ROOF MOUNT SOLAR PERMIT PACKAGE

ANAND PATEL
9.430 KW DC GRID TIED PHOTOVOLTAIC SYSTEM
137 OLD FERRY RD, METHUEN, MA 01844

PROPERTY BOUNDARY

AERIAL VIEW
36" FIRE SETBACK

CONTRACTOR INFO
ASHARE TEMPERATURE
LAWRENCE MUNI NEW COMBINER BOX
ELEV. HIGH TEMPERATURE LOW TEMPERATURE
SITE COORDINATES
NEW AC DISCONNECT
0.4% 2.0% EXTREME MINIMUM EXISTING MSP
LATITUDE: 42.75477°N
160 Ft 34°C 32°C -18°C EXISTING UTILITY LONGITUDE: -71.14556°W
DESIGN LOAD
GROUND SNOW LOAD : 50
FLAT ROOF SNOW LOAD : 50
WIND LOAD (MPH) : 160 ANAND PATEL
18" FIRE SETBACK
137 OLD FERRY RD,
METHUEN, MA 01844
CITY OF METHUEN TOWN
PROJECT DATA AHJ

UTILITY NATIONAL GRID (MA)


CODES: DRIVEWAY
PV SUMMARY
· NEC 2017(NFPA 70) INCLUDING AMMENDMENT
SYSTEM SIZE
AND MODIFICATION MADE BY THE BFPR AND (KWDC) : STC 410 X 23 = 9.430

DUTYPROMULGATED IN 527 CMR 12.00 : PTC 381.0 X 23 = 8.763


SYSTEM SIZE
· MA BUILDING CODE NINTH EDITION CMR 780 (KWAC) : 5.52 @240
QCELLS Q.PEAK DUO
MODULES : 23
ML-G10+ 410
ENPHASE
MICROINVERTER : 23
IQ8PLUS-72-2-US
SYSTEM DESCRTIPTION:
SOLAR ARRAYS: SITE OVERVIEW
DC OUTPUT (STC): 9.430 (±) KW DC
AC OUTPUT: 5.520 KW AC NOMINAL
5.520 KW MAXIMUM
Rev Description Date
YI PRODUCTION: 1.106 KWh
INTERCONNECTION DETAIL: A INITIAL DESIGN 8/19/2024

EQUIPMENT:
PANEL: (23) Q CELLS Q.PEAK DUO ML G10+ 410W INTERCONNECTION TYPE : BACKFEED
INVERTERS: (23) ENPHASE IQ8PLUS-72-2-US PROJECT # NA
RACKING (PITCH ROOF): UNIRAC SM LIGHT RAIL WITH OPRATING VOLTAGE :240V DATE DRAWN 8/19/2024
UNIRAC FLASHLOC OR FLASHKITPRO (UL 3741 SYSTEM) DRAWN BY E.R

