Solis-3-Phase-Manual 5-10kw
Solis-3-Phase-Manual 5-10kw
If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.
LED lights
LCD display
.2. .3.
2. Safety Instructions 2. Safety Instructions
2.1 Safety Symbols
Safety symbols used in this manual, which highlight potential safety risks and important
safety information, are listed as follows:
CAUTION:
The PV array (Solar panels) supplies a DC voltage when they are exposed to
WARNING: sunlight.
WARNING symbol indicates important safety instructions, which if not
correctly followed, could result in serious injury or death. CAUTION:
Risk of electric shock from energy stored in capacitors of the Inverter.
NOTE:
NOTE symbol indicates important safety instructions, which if not correctly Do not remove cover for 5 minutes after disconnecting all power sources
followed, could result in some damage or the destruction of the inverter. (service technician only). Warranty may be voided if the cover is removed
without unauthorized.
CAUTION:
CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety CAUTION:
instructions, which if not correctly followed, could result in electric shock.
The surface temperature of the inverter can exceed 75℃ (167F).
CAUTION: To avoid risk of burns, DO NOT touch the surface when inverter is operating.
CAUTION, HOT SURFACE symbol indicates safety instructions, which if not The inverter must be installed out of reach of children.
correctly followed, could result in burns.
cause serious damage to the inverter. 2.The electrical installation must meet all the applicable regulations and standards.
3.The inverter must be installed according to the instructions stated in this manual.
WARNING:
Electrical installations must be done in accordance with the local and national 4.The inverter must be installed according to the correct technical specifications.
electrical safety standards. 5.To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before
the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid Supply
WARNING: Main Switch (AC) must be switched off before the solar panel's DC isolator shall be
To reduce the risk of fire, over-current protective devices (OCPD) are
switched off.
required for circuits connected to the Inverter.
The DC OCPD shall be installed per local requirements. All photovoltaic
source and output circuit conductors shall have disconnects that comply
with the NEC Article 690, Part II. All Solis three phase inverters feature
an integrated DC switch.
CAUTION:
Risk of electric shock. Do not remove cover. There is no user serviceable
parts inside. Refer servicing to qualified and accredited service technicians.
.4. .5.
3. Overview 4. Product handing and storage
3.1 Front Panel Display 4.1 Product handling
Please review the instruction below for handling the inverter:
1 2 3 1 The red circles below denote cutouts on the product package.
Push in the cutouts to form handles for moving the inverter (see Figure 4.1).
4 5 6 7
2
Figure 3.1 Front Panel Display
Description
Figure 4.1 move the inverter
Light Status
ON The inverter can detect DC power.
1 POWER
OFF No DC power or low DC power. 2.Open the carton, then handle both sides of inverter through the area denoted dotted line.
ON The inverter is operating properly. ( see figure 4.2).
2 OPERATION OFF The inverter has stopped to supply power.
FLASHING The inverter is initializing.
ON Alarm or fault condition is detected.
3 ALARM
OFF The inverter is operating properly.
3.3 Keypad
There are four keys in the front panel of the Inverter(from left to right):
ESC, UP, DOWN and ENTER keys. The keypad is used for:
Scrolling through the displayed options (the UP and DOWN keys);
Access to modify the adjustable settings (the ESC and ENTER keys).
3.4 LCD
The two-line Liquid Crystal Display (LCD) is located on the front panel of the Inverter,
which shows the following information:
Figure 4.2 Inverter handles
Inverter operation status and data; Service messages for operator;
Alarm messages and fault indications.
.6. .7.
4. Product handing and storage 5. Installation
4.2 Product Storage 5.1 Select a Location for the Inverter
To select a location for the inverter, the following criteria should be considered:
Do not install in small closed spaces where air cannot circulate freely. To avoid
Use the original box to repackage the inverter, seal with adhesive tape with the desiccant overheating, always make sure the flow of air around the inverter is not blocked.
inside thebox. Exposure to direct sunlight will increase the operational temperature of the inverter and
may cause output power limiting. Ginlong recommends inverter installed to avoid
direct sunlight or raining.
To avoid over heating ambient air temperature must be considered when choosing
the inverter installation location. Ginlong recommends using a sun shade minimizing
direct sunlight when the ambient air temperature around the unit exceeds 104°F/40°C.
