0% found this document useful (0 votes)
839 views21 pages

Solis-3-Phase-Manual 5-10kw

Uploaded by

chrlok357
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
839 views21 pages

Solis-3-Phase-Manual 5-10kw

Uploaded by

chrlok357
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

Solis 4G Three Phase Inverter

(5-10kW) Installation and Operation Manual


Ver 1.1

Ningbo Ginlong Technologies Co., Ltd.


No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606

If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.

Ginlong (Ningbo) Technologies Co., Ltd.


Contents
1. Introduction …………………………………………………………………………………………………………………………… 2
1.1 Product Description ………………………………………………………………………………………………………… 2
1.2 Packaging ………………………………………………………………………………………………………………………… 3
2. Safety Instructions …………………………………………………………………………………………………………… 4
2.1 Safety Symbols ………………………………………………………………………………………………………………… 4
2.2 General Safety Instructions …………………………………………………………………………………………… 4
2.3 Notice For Use ………………………………………………………………………………………………………………… 5
3. Overview ……………………………………………………………………………………………………………………………… 6
3.1 Front Panel Display ……………………………………………………………………………………………………… 6
3.2 LED Status Indicator Lights …………………………………………………………………………………………… 6
3.3 Keypad …………………………………………………………………………………………………………………………… 6
3.4 LCD …………………………………………………………………………………………………………………………………… 6
4. Product handing and storage ………………………………………………………………………………… 7
4.1 Product handling …………………………………………………………………………………………………………… 7
4.2 Product Storage ……………………………………………………………………………………………………………… 8
5. Installation ……………………………………………………………………………………………………………………… 9
5.1 Select Location for the Inverter ……………………………………………………………………………………… 9
5.2 Mounting the Inverter ……………………………………………………………………………………………………… 11
5.3 Electrical Connections …………………………………………………………………………………………………… 13
6. Start & Stop ………………………………………………………………………………………………………………………… 21
6.1 Start the Inverter ……………………………………………………………………………………………………………… 21
6.2 Stop the Inverter ……………………………………………………………………………………………………………… 21
7. Operation ……………………………………………………………………………………………………………………………… 22
7.1 Main Menu ………………………………………………………………………………………………………………………… 22
7.2 Information ………………………………………………………………………………………………………………………… 22
7.3 Settings ……………………………………………………………………………………………………………………………… 24
7.4 Advanced Info. ……………………………………………………………………………………………………………………… 24
7.5 Advanced Settings ……………………………………………………………………………………………………………… 27
8. Maintenance ………………………………………………………………………………………………………………………… 31
9. Troubleshooting ………………………………………………………………………………………………………………… 31

10. Specifications …………………………………………………………………………………………………………………… 34


1. Introduction 1. Introduction
1.1 Product Description 1.2 Packaging
Solis 4G three phase inverters integrate DRM and backflow power control function, that When you receive the inverter, please ensure that all the parts listed below are included:
could suitable for smart grid requirement.
Three phase 4G series inverter contain 6 models which are listed below:
Solis-3P5K-4G, Solis-3P6K-4G, Solis-3P8K-4G, Solis-3P9K-4G, Solis-3P10K-4G
Solis-3P5K-4G-LV

Inverter x1 Back plate x1 Expansion screw x3

Solis 4G Three Phase Inverter


(5-10kW) Installation and Operation Manual
Ver 1.1

LED lights

Ginlong (Ningbo) Technologies Co., Ltd.

LCD display

Fastening screw x2 DC connector x2 User manual x1


4 buttons

Figure 1.1 Front view

WiFi/GPRS Monitor the rodsx1


(apolegamy)

If anything is missing, please contact your local Solis distributor.

Figure 1.2 Bottom view

.2. .3.
2. Safety Instructions 2. Safety Instructions
2.1 Safety Symbols
Safety symbols used in this manual, which highlight potential safety risks and important
safety information, are listed as follows:
CAUTION:
The PV array (Solar panels) supplies a DC voltage when they are exposed to
WARNING: sunlight.
WARNING symbol indicates important safety instructions, which if not
correctly followed, could result in serious injury or death. CAUTION:
Risk of electric shock from energy stored in capacitors of the Inverter.
NOTE:
NOTE symbol indicates important safety instructions, which if not correctly Do not remove cover for 5 minutes after disconnecting all power sources
followed, could result in some damage or the destruction of the inverter. (service technician only). Warranty may be voided if the cover is removed
without unauthorized.
CAUTION:
CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety CAUTION:
instructions, which if not correctly followed, could result in electric shock.
The surface temperature of the inverter can exceed 75℃ (167F).
CAUTION: To avoid risk of burns, DO NOT touch the surface when inverter is operating.
CAUTION, HOT SURFACE symbol indicates safety instructions, which if not The inverter must be installed out of reach of children.
correctly followed, could result in burns.

2.3 Notice For Use


2.2 General Safety Instructions
The inverter has been constructed according to the applicable safety and technical
guidelines. Use the inverter in installations that meet the following specifications only:
WARNING:
Please don’t connect PV array positive(+) or negative(-) to ground, it could 1.Permanent installation is required.

cause serious damage to the inverter. 2.The electrical installation must meet all the applicable regulations and standards.
3.The inverter must be installed according to the instructions stated in this manual.
WARNING:
Electrical installations must be done in accordance with the local and national 4.The inverter must be installed according to the correct technical specifications.
electrical safety standards. 5.To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before
the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid Supply
WARNING: Main Switch (AC) must be switched off before the solar panel's DC isolator shall be
To reduce the risk of fire, over-current protective devices (OCPD) are
switched off.
required for circuits connected to the Inverter.
The DC OCPD shall be installed per local requirements. All photovoltaic
source and output circuit conductors shall have disconnects that comply
with the NEC Article 690, Part II. All Solis three phase inverters feature
an integrated DC switch.