SUBSTATION NAME: NOT KNOW SHEET #

SITE PLAN
PV-1.0
TITLE

HOSTING CAPACITY: SUFFICIENT


COVER PAGE
SCALE: 3/64" = 1'
R324.6.1 PATHWAYS:
NOT LESS THAN TWO MINIMUM 36-INCH WIDE PATHWAYS ON
SEPARATE ROOF PLANES,
FROM LOWEST ROOF EDGE TO RIDGE, SHALL BE PROVIDED ON
ENLARGED VIEW
NOTE:
NO FENCES OR GATES SURROUND THE PROPERTY LEGEND
ALL BUILDINGS.
AT LEAST ONE PATHWAY SHALL BE PROVIDED ON THE STREET OR UM UTILITY METER
DRIVEWAY SIDE OF THE ROOF.
FOR EACH ROOF PLANE WITH A PHOTOVOLTAIC ARRAY,A MINIMUM
36 INCH-WIDE PATHWAY FROM THE LOWEST ROOF EDGE TO RIDGE
MSP MAIN SERVICE PANEL
SHALL BE PROVIDED ON THE SAME ROOF PLANE OR STRADDLING
THE SAME AND ADJACENT ROOF PLANES.PATHWAYS SHALL BE C COMBINER
OVER AREAS CAPABLE OF SUPPORTING FIRE FIGHTERS
ACCESSING THE ROOF.PATHWAYS SHALL BE LOCATED IN AREAS JB JUNCTION BOX
WITH MINIMAL OBSTRUCTIONS SUCH AS VENT PIPES,CONDUIT , OR
MECHANICAL EQUIPMENT. AC AC DISCONNECT
R324.6.2 SETBACK AT RIDGE:
FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33
UM MSP AC C MODULE
PERCENT OF THE PLAN VIEW TOTAL ROOF AREA,NOT LESS THAN
AN 18 INCH CLEAR SET BACK IS REQUIRED ON BOTH SIDES OF A
ROOF OBSTRUCTIONS
HORIZONTAL RIDGE.
FOR PHOTOVOLTAIC ARRAYS OCCUPYING MORE THAN 33
36" ACCESS PATHWAYS
PERCENT OF THE PLAN VIEW TOTAL ROOF AREA,NOT LESS THAN A
36-INCH CLEAR SET BACK IS REQUIRED ON BOTH SIDES OF A 18" ACCESS PATHWAYS
HORIZONTAL RIDGE.
ROOF ACCESS POINT
R324.6.4 EMERGENCY ESCAPE AND RESCUE OPENING: PANELS
AND MODULES INSTALLED ON DWELLINGS SHALL NOT BE PLACED
THE PORTION OF A ROOF THAT IS BELOW AN EMERGENCY ESCAPE
JB
AND RESCUE OPENING. A 36-INCH-WIDE PATHWAY SHALL BE
PROVIDED TO THE EMERGENCY ESCAPE AND RESCUE OPENING.
ROOF ACCESS POINT
NOTES:
1. MINOR FIELD ADJUSTMENTS ALLOWED BASED 271'-6"
ON ACTUAL SITE CONDITION AND
MEASUREMENTS. CONTRACTOR INFO
2. THE 30 SECOND SHUTDOWN REQUIREMENT IS
INCORPORATED INTO THE 2017 NEC AND UL
STANDARD 1741. 38'-11"
3. EXISTING ROOF VENT SHOULD NOT BE
COVERED.

UM MSP AC

125'-8"
C

SHED
OLD FERRY RD

93'-7" JB

ANAND PATEL
152'

144'-3"
137 OLD FERRY RD,
METHUEN, MA 01844
JB

AHJ CITY OF METHUEN TOWN

DRIVEWAY UTILITY NATIONAL GRID (MA)

PV SUMMARY
SYSTEM SIZE
(KWDC) : STC 410 X 23 = 9.430

: PTC 381.0 X 23 = 8.763


SYSTEM SIZE
: 5.52 @240
(KWAC)
44'-2" MODULES : 23
QCELLS Q.PEAK DUO
ML-G10+ 410
ENPHASE
MICROINVERTER : 23
IQ8PLUS-72-2-US

271'-5" ROOF OBSTRUCTION


ROOF ACCESS POINT
Rev Description Date
PROPERTY LINE
A INITIAL DESIGN 8/19/2024

ROOF LINE

PROJECT # NA
DATE DRAWN 8/19/2024
DRAWN BY

SITE PLAN
E.R
SHEET # PV-2.0

1 SCALE: 1/32" = 1'-0"


TITLE

SITE PLAN
ARRAY AREA
ROOF TOTAL
LEGEND
ARRAY ROOF
ROOF # OF AREA AREA
ROOF AZIMUTH AREA AREA UM UTILITY METER
TILT MODULES (Sq. Ft.) COVERED BY COVERED BY
(Sq. Ft.)
ARRAY (%) ARRAY (%) MSP MAIN SERVICE PANEL
#1 38° 233° 10 211.40 2395 8.83
#2 29° 142° 3 63.42 2395 2.65 32.66 C COMBINER
#3 32° 232° 10 211.40 2395 8.83 JUNCTION BOX
ROOF #3 JB

AC AC DISCONNECT
UM MSP AC C
MODULE
ROOF OBSTRUCTIONS
36" ACCESS PATHWAYS

18" ACCESS PATHWAYS

ROOF ACCESS POINT

JB ROOF #2
OLD FERRY RD CONTRACTOR INFO

ANAND PATEL
137 OLD FERRY RD,
METHUEN, MA 01844
AHJ CITY OF METHUEN TOWN

UTILITY NATIONAL GRID (MA)

PV SUMMARY
SYSTEM SIZE
(KWDC) : STC 410 X 23 = 9.430

: PTC 381.0 X 23 = 8.763


SYSTEM SIZE
: 5.52 @240
JB (KWAC)
QCELLS Q.PEAK DUO
MODULES : 23
ML-G10+ 410
ENPHASE
MICROINVERTER : 23
IQ8PLUS-72-2-US
ROOF #1

