuration of the controller. The listed interfaces to be
CANCEL key to return to the previous screen. configured will be from among the following:
NOTE: The time must be entered in the following format: • B-Port
HH:MM in 24 hour clock format; for example: 9:30
a.m. must be 09:30 and 9:30 p.m. must be 21:30. • C-Bus.
Press the CANCEL key to abort the operation or to • LON-Bus
cancel an incorrect entry before ENTER has been • Meter Bus
pressed. The value previously displayed will be • Modem
restored.
NOTE: The C-Bus configuration option may appear even on
controllers that do not have an application module

33 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

containing a C-Bus connection in order to support


use of the XI584 User Interface.
LON-Bus Config.
Contr. Neuron ID
B-Port <neuron ID number>
Select ‘B-Port” and confirm with ENTER. The following screen Bus ID !BACK
appears:

IMPORTANT
B-Port Config. The bus ID is a non-unique number (i.e. different
Excel 500 controllers can have the same bus ID in
Baudrate: !9600 common) between 0 and 99 (inclusive) which the
!BACK user can edit after a reset during the controller's
start-up sequence or by changing the configuration
property nciXL500BusSetup. The factory default is
Move the cursor with the arrow keys to the field to set baud "0", which enables C-Bus and Standard LONWORKS
rate for the B-Port. Use the '+' and '–' keys to edit the fields. communication. Assigning a bus ID other than "0" will
Confirm with ENTER. enable LONWORKS communication with Building
NOTE: Live CARE is now capable of autodetecting the con- Management functionality and disable C-Bus
troller baud rate setting, then switching it temporarily communication.
to 38.4 Kbaud. When Live CARE is disconnected,
the controller will switch back to the previous baud This screen displays the unique identification number for the
rate setting automatically within 15 seconds. Neuron chip in the controller.
Move the cursor to the 'BACK' field with the arrow keys. Move the cursor to the 'BACK' field with the arrow keys.
Confirm with ENTER. Confirm with ENTER.

C-Bus Meter-Bus
Select ‘C-Bus” and confirm with ENTER. The following screen Select ‘M-Bus” and confirm with ENTER. The following screen
appears: appears:

C-Bus Config. M-Bus Config.


Baudrate: !76800 Baudrate: !9600
Contr.No: !
!BACK !BACK
NOTE: If you set the bus ID to a non-zero value, the C-bus Move the cursor with the arrow keys to the field to set baud
baudrate will be immediately disabled (i.e. it is then rate for the Meter Bus. Use the '+' and '–' keys to edit the
no longer editable). See also section " fields. Confirm with ENTER.
LON-Bus (i.e. LonWorks Network)" below. Move the cursor to the 'BACK' field with the arrow keys.
Confirm with ENTER.
If 'Baudrate' is selected:
Move the cursor with the arrow keys to the field to set baud Modem Communication
rate for the C-Bus. Use the '+' and '–' keys to edit the fields. Select ‘Modem’ and confirm with ENTER. The following
Confirm with ENTER. screen appears:
If 'Contr. No.' is selected:
Set the controller number using the '+' or '–' keys. Confirm Enable/Disable
with ENTER. Modem Part:
IMPORTANT
<ENABLE/DISABLE>
If no controller number is set or if the number shown !NEXT
is not reconfirmed, the controller will not go online on
the C-Bus after start-up. This screen allows the user to enable modem communication.
Move the cursor to the 'BACK' field with the arrow keys. If modem communication is enabled, ‘DISABLE’ will appear,
Confirm with ENTER. while ‘ENABLE’ will appear if it is currently disabled. To
change the current setting, move the cursor to the
enable/disable field, and select it by pressing ENTER.
LON-Bus (i.e. LonWorks Network) Change the setting with the ‘+’ or ‘-‘ keys. Confirm with
Select ‘LON-Bus” and confirm with ENTER. The following ENTER.
screen appears:

