We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 20
FAULTS
Faults cause the operation of a power system may to depart from normal, giving
rise to abnomual conditions such as excessive curreats and voltages at certain
points on the system. Thes are usually guarded against with various types of
protective equipment.
Types of Faults
Faults in 3-phase power systems are mainly classified into two types. namely
open-circuit and stort civeult faults which can be symmetrical or
- unsymmetrical faults.Open circuit faults are also called as series faults, These are unsymmetrical or unbalanced
types of faults except three phase open circuit fault.
The most common causes of open circuit faults include joint failures of cables and
overhead lines, and failure of one or more phases of circuit breaker and also due to
melting of a fuse or conductor in one or mote phases.
The figure below illustrates open circuit faults.
a) Single-phase open-cet b) Two-phase open-cet
¢) Three-phase open-cetE.iieets of apem chrewit ‘salt
- Abnonmal operation of system,
~ Danger to the personnel,
+ Voliages beyoud normal values in certain parts of the network, which further leads to
insulation failures and shon circuit faults.
Although open circuit faults can be tolerated for longer periods than short circuit
faults, they must be removed as soon as possible to reduce the greater damage.A short circuit can be defined a an abnormal connection of very low impedance between
two points of different potentials, whether made intentionally of accidentally.
These ave the most common and severe kind of faults, resulting in the Now of sbeormal
high currents through equipment or traasmission lines.
If these faults persist, even for a short period, it cau lead 10 extensive damage to the
equipment,
Short circuit faults are also called shunt faults.
r =:
a) Single-phase to earth b) Phase-to-phace ¢)Double-phase to earth
{ Ee
d) 3-phase clear of eath J.
¢) 3ephase to earth aWy be due to intemal or external effects Internal effects include beesktows of
transinission lines c¢ equipment, aging insulation, deterioration of insulatiow in gecerstor.
tionaformer swt other electrical eqvipineut, ianproper i
Eternal effects sich
ailstions and sardequate design
overlords
nautstion failure dye to Lightainz svrges end
mechanical damage by public
Effects of short ciremit (9
HArcing faults can lead to fire and explosion in equipment 2
civcuit breakers
93 teantformers sad
2) Abnovmal curtents ease equipment to overheat, which fends to the reduction of Ife
pra of th tion
nO,
¢ voltages of the system ean go heloss oF above their rated valves jeoprnhiriig
the service rentered by the power syste:
4) Power How is severely restricted or even.
npletely Blocked 9s tous
foult persistsFAULT STUDY
A fault study includes:
L
Determination of the maximura and minimum three-phase short-circuit currents
Determination of unsymmetrical fault currents, as in single line-to-ground,
double fine-to-ground,linetoline, and open-circuit faults,
Determination of the ratings of required circuit breakers
Investigation of schemes of protective relaying
Determination of voltace levels at stratezic points during a foultSYMMETRICAL FAULT ANALYSIS
Abwonmalsystenn behaviour under conditions of syurunetsical short-circuit
(synnetsical three phase foul) ern emnee
+ insulation fsilore of equipment or
+ Alashover of lin
tinted by a lightoing stroke of
+ accident fulty operation
The systeun mat be protected against flow of leavy short-cizeuit everentetwhich exa
eau
ce permanent damage to major equipment by dissonseeting the faulry pan ef the
vstein by the use of cirvit breakers epersted by protective relaying.
Fer proper chsice ofeireult breaters andprotcenve relen ing. the w.agniruse of
correats that would flow vader short circuit conditions must be estimatedMost system faults are aot 3-phase faults but fruits eavolving one line ts groend
of occasionally two lines 10 ground These are unsymmetrice! faults requiring
special analysis tools like symmetncal components Symmetcal fault analysis i
simpler to carry out
Though the symmetrical fauits are rare, they generally lead to most severe fault
current and so symmetncal fault analysis must be carned out
A power network comprises syochronous generators, transformess, lines and
loads. Though operating conditions at the time of fault are important, the loads
can be neglected during fault, as voltages dip so Sow that curreats drawa by loads
can be neglected in comparison to fault currents.A power network comprises generators, transformers, lines and losds. Though
operating conditions at the time of fault ere important, the loads can be neglected
1p so low that currents drawn by loads are very low in
during fault, as voltages
comparison to fault currents.
Generation
Transmissionfre. The following reactance iatenar ef'a
Unter tenty
te, short elsvit eondioas, the aemture sesctica ef
themtor proces a eesargnetits
circuit, eau be ifentified
ith the induced ext
Center
(eneymuemeremirece Cyiggrensuenarenl tere Glaeoeseuntrateny
dayorsaasors— “Wimsmpestsesent OSE IEE ayes
f.93
aeConsider now the sudden short ciuit (ree-phase) of a syochrosces
‘generator initially operating under open cicuit conditions. The machine
eee eee ee ee
rca oal eee mee eaImmediately in the event of a short cireuit, the symmetrical short
Cizcuit current is limited only by the leakage redctance of the machine. Since the
air gap flux cannot change instantazecusly (theorem of constant fizz linkages),
to counter the demagnetization of the acaature short circuit cement, camects
appear in the field winding 2s well as in the damper winding in a direction to
help the main flux. These currents decay in 2ccozdance with the winding time
constants.