Rev Description Date


(N)23 QCELLS Q.PEAK DUO ML-G10+ 410 A INITIAL DESIGN 8/19/2024

PROJECT # NA
DATE DRAWN 8/19/2024
DRAWN BY

ROOF PLAN
E.R
SHEET # PV-2.1

2 SCALE: 1/8" = 1'-0"


TITLE

ROOF PLAN
TABLE 1 TABLE 2
S1 FRAMING TYPE RAFTER ROOF ROOF ROOFING FRAMING FRAMING OC MAX PENETRATION MAX
NO. TILT TYPE TYPE SIZE SPACING SPACING OVERHANG
S2 ATTACHMENT IRONRIDGE FLASHFOOT 2
ROOF 1 38° COMP SHINGLE RAFTER 2"X4" 24" 48" 24"
S3 RAIL IRONRIDGE XR-10 RAIL 29° 24" 48" 24"
ROOF 2 COMP SHINGLE RAFTER 2"X4"
ROOF 3 32° COMP SHINGLE RAFTER 2"X4" 24" 48" 24"

CONTRACTOR INFO

MID AND END CLAMP


MODULE
MODULE

S3
S3
TABLE : PENETRATION
GUIDE FOR INSTALL
ROOF S2 TWO OR MORE ROWS OF PANELS

ROOF
S2
FLASHING
FLASHING
5/16" X 4.75" STAINLESS STEEL LAG ANAND PATEL
5/16" X 4.75" STAINLESS STEEL LAG BOLT WITH 2-1/2" MIN. EMBEDMENT
BOLT WITH 2-1/2" MIN. EMBEDMENT 137 OLD FERRY RD,
S1 METHUEN, MA 01844
FRONT VIEW AHJ CITY OF METHUEN TOWN

ENLARGE VIEW S1
UTILITY NATIONAL GRID (MA)

PV SUMMARY
STACKED STAGGERED FULLY STAGGERED
SYSTEM SIZE
(KWDC) : STC 410 X 23 = 9.430

: PTC 381.0 X 23 = 8.763


ONE ROW OF PANELS SYSTEM SIZE
: 5.52 @240
(KWAC)
ROOF QCELLS Q.PEAK DUO
MODULES : 23
ML-G10+ 410
ENPHASE
MICROINVERTER : 23
IQ8PLUS-72-2-US
MODULE

FULLY STAGGERED STACKED/STAGGERED


Rev Description Date
A INITIAL DESIGN 8/19/2024

SEE ENLARGE VIEW


PROJECT # NA
DATE DRAWN 8/19/2024

ATTACHMENT DETAIL DRAWN BY E.R


SHEET # PV-3.0
TITLE

STRUCTURAL
BACKFEED BREAKER SIZING MODULE QCELLS
MAX. CONTINUOUS OUTPUT 1.21A @ 240V MANUFACTURER
ELECTRICAL EQUIPMENT LIST
1.21 X 1.25 = 1.51AMPS 40A BREAKER - OK Q.PEAK DUO ML-G10+
MODULE MODEL
SEE 705.12 OF 2017 NEC S. NO. ITEMS DESCRIPTION QTY. 410
225 X 1.20 = 270 QCELLS Q.PEAK DUO 410
1 PV MODULE 23 MODULE (W)
ML-G10+ 410
270 - 200 = 70A ALLOWABLE BACKFEED MODULE PTC (W) 381
2 MICROINVERTER ENPHASE IQ8PLUS-72-2-US 23
MODULE Isc (A) 11.22
NEMA 3R UL LISTED
3 JUNCTION BOX 3 MODULE Voc (V) 45.13
JUNCTION BOX
ENPHASE IQ COMBINER MODULE Imp (A) 10.76
4 COMBINER 1
4/4C MODULE Vmp (V) 38.11
60A RATED DU222URB
SQUARE D KNIFEBLADE
5 AC DISCONNECT 1
LOCKABLE NEMA 3R UL
LISTED

(E) UTILITY METER 4


TO UTILITY (E) 225A RATED
GRID
MAIN SERVICE PANEL
(N) ENPHASE
1PH, 120/240V 60HZ
COMBINER BOX
(E) 200A / 2P MAIN
BREAKER
CELL
UM (TOP FED) WIRE LESS
MODEM
COMMS

IQ GATEWAY

1
A CONTRACTOR INFO
(N)15A 2

TO OTHER
LOAD
1 BRANCH OF 12
INV PV MODULE
(N)20A
5 JUNCTION
(N) 60A NON-FUSED
(N) 40A / 2P PV (N)20A
BOX
AC DISCONNECT
BREAKER NEMA 3R

