MOD30ML Programing Guide
MOD30ML Programing Guide
ABB Instrumentation
ABB INSTRUMENTATION
The Company
ABB Instrumentation is an established world force in the design and manufacture of BS EN ISO 9001
instrumentation for industrial process control, flow measurement, gas and liquid analysis St Neots -
and environmental applications. Certificate No. Q5907
Stonehouse -
As a part of ABB, a world leader in process automation technology, we offer customers
Certificate No. FM 21106
application expertise, service and support worldwide.
ISO 9001
We are committed to teamwork, high quality manufacturing, advanced technology and
Rochester, USA -
unrivaled service and support.
Certificate No. AQ-8618
The quality, accuracy and performance of the Company's products result from over 100
years experience, combined with a continuous program of innovative design and
development to incorporate the latest technology.
EN 29001 (ISO 9001)
The NAMAS Calibration Laboratory No. 0255(B) is just one of the ten flow calibration Lenno, Italy -
plants operated by the Company, and is indicative of ABB Instrumentation's dedication to Certificate No. 90/90A
quality and accuracy.
Stonehouse -
Certificate No. 0255
Use of Instructions
∆ Warning. An instruction that draws attention to the risk of Note. Clarification of an instruction or additional
injury or death. information.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it
must be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process
system performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for
any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of ABB
Instrumentation.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with the
information given or injury or death could result.
4. Normal safety procedures must be taken to avoid the possibility of an accident occurring when operating in conditions of high
pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling
procedures must be used.
CONTENTS
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
CONTENTS
Page
SECTION 1 - INTRODUCTION
1.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 INSTALLATION INTEGRITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 DIAGNOSTIC TOOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3.1 MODCELL Status LEDs ........................................ 2
1.3.2 Application Builder Software ..................................... 2
1.3.3 MOD 30ML Display ........................................... 2
1.4 REPAIR PHILOSOPHY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 RELATED INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SECTION 4 - COMMUNICATIONS
4.1 COMMUNICATING WITH A REPLACEMENT INSTRUMENT . . . . . . . . . . . . . . . 27
4.2 COMMUNICATION TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.2.1 ICN Module Communication .................................... 29
4.2.2 Modbus Module Communication ................................. 32
4.2.3 Built-in ICN Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.2.4 Built-in Modbus Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.3 APPLICATION BUILDER/INSTRUMENT COMMUNICATION MESSAGES . . . . . . 37
i
MODCELL and MOD 30ML Maintenance
CONTENTS
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
CONTENTS (Cont’d)
Page
SECTION 7 - EVENT CODES AND TRANSITION MESSAGES
7.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
7.2 TRANSITION MESSAGE DESCRIPTIONS ........................... 65
7.3 EVENT CODE DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
SECTION 8 - PARTS
8.1 PARTS AVAILABILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.2 BASIC HARDWARE ........................................... 85
8.2.1 MODCELL Multiloop Processor .................................. 85
8.2.2 MOD 30ML Multiloop Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
8.3 I/O MODULES ............................................... 85
8.4 COMMUNICATION MODULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ILLUSTRATIONS
Figure Page
1 Component Location, 2001N Processor ................................. 7
2 Component Location, 2002N Processor ................................. 7
3 Application Builder Untitled - (Root) Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Serial Port Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5a Instrument Status Display, Version 4.0 and Lower Versions . . . . . . . . . . . . . . . . . . 16
5b Instrument Status Display, Version 4.01 ............................... 16
6 Communications Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 Example of Diagnostic Alarm Display .................................. 23
8 Device Status and Device Event Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9 Example of Display Pages for A Diagnostic Event ......................... 24
10 Voltage Traces for a Correctly Functioning ICN .......................... 31
10 Example of Extended Error Code (EXTERR) Data for a WRIM Module . . . . . . . . . . 53
ii
MODCELL and MOD 30ML Maintenance
CONTENTS
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
TABLES
Table Page
1 Status LED troubleshooting Guide ..................................... 8
2 Application Builder Startup Procedure ................................. 12
3 Serial Port Communication Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Communication Setup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 Instrument Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6 Commands Accessible from MOD 30ML Display .......................... 25
7 Communication Messages, Cause and Recommended Action . . . . . . . . . . . . . . . . . 37
8 I/O Module Identification Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9 Analog Input Module Extended Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
10 Analog Output Module Extended Error Codes ........................... 55
11 Event Transition Message Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
12 Event Codes, Description and Action ................................. 66
13 Hardware and Firmware Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
14 Software Revision History ......................................... 92
iii
MODCELL and MOD 30ML Maintenance
CONTENTS
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
iv
MODCELL and MOD 30ML Maintenance
INTRODUCTION
SECTION 1
INTRODUCTION
1.1 GENERAL
The MODCELL and MOD 30ML instruments contain extensive internal diagnostics which
continuously monitor instrument operation. If a malfunction is detected it is immediately
reported so that the user can take appropriate action. In addition, most routine instrument
events such as changes in operating state, switching of control modes, suppression or
enabling of various diagnostics, acknowledgement of alarm conditions, etc., are reported
for informational purposes. This diagnostic system provides, in effect, continuous
instrument maintenance. No periodic user maintenance activity is required when the
instrument is operating normally in the RUN state.
The purpose of this book is to provide detailed information about the instrument
diagnostics, and to provide procedures for accessing and using the diagnostic data to
isolate a problem and identify its cause. In the event that a malfunction is discovered,
guidelines for corrective action are provided.
If a host computer is used with the ICN, instructions for setup of the communications link
are are provided in the following manuals:
IB-23C001 Instructions for 1720N Communications Link
IB-23C003 Users guide for 17321N ICN Mini Link
IB-23C004 Users Guise for 1733N Mini Link/External
The instrument diagnostics can identify some installation related problems such as burnout
of a thermocouple or a mismatch between the physical location of an I/O module and its
specified location in the data base configuration. For the most part, avoidance of
installation related problems depends on careful adherence to the installation instructions.
Problems related to electrical noise, input and output signals, and communication signals
can result from an improper installation. The instrument installation manuals provide
detailed connection information and typical connection diagrams for every I/O and
communication module, and for the built-in I/O and communication circuits in MOD 30ML.
This information should be reviewed when it is necessary to rule out the installation as the
source of a malfunction.
1
MODCELL and MOD 30ML Maintenance
INTRODUCTION
Use of these tools can provide diagnostic information which helps identify most instrument
problems.
All instrument components which are identified by a catalog number are available for
purchase. The components and their numbers are listed in Section 8.