≤15°
Vertical
√ Backward
√
.8. .9.
5. Installation 5. Installation
5.2 Mounting the Inverter
Inverted Dimensions of mounting bracket:
× ×
The visibility of LED status indicator lights and LCD should be considered.
Install vertically (+/- 5°) or tilted backward (<=15°).
Don't mount inverter on the tilted forward wall.
Don't mount inverter on the horizontal.
300mm
Refer to figure 5.4 and figure 5.5. Inverter shall be mounted vertically.
The steps to mount the inverter are listed below.
1. Refer to Figure 5.4, the holes for expansion bolt based on the hole diameter of bracket
300mm 300mm 300mm
(ST6.3*60 cross recessed hexagon head tapping screws, HJ0108 10*50mm fished
expandable tubular), using the percussion drilling with the 10mm drill need to stay
vertically on the wall.And the drill hole must be vertically on the wall.
And all drill holes' depth is 60mm.
500mm
500mm
Bracket
NOTE:
2. Make sure the bracket is horizontal. And the mounting holes (in Figure 5.4) are marked
Nothing should be stored on or placed against the inverter.
correctly. Drill the holes into wall at your marks.
3. Use the suitable expansion screws to fix the bracket on the wall.
.10. .11.
5. Installation 5. Installation
5. Anti-theft lock mount(optional)
WARNING: Anti-theft lock( User-supplied) function is that inverter is fixed in bracket in case theft.
The inverter must be mounted vertically. The lock is selected by 5mm(the keyhole diameter), and the lock of stainless steel is
preferred.
Anti-theft lock
Locking screws
+ Positive DC input terminal
- Negative DC input terminal
DC 1 DC input terminal
DC 2 DC input terminal
DC SWITCH Switch of DC input terminals
COM RJ45 and terminal block for RS485 communication port
GRID Connecting terminal of the Grid
Table 5.1 Electrical connection symbols
The electrical connection of the inverter must follow the steps listed below:
3) Strip the ground cable insulation to a suitable length(see Figure 5.8). 5) Remove the screw from the heat sink ground point.
6) Connect the grounding cable to the grounding point on the heat sink,and tighten the
B grounding screw, Torque is 3Nm(see figure 5.10).
Grounding screw
Important:
Figure 5.10 Fixed cable
B (insulation stripping length) is 2mm~3mm longer than A (OT cable
terminal crimping area) 2mm~3mm.
Important:
For improving anti-corrosion performance,
4) Insert the stripped wire into the OT terminal crimping area and use the hydraulic after ground cable installed, apply silicone or paint is preferred to protect.
clamp to crimp the terminal to the wire (see Figure 5.9).
.14. .15.
5. Installation 5. Installation
5.3.2 Connect PV side of inverter
5. Measure PV voltage of DC input with multimeter, verify DC input cable polar
Before connecting inverter, please make sure the PV array open circuit (see figure 5.17), and ensure each string of PV voltage in range of inverter operation.
voltage is within the limit of the inverter. Connect DC connector with inverter until hearing a slight clicking sound indicates
connection succeed. (see figure 5.18)
Before connection, please make sure the polarity of the output voltage of
PV array matches the“DC+”and“DC-”symbols.
Before connecting inverter, please make sure the PV array open circuit
voltage is within the limit of the inverter.
Figure 5.14 Insert the Wire into the
Figure 5.13 Disassemble the Connector Cap nut
Connector Cap nut and contact pin
Crimping plier
Figure 5.15 Crimp the contact pin to the wire Figure 5.16 Connector with Cap nut Screwed on
Figure 5.11 DC+ Connector Figure 5.12 DC- Connector
-
Cross section(mm²) Figure 5.17 Multimeter measurement Figure 5.18 Connect the DC
Cable type Connectors to the Inverter
Range Recommended value
Industry generic PV cable 4.0~6.0
4.0(12AWG)
(model:PV1-F) (12~10AWG)
WARNING:
If DC input wire reverses, please not operate DC switch, DC1and DC2
The steps to assemble the DC connectors are listed as follows: instantly to avoid inverter damage.. Damage caused by this reason isn't
1. Strip off the DC wire for about 7mm, Disassemble the connector cap nut. (see Figure 5.13) covered by warranty.
2. Insert the wire into the connector cap nut and contact pin. (see Figure 5.14) Solution: Until reduced sun irradiance and PV voltage is below 0.5 A(mostly
3. Crimp the contact pin to the wire using a proper wire crimper. (see Figure 5.15) in evening), then put DC switch in “off” position, remove “+”, “-” connectors to
reconnect wires.