EN1B-0101GE51 R1105D 34
EXCEL 50 INSTALLATION INSTRUCTIONS

If modem communication has been enabled, the following two IMPORTANT


screens appear, otherwise the sequence returns to the If the application being downloaded exceeds the
ENABLE/DISABLE screen. Maximum Application Size entered in this screen, an
error message will occur and the download will not
be executed (see Excel 50 User Guide, EN2B-
Modem Config. 0137GE51).
Baudrate: 9600 When this screen appears again, the cursor is at NEXT. The
GSM PIN ******** new application memory size and the new number of trend
Reset Modm !NEXT samples calculated by the controller are shown. Confirm with
ENTER and continue to the next screen.
This screen appears only if modem communication is
enabled. Select:
Select Application
— ‘Baudrate.’ to set the baud rate for the modem/ISDN
terminal adapter. !Contr. Setup
— ‘GSM PIN’ to set the GSM Personal Identification !Select Applic.
Number (PIN). !Requ. Download
— 'Reset Modem' to return modem to factory settings, !DP Wiring Check
erasing any custom modem initialization. See section
"Remote Communications" for more information.
If 'Select Applic.' is then selected, the following screen will
Move the cursor with the arrow keys to the appropriate fields. appear listing applications and their burn dates:
Use the '+' and '–' keys to edit the fields.
NOTE: The GSM PIN must be entered right-justified.
NOTE: For GSM communication, the modem baud rate must
Select Applic.
be set at 9600. !AH01 ↑
Or select Reset Modem to send a reset command to the <applic.> <date.> 1
modem (if one is not yet attached to the controller, the <applic.> <date.> ↓
controller will send a reset when one is detected).
IMPORTANT Select the application using the ARROW keys. Confirm with
Resetting the modem will restore the factory defaults ENTER.
and erase any custom initialization.
Honeywell
Confirm with ENTER. Move the cursor to the 'NEXT' field with XL 50 V 2.03.00
the arrow keys. Confirm with ENTER. AH01 V 1.00
!NEXT
Appl. Mem. Size
128 KB RESTART The initialization screen of the chosen application will appear.
Rem. Trend Buf. It presents information about the versions of the controller
104 Entries!BACK and the application. Confirm with ENTER. If the Excel 50
controller is connected to a C-Bus, the following screen will
appear:
This screen is used to increase the size of the adjustable re-
mote trend buffer by reducing the application memory size.
The number of entries (trend samples) that can be stored in Append Busnumber
the buffer for Remote Building Central A is determined by a to User Addr. ?
calculation by the controller based upon the Application !YES
Memory Size entered in this screen (remote trend buffer = !NEXT
(128 Kbytes minus the Application Memory Size) * 1024 bytes
/ 47 bytes). The default for the Application Memory Size is
128; the min. Application Memory Size is 38 Kbytes. The Move the cursor to the 'YES' field. Confirm with ENTER.
default number of Remote Trend Buffer Entries is 104.
IMPORTANT
If a new value for Appl. Mem. Size has not been entered, the
If more than one Excel 50 Controller having the same
cursor is at NEXT. Confirm with ENTER and continue to the
application program is connected to the C-Bus, the
next screen.
user addresses must have the bus numbers
To increase the size of the buffer, use the arrow keys to appended to them.
select the digits for ‘Appl. Mem. Size’ and use the ‘+’ and '–'
keys to enter a new value. Then select RESTART and con-
firm with ENTER. The controller will reset again, and the Move the cursor to the 'NEXT' field using the ARROW keys.
‘Start-up’ sequence starts again from the beginning. Confirm with ENTER.