CAUTION:
Risk of electric shock. Do not remove cover. There is no user serviceable
parts inside. Refer servicing to qualified and accredited service technicians.

.4. .5.
3. Overview 4. Product handing and storage
3.1 Front Panel Display 4.1 Product handling
Please review the instruction below for handling the inverter:
1 2 3 1 The red circles below denote cutouts on the product package.
Push in the cutouts to form handles for moving the inverter (see Figure 4.1).

4 5 6 7
2
Figure 3.1 Front Panel Display

3.2 LED Status Indicator Lights

Description
Figure 4.1 move the inverter
Light Status
ON The inverter can detect DC power.
1 POWER
OFF No DC power or low DC power. 2.Open the carton, then handle both sides of inverter through the area denoted dotted line.
ON The inverter is operating properly. ( see figure 4.2).
2 OPERATION OFF The inverter has stopped to supply power.
FLASHING The inverter is initializing.
ON Alarm or fault condition is detected.
3 ALARM
OFF The inverter is operating properly.

Table 3.1 Status Indicator Lights

3.3 Keypad
There are four keys in the front panel of the Inverter(from left to right):
ESC, UP, DOWN and ENTER keys. The keypad is used for:
Scrolling through the displayed options (the UP and DOWN keys);
Access to modify the adjustable settings (the ESC and ENTER keys).

3.4 LCD
The two-line Liquid Crystal Display (LCD) is located on the front panel of the Inverter,
which shows the following information:
Figure 4.2 Inverter handles
Inverter operation status and data; Service messages for operator;
Alarm messages and fault indications.

.6. .7.
4. Product handing and storage 5. Installation
4.2 Product Storage 5.1 Select a Location for the Inverter
To select a location for the inverter, the following criteria should be considered:
Do not install in small closed spaces where air cannot circulate freely. To avoid
Use the original box to repackage the inverter, seal with adhesive tape with the desiccant overheating, always make sure the flow of air around the inverter is not blocked.
inside thebox. Exposure to direct sunlight will increase the operational temperature of the inverter and
may cause output power limiting. Ginlong recommends inverter installed to avoid
direct sunlight or raining.

To avoid over heating ambient air temperature must be considered when choosing
the inverter installation location. Ginlong recommends using a sun shade minimizing
direct sunlight when the ambient air temperature around the unit exceeds 104°F/40°C.

Figure 5.1 Recommended Installation locations

≤15°

Vertical
√ Backward

.8. .9.
5. Installation 5. Installation
5.2 Mounting the Inverter
Inverted Dimensions of mounting bracket:

× ×
The visibility of LED status indicator lights and LCD should be considered.
Install vertically (+/- 5°) or tilted backward (<=15°).
Don't mount inverter on the tilted forward wall.
Don't mount inverter on the horizontal.

Figure 5.3 Inverter wall mounting


300mm

300mm
Refer to figure 5.4 and figure 5.5. Inverter shall be mounted vertically.
The steps to mount the inverter are listed below.
1. Refer to Figure 5.4, the holes for expansion bolt based on the hole diameter of bracket
300mm 300mm 300mm
(ST6.3*60 cross recessed hexagon head tapping screws, HJ0108 10*50mm fished
expandable tubular), using the percussion drilling with the 10mm drill need to stay
vertically on the wall.And the drill hole must be vertically on the wall.
And all drill holes' depth is 60mm.
500mm

500mm

Bracket

Figure 5.2 Inverter Mounting clearance

Temperature of inverter heat sinker might 167℉/75℃.


Inverter is designed for working extreme environment, operation temperature range:
-15℉/25℃~149℉/65℃.
When 1 or more inverters are installed in one location, a minimum 12inchs clearance should
Suitable fixing screws
be kept between each inverter or other object. The bottom of the inverter should be 20inchs
clearance to the ground.
Figure 5.4 Inverter wall mounting

NOTE:
2. Make sure the bracket is horizontal. And the mounting holes (in Figure 5.4) are marked
Nothing should be stored on or placed against the inverter.
correctly. Drill the holes into wall at your marks.
3. Use the suitable expansion screws to fix the bracket on the wall.

.10. .11.
5. Installation 5. Installation
5. Anti-theft lock mount(optional)
WARNING: Anti-theft lock( User-supplied) function is that inverter is fixed in bracket in case theft.
The inverter must be mounted vertically. The lock is selected by 5mm(the keyhole diameter), and the lock of stainless steel is
preferred.

Anti-theft lock

Figure 5.7 Install security lock


Figure 5.5 Install the inverter
5.3 Electrical Connections
4. Lift the inverter and hang it on the backet, and fixing both sides of inverter with
Inverter designs quick-connect terminal, so top cover needn't open during electrical
locking screws (accessories).
connection. The sign meaning located the bottom of inverter, as shown below in table 5.1.
All electrical connections are suit for the local or national standard.