2 BRANCH OF 11
INV PV MODULE

D C B 3
ANAND PATEL
(E) GROUNDING ELECTRODE
CONDUCTOR #6 BARE COPPER 137 OLD FERRY RD,
METHUEN, MA 01844
AHJ CITY OF METHUEN TOWN
NOTE:
1)CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS UTILITY NATIONAL GRID (MA)
AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.
PV SUMMARY
2)ALL CONDUCTORS NOT UNDER ARRAY ARE TO BE IN CONDUIT MINIMUM 7/8" ABOVE ROOF WITH SYSTEM SIZE
: STC 410 X 23 = 9.430
PROPER JUNCTION BOX AT EACH END PER 690.31A (KWDC)
: PTC 381.0 X 23 = 8.763
SYSTEM SIZE
: 5.52 @240
WIRE CALCULATION (KWAC)
QCELLS Q.PEAK DUO
MODULES : 23
STARTING ADJUSTMENT MAXIMUM ML-G10+ 410
STARTING TEMPERATURE MICROINVERTER :
ENPHASE
CURRENT FACTOR FOR ADJUSTED CURRENT 23
IQ8PLUS-72-2-US
CONDUCTOR CONDUCTOR CONDUIT ALLOWABLE TEMPERATURE CORRECTION
TAG DESCRIPTION APPLIED TO MORE THAN 3 CONDUCTOR APPLIED TO
QTY. SIZE (AWG) SIZE & TYPE AMPACITY RATING (°C) FACTOR
CONDUCTORS CONDUCTORS AMPACITY CONDUCTORS
310.15(B)(16) 310.15(B)(2)(a)
IN RACEWAY 310.15(B)(3)(a) IN RACEWAY
2 10 ENPHASE Q CABLE, COPPER
A N/A FREE AIR 40 90° 12.1 0.96 1 38.40 18.15 Rev Description Date
1 6 THWN-2 BARE COPPER-(GROUND) A INITIAL DESIGN 8/19/2024

2 10 THWN-2 COPPER- (L1,L2)


B 3/4" EMT 40 90° 12.1 0.96 1 38.40 18.15
1 10 THWN-2 COPPER- (GROUND) PROJECT # NA
DATE DRAWN 8/19/2024
3 10 THWN COPPER- (L1,L2,N)
DRAWN BY
C 3/4" EMT 40 75° 44.77 0.96 1 38.40 34.78 E.R

1 10 THWN COPPER- (GROUND) SHEET # PV-4.0


TITLE
3 10 THWN COPPER- (L1,L2,N)
D 3/4" EMT 40 75° 44.77 0.96 1 38.40 34.78 ELECTRICAL 3LD
1 10 THWN COPPER- (GROUND)
BACKFEED BREAKER SIZING
MODULE QCELLS
MAX. CONTINUOUS OUTPUT 1.21A @ 240V MANUFACTURER
1.21 X 1.25 = 1.51AMPS 40A BREAKER - OK ELECTRICAL EQUIPMENT LIST
Q.PEAK DUO ML-G10+
SEE 705.12 OF 2017 NEC S. NO. ITEMS DESCRIPTION QTY. MODULE MODEL
410
225 X 1.20 = 270 QCELLS Q.PEAK DUO
1 PV MODULE 23 MODULE (W) 410
270 - 200 = 70A ALLOWABLE BACKFEED ML-G10+ 410
MODULE PTC (W) 381
2 MICROINVERTER ENPHASE IQ8PLUS-72-2-US 23
MODULE Isc (A) 11.22
NEMA 3R UL LISTED
3 JUNCTION BOX 3 MODULE Voc (V) 45.13
JUNCTION BOX
ENPHASE IQ COMBINER MODULE Imp (A) 10.76
4 COMBINER 1
4/4C MODULE Vmp (V) 38.11
60A RATED DU222URB
SQUARE D KNIFEBLADE
5 AC DISCONNECT 1
LOCKABLE NEMA 3R UL
LISTED

4 (E) UTILITY METER


(E) 225A RATED TO UTILITY
1 MAIN SERVICE PANEL GRID
A (N) ENPHASE
2 1PH, 120/240V 60HZ
COMBINER BOX
(N) 200A / 2P MAIN
BREAKER
CELL
1 BRANCH OF 10
INV MODEM
WIRE LESS (TOP FED) UM
PV MODULE COMMS