4. Insert metal connector into top of connector, and tighten nut with torque 2.5-3 Nm
(see figure 5.16).
.16. .17.
5. Installation 5. Installation
5.3.3 Connect grid side of inverter
For all AC connections, 2.5 – 6 mm², 105°C cable is required to be used. Please make sure the B) Insert the cable through the jacket and cap nut of connector, then insert the wires to the grid
resistance of cable is lower than 1.50hm. If the wire is longer than 20m, preferred to 6mm² cable. terminal and tighten the screws on the connector (see figure 5.22).
Please try to pull out the wire to make sure it is well connected.
Internal of AC connector signs "L1","L2","L3","N" and "PE " five connection
ports (see Figure 5.20). Three live wires are connected the "L1", "L2"and
"L3" terminals respectively; ground wire connects "PE "; neutral wire
connects "N" terminal:
Each inverter has a corresponding AC grid terminal connector. See figure 5.19.
PE
N L3
C) Assemble the connector and tighten up cap on the terminal. See Figure 5.21 right.
The steps to assemble AC grid terminal connector are listed as follows:
A) Strip the end of AC wire about 8mm. See figure 5.21 left. D) Connect AC grid terminal connector to the inverter, small click will confirm that connection
is appropriate. (see figure 5.23)
.18. .19.
5. Installation 6. Start & Stop
5.3.4 Max. over current protection device (OCPD) 6.1 Start the Inverter
To protect the inverter's AC grid connection conductors, Solis recommends installing To start up the Inverter, it is important that the following steps are strictly followed:
breakers that will protect against overcurrent. The following table defines OCPD ratings for
1. Switch the grid supply main Switch (AC) ON first.
the Solis 5-10kW three phase inverters.
2. Switch the DC switch ON. If the voltage of PV arrays are higher than start up voltage,
Rated output Current for protection the inverter will turn on. The red LED power will light.
Inverter Rated voltage(V)
current (A) device (A)
3. When both the DC and the AC sides supply to the inverter, it will be ready to generate
Solis-3P5K-4G 400 7.2 20 power. Initially, the inverter will check both its internal parameters and the parameters
Solis-3P6K-4G 400 8.7 20 of the AC grid, to ensure that they are within the acceptable limits. At the same time,
the green LED will flash and the LCD displays the information of INITIALIZING.
Solis-3P8K-4G 400 11.5 20
4. After 30-300 seconds (depending on local requirement), the inverter will start to
Solis-3P9K-4G 400 13.0 32
generate power. The green LED will be on continually and the LCD displays
Solis-3P10K-4G 400 14.4 32 GENERATING.
Internet
PC monitoring
Wi-Fi box
Wi-Fi monitoring
.20. .21.
7. Operation 7. Operation
Display Duration Description
In normal operation, LCD screen alternatively shows inverter power and operation status
(see Figure 7.1). The screen can be scrolled manually by pressing the UP/DOWN keys. V_DC1 350.8V V_DC1: Shows input 01 voltage value.
Pressing the ENTER key gives access to Main Menu. I_DC1 5.1A 10 sec
I_DC1: Shows input 01 current value.
Total Energy
0258458 kwh 10 sec Total generated energy value.
Figure 7.1 Operation Overview
This Month: 0123kwh This Month: Total energy generated this month.
Last Month: 0123kwh 10 sec
Last Month: Total energy generated last month.
7.1 Main Menu Today: 15.1kwh Today: Total energy generated today.
Yesterday: 13.5kwh 10 sec
There are four submenus in the Main Menu (see Figure 7.1): Yesterday: Total energy generated yesterday.
1. Information
Inverter SN
2. Settings 00000000000000 10 sec Display series number of the inverter.
3. Advanced Info.
4. Advanced Settings Table 7.1 Information list
.22. .23.