2
MODCELL and MOD 30ML Maintenance
INTRODUCTION
Installation and setup information for the communications link can be found in the following
documents:
• IB-23C001 Instructions for 1720N Communications Link
• IB-23C003 Users guide for 17321N ICN Mini Link
• IB-23C004 Users Guise for 1733N Mini Link/External
Reference information on the data base structure and configuration parameters applicable
to both MODCELL and MOD 30ML instruments can be found in the following documents.
• IB-23G600 Data Base Reference for Logic I/O and Communication Functions
• IB-23G601 Data Base Reference for Advanced Control Functions
• IB-23G602 Data Base Reference for Algorithm, Table and Sequencer Functions
• IB-23H141 User’s Guide for MODCELL Application Builder Software
General operation and setup information, and reference information on the data base
structures and configuration parameters which apply only to the MOD 30ML Multiloop
Controller can be found in the following documents.
• IB-1800R-OPR Operation for MOD 30ML Multiloop Controller
• IB-1800R-APP Data Base Reference for Display, Alarm, and Built-in I/O Functions
3
MODCELL and MOD 30ML Maintenance
INTRODUCTION
4
MODCELL and MOD 30ML Maintenance
SECTION 2
MODCELL STATUS INDICATORS
2.1 GENERAL
The red and green status LEDs on each MODCELL instrument, Figure 1 or 2, provide
continuous visual indication of the operational condition of the instrument. These LEDs
have five possible conditions as follows:
• Red off; Green off
• Red on; Green off
• Red off; Green on
• Red on; Green on
• Red flashing; Green on
Normal operation of the instrument in the RUN state is indicated by red off and green on.
The other conditions provide useful operational information when observed in conjunction
with events and conditions such as initial application of power, the instrument initialization
sequence, power-up after a shutdown, presence of a valid data base, use of a portable
memory module, and an I/O mismatch condition. The status LED indications are described
in detail in Section 2.2.
• Initial power-up
When power is applied to the instrument, the red LED turns on indicating presence of
power to the instrument. If the red LED remains on and the green LED fails to turn on,
a fault condition is present in the instrument. Examples of problems in this case
include identity module not present, select module failure, processor failure, memory
failure, etc.
5
MODCELL and MOD 30ML Maintenance
The instrument can not be removed from the DEFAULT state in this case until the
shutdown is acknowledged with the ACK shutdown fault message (see Section 6).
When this message is received, the instrument continues through the startup process
and advances to the appropriate state.
If there is not a valid main database or memory module database available for
download, the instrument enters the DEFAULT state, leaving the red and green LEDs
on.
If an I/0 mismatch is found and this mismatch has not been previously acknowledged,
the instrument will enter the HOLD state unless it is configured to run on I/O
mismatch. An I/O mismatch can be acknowledged and overridden by sending a
run/warmstart command to the instrument (writing this value to the IF1,NXTISTAT
attribute). When this message is received, the instrument advances from the HOLD
state. Both the red and green LEDs remain on in the HOLD state. (See Section 3 for
information on read/write commands.)
If the instrument is powered down and powered up again, it will note that the
mismatched physical I/O complement matches the complement that was previously
acknowledged and overridden, and progress beyond the HOLD state.
6
MODCELL and MOD 30ML Maintenance
7
MODCELL and MOD 30ML Maintenance
Status LED
Problem Probable Cause Action
Condition
Red off No power 1. Power not turned on. 1. Turn on power.
Green off
2. Power not connected at 2. Connect power.
distribution panel(AC source).
3. Instrument power supply 3. Return instrument for repair
failed. or replacement.
Red on Green does not 1. Termination facility on front of 1. Tighten housing screw.
Green off turn on when Eurocard instrument, Figure
power is applied 1, not properly engaged.
2. Identity module not present. 2. Install identity module.
3. Select module failure, 3. Return instrument for repair
processor failure or memory or replacement.
failure.
4. Green LED failed. 4. Return instrument for repair
or replacement.
Red off None; normal 1. A valid data base was 1. None, wait for instrument to
Green on condition after previously loaded. Instrument enter next state.
power-up is initializing and checking
other parameters.
2. A data base has been 2. None
successfully downloaded.
8
MODCELL and MOD 30ML Maintenance
Status LED
Problem Probable Cause Action
Condition
Red on After power-up Memory module switch is set Change memory module
Green on instrument is in at LOAD; main database has switch setting to NORMAL.
(Cont’d) UPLOAD state been successfully copied to
memory module.
9
MODCELL and MOD 30ML Maintenance
10
MODCELL and MOD 30ML Maintenance
SECTION 3
VIEWING DIAGNOSTIC DATA
3.1 INTRODUCTION
The purpose of this section is to provide specific how-to instructions for viewing diagnostic
data and issuing commands to the instrument. Two methods are available:
Diagnostic data on all active and unacknowledged diagnostic conditions can be obtained
using a single read command. When the System Event Block is configured to report all
diagnostics, a history of diagnostic events is stored in the system event queue. Reading
the queue displays the events in order of occurrence. The capacity of the queue can be
configured to contain as many as 1000 events. If the capacity is exceeded, the oldest
events are overwritten by incoming events.
Users of the procedures in this section should have general knowledge of the Application
Builder software. Comprehensive user information is available in IB-23H141, User’s
Guide for MODCELL Application Builder Software.
11
MODCELL and MOD 30ML Maintenance
12
MODCELL and MOD 30ML Maintenance
Mouse Cursor
Serial Port Setup Instrument Functions
Workspace
13
MODCELL and MOD 30ML Maintenance
14
MODCELL and MOD 30ML Maintenance
• Select the ICN Number field and If an ICN communications module is used, the target
enter the applicable ICN number: instrument number is determined by the setting of the
0 - 7 for standard link (depends on address switch on the module. This switch is read
board position) or 0-1 for a Minilink only at power up; cycle the power if the setting is
(depends on labeled connection changed.
port).
If the MOD 30ML built-in ICN communications circuit
• Select the Instrument Number field is used, the communications jumper must be set on
and enter the number (0-15) of the the ICN position, and the target instrument number is
target instrument. determined by configuring the ICN address and
enabling the ICN on the front panel device setup
display.
4 If Modbus communication was If a Modbus Communication module is used,the
selected, select the Modbus Address address of the target instrument is determined by the
field and enter the address (1 - 247) of settings of the two address switches on the module.
the target instrument. These switches are read only at power up; cycle the
power if the settings are changed.
15
MODCELL and MOD 30ML Maintenance
16
MODCELL and MOD 30ML Maintenance
17
MODCELL and MOD 30ML Maintenance
Active Diagnostics
An effective way to quickly check for active diagnostics is to use the R DIAGS command
without specifying a type. This returns all points that are active or unacknowledged. An
example of the message returned in response to an R DIAGS command is:
WRIM1 NEW/CLR UAK G ACT G
8 WRIM MODULE ERROR
This message, as it appears on the status display, is shown in Figure 10 (page 53, Section
5). The information contained is as follows:
• Block Type and Occurrence Number - This identifies the block reporting the
diagnostic (WRIM1 in the example).