IQ GATEWAY
CONTRACTOR INFO

(N)15A
2 BRANCH OF 9
INV (N)20A
PV MODULE
(N)20A
JUNCTION (N) LINESIDE TAP VIA UL
BOX LISTED CONNECTOR
NEMA 3R (N)20A
5
(N) FUSED
3 BRANCH OF 9 (N)20A AC DISCONNECT
INV
PV MODULE

4 BRANCH OF 9
PV MODULE INV

C D ANAND PATEL
B
137 OLD FERRY RD,
3 (E) GROUNDING ELECTRODE
CONDUCTOR #6 BARE COPPER
METHUEN, MA 01844
AHJ CITY OF METHUEN TOWN
NOTE:
1)CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS UTILITY NATIONAL GRID (MA)
AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.
PV SUMMARY
2)ALL CONDUCTORS NOT UNDER ARRAY ARE TO BE IN CONDUIT MINIMUM 7/8" ABOVE ROOF WITH SYSTEM SIZE
: STC 410 X 23 = 9.430
PROPER JUNCTION BOX AT EACH END PER 690.31A (KWDC)
: PTC 381.0 X 23 = 8.763
SYSTEM SIZE
: 5.52 @240
WIRE CALCULATION (KWAC)
QCELLS Q.PEAK DUO
MODULES : 23
STARTING ADJUSTMENT MAXIMUM ML-G10+ 410
STARTING TEMPERATURE MICROINVERTER :
ENPHASE
CURRENT FACTOR FOR ADJUSTED CURRENT 23
IQ8PLUS-72-2-US
CONDUCTOR CONDUCTOR CONDUIT ALLOWABLE TEMPERATURE CORRECTION
TAG DESCRIPTION APPLIED TO MORE THAN 3 CONDUCTOR APPLIED TO
QTY. SIZE (AWG) SIZE & TYPE AMPACITY RATING (°C) FACTOR
CONDUCTORS CONDUCTORS AMPACITY CONDUCTORS
310.15(B)(16) 310.15(B)(2)(a)
IN RACEWAY 310.15(B)(3)(a) IN RACEWAY
2 10 ENPHASE Q CABLE, COPPER
A N/A FREE AIR 40 90° 12.1 0.96 1 38.40 18.15 Rev Description Date
1 6 THWN-2 BARE COPPER-(GROUND) A INITIAL DESIGN 8/19/2024

2 10 THWN-2 COPPER- (L1,L2)


B 3/4" EMT 40 90° 12.1 0.96 1 38.40 18.15
1 10 THWN-2 COPPER- (GROUND) PROJECT # NA
DATE DRAWN 8/19/2024
3 10 THWN COPPER- (L1,L2,N)
DRAWN BY
C 3/4" EMT 40 75° 44.77 0.96 1 38.40 34.78 E.R

1 10 THWN COPPER- (GROUND) SHEET # PV-4.1


TITLE
3 10 THWN COPPER- (L1,L2,N)
D 3/4" EMT 40 75° 44.77 0.96 1 38.40 34.78 ELECTRICAL SLD
1 10 THWN COPPER- (GROUND)
MATERIAL LIST
ELECTRICAL EQUIPMENTS
QTY. PART TYPE PART NUMBER DESCRIPTION
23 MODULE Q.PEAK DUO ML-G10+ 410 QCELLS Q.PEAK DUO ML-G10+ 410
23 MICROINVERTER IQ8PLUS-72-2-US ENPHASE IQ8PLUS-72-2-US
3 JUNCTION BOX 480-276 NEMA 3R UL LISTED JUNCTION BOX
1 AC DISCONNECT DU222URB 60A RATED 240VAC NEMA 3R UL LISTED
1 COMBINER X-IQ-AM1-240-4/4C Enphase IQ Combiner 4/4C

CONTRACTOR INFO

BREAKER / FUSES
QTY. PART TYPE PART NUMBER DESCRIPTION

ANAND PATEL
137 OLD FERRY RD,
METHUEN, MA 01844
AHJ CITY OF METHUEN TOWN
RACKING
QTY. PART TYPE PART NUMBER DESCRIPTION UTILITY NATIONAL GRID (MA)