Locking screws
+ Positive DC input terminal
- Negative DC input terminal
DC 1 DC input terminal
DC 2 DC input terminal
DC SWITCH Switch of DC input terminals
COM RJ45 and terminal block for RS485 communication port
GRID Connecting terminal of the Grid
Table 5.1 Electrical connection symbols

The electrical connection of the inverter must follow the steps listed below:

1. Switch the Grid Supply Main Switch (AC) OFF.


2. Switch the DC Isolator OFF.
Figure 5.6 Fixed the inverter
3. Assemble PV input connector to the Inverter.
.12. .13.
5. Installation 5. Installation
5.3.1 Grounding
Solis recommends 2 ground protection methods: Through grid terminal connection
and external heat sink connection. C
If AC terminal is used to connect ground, please refer to the contents of 5.3.2.
If the heat sink is used to connect the ground, please follow the steps below:

1) Prepare the grounding cable: recommend to use the ≥ 6mm² outdoor


copper-core cable. D

2) Prepare OT terminals: M6.


Figure 5.9 strip wire
Important:
For multiple inverters in parallel , all inverters should be connected to the
Important:
same ground point to eliminate the possibility of a voltage potential existing
After crimping the terminal to the wire, inspect the connection to ensure the
between inverter grounds.
terminal is solidly crimped to the wire.

3) Strip the ground cable insulation to a suitable length(see Figure 5.8). 5) Remove the screw from the heat sink ground point.
6) Connect the grounding cable to the grounding point on the heat sink,and tighten the
B grounding screw, Torque is 3Nm(see figure 5.10).

Grounding screw

Figure 5.8 suitable length

Important:
Figure 5.10 Fixed cable
B (insulation stripping length) is 2mm~3mm longer than A (OT cable
terminal crimping area) 2mm~3mm.
Important:
For improving anti-corrosion performance,
4) Insert the stripped wire into the OT terminal crimping area and use the hydraulic after ground cable installed, apply silicone or paint is preferred to protect.
clamp to crimp the terminal to the wire (see Figure 5.9).

.14. .15.
5. Installation 5. Installation
5.3.2 Connect PV side of inverter
5. Measure PV voltage of DC input with multimeter, verify DC input cable polar

Before connecting inverter, please make sure the PV array open circuit (see figure 5.17), and ensure each string of PV voltage in range of inverter operation.
voltage is within the limit of the inverter. Connect DC connector with inverter until hearing a slight clicking sound indicates
connection succeed. (see figure 5.18)
Before connection, please make sure the polarity of the output voltage of
PV array matches the“DC+”and“DC-”symbols.

Before connecting inverter, please make sure the PV array open circuit
voltage is within the limit of the inverter.
Figure 5.14 Insert the Wire into the
Figure 5.13 Disassemble the Connector Cap nut
Connector Cap nut and contact pin

Crimping plier

Figure 5.15 Crimp the contact pin to the wire Figure 5.16 Connector with Cap nut Screwed on
Figure 5.11 DC+ Connector Figure 5.12 DC- Connector

Please use approved DC cable for PV system. +

-
Cross section(mm²) Figure 5.17 Multimeter measurement Figure 5.18 Connect the DC
Cable type Connectors to the Inverter
Range Recommended value
Industry generic PV cable 4.0~6.0
4.0(12AWG)
(model:PV1-F) (12~10AWG)
WARNING:
If DC input wire reverses, please not operate DC switch, DC1and DC2
The steps to assemble the DC connectors are listed as follows: instantly to avoid inverter damage.. Damage caused by this reason isn't
1. Strip off the DC wire for about 7mm, Disassemble the connector cap nut. (see Figure 5.13) covered by warranty.
2. Insert the wire into the connector cap nut and contact pin. (see Figure 5.14) Solution: Until reduced sun irradiance and PV voltage is below 0.5 A(mostly
3. Crimp the contact pin to the wire using a proper wire crimper. (see Figure 5.15) in evening), then put DC switch in “off” position, remove “+”, “-” connectors to
reconnect wires.
4. Insert metal connector into top of connector, and tighten nut with torque 2.5-3 Nm
(see figure 5.16).

.16. .17.
5. Installation 5. Installation
5.3.3 Connect grid side of inverter
For all AC connections, 2.5 – 6 mm², 105°C cable is required to be used. Please make sure the B) Insert the cable through the jacket and cap nut of connector, then insert the wires to the grid
resistance of cable is lower than 1.50hm. If the wire is longer than 20m, preferred to 6mm² cable. terminal and tighten the screws on the connector (see figure 5.22).
Please try to pull out the wire to make sure it is well connected.
Internal of AC connector signs "L1","L2","L3","N" and "PE " five connection
ports (see Figure 5.20). Three live wires are connected the "L1", "L2"and
"L3" terminals respectively; ground wire connects "PE "; neutral wire
connects "N" terminal:

Each inverter has a corresponding AC grid terminal connector. See figure 5.19.

PE
N L3

Figure 5.22 Connected cable


L1 L2

Please fixed cable with PH1 cross screwdriver.