• Classification of the diagnostic:
- NEW/CLR - Diagnostics having a sustained active state which is cleared when
normal conditions are restored.
- ACK ONLY - Diagnostics resulting from a momentary occurrence where the
abnormal condition is not sustained. This class is sometimes accompanied by
a counter attribute which counts the number of occurrences.
• Status - The diagnostic status at the time the read command is received (UAK G
ACT G in the example). This status data indicates that the diagnostic is
unacknowledged (UAK), unacknowledged attribute quality is good (G), diagnostic
condition is active (ACT), and active status quality is good (G). After
acknowledgement, the status changes to ACK G ACT G.
• Event Code and Message Text - Each diagnostic in a block has a unique code
number (8 in the example), and a brief text message (WRIM MODULE ERROR) is
appended to the code to indicate the nature of the problem.
18
MODCELL and MOD 30ML Maintenance
Use the block type and event code to locate the diagnostic description and corrective
action listed in Section 7. The description/action listed for WRIM,code 8 states that the
module has reported an extended error code, and references Section 5 which provides
detailed information about the error.
Diagnostic History
When the System Event block is configured to report all diagnostics, the block stores both
new/clear and acknowledge only diagnostics reported by the data base blocks. Viewing the
system event queue provides data on all diagnostics which have occurred since the
current data base was down loaded or the queue was cleared. The command for reading
the queue is:
RQ
This command returns the most recent event first (other types of system events such as
informational only, process alarms etc. are stored with the diagnostic events). The screen
displays up to 15 events and a prompt to continue appears if necessary. An example of
an event queue entry is as follows;
The first line lists the time the diagnostic was reported, the date,and a transition message
(CLR/ACK). The second line lists the block type and occurrence number (IF1), event
code number (41), and diagnostic message text. See Section 7.2 for a description of the
transition messages, and use the block type and event code to find description/action
information in Section 7.3
O_OOOO,OOOOOOOO_OOOOOOOO _ = Space
Attribute Mnemonic
19
MODCELL and MOD 30ML Maintenance
All attribute data required for composing the read and write commands is provided in the
data base reference books listed in Section 1.4. The block identifiers for the data base
blocks are listed at the beginning of Section 7.3, and the block occurrence numbers are
listed in the .CRF file for your data base (see IB-23H141, Appendix A).
3.2.5 Commands
In addition to the read/write commands for diagnostics and block attributes, the status
display supports several other commands which provide for, reading the instrument
version number, setting the instrument time and date, etc. A list of all commands is
shown in Table 5 and the associated notes provide additional descriptive information. The
commands must be typed exactly as shown in the command column. Note that an
underscore is required in those commands which are not prefixed with an R or W. The
letters R (Read) and W (write) are always followed by a space.
20
MODCELL and MOD 30ML Maintenance
Equivalent
Command Description
Command
R VERSION 1 Read instrument version None
R SD type 2 Read instrument shutdown area type None
R lsp Read specified attribute None
R lsp type 3 Read Byte Before attribute None
RS lsp Read specified string attribute (RS IF1,USRTAG) None
RS lsp type 3 Read Byte Before string attribute (RS EX1,13 H) None
W lsp data Write specified attribute None
W lsp data type 3 Write Byte Before attribute None
ACK blkocc# diag# 4 acknowledge diagnostic point (e.g. ACK IF1 9) None
21
MODCELL and MOD 30ML Maintenance
NOTE: If the Application Builder software is available for use with the MOD 30ML
instrument, use of this software as described in Section 3.2 provides more
comprehensive diagnostic data and offers a wider command selection than the
instrument display.
Active Diagnostics
An unacknowledged diagnostic condition is always indicated by flashing of the alarm LED.
The indication may also include a flashing display and a beep signal depending on
configuration. A dedicated alarm display provides information on all active diagnostics. An
example of the display with control key information is shown in Figure 7.
When the alarm light indicates an alarm condition, press the alarm key to access the alarm
displays. Pressing the key repeatedly scrolls through a series of displays covering all
unacked alarms and acknowledged alarms which are still active. Unacknowledged
diagnostics are always displayed first in the viewing sequence. See IB-1800R-OPR,
Section 3 for more information.
22
MODCELL and MOD 30ML Maintenance
[UAK] indicates that the alarm is active and has not been
acknowledged. Press the ‘A' key to acknowledge the alarm. If
alarm is still active [ACT] appears. If alarm is no longer active
[CLR] appears, and this display is deleted upon exit.
Diagnostic History
The System Event block stores diagnostics reported by the data base blocks. Viewing the
system event queue provides data on all diagnostics which have occurred since the
current data base was down loaded or the queue was cleared. The queue contains both
informational and diagnostic data. The data for each event in the queue is displayed on
two pages. View the data in the event queue using the following procedure:
1. Press and hold the TAG key to obtain the Device Status display, Figure 8.
3 Press down arrow to enter the event queue. Page 1 for the first event in the queue
appears, Figure 9.
5. Continue using the NXT, Down, Up sequence to view all the event data in the queue.
6. Press the TAG key to return to the DEVICE/EVENTS display, then press again to
return to the runtime display.
23
MODCELL and MOD 30ML Maintenance
Abbreviated
Event
Message Date
Time
Hr:Min:Sec
Event
Code
Time (msec)
Block Transition
Type Message
Block
Occurrence
Number Page 1 Page 2
24
MODCELL and MOD 30ML Maintenance
1. Press and hold the TAG key to obtain the Device Status display, Figure 8.
2. Press the down arrow to enter the the status setup sequence. The Device State
(DEV STAT) display or password request (CONFIG PASSWORD) display appears.
4. From the DEV STAT display press NXT until COMMANDS appears on Line 2.
5. Press the down arrow to enter the command sequence. The Clear Q command
appears.
6. To execute this command, use the arrow keys to select YES, then press the scroll key
while the ENT prompt is flashing.
7. Press NXT repeatedly to scroll through the available status commands, Table 6, and
execute any required command using the method of Step 6.
Command Description
CLR Q Use to clear system event queue.
CLR MT Use to clear maximum scan times for all scan groups.
ACK ALL Use to send global acknowledge command causing all
diagnostics, notification/request messages, and process
alarms to be acknowledged.
RESET Use to complete tasks then perform a power-up.
KILL Use to perform an immediate power-up.
DEL MAIN Use to mark the main data base as bad and set the
instrument state to DEFAULT.
RES MAIN Use to mark the main data base as good in case DEL MAIN
command was issued by mistake. If data base is verified as
good, attempts to set instrument state to RUN.
