INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-1992-002
Figure 2: System Diagram

To next detector or module


Honeywell Fire and Security Systems(Shanghai) Co., Ltd.
Model JTY-GD-ND751PM 430,Li Bing Road, Zhangjiang Hi-Tech Park

Compatible Control Panel


Pudong New Area, 201203, Shanghai
Photoelectric Smoke Detector Tel: 021 -28942000 Fax: 021 -58559612
+ IN/OUT + IN/OUT

SPECIFICATIONS - OUT - OUT


Diameter: 102 mm
Height: 52 mm A5665‐104
Weight: 80 g (without the base)
Operating Temperature Range: -10°C ~ 55°C (14°F ~131°F)
Operating Humidity Range: 5% ~ 95% Relative Humidity, Non-condensing To next detector or module
Operating Voltage Range: 15 ~32VDC
Avg. Standby Current: 350μA @ 24VDC (one communication every 5 sec. with LED blink enabled)
Max. Alarm Current: (LED on) 2.5mA @ 24VDC TESTING
Figure 3: Smoke Entry Test Position
Standard: GB4715-2005 Before testing, notify the proper authorities that the system is
Software: A undergoing maintenance, and will temporarily be out of service.
Disable the system to prevent unwanted alarms.
Certification:
Detectors must be tested after installation and Following
periodic maintenance.
Before installing and using the product, please read the system This model detector is used with a mounting base (B601 or The detector can be tested in the following ways:
wiring and installation manual thoroughly. If the products will B601BH) that permits it to be mounted directly to a 50 or Calibrated Sensitivity Test (Gemini 501) or Smoke Entry Test
be installed in an existing operational system, inform the 60mm junction box as Figure 1 showed. The GEMINI model 501 aerosol generator can be used for smoke
operator and local authority that the system will be temporarily 1. Verify that the detector type matches the type written on entry testing. Set the generator to represent 4%/ft to 5%/ft
out of service, disconnect power to the control panel before the label in the base. obscuration as described in the GEMINI 501 manual. Using the
installing the products. 2. Set the detector to a desired address with the model bowl shaped applicator, apply aerosol until the panel alarms. Or Smoke entrance
NOTICE: This manual should be left with the owner/user of this hold a smoldering punk stick or cotton wick at the side of the
CP900M and then write the address on the label of the detector (see figure 3) and gently blow smoke through the
equipment.
The model CP900M handheld programmer should be used for base. detector until it alarms.
this detector to write the address from 0 to 199 in the general 3. Place the detector into the base. A detector that fails any of these tests should be cleaned as A5665‐107
wire. 4. Turn the detector clockwise until it drops into place. described under MAINTENANCE, and retested. If the sensor
5. Continue turning the detector clockwise to lock it in place fails after cleaning, it must be replaced.
GENERALDESCRIPTION
(See Figure 1). When testing is complete, restore the system to normal
Model JTY-GD-ND751PM is a 2-wire photoelectric smoke operation and notify the proper authorities that the system is
6. If to be connected with the polarity reversal wire, the
detector that uses a state-of-the-art optical sensing chamber. back in operation.
This detector is designed to provide open area protection and detector will not operate normally. But, other units can
to be used with compatible panels only. still operate as usually in the loop.
MAINTENANCE
One LED on each detector provides a local, visible indication. TAMPER-RESISTANT FEATURE NOTE: Before removing the detector, notify the proper
The LED can be latched on by code command from the control This detector includes a tamper-resistant feature that prevents authorities that the smoke detector system is undergoing
panel for an alarm indication. The LED can also be unlatched
its removal from the mounting base without the use of a key. maintenance and will temporarily be out of service. Disable the
to the normal condition by code command.
The details refer to the base installation instructions. zone or system undergoing maintenance to prevent unwanted
WIRING INSTALLATION GUIDELINES alarms.
All wiring must comply with all applicable national codes of 1. Remove the detector from the mounting base by rotating it
practice and regulations. Refer to the installation instructions counter-clockwise.
for the plug-in detector base. For the detector and the control CAUTION 2. Remove the detector cover by turning it counter-clockwise.
panel wiring instructions refer to Figure 2. Dust covers provide limited protection against airborne dust 3. Vacuum the cover carefully.
4. Remove the sensing chamber cover. PRODUCT NAMEPLATE DATE CODE NOTE
INSTALLATION particles during shipping. Dust covers must be removed before Product date code consists of four digits: The first represents the
the sensors can sense smoke. Remove sensors prior to heavy 5. Replace the sensing chamber cover by aligning the two
NOTE: Verify that all detector bases are installed, the initiating- holes on the cover with the two posts on the chamber. end number of the producing year, the second and the third
device circuits have been tested, and all the wiring is right. remodeling or construction. represent the producing month, and the fourth represents the
6. Replace detector cover, tightening two screw of the detector
WARNING: Remove power from initiating-device circuits before back with screwdriver. week of the month.
installing detectors. 7. Reinstall the detector. Test the detector as described in
Figure 1: Surface Mounting of JTY-GD-ND751PM Smoke X XX X
MOUNTING Testing.
Detector on 50 or 60mm Junction Box: 8. Notify the proper authorities the system is back in operation.
Address setting instructions: The address of the detector is set The end number of the The producing The week of
by the CP900M handheld address programmer manufactured by Alignment when the detector producing year month the month
Xi’an System Sensor Electronics Ltd. Note: Please dispose electronic waste following national or
mounted onto the base
Steps of operation: local regulations after being scrapped or replaced. Do LIMITATIONS OF FIRE ALARM SYSTEMS
1. Plug the detector into the detector base that comes with not discard.
This smoke detector is designed to activate and initiate
the address programmer; emergency action. It will not work without power and it has
2. Set the address on the address programmer; its limitations. It also can not last forever.
For example, set the product address as 001 by pressing on
buttons 0 0 1 W respectively and wait for 2 seconds. Once the THREE-YEAR LIMITED WARRANTY
address programmer displays back to 000, the address setting is Notifier warrants its enclosed smoke detector to be free from
completed successfully. The addressable range of the detector is defects in materials and workmanship under normal use and
from 000 to 199. Please select the appropriate address code service for a period of three years from date of manufacture. The
according to the limited address range of the controller. company’s obligation of this Warranty shall be limited to the
3. Read the set address of a product by pressing R key on the repair or replacement of any art of the smoke detector which is
programmer. found to be defective in materials or workmanship under normal
4. More detailed instructions, please refer to the product A5665‐106 use and Service during the three year period commencing with
manual of CP900M address programmer. the date of manufacture.
3 I56-1992-002 4 I56-1992-002
Ver. E