7. Operation 7. Operation
7.3 Settings
The following submenus are displayed when the Settings menu is selected: Select “Advanced Info.” from the Main Menu. The screen will require the password as below:
1.Set Time
2.Set Address
YES=<ENT> NO=<ESC>
Password:0000
7.3.1 Set Time
This function allows time and date setting. When this function is selected, the LCD will Figure 7.5 Enter password
display a screen as shown in Figure 7.3.
After enter the correct password the Main Menu will display a screen and be able to access
to the following information.
NEXT=<ENT> OK=<ESC>
01-01-2016 16:37 1.Alarm Message 2. Running message 3.Version 4. Daily Energy
5. Monthly Energy 6. Yearly Energy 7. Daily Record 8.Communication Data
Figure 7.3 Set Time
The screen can be scrolled manually by pressing the UP/DOWN keys. Pressing the ENTER
key gives access to a submenu. Press the ESC key to return to the Main Menu.
Press the UP/DOWN keys to set time and data. Press the ENTER key to move from one
digit to the next (from left to right). Press the ESC key to save the settings and return to 7.4.1 Alarm Message
the previous menu.
The display shows the 100 latest alarm messages (see Figure 7.6). Screens can be scrolled
manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous
7.3.2 Set Address menu.
This function is used to set the address when muti inverters are connected to three monitor.
The address number can be assigned from “01”to “99”(see Figure 7.4). The default address Alarm001: OV-G-V
Time: 27-11 Data: 7171
number of Solis Three Phase Inverter is “01”.
7.4.3 Version
7.4 Advanced Info - Technicians Only The screen shows the model version and the software version of the Inverter
(see Figure 7.7).
NOTE:
To access to this area is for fully qualified and accredited technicians only. Model: 08
Software Version: D20001
Enter menu “Advanced Info.” and “Advanced settings” (need password).
.24. .25.
7. Operation 7. Operation
7.4.4 Daily Energy 7.4.7 Communication Data
The function is for checking the energy generation for selected day. The screen shows the internal data of the Inverter (see Figure 7.14), which is for service
technicians only.
YES=<ENT> NO=<ESC>
Select: 2015-02-23
01-05: 01 25 E4 9D AA
Figure 7.8 Select date for daily energy 06-10: C2 B5 E4 9D 55
Press UP/DOWN key to move one date from another. Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard 2. Grid ON/OFF 3. Clear Energy 4. New Password
7.4.5 Monthly Energy and Yearly Energy 5. Power Control 6. Calibrate Energy 7.STD. Mode Settings
The two functions are for checking the energy generation for selected month and Year.
7.5.1 Selecting Standard
This function is used to select the grid's reference standard (see Figure 7.15).
Press DOWN key to move the cursor, press UP key to change the
digit. Press Enter after the month/year is fixed. Press the UP/DOWN keys to select the standard (AS4777, VDE4105, VDE0126, UL-240V-A,
UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3 (for 4-5kW
models), EN50438 DK, EN50438 IE, EN50438 NL and “User-Def” function). Press the
2015-02: 0510kWh 2015: 0017513kWh ENTER key to confirm the setting. Press the ESC key to cancel changes and returns to
2015-01: 0610kWh 2014: 0165879kWh
previous menu.
NOTE:
Press UP/DOWN key to move one date from another.
This function is for technicians use only.
7.4.6 Daily record
The screen shows history of changing settings. Only for maintance personel.
.26. .27.
7. Operation 7. Operation
7.5.3 Clear Energy
Selecting the “User-Def” menu will access to the following submenu (see Figure 7.16), Clear Energy can reset the history yield of inverter
OV-G-V1: 260V
OV-G-V1-T: 1S These two functions are applicable by maintenance personnel only, wrong
operation will prevent the inverter from working properly.
Figure 7.16
.28. .29.
7. Operation 8. Maintenance
Solis Three Phase Inverter does not require any regular maintenance. However, cleaning
YES=<ENT> NO=<ESC> the dust on heat-sink will help the inverter to dissipate the heat and increase its life time.
Energy:0000000kWh The dust can be removed with a soft brush.
In case of failure, the LCD screen will display an alarm message. In this case, the inverter
may stop feeding into the grid. The failure descriptions and their corresponding alarm
messages are listed in Table 9.1:
.30. .31.