25
MODCELL and MOD 30ML Maintenance
26
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
SECTION 4
COMMUNICATIONS
Connection of a MOD 30ML with an unknown address allows the possibility that the
unknown address matches the address of another device on the network. When two
devices with identical addresses are connected, the entire network communication is
disrupted. In the case of an ICN all communication ceases until the replacement is
disconnected. This problem can be avoided by using the following procedure when
installing a replacement MOD 30ML with an unknown address setting:
2. Install the instrument and apply power. The Device Status display appears with the
instrument state indicated on line 3 as follows:
• LHD indicates the instrument is in the local hold state and has a valid database.
• DEF indicates the instrument is in the default state and may or may not have a
valid database. This procedure can be successfully completed with the instrument
in the default state.
3. Press the alarm key and ACK key as required to view, acknowledge and clear the
power up/power down alarm, and any other alarms or diagnostics which are present.
27
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
4. Press the NXT key to access the Device Setup Display, then press the down ( ) key
to enter the setup sequence.
6. If a memory module is not being used, download a valid database from the Application
Builder.
NOTE: Because the RUN/SERV switch is at SERV, the application builder generates
the following message after completion of a successful download:
“Cannot change to run. State changed to LOCAL_HOLD.“
28
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
2. Note the address switch setting on the ICN module. The address is indicated in
hexadecimal, with A through F representing 10 through 15.
On Model A modules, a rotary switch on the side of the module points to the
configured address. On Model B modules, a rotary switch is located on the top of the
module; the address is indicated by the flat side of the switch spindle.
29
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
4. If a 1731N Mini Link or 1733N Mini Link/External is being used, verify the setup as
follows:
• The mini links provide the required interface for one ICN, and an optional interface
board supports a second ICN. Each ICN can be connected to as many as 15
instruments. The interface board and instruments on each ICN must have unique
addresses. The hexadecimal address switch on the interface board is factory set
at 0; this allows addresses 1-15 ($1-$F) to be assigned to the instruments via the
ICN module address switch. The interface board can be assigned any address (1-
15). Be sure the interface board address does not match the address of any
instrument on the ICN.
• On the 1731N link which is installed in the computer chassis, ensure that the link
address and interrupt settings are different from other ports in the PC. In most
cases, it is acceptable to share an interrupt with a parallel port.
• Note the number of each ICN. If a single ICN is connected its number is 0. The
optional second ICN is number 1. The ICN number is not related to the ICN
interface board address; they can have the same numerical value.
• Note the link jumper locations. The locations determine the communication
parameters for the two serial ports. The factory settings provide the following
values:
- 9600 baud
- No parity, 8 data bits, 1 stop bit (these parameters are not configurable)
- Clear-to-send (CTS) ignored
- RS-232 transmission standard (not configurable)
5. Verify that a wire is connected from the common of the ICN connector on the link
interface board to the common connection for the module. Be sure this wire is not
connected to earth or chassis ground. Note that the common terminal on the Mini
Link ICN connector is labeled with a ground symbol; disregard this marking because
the terminal functions as the common connection.
6. Apply power to the equipment. If the network contains a Mini Link, allow at least 30
seconds for the link to initialize.
7. Verify that the ICN has proper termination. The most common termination method
uses the 2030F ICN terminator connected to the terminal block of one instrument on
the network.
NOTE; Successful communication with any instrument on the network indicates that
the ICN is properly terminated and functioning correctly. Another method of
verifying proper ICN operation is to check the voltage pattern with an
oscilloscope. Typical voltage traces for a properly functioning ICN are shown
in Figure 10.
30
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
24V
+ICN 13V
ICN Com 9V
0V
250 ms
24V
–ICN
ICN Com 12V
10V
0V
250 ms
8. Start the Application Builder software and access the Serial Port Setup menu, Figure 4
(see Section 3.2.1 for procedure). Select the serial port that is connected to the link
and confirm that the port settings match the link configuration. If uncertain of the link
configuration, select the default configuration parameters from Table 3.
9. Access the Communications Setup menu, Figure 6, (See Section 3.2.2 for
procedure). Set the Communication Type to Link Set the ICN number and
Instrument address to match the values determined in Step 3 or 4.
10. Access the Instrument Status Display and click on the command line at the bottom of
the screen. Type R VERSION and click on Enter. This command returns the
version of any instrument connected to the ICN, even MOD 30. If the instrument
responds, confirm that the reported version agrees with the type of instrument that is
being tested. The version return data is listed in Section 3.2.5.
31
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
• If you are unsure of the link configuration, first access the serial port setup menu again
and change the baud rate to another setting. In most cases, the link is set at 9600 or
19200.
• If the problem still exists, change the parity setting. If a Mini Link is being used,
always set the parity at none. The data and stop bits are likely to be set at 8 and 1
respectively.
• If unable to establish communications, disconnect power and remove all analog and
communications modules, except for the ICN module being used. Restore power and
try to communicate again via the R VERSION command.
• If still unable to communicate, replace the ICN module, preferably with a Model B
version and terminator.
NOTE: The extended Modbus communications required for diagnostics and downloading
is supported by the 2033N and 2034N modules only. On Modcell, the Identity
module firmware must be at least version 4 Logic, version 3 Regulatory, Batch,
Advanced. Refer to Section 9 for details of hardware and software compatibility.
1. Remove power from the instrument.
2. Note the switch settings on the Modbus module. Two rotary switches are used to
select the address. The address is indicated in hexadecimal, by the flat side of the
spindle, with A through F representing 10 through 15.
3. Set the COMM DEFAULTS switch to YES. This forces the module to communicate at
9600 baud, 8 data bits, 1 stop bit and no parity, regardless of the database
configuration.
4. If using an RS-485 module, set the TERM switch to NO. This switch provides pull-up
and pull-down resistors to stabilize the network. This function is defined by the
Modbus specification as the responsibility of the Modbus Master node, which is the
PC in this case. If the PC does not contain an RS-485 interface card with the required
bus stabilizing resistors, the TERM switch on one communications module on the
network can be set to YES to provide the required resistors.
32
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
6. Start the Application Builder software and access the Serial Port Setup menu, Figure 4
(see Section 3.2.1 for detailed procedure). Select the serial port that is connected to
the instrument and confirm the port settings. The standard Base Addresses are 3F8,
2F8, 3E8 and 2E8 for Com1 through Com4 respectively. If unsure of the address,
check the computer hardware manual for configuration information. Set the Baud
Rate to 9600, Data Bits to 8, Parity to None and Stop Bits to 1.
7. Access the Communications Setup Menu, Figure 6 (see Section 3.2.2 for detailed
procedure), Set the Communications Type to Extended Modbus, set the Modbus
Address to match the module setting, and select the com port to be used. The ICN
and Instrument number settings listed on the menu have no effect when modbus
communication is selected.
