Form DETC DTW ODS 1ZUA4643-202r4
Form DETC DTW ODS 1ZUA4643-202r4
Transformer data
Please provide the following transformer data as it pertains to the application of the DTW™ de-energized tap changer.
Is additional documentation being included with this form? e.g. nameplate, wiring, etc. Yes No
Between phases = kV BIL If less than 5 positions, please select the contact locations.
With appropriate shielding, the maximum suggested BIL is 1050 kV
A B C D E F
Between adjacent contacts = kV BIL
The maximum suggested voltage is 75 kV and 180 kV BIL. If application requires
B
greater than 180 kV BIL, please refer to the Technical Guide (1ZUA4643-211) or contact C
Hitachi ABB Power Grids. A
Per deck = A
Nominal current rating is 845 A. The maximum continuous overload rating is 1014 A at 15° rise
F
D
Decks per phase
E
Please select one of the following options:
01 View from tank wall
Single
Operation side
Double
Please select one of the following options:
Refer to Figure 03.
Shielding
Please select one of the following options: Left hand
For more information, please contact your Hitachi
Right hand
ABB Power Grids representative.
English
Spanish
French
B1upper =
Handle drive rotation
By default, the handle rotation to change the tap from position 1 to B2lower =
position 2 is clockwise (CW). Unless otherwise specified, Hitachi
B2upper =
ABB Power Grids will select the rotation best suited for the
Minimum allowable B1 or B2 dimension is 22.64 inches (575 mm)
application
C=
No preference (Standard)
C2 =
Clockwise “CW”
The C2 dimension is only required if handle is not at Position 1 or 4
Counterclockwise “CCW” For the ABB boss, please provide L dimension in 0.25 inch (6 mm) increments
Clockwise “CW”
Operation mechanism orientation
Counterclockwise “CCW” These diagrams indicate potential locations for handle drives.
Locations 1 and 4 represent the locations of the decks as well.
Please select the desired location of the handle. Additional notes
B
C may be provided in the Comments section.
A Refer to Figures 04 and 05.
F
D
E
E
D
F
A
C
B
02 View from tank wall
Upper: Clockwise rotation shown in Position 1
Lower: Counterclockwise rotation shown in Position 1
Upper deck
Lower deck
TK A
C
B2
B1
A
C2
L
03 DTW mechanism as mounted within a transformer
3
7 4 8
5 1 6 5 1 6
2 2
04 Single deck operation mechanism configuration 05 Double deck operation mechanism configuration
7.7.2021
Hitachi ABB Power Grids We reserve the right to make technical changes We reserve all rights in this document and in ABB is a registered trademark of ABB
Alamo, Tennessee 38001, USA or modify the contents of this document with- the subject matter and illustrations contained Asea Brown Boveri Ltd. Manufactured
out prior notice. With regard to purchase or- therein. Any reproduction, disclosure to third by/for a Hitachi Power Grids company.
ders, the agreed particulars shall prevail. ABB parties or utilization of its contents – in whole or
1ZUA4643-202 r 4