35 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

!CONFIG Request Download


C1!-1 C2!-1 !Contr. Setup
C3!-1 C4!-1 !Select Applic.
C5!-1 C6!-1 !Requ. Download
!DP Wiring Check
The codes of the configurable application can be changed In
this screen. The application codes can be generated with the
'LIZARD-Excel 50 Application Selector'. This screen does not If 'Requ. Download’ has been selected from the screen shown
appear with standard and custom CARE applications. above, the following screen appears.
NOTE: Not all applications have six configuration code
numbers. Applications with eight configuration codes
have two on a second screen as shown below. Please execute
First screen: Download
C1!-1 C2!-1
C3!-1 C4!-1
C5!-1 C6!-1 Follow the instructions for a download given in the XI584 User
!NEXT Guide or Lizard User Guide (if downloading via B-Port) or the
User Guide for the Building Central (if by C-Bus).
Second screen: NOTE: After download of an application, the controller
checks the user ID via its checksum and will not start
!CONFIG the application if it is invalid. An alarm “Invalid User
ID” will be issued.
C7!-1 C8!-1
Datapoint Wiring Check
NOTE If the 'LIZARD-Excel 50 Application Selector' is not !Contr. Setup
available, please contact your local Honeywell branch !Select Applic.
for support.
!Requ. Download
Select the appropriate code and change its value using the '+'
and '–' keys.
!DP Wiring Check
Move the cursor to the 'CONFIG' field. Confirm with ENTER.
If the codes entered in the screen are allowed, the default If 'DP Wiring Check’ has been selected from the screen
screen of normal operation will show up: shown above, default user addresses are generated following
the following pattern:
• AI0101: Analog input, board 1, input 1
<1. time program>Init • AO0201: Analog output, board 2, output 1
MON 13.06. 10:27
• DI0301: Digital input, board 3, input 1
TO: 20:30 20°C
!TODAY !NEXT • DO0401: Digital output, board 4, output 1
NOTE: The board numbers shown above are internal
references and are not relevant to the user. In Excel
If one or more codes entered are not allowed, the initialization 50 Controllers the numbers are fixed for the I/O type,
screen will show up again. Change the screens by selecting i.e. analog inputs are always AI01, digital inputs are
NEXT and confirming with ENTER until you have reached the always DI03, etc.
configuration screen again. Codes which are not allowed have
After generating the default addresses, the following screen
the value '-1' instead of the previously entered code. Change
appears:
the codes until all codes are correct.
You will now come to the default screen of normal operation:

<1. time program>Init !Default Points


MON 13.06. 10:27 !Alarm History
TO: 20:30 20°C
!TODAY !NEXT
Select
— 'Default Points' to display I/O points for checking values
and manually setting outputs for testing.
— 'Alarm History' to display current alarms. This feature
allows the system to be checked out by a single person
opening and closing inputs and then later reading the

EN1B-0101GE51 R1105D 36
EXCEL 50 INSTALLATION INSTRUCTIONS

alarm buffer to see if they were detected by the con- Press ENTER to select the value. Change the value/state
troller. using the '+' or '–' keys. Confirm with ENTER.
Confirm with ENTER. Press CANCEL to return to the previous screen (list of user
If ‘Default Points’ has been selected, the following screen will addresses).
be displayed showing all default user addresses and their If ‘Alarm History’ has been selected, the following screen will
current values. be displayed showing all points in alarm as well as any
system alarms (max. 100 entries):
!<user addr.> <val>↑
!<user addr.> <val>1 !<user addr.> ↑
!<user addr.> <val> !<user addr.> 1
!<user addr.> <val>↓ !<user addr.>
!<user addr.> ↓
To manually set outputs, move the cursor to select the output
point from the list box using the arrow keys. Confirm with
NOTE: Alarms are generated for changes of state/value on
ENTER.
inputs, which allows shorting and opening the inputs
In the case of analog points, the following screen is displayed. at the switches and/or sensors and then checking the
alarm buffer to verify the wiring.
<user addr.> To view an alarm, move the cursor to select the default user
STATE/VALUE: address from the list box using the arrow keys. Confirm with
!0.00% ENTER. The following screen will appear:

<date.> <time>
Press ENTER to select the value. Change the value using the <user addr.>
'+' or '–' keys. Confirm with ENTER. In the case of digital <value>
points, the following screen is displayed. <alarm text>

<user addr.> Press CANCEL to return to the previous screen.


STATE/VALUE: IMPORTANT
!0 % Reset the controller after using the test options to
clear the alarm buffer.