PV SUMMARY
20 RAILS & SPLICES XR-100-168A XR100, RAIL 168" CLEAR SYSTEM SIZE
: STC 410 X 23 = 9.430
(KWDC)
12 RAILS & SPLICES XR100-BOSS-01-M1 BONDED SPLICE, XR100 : PTC 381.0 X 23 = 8.763
SYSTEM SIZE
: 5.52 @240
88 CLAMPS & GROUNDING UFO-CL-01-A1 UNIVERSAL MODULE CLAMP, CLEAR (KWAC)
QCELLS Q.PEAK DUO
MODULES : 23
ML-G10+ 410
28 CLAMPS & GROUNDING UFO-STP-40MM-M1 STOPPER SLEEVE, 40MM, MILL MICROINVERTER : 23
ENPHASE
IQ8PLUS-72-2-US

7 CLAMPS & GROUNDING XR-LUG-03-A1 GROUNDING LUG, LOW PROFILE


85 ATTACHMENTS ATH-01-M1 ALL TILE HOOK (INCL. 2 LAGS)
85 ATTACHMENTS BHW-SQ-02-A1 SQUARE-BOLT BONDING HARDWARE
Rev Description Date
A INITIAL DESIGN 8/19/2024

PROJECT # NA
DATE DRAWN 8/19/2024
DRAWN BY E.R
SHEET # PV-5.0
TITLE

BOM
CAUTION
M
MULTIPLE SOURCE OF POWER
PHOTOVOLTAIC SYSTEM,
EQUIPPED WITH RAPID SHUTDOWN COMBINER BOX
AC DISCONNECT
690.12 MAIN SERVICE PANEL
UTILITY METER

SOLAR PV SYSTEM EQUIPPED UM MSP AC C

WITH RAPID SHUTDOWN

TURN RAPID PV SYSTEM AC DISCONNECT


SHUTDOWN SWITCH TO RATED AC OUTPUT CURRENT - 34.78 AMPS
THE "OFF" POSITION TO SOLAR ELECTRIC
AC AC NORMAL OPERATING VOLTAGE - 240 VOLTS

OLD FERRY RD
PV PANELS
JB

SHUT DOWN PV SYSTEM 690.14, 690.15, 690.54


AND REDUCE SHOCK
HAZARD IN THE ARRAY
"WARNING"
690.56(C)(1)(B)
PM DUAL POWER SOURCES
SECOND SOURCE IS PHOTO- VOLTAIC SYSTEM
RATED AC OUTPUT CURRENT - 34.78 AMPS CONTRACTOR INFO
AC NORMAL OPERATING VOLTAGE - 240 VOLTS

690.54
OPTIONAL SOLAR LOAD CENTER
JB

ARRAY

J/B
PHOTOVOLTAIC BACK-FED CIRCUIT BREAKER IN MAIN ELECTRICAL ANAND PATEL
"WARNING" PANEL IS AC DISCONNECT PER NEC690.17 137 OLD FERRY RD,
INVERTER OUTPUT CONNECTION METHUEN, MA 01844
DO NOT RELOCATE THIS NEC 690.31(G)(3) & (4), CRC R324.7 AHJ CITY OF METHUEN TOWN

OVERCURRENT DEVICE NATIONAL GRID (MA)


"WARNING" UTILITY

(UNLESS BUSBAR IS FULLY RATED)


705.12(D)(2) PHOTOVOLTAIC POWER SOURCE SYSTEM SIZE
:
PV SUMMARY

STC 410 X 23 = 9.430


(KWDC)
: PTC 381.0 X 23 = 8.763
EVERY 10' ON CONDUIT AND ENCLOSURES SYSTEM SIZE
: 5.52 @240
(KWAC)
QCELLS Q.PEAK DUO
MODULES : 23
ML-G10+ 410
ENPHASE
MICROINVERTER : 23
IQ8PLUS-72-2-US

NOTES:
1. NEC ARTICLES 690 AND 705 AND NEC SECTION R324 MARKINGS
SHOWN HEREON.
2. ALL MARKING SHALL CONSIST OF THE FOLLOWING: Rev Description Date

A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED OR A INITIAL DESIGN 8/19/2024

MACHINE PRINTED LETTERS OR ELECTRO-PLATING.


B. RED BACKGROUND COLOR WHITE TEXT AND LINE
PROJECT # NA
WORK.
DATE DRAWN 8/19/2024
C. AERIAL FONT.
DRAWN BY E.R
3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED IN
SHEET # PV-6.0
THE LOCATIONS SPECIFIED. SIGNAGE CANNOT BE
TITLE
HAND-WRITTEN.
4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH SIGNAGE
POP-RIVETS OR SCREWS.