8. Access the Instrument Status Display and click on the command line at the bottom of
the screen. Type R VERSION and click on Enter. This command returns the version
of the instrument. If the instrument responds, confirm that the reported version agrees
with the type of instrument that is being tested. The version return data is listed in
Section 3.2.5.
2. Verify that the communications jumper in the instrument is in the correct location for
built-in communication via the ICN.
3. Verify that a communication module is not installed in instrument slots S9 and S10.
33
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
5. If a 1731N Mini Link or 1733N Mini Link/External is being used, verify the setup:
• The mini links provide the required interface for one ICN, and an optional interface
board supports a second ICN. Each ICN can be connected to as many as 15
instruments. The interface board and instruments on each ICN must have unique
addresses. The hexadecimal address switch on the interface board is factory set
at 0; this allows addresses 1-15 ($1-$F) to be assigned to the instruments via the
Device Setup display on the instrument front panel. The interface board can be
assigned any address (1-15). Be sure the interface board address does not match
the address of any instrument on the ICN.
• On the 1731N link which is installed in the computer chassis,ensure that the link
address and interrupt settings are different from other ports in the PC. In most
cases, it is acceptable to share an interrupt with a parallel port.
• Note the number of each ICN. If a single ICN is connected its number is 0. The
optional second ICN is number 1. The ICN number is not related to the ICN
interface board address: they can have the same numerical value.
• Note the link jumper locations. The locations determine the communication
parameters for the two serial ports. Factory settings provide the following values:
- 9600 baud
- No parity, 8data bits, 1 stop bit (these parameters are not configurable)
- Clear-to-send (CTS) ignored
- RS-232 transmission standard (not configurable)
34
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
6. Verify that a wire is connected from the common of the ICN connector on the link
interface board to terminal 1 (common) on the instrument. Be sure this wire is not
connected to earth or chassis ground. Note that the common terminal on the mini link
ICN connector is labeled with a ground symbol; disregard this marking because the
terminal functions as the common connection.
7. Apply power to the equipment. If the network contains a Mini Link, allow at least 30
seconds for the link to initialize.
8. Verify that the ICN has proper termination. The most common termination method
uses the 2030F ICN terminator connected to the terminal block of one instrument on
the network.
NOTE: Successful communication with any instrument on the network indicates that
the ICN is properly terminated and functioning correctly. Another method of
verifying proper ICN operation is to check the voltage pattern with an
oscilloscope. The voltage traces for a properly functioning ICN are shown in
Figure 10.
9. Access the Device Setup display on instrument front panel and verify the following:
• The instrument being tested is set at a different ICN address than the address
switch on the ICN interface board in the link.
• ICN communication is enabled
10. Start the Application Builder software and access the Serial Port Setup menu, Figure 4
(see Section 3.2.1 for procedure). Select the serial port that is connected to the link
and confirm that the port settings match the link configuration. If uncertain of the link
configuration, select the default configuration parameters from Table 3.
11. Access the Communications Setup menu, Figure 6 (see Section 3.2.2 for procedure).
Set the Communication Type to Link . Set the ICN number and Instrument address to
match the values determined in Step 4 or 5.
12. Access the Instrument Status Display and click on the command line at the bottom of
the screen. Type R VERSION and click on Enter. This command returns the version
of any instrument connected to the ICN , even MOD 30. If the instrument responds,
confirm that the reported version agrees with the type of instrument that is being
tested. The version return data is listed in Section 3.2.5.
35
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
2. Verify that the communications jumper is in the correct location for built-in
communication via either RS-232 Modbus or RS-485 Modbus.
4. If RS-485 communication is being used, verify that the connection at the computer
(Modbus Master) is made via an RS-485 interface card containing the required bus
stabilizing resistors.
NOTE: The Port Functionality attribute of the MSC block must be configured as a
slave.
7. Access the device setup display on the instrument front panel. Note the instrument
address and communication parameter settings, and verify that built-in (BI) MSC
communication is enabled.
8. Start the Application Builder software and access the Serial Port Setup menu, Figure 4
(see Section 3.2.1 for procedure). Select the serial port that is connected to the
instrument and confirm the port settings. The standard Base Addresses are 3F8, 2F8,
3E8 and 2E8 for Com1 through Com4 respectively. If unsure of the address, check
the computer hardware manual for configuration information. Set the Baud Rate, Data
Bits, Parity, and Stop Bits to match the instrument values noted in Step 7.
9. Access the Communications Setup menu, Figure 6 (see Section 3.2.2 for procedure).
Set the communications type to Extended Modbus. Set the Modbus Address to match
the instrument setting and select the com port to be used. The ICN and Instrument
number settings listed on the menu have no effect when modbus communication is
selected.
10. Access the Instrument Status Display and click on the command line at the bottom of
the screen. Type R VERSION and click on Enter. This command returns the version
of the instrument. If the instrument responds, confirm that the reported version agrees
with the type of instrument that is being tested. The version return data is listed in
Section 3.2.5.
36
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
11. If you are unable to establish communications in Step 10, proceed as follows:
• Disconnect power and remove all analog and communications modules. Restore
power and try to communicate again via the R VERSION command.
• If the problem still exists,do the following:
- Disconnect power.
- Disconnect all instruments from the network, other than the one being tested.
- Restore power and try to communicate again via the R VERSION command.
• If still unable to communicate, replace the instrument.
These messages include both status and error information. The status messages simply
provide the user with information about a specific communication activity. For example,
the message Downloading notifies the user that the software is in the process of
transmitting a successfully compiled data base to an instrument. The error messages
provide the user with information about communication problems. For example, the
message No response was received notifies the user that the personal computer is not
communicating with the instrument, possibly because the configured ICN or Modbus
address is incorrect.
A list of the messages is provided in Table 7. The messages are listed in alphabetical
order. The table includes information about the probable cause of each message
appearance and recommended action as appropriate.
37
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
38
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
NOTE:
Selection of the About icon in
the Application Builder tool bar
displays configuration
capability of the installed
software.
Deferred response overrun, 1. Momentary communication 1. Try again.
parity or framing error fault.
2. Parity mismatch between 2. Check that parity configured in
instrument and Serial Port Setup menu, Figure
Communications Link. 4, matches setting of parity
status switch in link.
Do you wish to retain block This message appears whenever a If a compound is saved and then
occurrence numbers in the compound is loaded. loaded within the same database
compound being loaded? for the purpose of moving (not
copying) a group of blocks from
one location to another in the
workspace, answer YES.
Otherwise answer NO because
retaining occurrence numbers
leads to duplicates if blocks with
the same numbers already exist in
the database.