Figure 5.19 Figure 5.20
AC Grid Terminal Connector AC Grid Terminal Connector Inside PH1 cross screwdriver

C) Assemble the connector and tighten up cap on the terminal. See Figure 5.21 right.
The steps to assemble AC grid terminal connector are listed as follows:
A) Strip the end of AC wire about 8mm. See figure 5.21 left. D) Connect AC grid terminal connector to the inverter, small click will confirm that connection
is appropriate. (see figure 5.23)

Figure 5.23 AC connector to inverter


Figure 5.21 Connect Wires to the Grid Terminal

.18. .19.
5. Installation 6. Start & Stop
5.3.4 Max. over current protection device (OCPD) 6.1 Start the Inverter
To protect the inverter's AC grid connection conductors, Solis recommends installing To start up the Inverter, it is important that the following steps are strictly followed:
breakers that will protect against overcurrent. The following table defines OCPD ratings for
1. Switch the grid supply main Switch (AC) ON first.
the Solis 5-10kW three phase inverters.
2. Switch the DC switch ON. If the voltage of PV arrays are higher than start up voltage,
Rated output Current for protection the inverter will turn on. The red LED power will light.
Inverter Rated voltage(V)
current (A) device (A)
3. When both the DC and the AC sides supply to the inverter, it will be ready to generate
Solis-3P5K-4G 400 7.2 20 power. Initially, the inverter will check both its internal parameters and the parameters
Solis-3P6K-4G 400 8.7 20 of the AC grid, to ensure that they are within the acceptable limits. At the same time,
the green LED will flash and the LCD displays the information of INITIALIZING.
Solis-3P8K-4G 400 11.5 20
4. After 30-300 seconds (depending on local requirement), the inverter will start to
Solis-3P9K-4G 400 13.0 32
generate power. The green LED will be on continually and the LCD displays
Solis-3P10K-4G 400 14.4 32 GENERATING.

Solis-3P5K-4G-LV 208/220/240 13.1 32

Table 5.2 Rating of grid OCPD WARNING:


Do not touch the surface when the inverter is operating. It may be
hot and cause burns.
5.3.5 Inverter monitoring connection
The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are
optional (Figure 5.24). For connection instructions, please refer to the Solis Monitoring 6.2 Stop the Inverter
Device installation manuals.
To stop the Inverter, the following steps must be strictly followed:
1. Turn off the ac switch.
Smart phone monitoring 2. Put the DC SWITCH on the inverter in the position of "OFF".
3. Remove the positive and negative dc lines and remove the ac lines.
GPRS monitoring

Internet

Wi-Fi monitoring Router Web server

PC monitoring

Wi-Fi box
Wi-Fi monitoring

Figure 5.24 Wireless communication function

.20. .21.
7. Operation 7. Operation
Display Duration Description
In normal operation, LCD screen alternatively shows inverter power and operation status
(see Figure 7.1). The screen can be scrolled manually by pressing the UP/DOWN keys. V_DC1 350.8V V_DC1: Shows input 01 voltage value.
Pressing the ENTER key gives access to Main Menu. I_DC1 5.1A 10 sec
I_DC1: Shows input 01 current value.

V_DC2 350.8V V_DC2: Shows input 02 voltage value.


I_DC2 5.1A 10 sec
Pressing the I_DC2: Shows input 02 current value.
ESC key Main Menu
calls back the
previous menu. V_A 230.4V V_A: Shows the grid's voltage value.
Information
I_ A 8.1A 10 sec
Power 3424W UP/DOWN I_A: Shows the grid's current value.
01-01-2014 12:04
Settings V_C 230.4V V_C: Shows the grid's voltage value.
5 sec UP/DOWN or I_ C 8.1A 10 sec
Start auto-scroll UP/DOWN I_C: Shows the grid's current value.
(10 sec)
Advanced Info. Status: Generating Status: Shows instant status of the Inverter.
Status: Generating Power: 1488W 10 sec
01-01-2014 12:04 UP/DOWN Power: Shows instant output power value.

Pressing the Advanced settings


Grid Frequency
ENTER key F_Grid 50.06Hz 10 sec F_Grid: Shows the grid's frequency value.
gives access to
the main menu.

Total Energy
0258458 kwh 10 sec Total generated energy value.
Figure 7.1 Operation Overview

This Month: 0123kwh This Month: Total energy generated this month.
Last Month: 0123kwh 10 sec
Last Month: Total energy generated last month.

7.1 Main Menu Today: 15.1kwh Today: Total energy generated today.
Yesterday: 13.5kwh 10 sec
There are four submenus in the Main Menu (see Figure 7.1): Yesterday: Total energy generated yesterday.
1. Information
Inverter SN
2. Settings 00000000000000 10 sec Display series number of the inverter.
3. Advanced Info.
4. Advanced Settings Table 7.1 Information list

7.2 Information 7.2.1 Lock screen


The Solis three Phase 4G Inverter main menu provides access to operational data and Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks
information. The information is displayed by selecting "Information" from the menu (Figure 7.2(a)) or unlocks (Figure 7.2 (b)) the screen.
and then by scrolling up or down.

5.2 Stop the Inverter


(a) (b)
Figure 7.2 Locks and Unlocks the Screen of LCD

.22. .23.
7. Operation 7. Operation
7.3 Settings
The following submenus are displayed when the Settings menu is selected: Select “Advanced Info.” from the Main Menu. The screen will require the password as below:
1.Set Time
2.Set Address
YES=<ENT> NO=<ESC>
Password:0000
7.3.1 Set Time
This function allows time and date setting. When this function is selected, the LCD will Figure 7.5 Enter password
display a screen as shown in Figure 7.3.
After enter the correct password the Main Menu will display a screen and be able to access
to the following information.
NEXT=<ENT> OK=<ESC>
01-01-2016 16:37 1.Alarm Message 2. Running message 3.Version 4. Daily Energy
5. Monthly Energy 6. Yearly Energy 7. Daily Record 8.Communication Data
Figure 7.3 Set Time
The screen can be scrolled manually by pressing the UP/DOWN keys. Pressing the ENTER
key gives access to a submenu. Press the ESC key to return to the Main Menu.
Press the UP/DOWN keys to set time and data. Press the ENTER key to move from one
digit to the next (from left to right). Press the ESC key to save the settings and return to 7.4.1 Alarm Message
the previous menu.
The display shows the 100 latest alarm messages (see Figure 7.6). Screens can be scrolled
manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous
7.3.2 Set Address menu.
This function is used to set the address when muti inverters are connected to three monitor.
The address number can be assigned from “01”to “99”(see Figure 7.4). The default address Alarm001: OV-G-V
Time: 27-11 Data: 7171
number of Solis Three Phase Inverter is “01”.