37 EN1B-0101GE51 R1105D
EXCEL 50 INSTALLATION INSTRUCTIONS

voltage terminal block max. current draw is 0.5 A. For


APPENDIX 1: SMOKE CONTROL MODE 220/240 Vac (50/60 Hz) applications, verify that no
potential between any conductor and earth ground
Smoke Control Configuration exceeds 150 Vac. See Table 14 for 1450 power
supply to be used.
Excel 50, 100, 500, 600 Controller or LonWorks I/O
9
11 All external field wiring must be limited to 3277 feet
UL-listed Fire Alarm
Control Unit supply
(999 meters) and be terminated to 14506944-001
AO fan 4
transient protector (35 V, 290 mA max.) except C-
8 11
airflow bus field wiring communicating at 1 MHz, which uses
sensor
12 14502412-010 transient protector (19 V, 500 mA. AI
exhaust
fan 5 on Excel 50 does not require protector.
2 AO
12 Distributed LONWORKS I/O (Distributed I/Os) wiring
C-BUS
XBS/XBSi/EBI must be in the same enclosure or less than 20 feet
damper
AO
3
(6 meters) from the adjacent enclosure. No pro-
Firefighters Smoke
Control Panel (FSCS) verification tection is required.
1
14505068 audible
annunciator 10 6 7
status control
Data File Set-Up
Generate the (Excel CARE) data file for the Excel 50 (non-
equipment side MMI model), 100, 500, or 600 Controllers. This data file has a
mix of hardware points for the necessary inputs and outputs
R6 R5
L3 L1 signal line to control fans, dampers, and other equipment. In addition to
2.2 ohm
CR6
2.2 ohm
CR4
the inputs and outputs, a customer-control program is written
20V 75V
to control the outputs per the sequence. The Excel 500/600
earth
GND GND ground controllers can reset the program once the data from the
CR2
10V
CR5
75V
operator interface indicates a normal condition for the
R3 R4 dedicated smoke control equipment. Wire conditions must be
L6 L5 common
2.2 ohm 2.2 ohm programmed to provide annunciation of trouble conditions.
CR1 CR3
W1 13V 75V Also required for a dedicated application for the Excel 50,
R2
L4 L2 signal line 500, or 600 Controller is a weekly time program to test control
2.2 ohm points, fans, and dampers by exercising the equipment and
schematic diagram of 14502412-010 transient protector verifying feedback automatically during low building activity
periods. The XL 100CUUKL is for non-dedicated smoke
control.
Fig. 52. Typical smoke control configuration
NOTES:
1 Locate and configure per NFPA 92A Section 3-4.3.4.
Panel Reset
UL-listed annunciator / FSCS panel switches have a Wen in the smoke control mode, panel reset is accomplished
min. rating of 24 V, 0.1 A, and lamps/LEDs have a by resetting the initiating panel contact circuit or by separating
rating of 24 V, limited to 50 mA. the initiating/reset switch on the FSCS panel.
2 Locate to minimize control wiring and piping. Avoid
running wires or piping through areas that have a

3
high fire risk.
Locate per UL 555S.
CAUTION
4 Locate separate from and below all building exhaust Equipment damage hazard.
fans and upstream of any prevailing winds. Failure to use listed/approved replacement parts can
damage the product, degrade operation, and result in
5 Exhaust to outside of building.
loss of safety function.
6 Locate airflow differential switch per CLEAFS405 and This product must be installed and operated within its
CLEAFS460 Airflow Differential Switches Installation environmental, mechanical, and electrical speci-
Instructions 95-6001. fications as contained in this document.
7 Locate UL-listed damper pressure / position indicator When servicing, use only listed/approved replace-
per damper installation instructions. ments parts ordered directly from the manufacturer.
8 Smoke control must be initiated by a listed fire alarm
control unit or in zone automatic alarm devices and
not devices located outside of the smoke control
zone interconnecting wiring must be within 20 feet (6
meters) and in conduit.
9 Refer to Smoke Control Fundamentals 77-1134.
10 Verify that the AC voltage source connected to inside
of main line voltage terminal block is from a UL 1481-
listed uninterruptible power supply. The main line

EN1B-0101GE51 R1105D 38
EXCEL 50 INSTALLATION INSTRUCTIONS

EN1B-0101GE51 R1105D 39
EXCEL 50 INSTALLATION INSTRUCTIONS

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:

Automation and Control Solutions


Honeywell GmbH
Böblinger Straβe 17
D-71101 Schönaich
Germany
http://europe.hbc.honeywell.com

EN1B-0101GE51 R1105D printed in Germany


95-7568-10

You might also like