Download completed without Information only None
error
Downloading Information only None
Ending, changing instrument Information only (3-10second None
state duration)
39
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
40
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
Instrument reports an error 1. Block containing the attribute 1. Configure the required block.
reading that attribute is not configured.
2. Attribute does not exist in the 2. Check block configuration.
specified block.
Instrument state in transition Information only. An instrument None
state transition is in process.
instrument version too low to Data base being downloaded Replace instrument identity module
run data base contains functions not supported with a version which accepts the
by the instrument. data base, or modify the
configuration to run on the existing
instrument version.
Interpreting database Information only None
Invalid ACK Diagnostic acknowledgement Retype command using correct
specifies nonexistent block number (See Section 3.2.5)
occurrence number, or inactive
diagnostic number.
Invalid ASCII string Specified ASCII data is invalid. Correct entry and try again.
e.g., W IF1,USRTAG 1
(ASCII data expected; 1 specified)
41
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
42
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
Invalid diagnostic code Specified diagnostic number is Correct entry and try again. Refer
invalid. to Section 7 for a list of code
e.g., ACK AIN1 A numbers.
(Letter A is not valid, code must
be a number)
Invalid entry A command or part of a command Correct entry and try again.
is not understood.
e.g., W TIM 2:04:00.0
(TIME is misspelled TIM.)
Invalid hexadecimal number Specified hex number is invalid. Correct entry and try again.
e.g., W EX1,I3 $G H
(G is not a valid hex digit)
Invalid message function Momentary fault in Modbus Try again.
code communication.
Invalid mode The write message is not accepted Change the mode attribute to the
because of the state of the mode appropriate state.
attribute.
Invalid occurrence number An invalid block occurrence Correct entry and try again.
number was specified. Occurrence numbers are listed in
e.g. , R SE2,PKDLEN the Cross Reference Database
(block must be SE1 because there (.CRF) file which is created by the
is only one SE block in a Application Builder after a
database) database is successfully compiled.
43
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
44
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
45
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
46
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
47
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
48
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
49
MODCELL and MOD 30ML Maintenance
COMMUNICATIONS
50
MODCELL and MOD 30ML Maintenance
SECTION 5
DIAGNOSING ANALOG I/O MODULE PROBLEMS
5.1 GENERAL
The status display in the Application Builder Software allows access to Extended Error
Codes which can help trouble shoot the instrument. The extended error data includes
both status information and fault information for analog I/O modules.
The extended error code is a two byte (16 bit) code from the module that is presented as
a count value. When the status display in the Application Builder Software is used to view
the code, the decimal count value is shown and the program automatically converts the
value to binary and displays a text message for each status bit and for any error bit
indicating an error. An example of the data for a WRIM module containing a fault is shown
in Figure 7. The count value, 14368, has been decoded to provide six status messages
and one error message. A complete list of the extended error code messages with
recommended action for fault conditions is shown in Tables 9 and 10.
NOTE: When PC-30 or a similar host system is used to view the error codes, the host
reads the Extended Error (EXTERR) attribute and returns only the decimal count
value. The user must program the host software to decode (or manually decode)
the bitmapped error pattern shown in Table 9 or 10.
51
MODCELL and MOD 30ML Maintenance
• Observe the data returned. An example of the data for a WRIM module with a
fault is shown in Figure 7. The decimal error code number, 14368, is converted to
a 16-bit binary number in which one group of bits provide status information and
the second group indicates errors. The software converts the decimal code and
groups the information as Status bits and Error Bits as shown in Figure 7.
4. Refer to Section 5.3 for information on interpreting the error code data.
52
MODCELL and MOD 30ML Maintenance
Figure 10. Example of Extended Error Code Data for a WRIM Module
If condition 2 or 3 exists the data is not current and should be ignored. Also note that
because the data is not current, the reported Status Bit information may not represent the
actual current status of the module.
When it has been established that a current problem exists, refer to Table 10 or 11 for
additional information and recommended action.
53
MODCELL and MOD 30ML Maintenance
54
MODCELL and MOD 30ML Maintenance
55
MODCELL and MOD 30ML Maintenance
56
MODCELL and MOD 30ML Maintenance
SECTION 6
DIAGNOSING SHUTDOWN FAULTS
If an instrument with a memory module shuts down (watchdogs for example) and cannot
run again, it may still be possible to read the shutdown information in the memory module
using the procedure in Section 6.2.3.
• MODCELL
The red status LED turns on, the green LED turns off, and shutdown information is
stored in the instrument memory. Also, the instrument stops communicating and all
outputs go to their configured failsafe values.
• MOD 30ML
The beeper sounds, the red alarm indicator flashes, the word FAILURE appears on the
display, the control keys become inoperative, and shutdown information is stored in
the instrument memory. Also, the instrument stops communicating and all outputs go
to their configured failsafe values.
Use the method described in one of the following sections to obtain a record of the
shutdown fault information, and transmit the data to ABB Instrumentation support
personnel for analysis.
• For Modcell instruments, use the Application Builder Method, Section 6.2.1.
• For a MOD 30ML instrument which can be connected to a PC running the Application
Builder software, use the Application Builder Method, Section 6.2.1.
• For a MOD 30ML instrument without the Application Builder, use the MOD 30ML
Display Method, Section 6.2.2.
• The Memory Module Method, Section 6.2.3, is used only as an alternate approach
when specified in one of the other methods.
57
MODCELL and MOD 30ML Maintenance
1. Turn off power to the instrument, then turn power back on.
2. Start the Application Builder Software. If communication with the instrument is via an
RS-232 or RS-485 port, the default parameters (9600 baud, no parity, 8 data bits, 1
stop bit) must be used. See Section 3 for the software startup procedure.
4. On the status display command line, type the command R SD and click on ENTER. A
display providing shutdown data should appear.
• If the display appears, go to with Step 6.
• If the display does not appear and a memory module is present, continue with
Step 5.
• If a memory module is not installed, and the shutdown display cannot be obtained,
return the instrument for repair.
6. Make a copy of the shutdown record form at the end of this section. The form
illustrates the shutdown display with blank data fields.
NOTES: If a facility for printing the display screen is available, it can be used to
generate a copy of the shutdown data. Starting with Application Builder 4.01,
the print button on the Status Display can be used to print the shutdown
record (or anything else that appears on the Status Display).
Starting with Application Builder 4.00, when the R SD command is issued, the
shutdown record is saved as a text file in the current directory. It is given the
instrument tag name and the extension SD1. If this file already exists, it is
overwritten. The current directory is the directory in which a database was
most recently saved or loaded, or if no save or load has taken place, the
directory from which the Application Builder was started.
