R-806-Fapa Boq SBV1
R-806-Fapa Boq SBV1
SITC of fire alarm control panels generally conforming to the intents of Supply, installation
1.1
and testing of:-
6 Loop fire panel expandable up to 8 loop Each 1 EATON-COOPER ULCF30004G+DF61NETKIT+EFVCC5 259,500.00 259,500.00
Supply, installation and testing & comminssioning of Repeater Panel with 600 character Each 1 EATON-COOPER ULCF3000PRG+DF61NETKIT 58,600.00 58,600.00
backlit Liquid Crystal Display. The LCD shall Display all events / detectors, devices status
1.1.2 of complete systems and and provide remote reset, acknowledge, drill and silence of the
control panel from remote locations.
Field Devices: The fied devices shall be user friendly to configure. The devices shall not
require any special tool/programmer/software to set address to each devices to avoid
dependency on specific system integrator/OEM.
Supply installation and testing of signal loop components in a suitable galvanised steel
1.1.3
junction box.
1.1.3.1 Monitor Modules (UL Listed and FM Approved.) Each 129.00 EATON-COOPER ULMCIM 1,510.00 194,790.00
1.1.3.2 Control Modules (UL Listed and FM Approved.) Each 130.00 EATON-COOPER ULMCOM 1,810.00 235,300.00
1.1.3.3 Control Relay Module (UL Listed and FM Approved.) Each 48.00 EATON-COOPER ULMCOM 1,810.00 86,880.00
Fault Isolator Module (Note : If these modules form part of the detector base, separate Each INBUILT IN EACH
1.1.3.4 48.00
rates need not be quoted.) (UL Listed and FM Approved.) DEVICE
Hooters (with minimum 85db sound level) with required necessary cabling from power Each EATON-COOPER 351,000.00
supply unit. Note that above shall include necessary accessories required for Hooters to
1.1.3.5 give sound on same & immediate alternate floor when detector/MCP activated on that 78.00 ELHNR+ULMCOM-S 4,500.00
floor.
Supply, installation and testing of signal initiating devices complete with galvanised steel,
1.1.4 back of signal initiating devices com-box, detector base, detector etc.complete as
specified.
1.1.4.1 Microprocessor based Addressable intelligent Multicriteria detector Each 12.00 EATON-COOPER ULCAPT340+UCAB300 2,110.00 25,320.00
1.1.4.2 Microprocessor based Addressable intelligent smoke detectors Each 189.00 EATON-COOPER ULCAP320+UCAB300 1,810.00 342,090.00
1.1.4.3 Microprocessor based Addressable intelligent Heat detectors Each 5.00 EATON-COOPER ULCAH330+UCAB300 1,800.00 9,000.00
SITC Point Wiring for Cable for Hooter In Lobby - 2C X 1.5 sq. mm. Armoured FRLS, Points
1.1.4.4 Copper Cable From Power Supply Units to Control Module and Control Module to 78.00
Hooter.
LPG detector for kitchen area. It should be capable of giving potential free contacts for Nos
1.1.4.5 QRO
integration with Main FACP.
Power Supply Unit for Gas Leak Detector with suitable enclosure with required Nos
1.1.4.6 QRO
accessories
Cable for GLD in Kitchen - 2C X 1.0 sq. mm. Flexible FR Cable From Moniter Module to Points
1.1.4.7 QRO
GLD
Cable for GLD in Kitchen - 2C X 1.0 sq. mm. Flexible FR Cable From Power Supply Units Points
1.1.4.8 QRO
to GLD
Supply, installation and testing & comminssioning of Intelligent Addressable Indoor Nos. EATON-COOPER
Application Manual Pull Stations / Manual Call Points suitable for wall/column complete
1.1.5 with Metal boxes Junction Box with Knock out as per matching diameter of glands for 78.00 SG42BK2+ULMCIM-C 5,252.00 409,656.00
mouting on Surface Floor, Cable lugs at Ends, cable compression SS glands, cable tags
and Ferruling.
MAKE MODEL NO TOTAL
Sr. No. PARTICUALRS UNIT QTY RATE
AMOUNT
Supply, installation and testing & comminssioning of 24V DC power supply unit for hooter LOT
cum strobes. The unit shall have in built battery charger & sufficient back of 24 hours in
1.1.6 standby & 30 mins in alarm condition with suitable enclosure with required accessories 10.00 -
Supply, installation and testing & comminssioning of Fire fighter's telephone jack with Nos. EATON-COOPER
1.1.7 53.00 CFVCRJP+ULMCIM 4,100.00 217,300.00
suitable interface module complete with required mountings.
Supply, installation and testing & comminssioning of portable type fireman telephone Nos. EATON-COOPER
1.1.8 2.00 CFVCRHS 2,500.00 5,000.00
handsets.
Supply, installation and testing & comminssioning of a Auto dialer to signal pre-recorded Nos.
1.1.9 text messages (fault etc) for different messages (fault etc) for different events to atleast 1.00 -
six telephone mobile numbers for the Fire Alarm conditions.
SITC Point Wiring for fire men telephone jack, consisting of exposed 2C X 1.5 Sq.mm.
1.1.10 PVC Cu. ARMOURED WITH 2 HRS FIRE RATED CABLE on surface / Shaft as per Points 53.00
required. Rates shall be inclusive of cable terminations.