Figure 7.6 Alarm Message


YES=<ENT> NO=<ESC>
Set Address: 01
7.4.2 Running Message
Figure 7.4 Set Address
This function is for maintaince person to get running message such as internal temperature,
Standard No.1,2,etc.
Press the UP/DOWN keys to set the address. Press the ENTER key to save the settings.
Screens can be scrolled manually by pressing the UP/DOWN keys.
Press the ESC key to cancel the change and return to the previous menu.

7.4.3 Version
7.4 Advanced Info - Technicians Only The screen shows the model version and the software version of the Inverter
(see Figure 7.7).

NOTE:
To access to this area is for fully qualified and accredited technicians only. Model: 08
Software Version: D20001
Enter menu “Advanced Info.” and “Advanced settings” (need password).

Figure 7.7 Model Version and Software Version

.24. .25.
7. Operation 7. Operation
7.4.4 Daily Energy 7.4.7 Communication Data
The function is for checking the energy generation for selected day. The screen shows the internal data of the Inverter (see Figure 7.14), which is for service
technicians only.
YES=<ENT> NO=<ESC>
Select: 2015-02-23
01-05: 01 25 E4 9D AA
Figure 7.8 Select date for daily energy 06-10: C2 B5 E4 9D 55

Figure 7.14 Communication Data


Press DOWN key to move the cursor to day, month and year, press UP key to change the
digit. Press Enter after the date is fixed.
7.5 Advanced Settings - Technicians Only
2015-02-22: 051.3kWh
2015-02-23: 061.5kWh NOTE:
To access to this area is for fully qualified and accredited technicians only.
Figure 7.9 Daily energy Please follow 7.4 to enter password to access this menu.

Press UP/DOWN key to move one date from another. Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard 2. Grid ON/OFF 3. Clear Energy 4. New Password
7.4.5 Monthly Energy and Yearly Energy 5. Power Control 6. Calibrate Energy 7.STD. Mode Settings

The two functions are for checking the energy generation for selected month and Year.
7.5.1 Selecting Standard
This function is used to select the grid's reference standard (see Figure 7.15).

YES=<ENT> NO=<ESC> YES=<ENT> NO=<ESC> YES=<ENT> NO=<ESC>


Select: 2015-02 Select: 2015 Standard:AUS-Q-0.8
Figure 7.10 Select month for monthly energy Figure 7.11 Select year for yearly energy
Figure 7.15

Press DOWN key to move the cursor, press UP key to change the
digit. Press Enter after the month/year is fixed. Press the UP/DOWN keys to select the standard (AS4777, VDE4105, VDE0126, UL-240V-A,
UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3 (for 4-5kW
models), EN50438 DK, EN50438 IE, EN50438 NL and “User-Def” function). Press the
2015-02: 0510kWh 2015: 0017513kWh ENTER key to confirm the setting. Press the ESC key to cancel changes and returns to
2015-01: 0610kWh 2014: 0165879kWh
previous menu.

Figure 7.12 Month energy Figure 7.13 Yearly energy

NOTE:
Press UP/DOWN key to move one date from another.
This function is for technicians use only.
7.4.6 Daily record
The screen shows history of changing settings. Only for maintance personel.

.26. .27.
7. Operation 7. Operation
7.5.3 Clear Energy
Selecting the “User-Def” menu will access to the following submenu (see Figure 7.16), Clear Energy can reset the history yield of inverter

OV-G-V1: 260V
OV-G-V1-T: 1S These two functions are applicable by maintenance personnel only, wrong
operation will prevent the inverter from working properly.
Figure 7.16

NOTE: 7.5.4 New Password


The " User-Def" function can be only used by the service engineer and
This function is used to set the new password for menu “Advanced info.” and “Advanced
must be allowed by the local energy supplier.
information” (see Figure 7.18).
Below is the setting range for “User-Def”. Using this function, the limits can be changed
manually. YES=<ENT> NO=<ESC>
Password: 0000
OV-G-V1: 220---290V OV-G-F1: 50.2-53Hz(60.2-64Hz)
OV-G-V1-T: 0.1---9S OV-G-F1-T: 0.1---9S Figure 7.18 Set new password
OV-G-V2: 220---290V OV-G-F2: 50.2-53Hz(60.2-64Hz)
OV-G-V2-T: 0.1---1S OV-G-F2-T: 0.1---9S
Enter the right password before set new password. Press the DOWN key to move the cursor,
Press the UP key to revise the value. Press the ENTER key to execute the setting.
UN-G-V1: 90---210V UN-G-F1: 47-49.5Hz(56-59.8Hz)
Press the ESC key to return to the previous menu.
UN-G-V1-T: 0.1---9S UN-G-F1-T: 0.1---9S
UN-G-V2: 90---210V UN-G-F2: 47-49Hz(56-59.8Hz)
UN-G-V2-T: 0.1---1S UN-G-F2-T: 0.1---9S 7.5.5 Power control
Startup-T:10---600S
Active and reactive power can be set through power setting button.
There are 5 item for this sub menu:
Restore-T:10---600S
1. Set output power 2. Set Reactive Power 3. Out_P With Restore
Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the highlighted
4. Rea_P With Restore 5. Select PF Curve
item. Press the UP/DOWN keys again to change the setting. Press the ENTER key to save the
setting. Press the ESC key to cancel changes and returns to the previous menu.
This function is applicable by maintenance personnel only, wrong operation
7.5.2 Grid ON/OFF will prevent the inverter from reaching maximum power.
This function is used to start up or stop the power generation of Solis Three Phase
Inverter (see Figure 7.17).