7. Fill in the blank fields on the copy using the data from the display.
8. Type the command R VERSION and click on ENTER. The instrument version data
appears near the bottom of the status display.
58
MODCELL and MOD 30ML Maintenance
2. Turn power back on. The device status [DEV STAT] display, Figure 8, should
appear.
• If the display appears continue with Step 2.
• If a different display appears, press and hold the TAG key to obtain the device
display, then continue with Step 2.
• If the front panel keys are inactive and the device status display cannot be
obtained, the instrument must be returned for repair.
59
MODCELL and MOD 30ML Maintenance
3. Press the down arrow key to enter the status sequence, then press [NXT] to obtain
the [SHUTDOWN] entry display. Line 6 displays [YES] indicting that a shutdown
condition exists. Shutdown information is provided on the next 4 displays (Shutdown
pages 1-4). A form for recording the data on these pages is provided at the end of
this section.
4. Make a copy of the form and record the shutdown data as follows:
• Press the down arrow key to advance to page 1 and record the data displayed on
lines 1 and 2.
• Press NXT to advance through pages 2, 3 and 4 and record the data from each
page.
5 After completing the shutdown data record , determine the instrument firmware and
display version numbers as follows:
• Press the TAG key to return to the device status [DEV STAT] display.
• Press the down arrow key to obtain the firmware version and record the version
number.
• Press [NXT] to obtain the display version and record the version number.
• Press the up arrow key to return to the [ABOUT] display, then press [NXT]
repeatedly until the device status display appears.
ABB Instrumentation
Advanced Control Support
FAX: 716-273-6242
60
MODCELL and MOD 30ML Maintenance
• Observe the display. Depending upon the instrument configuration, either the
Device Status display or a user configured display will appear. The alarm light
should be off unless there is still an active problem in the instrument.
If the alarm light is on or flashing, press the alarm key to access the diagnostic
alarm display. The display shows the diagnostic event code number and block
type. Refer to Section 7 for descriptions of diagnostic event codes.
2. Change the READ/WRITE setting to READ ONLY, and NORMAL to MODULE LOAD.
This prevents the shutdown data from being overwritten and also prevents the module
database from being downloaded when the module is put into the spare instrument.
3. With power off, install the memory module in an operable spare instrument (either
MODCELL or MOD 30ML).
7. On the Instrument Status display command line, type the command R SD M and click
on ENTER. A display providing shutdown data appears. A form illustrating this
display with blank data fields is provided at the end of this section.
NOTE: If a facility for printing the display screen is available, it can be used to generate a
copy of the shutdown data.
8. Make a copy of the form and fill in the blank fields on the copy using the data from the
display.
9. Copy the Catalog No. and Version number from the identity module in the failed
instrument onto the shutdown data form.
ABB Instrumentation
Advanced Control Support
FAX: 716-273-6242
61
MODCELL and MOD 30ML Maintenance
62
MODCELL and MOD 30ML Maintenance
Line 1
Line 2
Line 6
Shutdown
Page 1 S —— —— —— —— —— —— 1 —— —— —— —— —— —— —— ——
Shutdown
Page 2 S —— —— —— —— —— —— 2 —— —— : —— —— : —— —— : —— —— —— —— / —— —— / —— ——
Shutdown
Page 3 S —— —— —— —— —— —— 3 —— —— —— —— —— —— —— —— —— —— —— —— —— —— —— ——
Shutdown
Page 4 S —— —— —— —— —— —— 4 —— —— —— —— —— —— —— —— —— —— —— —— —— —— —— ——
63
MODCELL and MOD 30ML Maintenance
64
MODCELL and MOD 30ML Maintenance
SECTION 7
EVENT CODES AND TRANSITION MESSAGES
7.1 GENERAL
The transition messages and diagnostic and informational event codes described in
the following sections can be viewed on the status display in the Application Builder
Software or from the MOD 30ML display. Refer to Section 3 for information on
accessing the status display, and issuing the commands required to read the codes
and messages.
65
MODCELL and MOD 30ML Maintenance
66
MODCELL and MOD 30ML Maintenance
67
MODCELL and MOD 30ML Maintenance
68
MODCELL and MOD 30ML Maintenance
69
MODCELL and MOD 30ML Maintenance
70
MODCELL and MOD 30ML Maintenance
71
MODCELL and MOD 30ML Maintenance
72
MODCELL and MOD 30ML Maintenance
73
MODCELL and MOD 30ML Maintenance
74
MODCELL and MOD 30ML Maintenance
75
MODCELL and MOD 30ML Maintenance
76
MODCELL and MOD 30ML Maintenance
77
MODCELL and MOD 30ML Maintenance
78
MODCELL and MOD 30ML Maintenance
79
MODCELL and MOD 30ML Maintenance
80
MODCELL and MOD 30ML Maintenance
81
MODCELL and MOD 30ML Maintenance
82
MODCELL and MOD 30ML Maintenance
83
MODCELL and MOD 30ML Maintenance
84
MODCELL and MOD 30ML Maintenance
PARTS
SECTION 8
PARTS
85
MODCELL and MOD 30ML Maintenance
PARTS
86
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
SECTION 9
HARDWARE, FIRMWARE AND SOFTWARE REVISION HISTORY
9.1 GENERAL
This section provides information about revisions introduced for Modcell and MOD 30ML
instruments and associated firmware, and revisions introduced for configuration software
and device driver software since the initial introduction of these products.
The starting point of these historical records is either the date of the initial product
introduction or the date of the revision which made the product usable with Modcell or
MOD 30ML instruments. The product revisions are identified by either a number or a
model letter. The numbers apply to firmware and software revisions; the model letters
apply to hardware revisions.
87
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
5.0 Aug 1986 Enhanced Link CPU and ICN boards both at
communications for Ver 5
MOD 300 compatibility
Communications 5.2 Jan 1992 Added support for Required for MODCELL and
Links, ICN MODCELL foreground MOD 30ML instruments
Controller only size.
Link CPU board current version is
(1720N, 1731N,
5.1, and Link ICN controller board
1733N, 1734N)
current version is 5.2
MOD 30ML Model A Mar 1996 Initial release Requires 2006S Ver 4.0
Multiloop Application Builder software
Controller
1.01 1.01 Requires 1716S Ver 9.0
1800R
ICN Driver for PC-30
MODCELL Model A Oct 1991 BETA release hardware; All BETA sites updated to
Multiloop limited shipment Model B
2001N, 2002N Base
Model B Dec 1991 Initial production hardware
Board
release
88
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
MODCELL 1.0 Jun 1992 PID, RTD support Requires Ver 5.2 firmware for
Multiloop ICN controller in link and mini-
links
2002P Regulatory
Control Identity
2.0 Mar 1993 Supervisory, Notification, Requires 1716S Ver 6 ICN driver
Module
Expression block for PC-30.
enhancements; Modbus Requires 1706S Ver 5.0
slave communications Configuration software or 2006S
Ver 1.5 Application Builder.