Points wiring for signal initiating devices, control, monitor, & fault isolator (From connector
box) consisting of minimum GI JB's, pull boxes etc. using 2C X 1.5 SQ.MM FRLS
armoured, Copper cable ATC CONDUCTOR STRANDED, PVC INSULATED TO FORM
1.1.11 A CORE, CORES LAID UP, OVERALL SHIELDED WITH ALU-MYLAR TAPE WITH Points 355.00
TINNED COPPER DRAIN WIRE OF SIZE 0.5SQMM (COLOUR: RED). Rates shall be
inclusive of cable terminations.
NOTE:
1) Where control & other elements form part of the detector base, separate points
shall not be measured. Cabling /point wiring work shall be inclusive of cable
terminations on both ends.
Submains Wiring Detector and other modules (from panel to 1st detector, last detector to Mtr
1.1.11.1 panel, Quantity mentioned is indicative and shall be as per approved shop drgs. and 1,500.00
cable route on site)
Supply & Installation of 4 PAIR UNSHIELDED TWISTED PAIR (UTP) CAT-6 Mtr
1.1.12 QRO
UNARMOURED CABLES with all accessories as required.
Supply and fixing of 20/25/32mm dia. 2mm thick G.I. conduit of following sizes including Mtr
1.1.13 cost of junction boxes, bends, elbows, sockets, tees etc. laying in slab, cutting chasis and QRO
making good or surface mounted including all fixing hardware.
Fire Alarm Operator Workstation to be provided with Windows compatible licenced Nos.
1.1.14 1.00 EATON EFGVS1-2 178,000.00 178,000.00
software etc. for Graphics User Interface. Computer & Monitor shall be provided.
SITC of On-Off push button set with enclosure on each floor for operation of booster Nos.
Pumps on Terrace floor, Fire Hydrant pump, Fire Sprinkler pump, Fire jockey pumps
1.1.15 located at UG tank , inclusive of necessary accessories like Back Box, glass front door, 1.00
Face Plate.etc.
SITC Point Wiring for push button, consisting of 2C X 2.5 sq. mm. FRLS wires including Nos.
1.1.16 MMS PVC concealed conduits of required size, accessories likes bends, JB etc. with 1.00
necessary civil work such as chasing in wall & finishing complete in all respect.
Supply, installation and testing & comminssioning of 10Watt wall mount speaker with ABS
2.1 Nos. QRO
body. Speaker shall min. 10W/5W tappings.
Supply, installation and testing & comminssioning of 15W horn type speaker with max
2.2 SPL1M/1W 106dB . Frequency response of 350Hz-15KHz. The speaker shoud have Nos. 7
tappings at 15W/7.5W
Supply, installation and testing & comminssioning of 6W Wall mount, Box type Speaker.
2.4 Nos. 11
Speaker shall min. 6W/3W/1.5W tappings.
Supply, installation and testing & comminssioning of set of multiple 48 zone IP based Lot 1
Digital Voice Alarm controllers suitable for 50 zones requirement. The voice alarm
controller should be able to connect directly over Ethernet without any additional
hardware or convertor. Master - Slave configuration is not allowed. It should have
functions like the audio playing, zone control, fault monitoring, log recording, volume
control and amplifier switchover. The voice alarm controller shall be truly IP based & do
not require any server interface for system operation. The Voice alarm controller should
also have the following functions:
2.6 . 255 Priorities -
. Time schedule broadcasts
. Capable of amplifier redundancy
. 8 trigger inputs/outputs
. EN54-16 Compliant
Note: Contractor shall furnish the qty & unit rate of controller as per OEM
recomended configuration.
Supply, installation and testing & comminssioning of Single channel class D 480W Power LOT 3
Amplifier for parking area & banquet area speakers
2.7 Note: Contractor shall furnish the qty & unit rate of each type of amplifier as per -
OEM recomended configuration.
Supply, installation and testing & comminssioning of Single channel 240W Class D LOT 2
2.8 Power Amplifier for parking area speakers
Note: Contractor shall furnish the qty & unit rate of each type of amplifier.
Supply, Installation, testing & Commissioning of IP based Networkable Touch screen 50 Lot
zone call station for selection of zones, supervision of system status, setting of
scheduled broadcasts. The call station shall be truly IP based & do not require any server
interface for system operation with the following functions:
2.9 . Built-in monitoring loudspeaker 1 -
. Detachable goose-neck microphone
. LCD touchscreen display
. Audio input
Supply installation,Testing & Commisioning of minimum 32U PA rack suitable for above Lot
2.10 power amplifiers & controllers with inspection door, exhaust fans on top & suitable 1 -
extension board with 230VAC 6A power sockets.
Submains wiring for PA system speakers consisting of 25mm dia 1.8mm thick GI conduit
2.11.1 & JB's, pull boxes wherever required etc.using 2C X 1.5 sq.mm FRLS armoured, Copper Mtr 1500
cable, including cable terminations at both ends as required.
SITC Points wiring for speakers & volume control and Relays consisting of GI 25mm dia
2.11.2 1.8mm thick GI conduit & JB's, pull boxes wherever required etc.using 2C X 1.5 sq.mm Points 187
FRLS armoured, Copper cable, including cable terminations at both ends as required.
MAKE MODEL NO TOTAL
Sr. No. PARTICUALRS UNIT QTY RATE
AMOUNT
SITC of Perforated type GI. cable trays of 50 mm in Height & 2mm thick with necessory
2.12
supporting frame etc. as 'specified & as shown on drawings.
Supply & installation of 32mm dia HMS PVC conduits with junction boxes, reducer etc.
2.12.4 mtr 100 -
complete concealed/surface mounting as required.