9. Trouble Shooting 9. Trouble Shooting
Alarm Message Failure description Solution Alarm Message Failure description Solution
1.Check if the connector on main ILeak-PRO Leakage current protection 1.Check AC and DC connection
LCD show initializing board or power board are fixed. 01/02/03/04 2.Check inverter inside cable connection.
Can not start-up
all the time 2.Check if the DSP connector to
power board are fixed. RelayChk-FAIL Relay check fail
1.Restart inverter or contact installer.
1.Resistant of AC cable is too high. DCinj-FAULT High DC injection current
Change bigger size grid cable
OV-G-V01/02/03/04 Over grid voltage AFCI self-detection
2.Adjust the protection limit if it’s
allowed by electrical company. (model with AFCI AFCI module self-detect fault 1.Restart inverter or connect technician.
module)
UN-G-V01/02 Under grid voltage
Over grid frequency 1.Use user define function to adjust the Arcing protection
OV-G-F01/02 1. Check inverter connection whether arc
protection limit if it’s allowed by (model with AFCI Detect arc in DC circuit
module) exists and restart inverter.
UN-G-F01/02 Under grid frequency electrical company.
G-IMP High grid impedance
1.Check connections and grid switch.
Table 9.1 Fault message and description
NO-GRID No grid voltage 2.Check the grid voltage inside inverter
terminal.
OV-DC01/02/03/04 Over DC voltage 1.Reduce the module number in series
NOTE:
If the inverter displays any alarm message as listed in Table 9.1; please
OV-BUS Over DC bus voltage 1.Check inverter inductor connection turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5
UN-BUS01/02 Under DC bus voltage 2.Check driver connection
minutes before restarting it (refer to Section 5.1 to start your inverter). If the
GRID-INTF01/02 Grid interference failure persists, please contact your local distributor or the service center.
1.Restart inverter
OV-G-I Over grid current Please keep ready with you the following information before contacting us.
2.Change power board
IGBT-OV-I Over IGBT current
1.Restart inverter
DC-INTF DC input overcurrent 2.Identify and remove the string to the fault MPPT
OV-DCA-I 2.Change power board 1. Serial number of Solis Three Phase Inverter;
IGFOL-F Grid current tracking fail 2. The distributor/dealer of Solis Three Phase Inverter (if available);
1.Restart inverter or contact installer.
IG-AD Grid current sampling fail 3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
1.Check inverter surrounding ventilation.
OV-TEM Over Temperature 2.Check if there’s sunshine direct on of the LED status indicator lights. Other readings obtained from the Information submenu
inverter in hot weather. (refer to Section 6.2) will also be helpful.);
Initialization system fault
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings
INI-FAULT
, etc.);
Comm. failure between main
DSP-B-FAULT
and slave DSP
1.Restart inverter or contact installer. 6. Your contact details.
.32. .33.
10. Specifications 10. Specifications
Model Solis-3P5K-4G Model Solis-3P6K-4G
Max. DC input power (Watts) 6000 Max. DC input power (Watts) 7200
Max. DC input voltage (Volts) 1000 Max. DC input voltage (Volts) 1000
Rated DC voltage (Volts) 600 Rated DC voltage (Volts) 600
Start-up voltage (Volts) 180 Start-up voltage (Volts) 180
MPPT voltage range (Volts) 160...850 MPPT voltage range (Volts) 160...850
Max. input current (Amps) 11+11 Max. input current (Amps) 11+11
Max short circuit input current (Amps) 17.2+17.2 Max short circuit input current (Amps) 17.2+17.2
MPPT number/Max input strings number 2/2 MPPT number/Max input strings number 2/2
Rated output power (Watts) 5000 Rated output power (Watts) 6000
Max. output power (Watts) 5500 Max. output power (Watts) 6600
Max. apparent output power (VA) 5500 Max. apparent output power (VA) 6600
Rated grid voltage (Volts) 3/N/PE~400 Rated grid voltage (Volts) 3/N/PE~400
Grid voltage range (Volts) 313...470 Grid voltage range (Volts) 313...470
Rated output current (Amps) 7.2 Rated output current (Amps) 8.7
Power Factor (at rated output power) 0.8leading~0.8lagging Power Factor (at rated output power) 0.8leading~0.8lagging