89
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
MODCELL 1.0 Jan 1992 Sequence of events Requires PC-30 ICN driver
Multiloop recording for as many as version 8.0or higher.
29 digital inputs.
2005P Sequence of
Events Recorder
2.0 Jan 1995 Added Extended Modbus
Identity Module
communication and
Omega Clock support.
90
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
MODCELL Model A Aug 1994 Master or slave serial Replaces 2031N Communications
Multiloop communications via module in new systems.
Modbus. Requires 2006S Ver 2.0
2033NZ RS-232
Supports download via Application Builder.
Communications
Modbus.
module
Isolated
MODCELL Model A Aug 1994 Serial communications via Required Logic 4, Regulatory 3 or
Multiloop Modbus. Batch 1 Identity module.
Supports host Requires 2006S Ver 2.0
2034NZ RS-485
communication and Application Builder software.
Communications
download via Modbus.
module (4-wire)
Isolated
MODCELL Model B Jan 1996 Interface for Requires 2006S Ver 2.0
Multiloop Communication with Application Builder .
remote I/O modules on Requires 1716S Ver 8.0 ICN
2020NZ Remote I/O
CS-31 bus. Driver for PC-30.
Interface module
91
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
Instruments
Package Rev Date Added Features Comments
Supported
Instrument 3.0 Jan 1992 MODCELL 2000 MODCELL with 1706S software does
Configurator support. 2001P Ver 1.0 Logic NOT support
Help menus. Identity module Batch/Advanced
1706S
Subdirectory support. control Identity
Can use PC-30 modules for
Workstation MODCELL Multiloop
protection key. Processors and MOD
30ML Controller.
4.0 Jun 1992 MODCELL 2000 PID, MODCELL with LCP must be Model C
RTD support. 2001P Ver. 1 or 2
Upload/download of Logic Identity
LCP databases. module.
Fixed communication MODCELL with
problems with 486 2002P Ver 1
PCs. Regulatory Identity
module.
LCP firmware
Ver. 4.
92
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
Instruments
Package Rev Date Added Features Comments
Supported
Instrument 5.2 Jun 1993 Resolve minor bugs MODCELL with
Configurator (refer to Rochester 2001P Ver 1,2 or 3
for more info). Logic Identity
1706S
module.
(Cont’d)
MODCELL with
2002P Ver 1&2
Regulatory Identity
module.
5.3 Feb 1994 Resolve minor bugs Same as above Most users
(refer to Rochester unaffected.
for more info).
5.4 Oct 1994 Resolve minor bugs. Same as above Does not provide new
Download lower features for Logic 4.0,
version MODCELL Regulatory 3.0, or
databases to higher any higher version.
version identity Does not support
modules without new Batch/Advanced
feature support. Control identity
module or MOD 30ML
Controller.
5.5 June 1996 Resolve minor bugs. Same as above Company name
changed to ABB
Instrumentation.
Application 1.00 May 1993 Initial release MODCELL with: Requires 1716N
Builder Logic Ver 1, 2, or 3 Ver 6 or higher ICN
Regulatory Ver 1 or Driver for PC-30.
2006S
2.0 No MOD 30 support.
1.01 Aug 1993 Maintenance release Same as above All users updated
automatically, no-
charge
93
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
Instruments
Package Rev Date Added Features Comments
Supported
Application 1.02 Nov 1993 Maintenance release MODCELL with: Correct password
Builder Logic Ver 1, 2, or 3 protect problem;
Regulatory Ver 1 or some fields in PID
2006S
2.0 block did not allow
Continued
negative values.
1.03 Nov 1993 Maintenance release Same as above PC Comm Port setup
menu did not appear
in 1.02.
1.05 Feb 1994 Maintenance release Same as above Databases >32K did
not compile properly
94
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
Instruments
Package Rev Date Added Features Comments
Supported
ICN 4.0 Mar 1991 Support for MODCELL with
Communication (3.50) MODCELL 2000 2001P Ver 1 Logic
Driver Logic identity. Identity module
Name changed to ICN
1716S
Communications.
Note:
5.0 Jul 1992 Support for MODCELL with
Genesis revision
MODCELL PID, RTD 2001P Ver 1 or 2
equivalents are
Logic Identity
in brackets.
module.
MODCELL with
2002P Ver 1
Regulatory Identity
module .
95
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
Instruments
Package Rev Date Added Features Comments
Supported
ICN 8.0 Jan 1995 Support for Same as previous
Communication (3.62) MODCELL Sequence page plus:
Driver of Events Recorder. MODCELL with
Support for CS-31 2005P Sequence of
1716S
Remote I/O. Events, or 2004P
Continued
Ver 2 Advanced
Control identity
module.
9.0 Mar 1996 MOD 30ML support Same as above plus Supports operation of
(3.64) MOD 30ML a PC-30 system with
Multiloop Controller two computers.
Modbus Driver 1.0 Mar 1993 Initial release MODCELL Multiloop Requires RS-232 or
for PC-30 with all versions of RS-485
all identity modules Communications
1719S
module
Extended 3.0 Aug 1996 Initial release MODCELL Multiloop Extended Modbus
Modbus Driver with all versions of protocol driver.
for PC-30 all identity modules Requires an RS-232
and MOD 30ML. or RS-485
1733S
Communications
module, or built-in
communications
circuit in MOD 30ML.
96
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
Instruments
Package Rev Date Added Features Comments
Supported
EMP 5.3 May 1996 Initial release MODCELL Multiloop Extended Modbus
Communication with all versions of protocol driver.
Driver for FIX all identity modules Requires an RS-232
DMACS - 16 Bit and MOD 30ML. or RS-485
Communications
2010S
module, or built-in
communications
circuit in MOD 30ML.
EMP 6.0 Sept1996 Initial release Same as above Same as above
Communication
Driver for FIX
DMACS - 32 Bit
2011S
97
MODCELL and MOD 30ML Maintenance
REVISION HISTORY
98
PRODUCTS AND SERVICING
Italy
Indicators, recorders, controllers and process man- Lenno (Como)
agement systems ABB Kent-Taylor SpA
Tel: (0344) 58111
Recorders Fax: (0344) 56278
circular and strip-chart types - single and multi-point - for
temperature, pressure, flow and many other process mea-
surements.
Controllers
digital display, electronic, pneumatic. Discrete single-loop
and multi-loop controllers which can be linked to a common
display station, process computer or personal computer.
Gas analyzers
Zirconia, paramagnetic, infrared, thermal conductivity.
IB-23M601, Issue 1 10.96