Grid ON 7.5.6 Calibrate Energy


Grid OFF Maintenance or replacement could clear or cause a different value of total energy. Use this
function could allow user to revise the value of total energy to the same value as before. If
Figure 7.17 Set Grid ON/OFF the monitoring website is used the data will be synchronous with this setting automatically.
(see Figure 7.19).
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key
to save the setting. Press the ESC key to return to the previous menu.

.28. .29.
7. Operation 8. Maintenance
Solis Three Phase Inverter does not require any regular maintenance. However, cleaning
YES=<ENT> NO=<ESC> the dust on heat-sink will help the inverter to dissipate the heat and increase its life time.
Energy:0000000kWh The dust can be removed with a soft brush.

Figure 7.19 Calibrate energy


CAUTION:
Do not touch the inverter's surface when it is operating. Some parts of the
Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the inverter may be hot and cause burns. Turn off the inverter (refer to Section
ENTER key to execute the setting. Press the ESC key to return to the previous menu. 6.2) and wait for a cool-down period before before any maintenance or
cleaning operation.
7.5.7 STD setting
Solis 4G inverter could set different work mode to work with different grid requirement. The LCD and the LED status indicator lights can be cleaned with a damp cloth if they are too
There are 4 items under STD mode setting. dirty to be read.
1. Working Mode Set 2. Power Rate Limit 3. Freq Derate Set
4. 10mins Voltage Set 5. Initial Settings.
There are 6 items in working mode submenu. NOTE:
1. NULL,Volt-watt 2. Volt-var 3. Fixed-PF 4. Reac-power 5. Power-PF Never use any solvents, abrasives or corrosive materials to clean the inverter.
There are 2 items in power rate limit submenu.
1. Power Rate: 0-100% 2. RateP_Sts-US: stop/run
There are 3 items in Freq Derate Set submenu.
1. over Freq 2. under Freq 3. Derate mode. 9. Troubleshooting
There is 1 item in 10mins voltage set submenu.
1. 10mins voltage:244-258V. The inverter is designed in accordance with the most important international grid-tied
There are 5 items in initial setting submenu. standards and safety and electromagnetic compatibility requirements. Before delivering to
the customer, the inverter has been subjected to several tests to ensure its optimal operation
1. Work mode default 2. Power rate default 3. Fre Derate Default
and reliability.
4. 10mVvoltage Default 5. DRM ON/OFF

In case of failure, the LCD screen will display an alarm message. In this case, the inverter
may stop feeding into the grid. The failure descriptions and their corresponding alarm
messages are listed in Table 9.1:

.30. .31.
9. Trouble Shooting 9. Trouble Shooting
Alarm Message Failure description Solution Alarm Message Failure description Solution

1.Check PV input connections 1.Remove all DC input, reconnect and


No power Inverter no power 2.Check DC input voltage PV ISO-PRO restart inverter one by one.
PV isolation protection
on LCD (single phase >120V, three phase >350V) 01/02 2.Identify which string cause the fault and
3.Check if PV+/- is reversed check the isolation of the string.

1.Check if the connector on main ILeak-PRO Leakage current protection 1.Check AC and DC connection
LCD show initializing board or power board are fixed. 01/02/03/04 2.Check inverter inside cable connection.
Can not start-up
all the time 2.Check if the DSP connector to
power board are fixed. RelayChk-FAIL Relay check fail
1.Restart inverter or contact installer.
1.Resistant of AC cable is too high. DCinj-FAULT High DC injection current
Change bigger size grid cable
OV-G-V01/02/03/04 Over grid voltage AFCI self-detection
2.Adjust the protection limit if it’s
allowed by electrical company. (model with AFCI AFCI module self-detect fault 1.Restart inverter or connect technician.
module)
UN-G-V01/02 Under grid voltage
Over grid frequency 1.Use user define function to adjust the Arcing protection
OV-G-F01/02 1. Check inverter connection whether arc
protection limit if it’s allowed by (model with AFCI Detect arc in DC circuit
module) exists and restart inverter.
UN-G-F01/02 Under grid frequency electrical company.
G-IMP High grid impedance
1.Check connections and grid switch.
Table 9.1 Fault message and description
NO-GRID No grid voltage 2.Check the grid voltage inside inverter
terminal.
OV-DC01/02/03/04 Over DC voltage 1.Reduce the module number in series
NOTE:
If the inverter displays any alarm message as listed in Table 9.1; please
OV-BUS Over DC bus voltage 1.Check inverter inductor connection turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5
UN-BUS01/02 Under DC bus voltage 2.Check driver connection
minutes before restarting it (refer to Section 5.1 to start your inverter). If the
GRID-INTF01/02 Grid interference failure persists, please contact your local distributor or the service center.
1.Restart inverter
OV-G-I Over grid current Please keep ready with you the following information before contacting us.
2.Change power board
IGBT-OV-I Over IGBT current
1.Restart inverter
DC-INTF DC input overcurrent 2.Identify and remove the string to the fault MPPT
OV-DCA-I 2.Change power board 1. Serial number of Solis Three Phase Inverter;
IGFOL-F Grid current tracking fail 2. The distributor/dealer of Solis Three Phase Inverter (if available);
1.Restart inverter or contact installer.
IG-AD Grid current sampling fail 3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
1.Check inverter surrounding ventilation.
OV-TEM Over Temperature 2.Check if there’s sunshine direct on of the LED status indicator lights. Other readings obtained from the Information submenu
inverter in hot weather. (refer to Section 6.2) will also be helpful.);
Initialization system fault
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings
INI-FAULT
, etc.);
Comm. failure between main
DSP-B-FAULT
and slave DSP
1.Restart inverter or contact installer. 6. Your contact details.