THDi (at rated output power) <1.5% THDi (at rated output power) <1.5%
Rated grid frequency (Hertz) 50/60 Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 47...52 or 57...62 Operating frequency range (Hertz) 47...52 or 57...62
Max.efficiency 98.3% Max.efficiency 98.3%
EU efficiency 97.8% EU efficiency 97.8%
MPPT efficiency >99.5% MPPT efficiency >99.5%
Dimensions 310W*538H*158D (mm) Dimensions 310W*538H*158D (mm)
Weight 13.6kg Weight 13.6kg
Topology Transformerless Topology Transformerless
Operating ambient temperature range -25℃...60℃ Operating ambient temperature range -25℃...60℃
Ingress protection IP65 Ingress protection IP65
Noise emission (typical) <30 dBA Noise emission (typical) <30 dBA
Cooling concept Natural convection Cooling concept Natural convection
Max.operation altitude 4000m Max.operation altitude 4000m
Designed lifetime >20 years Designed lifetime >20 years
EN50438, G83/2, AS4777.2:2015, EN50438, G83/2, AS4777.2:2015,
Grid connection standard Grid connection standard
VDE0126-1-1, IEC61727, VDE N4105 VDE0126-1-1, IEC61727, VDE N4105
Operating surroundings humidity 0...100% Condensing Operating surroundings humidity 0...100% Condensing
Connention Mc4 connector and Ip67 rated plug Connention Mc4 connector and Ip67 rated plug
Display LCD, 2×20 Z. Display LCD, 2×20 Z.
Communication connections 4 pins RS485 connector Communication connections 4 pins RS485 connector
Monitoring WiFi or GPRS Monitoring WiFi or GPRS
Warranty Terms 5 Years STD (Extendable to 20 Years) Warranty Terms 5 Years STD (Extendable to 20 Years)
.34. .35.
10. Specifications 10. Specifications
Model Solis-3P8K-4G Model Solis-3P9K-4G
Max. DC input power (Watts) 9600 Max. DC input power (Watts) 10800
Max. DC input voltage (Volts) 1000 Max. DC input voltage (Volts) 1000
Rated DC voltage (Volts) 600 Rated DC voltage (Volts) 600
Start-up voltage (Volts) 180 Start-up voltage (Volts) 180
MPPT voltage range (Volts) 160...850 MPPT voltage range (Volts) 160...850
Max. input current (Amps) 11+11 Max. input current (Amps) 11+11
Max short circuit input current (Amps) 17.2+17.2 Max short circuit input current (Amps) 17.2+17.2
MPPT number/Max input strings number 2/2 MPPT number/Max input strings number 2/2
Rated output power (Watts) 8000 Rated output power (Watts) 9000
Max. output power (Watts) 8800 Max. output power (Watts) 9900
Max. apparent output power (VA) 8800 Max. apparent output power (VA) 9900
Rated grid voltage (Volts) 3/N/PE~400 Rated grid voltage (Volts) 3/N/PE~400
Grid voltage range (Volts) 313...470 Grid voltage range (Volts) 313...470
Rated output current (Amps) 11.5 Rated output current (Amps) 13
Power Factor (at rated output power) 0.8leading~0.8lagging Power Factor (at rated output power) 0.8leading~0.8lagging
THDi (at rated output power) <1.5% THDi (at rated output power) <1.5%
Rated grid frequency (Hertz) 50/60 Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 47...52 or 57...62 Operating frequency range (Hertz) 47...52 or 57...62
Max.efficiency 98.7% Max.efficiency 98.7%
EU efficiency 98.1% EU efficiency 98.1%
MPPT efficiency >99.5% MPPT efficiency >99.5%
Dimensions 310W*538H*158D (mm) Dimensions 310W*538H*158D (mm)
Weight 14.1kg Weight 14.1kg
Topology Transformerless Topology Transformerless
Operating ambient temperature range -25℃...60℃ Operating ambient temperature range -25℃...60℃
Ingress protection IP65 Ingress protection IP65
Noise emission (typical) <30 dBA Noise emission (typical) <30 dBA
Cooling concept Natural convection Cooling concept Natural convection
Max.operation altitude 4000m Max.operation altitude 4000m
Designed lifetime >20 years Designed lifetime >20 years
EN50438, G83/2, AS4777.2:2015, EN50438, G83/2, AS4777.2:2015,
Grid connection standard Grid connection standard
VDE0126-1-1, IEC61727, VDE N4105 VDE0126-1-1, IEC61727, VDE N4105
Operating surroundings humidity 0...100% Condensing Operating surroundings humidity 0...100% Condensing
Connention Mc4 connector and Ip67 rated plug Connention Mc4 connector and Ip67 rated plug
Display LCD, 2×20 Z. Display LCD, 2×20 Z.