The time constant of the damper winding which hes low leakage
inductance is much less than that of the field winding, which bas high lexkage
inductance, Thus during the initial Lew of the short circuit, ne Comper and field
their rcectances =X, sar eee ingamllel with 3 (Fie. 938)
Uely tum ratio is 5 memes here.
Fe 04 tikgmess ore re ory
Seraetrest? ex ont‘The reactance presented by the machine in the initial period of the short circuit,
X} is the Subiransleénf reactance of the machine Le.
1
1X) +UX,,)
Xp= X+
fia a TF
(9.5)
‘The reactance clfective after the damper winding currents have died out is
Xy= Xp + (X,0X) (9.6)
X", is the transient reactance of the machine.
Of course, the reactance under steady conditions is the synchronous reactance
of the machine. Obviously X"}< X}< X,
The machine thus offers a time-varying reactance which changes from X"4 to XY
and finally to Xy.The envelope of the current wave shape is plotted in Fig. 9.4b.
iepotated
Gurvemtenvelopt sea syatate
current
ig 7
Fig. 9.4(0) Envelope of syncmioncus machine symmetneal shew excust extent
If the transient envelope is extrapolated backwards in time, the difference
between the transient and subtransient cnvelopes is the cument Qe" (c1
sponding to the damper winding current) which decays fast according to the
ce
damper winding time constant. Similarly, the difference Ai’ between the st steady
state and transient envelopes decays in accordance with the field time constant,
SSEIf the transient envelope is extrapolated backwards in time, the difference
between the trunsicnt and sublrensient envelopes is the current Av" (cont-
sponding to the damper winding current) which decays fast according to the
damper winding time constant. Similarly, the difference Ai’ between the steady
skate and transient envelopes decays in accordance with the field time constant.
state current (ims)
4 Current (rms) excluding DC compenect
ta) insient current (rms) excluding DC cemperect
X= ditect auis synchronous reactPig, 9.4 (2) Spprmenicat thon eeu ermotine tuirend in eyreivencnn mnehie
In terms of the oscillogram,
the currents and reactonoes:
ar where
we Sas (9.72) ‘= sesdy state carret (pms)
te ‘Pi = transient curreat (rms) excioding DC compecest
Wie a (9.7) "i= sabtransieat coment (ra) exclading DC curmpeneat
\c X,-2 direct ats synchyoncus ractusce
a SE ew coker
We yay O70X)= direct axis transient reactance
X'/= direct avis subtransient reactance
11 = per phase no load voltage (rms)
0a,0b,Oc = intercepts shown in Figs. 9.4a and b.
‘The intercept Ob for finding transient reactance can be determined
accurately by means of a logarithmic plot. Both di’ and Ar’ decay
exponentially as
Ai = Ail} exp (- ry.)
Ai’ = Aig exp (- 7)
where 7, and 7 are respectively damper, and field winding time constants with
Tuy <1 Altime ty». 7,,, di” practically dies out and we can write
log (A+, n= log At = = AigExample 9.2
A 25 MVA, Il kV generator with X} = 20% is connected through 2
transformer, line and a ensformer to a bus that supplies three identical motors
as shown in Fig. 9.8 Each motor has Xj = 25% and Xj, = 30% on a base of
5 MVA, 6.6 kV. The three-phase rating of the step-up transformer is 25 MVA,
11/66 kV with a leakage reactance of 10% 2nd that of the step-dows
transformer is 25 MVA, 66/6.6 KV with a leakage reactance of 10%. The 625
voltage at the motors is 6.6 kV when 2 three-phase fault cecurs at the point F.
For the specified fault, calculate
(a) the subtransient current in the fault,
(b) the subtransient current in the breaker B,
(c) the momentary curtent in breaker 3, and
(d) the current to be interrupted by breaker B ia five cycles.
Given: Reactance of the transmission line = 15% on a base of 25 MVA, 66
kV. Assume that the system is operating on ao load when the (Gul: occurs.
| a3ge 3 oO
io Tee SFP] Comes
11765 V evagay - £0)ion Choose a system base of 25 MVA.
For a generator vollage base of 11 KV, line voltage base is 66 kV and moter
voltage base is 6.6 kV. eae
(a) For cach motor y cae pe
Line, transformers and generator rezctances are already given on proper base
values.
The circuit model of the system for fault calculations is given in Fig. 9.93.
‘The system being initially on no load, the generator and motor induced emfs are
identical. The circuit can thezefore be reduced to that of Fig. 9.9b and then to
Fig. 9.9c. Now
1
Ise = 3x = j4.22 pu
jl25 > 0.55
Base current in 6.6 KV circuit =
Ise = 4.22 x 2,187 = 9,229 AIs¢(Circuit breaker)
(c)
(3)
Fig. 9.9
(b) From Fig. 9.9c, current through circuit breaker B is
1 I 5
Isc(B) = 2% —— + —— = -j3.42
sc(B) = 2x E+ sg I
= 3.42 x 2,187 = 7,479.5 A