12Power-FAULT 12V power supply fault

.32. .33.
10. Specifications 10. Specifications
Model Solis-3P5K-4G Model Solis-3P6K-4G
Max. DC input power (Watts) 6000 Max. DC input power (Watts) 7200
Max. DC input voltage (Volts) 1000 Max. DC input voltage (Volts) 1000
Rated DC voltage (Volts) 600 Rated DC voltage (Volts) 600
Start-up voltage (Volts) 180 Start-up voltage (Volts) 180
MPPT voltage range (Volts) 160...850 MPPT voltage range (Volts) 160...850
Max. input current (Amps) 11+11 Max. input current (Amps) 11+11
Max short circuit input current (Amps) 17.2+17.2 Max short circuit input current (Amps) 17.2+17.2
MPPT number/Max input strings number 2/2 MPPT number/Max input strings number 2/2
Rated output power (Watts) 5000 Rated output power (Watts) 6000
Max. output power (Watts) 5500 Max. output power (Watts) 6600
Max. apparent output power (VA) 5500 Max. apparent output power (VA) 6600
Rated grid voltage (Volts) 3/N/PE~400 Rated grid voltage (Volts) 3/N/PE~400
Grid voltage range (Volts) 313...470 Grid voltage range (Volts) 313...470
Rated output current (Amps) 7.2 Rated output current (Amps) 8.7
Power Factor (at rated output power) 0.8leading~0.8lagging Power Factor (at rated output power) 0.8leading~0.8lagging
THDi (at rated output power) <1.5% THDi (at rated output power) <1.5%
Rated grid frequency (Hertz) 50/60 Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 47...52 or 57...62 Operating frequency range (Hertz) 47...52 or 57...62
Max.efficiency 98.3% Max.efficiency 98.3%
EU efficiency 97.8% EU efficiency 97.8%
MPPT efficiency >99.5% MPPT efficiency >99.5%
Dimensions 310W*538H*158D (mm) Dimensions 310W*538H*158D (mm)
Weight 13.6kg Weight 13.6kg
Topology Transformerless Topology Transformerless
Operating ambient temperature range -25℃...60℃ Operating ambient temperature range -25℃...60℃
Ingress protection IP65 Ingress protection IP65
Noise emission (typical) <30 dBA Noise emission (typical) <30 dBA
Cooling concept Natural convection Cooling concept Natural convection
Max.operation altitude 4000m Max.operation altitude 4000m
Designed lifetime >20 years Designed lifetime >20 years
EN50438, G83/2, AS4777.2:2015, EN50438, G83/2, AS4777.2:2015,
Grid connection standard Grid connection standard
VDE0126-1-1, IEC61727, VDE N4105 VDE0126-1-1, IEC61727, VDE N4105
Operating surroundings humidity 0...100% Condensing Operating surroundings humidity 0...100% Condensing
Connention Mc4 connector and Ip67 rated plug Connention Mc4 connector and Ip67 rated plug
Display LCD, 2×20 Z. Display LCD, 2×20 Z.
Communication connections 4 pins RS485 connector Communication connections 4 pins RS485 connector
Monitoring WiFi or GPRS Monitoring WiFi or GPRS
Warranty Terms 5 Years STD (Extendable to 20 Years) Warranty Terms 5 Years STD (Extendable to 20 Years)