Communication connections 4 pins RS485 connector Communication connections 4 pins RS485 connector
Monitoring WiFi or GPRS Monitoring WiFi or GPRS
Warranty Terms 5 Years STD (Extendable to 20 Years) Warranty Terms 5 Years STD (Extendable to 20 Years)
.36. .37.
10. Specifications 10. Specifications
Model Solis-3P10K-4G Model Solis-3P5K-4G-LV
Max. DC input power (Watts) 12000 Max. DC input power (Watts) 6000
Max. DC input voltage (Volts) 1000 Max. DC input voltage (Volts) 600
Rated DC voltage (Volts) 600 Rated DC voltage (Volts) 330
Start-up voltage (Volts) 180 Start-up voltage (Volts) 180
MPPT voltage range (Volts) 160...850 MPPT voltage range (Volts) 160...500
Max. input current (Amps) 11+11 Max. input current (Amps) 11+11
Max short circuit input current (Amps) 17.2+17.2 Max short circuit input current (Amps) 17.2+17.2
MPPT number/Max input strings number 2/2 MPPT number/Max input strings number 2/2
Rated output power (Watts) 10000 Rated output power (Watts) 5000
Max. output power (Watts) 11000 Max. output power (Watts) 5500
Max. apparent output power (VA) 11000 Max. apparent output power (VA) 5500
Rated grid voltage (Volts) 3/N/PE~400 Rated grid voltage (Volts) 3/PE~208/220/240
Grid voltage range (Volts) 313...470 Grid voltage range (Volts) 180...270
Rated output current (Amps) 11.5 Rated output current (Amps) 13.1
Power Factor (at rated output power) 0.8leading~0.8lagging Power Factor (at rated output power) 0.8leading~0.8lagging
THDi (at rated output power) <1.5% THDi (at rated output power) <1.5%
Rated grid frequency (Hertz) 50/60 Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 47...52 or 57...62 Operating frequency range (Hertz) 47...52 or 57...62
Max.efficiency 98.7% Max.efficiency 98.0%
EU efficiency 98.1% EU efficiency 97.5%
MPPT efficiency >99.5% MPPT efficiency >99.5%
Dimensions 310W*538H*158D (mm) Dimensions 310W*538H*158D (mm)
Weight 14.1kg Weight 14.1kg
Topology Transformerless Topology Transformerless
Operating ambient temperature range -25℃...60℃ Operating ambient temperature range -25℃...60℃
Ingress protection IP65 Ingress protection IP65
Noise emission (typical) <30 dBA Noise emission (typical) <30 dBA
Cooling concept Natural convection Cooling concept Natural convection
Max.operation altitude 4000m Max.operation altitude 4000m
Designed lifetime >20 years Designed lifetime >20 years
EN50438, G83/2, AS4777.2:2015, EN50438, G83/2, AS4777.2:2015,
Grid connection standard Grid connection standard
VDE0126-1-1, IEC61727, VDE N4105 VDE0126-1-1, IEC61727, VDE N4105
Operating surroundings humidity 0...100% Condensing Operating surroundings humidity 0...100% Condensing
Connention Mc4 connector and Ip67 rated plug Connention Mc4 connector and Ip67 rated plug
Display LCD, 2×20 Z. Display LCD, 2×20 Z.
Communication connections 4 pins RS485 connector Communication connections 4 pins RS485 connector
Monitoring WiFi or GPRS Monitoring WiFi or GPRS
Warranty Terms 5 Years STD (Extendable to 20 Years) Warranty Terms 5 Years STD (Extendable to 20 Years)
.38. .39.