.34. .35.
10. Specifications 10. Specifications
Model Solis-3P8K-4G Model Solis-3P9K-4G
Max. DC input power (Watts) 9600 Max. DC input power (Watts) 10800
Max. DC input voltage (Volts) 1000 Max. DC input voltage (Volts) 1000
Rated DC voltage (Volts) 600 Rated DC voltage (Volts) 600
Start-up voltage (Volts) 180 Start-up voltage (Volts) 180
MPPT voltage range (Volts) 160...850 MPPT voltage range (Volts) 160...850
Max. input current (Amps) 11+11 Max. input current (Amps) 11+11
Max short circuit input current (Amps) 17.2+17.2 Max short circuit input current (Amps) 17.2+17.2
MPPT number/Max input strings number 2/2 MPPT number/Max input strings number 2/2
Rated output power (Watts) 8000 Rated output power (Watts) 9000
Max. output power (Watts) 8800 Max. output power (Watts) 9900
Max. apparent output power (VA) 8800 Max. apparent output power (VA) 9900
Rated grid voltage (Volts) 3/N/PE~400 Rated grid voltage (Volts) 3/N/PE~400
Grid voltage range (Volts) 313...470 Grid voltage range (Volts) 313...470
Rated output current (Amps) 11.5 Rated output current (Amps) 13
Power Factor (at rated output power) 0.8leading~0.8lagging Power Factor (at rated output power) 0.8leading~0.8lagging
THDi (at rated output power) <1.5% THDi (at rated output power) <1.5%
Rated grid frequency (Hertz) 50/60 Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 47...52 or 57...62 Operating frequency range (Hertz) 47...52 or 57...62
Max.efficiency 98.7% Max.efficiency 98.7%
EU efficiency 98.1% EU efficiency 98.1%
MPPT efficiency >99.5% MPPT efficiency >99.5%
Dimensions 310W*538H*158D (mm) Dimensions 310W*538H*158D (mm)
Weight 14.1kg Weight 14.1kg
Topology Transformerless Topology Transformerless
Operating ambient temperature range -25℃...60℃ Operating ambient temperature range -25℃...60℃
Ingress protection IP65 Ingress protection IP65
Noise emission (typical) <30 dBA Noise emission (typical) <30 dBA
Cooling concept Natural convection Cooling concept Natural convection
Max.operation altitude 4000m Max.operation altitude 4000m
Designed lifetime >20 years Designed lifetime >20 years
EN50438, G83/2, AS4777.2:2015, EN50438, G83/2, AS4777.2:2015,
Grid connection standard Grid connection standard
VDE0126-1-1, IEC61727, VDE N4105 VDE0126-1-1, IEC61727, VDE N4105
Operating surroundings humidity 0...100% Condensing Operating surroundings humidity 0...100% Condensing
Connention Mc4 connector and Ip67 rated plug Connention Mc4 connector and Ip67 rated plug
Display LCD, 2×20 Z. Display LCD, 2×20 Z.
Communication connections 4 pins RS485 connector Communication connections 4 pins RS485 connector
Monitoring WiFi or GPRS Monitoring WiFi or GPRS
Warranty Terms 5 Years STD (Extendable to 20 Years) Warranty Terms 5 Years STD (Extendable to 20 Years)

.36. .37.
10. Specifications 10. Specifications
Model Solis-3P10K-4G Model Solis-3P5K-4G-LV
Max. DC input power (Watts) 12000 Max. DC input power (Watts) 6000
Max. DC input voltage (Volts) 1000 Max. DC input voltage (Volts) 600
Rated DC voltage (Volts) 600 Rated DC voltage (Volts) 330
Start-up voltage (Volts) 180 Start-up voltage (Volts) 180
MPPT voltage range (Volts) 160...850 MPPT voltage range (Volts) 160...500
Max. input current (Amps) 11+11 Max. input current (Amps) 11+11
Max short circuit input current (Amps) 17.2+17.2 Max short circuit input current (Amps) 17.2+17.2
MPPT number/Max input strings number 2/2 MPPT number/Max input strings number 2/2
Rated output power (Watts) 10000 Rated output power (Watts) 5000
Max. output power (Watts) 11000 Max. output power (Watts) 5500
Max. apparent output power (VA) 11000 Max. apparent output power (VA) 5500
Rated grid voltage (Volts) 3/N/PE~400 Rated grid voltage (Volts) 3/PE~208/220/240
Grid voltage range (Volts) 313...470 Grid voltage range (Volts) 180...270
Rated output current (Amps) 11.5 Rated output current (Amps) 13.1
Power Factor (at rated output power) 0.8leading~0.8lagging Power Factor (at rated output power) 0.8leading~0.8lagging
THDi (at rated output power) <1.5% THDi (at rated output power) <1.5%
Rated grid frequency (Hertz) 50/60 Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 47...52 or 57...62 Operating frequency range (Hertz) 47...52 or 57...62
Max.efficiency 98.7% Max.efficiency 98.0%
EU efficiency 98.1% EU efficiency 97.5%
MPPT efficiency >99.5% MPPT efficiency >99.5%
Dimensions 310W*538H*158D (mm) Dimensions 310W*538H*158D (mm)
Weight 14.1kg Weight 14.1kg
Topology Transformerless Topology Transformerless
Operating ambient temperature range -25℃...60℃ Operating ambient temperature range -25℃...60℃
Ingress protection IP65 Ingress protection IP65
Noise emission (typical) <30 dBA Noise emission (typical) <30 dBA
Cooling concept Natural convection Cooling concept Natural convection
Max.operation altitude 4000m Max.operation altitude 4000m
Designed lifetime >20 years Designed lifetime >20 years
EN50438, G83/2, AS4777.2:2015, EN50438, G83/2, AS4777.2:2015,
Grid connection standard Grid connection standard
VDE0126-1-1, IEC61727, VDE N4105 VDE0126-1-1, IEC61727, VDE N4105
Operating surroundings humidity 0...100% Condensing Operating surroundings humidity 0...100% Condensing
Connention Mc4 connector and Ip67 rated plug Connention Mc4 connector and Ip67 rated plug
Display LCD, 2×20 Z. Display LCD, 2×20 Z.
Communication connections 4 pins RS485 connector Communication connections 4 pins RS485 connector
Monitoring WiFi or GPRS Monitoring WiFi or GPRS
Warranty Terms 5 Years STD (Extendable to 20 Years) Warranty Terms 5 Years STD (Extendable to 20 Years)

.38. .39.

You might also like