NEAM - CC 1 2009 Contains 2012 Errata WATERMARKED - Electric Power Connection For Substation
NEAM - CC 1 2009 Contains 2012 Errata WATERMARKED - Electric Power Connection For Substation
ANSINEMA CC 1-2009
Published by:
National B e d r i d Manufacturers-ciation
1300 North 17th Street
Rmslyn, Virginia 22209
Q Copyright 2009 by the National Eledrical ManuWum Assodation. All rights inchding translation into
other languages, r e s m d under the Uniwrsal CopyrigM Comntion, the Berne Conwntion for the
Protection of Literary and Artistic Worb, and the Internationaland PanAmericern Copyright Cmntions.
CC 1-2009
Page ii
(In f o mtional) B dt Hole Spacings and Pad Dimnsians for Other mu n t h r ........... .50
(Infomrsrtbmal) C a m o n Types of S u W t b n Connectors........................................ 52
Tables
Figutes
The purpose of this publicationis to p d d e standard test methods and performance rqui~merrts
fnr the
electrical and mechanical characteristics of connectors under normal operating conditions.
User needs in the daopment of this Standards Publication ha* been recognized through the normal
marketing determination of customer acceptance done by indiudual NEMA members, and through the
procedures inherent in its ap-l as an American National Standard.
The ElectricalConnector Section of NEMA, in its constmt d e w of the publication, conlinues to s e k out
the uews of responsible users, which will contribute to the dewloprnent of better standards.
These standards are periodicalty d e w d by the Electrical Connector Section for any d s i o n s
necessary to k e q them up to date with admncingtechnology. Proposed or recommended h s i o n s are
wlcorne and should be submitted to:
Vice President,Tec hniml SeAces
National Electrical Manufacturers Association
1300 North 17th Street
t~ectricalConnecror
-
Section of the National Electrirl ManufacturersAssociation. At the time it was approwd, r!ectrical
Name of Remntatlw:
Carl Wentzel
ACA Conductor Acoessories Gary Harter
Connector ManufacturingCompany Greg
Nienaber
ERICO, Inc. Mike
Gassman
FCI Bumdy Ronald Lai
Galvan Industries, Inc. Roger
Montambo
Hubbell P w r System, Inc. Jason
Bundren
ILSCO Corporation Carl Taylor
lmplo Technologies Inc. Genti Goja
Panduit Corporation Joe Chopp
Section I
GENERAL
1.1 SCOPE
This standard coers uninsulated connectors and bus supports that are made of metal and intended for
use with conductors or bus made of copper or aluminum alloy and hund in substations. Connectors that
are supplied in equipment are cowred by the equipment standards and are excluded from this standard.
The bllowing publidions are adopted in part, by reference in this publication, and are amilable from the
organizations helm
1.3 DEFINITIONS
bolbd-lype comector: A connector in which the contact betwen the conductor and the connector is
made by pressure exerted by one or more clamping tmlts.
bus awpport: A metal member, usually mounted on an insulator, which supports a bus conductor.
conductor: A carrier of electric current that is constwcted from conducti~gmaterial.
connector: A d d c e t h t joins two or more cmdudnrs for the purpose of w d i q a contiruous electrical
path.
HV (high vokage): A class of nominal svstem mltaaes equal to or greater than 100 kV and>eaual to or
less than 230 kV.
stud term lnal connector: A te'rminal connector that joins a conductor to the round terminal sfud of
electrical appamtus.
tang: That podion of a connector that is wed to fasten a connector to a terminal pad.
b r m i m l mnector: A co-r thatjoim a conductwto a lead, termind pad (solid or laminated block),
or round terminal stud of electrical apparatus.
brminal pad: The flat conductiq part of a d d c e to which a terminal connector is fastened.
UHV ( u l m h u h vokqe): A class of nominal system wltages equal to or greater than 1000 kilowlts.
welcLtype connector: A con- in which the contact betwen the conductor and the comector is made
by wlding.
Section 2
PERFORMANCE REQUIREMENTS
2.1.2 The cumnt rating ofthe connector may be based upon either the conductor sizes from tables
B-1 or B-2 or the cumnt rating of the equipment to which the connector is attached if it is specifically
designed to connect to one piece or type of equipment.
2.2.2 The current rating ofthe connector may be based upon either the conductor sizes from tables
B-3 or B-4 or the current rating of the equipment to which the connector is attached, if it is specifically
designed to connect to one piece or type of equipment.
2.3 CONNECTORCLASSES
Connector Classez-The connector class is based upon the operating voltage as follows:
2.3.1 HV (high v o l t a g e b q u a l to or greater than 100 kV and equal to or less than 230 kV.
2.3.2 EHV (extra high voltage)-greater than 230 kV but less than 1000 kl
Table 2-1
MINIMUM PHASE SPACINGS AND GROUND CLEARANCES
Nomlnal
Opemtlng Phase Spadng Motance from
Voltage mound Plane
kV m (ft) m (ft)
230 3.4 (11) 4.8 (1 5)
345 4.9 (16) 7.6 (25)
500 7.6 (25) 9.1 (30)
765 13.7 (45) 13.7 (45)
1100" 16.8 (55) 16.8 (55)
"1100 Wspaang and heightwre b m d uponwrkperformed forthemHz Mill, PA Teat Stahon.
2.5 FREQUENCY
The frequency of the power conn&ors cmred by this publication shall be 50 or 60 M z . -4
TEMPERATURERISE(SE
1
2.6.1
.6
Temperature Rlse of the Conn or
The temperature cise of an e l W c p m r wnne
the conductor wilh which it is intended to be used. lhe temperatm rise of an e l a c m r connedor that
connects conductorsof th ur ductor
highest temperature ri
Table 2-3
MINIMUM CONNECTOR PULLOUT STRENGTH
(Metric Cable Sizes)
Pullout Slmnuth
Table 2 4
MINIMUM CANTILEVER STRENGTH OF BUS SUPPOKE
Bronze Alumlnum
N (Ibf) N Ilbf)
2224 (500) 8896 (2000)
2.9
---
TORQUE STRENGTH OF BOLTED CONNECTORS
The connector shall withstand, without damage, a torque d u e 50% abow the appropriate torque values
gien in Table 4 4 , Nominal Torque Vdues. Damage is
naked eye.
The wlded connections shall haw an electrical conductility equal to or greater than the original bus.
The recommended wlding methods are tuwsten inert gas (llG) or metallic inert gas (MIG).
Section 3
TEST METHODS
3.132.3 'T'Connectas
The test current shall be based upon:
a. The smallest conductor grooe, and
b. The highest ampacity conductor accommodated in that gmoe
LOCATlON OF mERMOCOUPLES
(CENTER-TOP SURFACE)
H
LENGTH OF
FREE BRAID
The highest temperatue s hdl be recordedand compared to the requirements giwn in 2.5.
c. All of the temperature measurements shdl be awraged to obtain the awrage temperature
rise of the expansion connector.
a. Determine the conductorwltage gradient by usirg the corona-extinction test wltage and
the test condition in the formulae in Figures 3-2 and 3-3.
b. Determine the line-to-ground wltage at which the connector will operate by using the
wltage gradient determined in item 1 and the actual "operating rating" conditions in the
formulae in Figures 3-4 and 3-5.
Where:
GROUND PLANE
Figure 3-2
CONDUCTOR VOLTAGE GRADIENT
FOR SINGLE CONDUCTOR
GROUND PLANE
Figure 3 3
CONDUCTOR VOLTAGE GRADIENT FOR BUNDLED CONDUCTOR
i
GROUND PLANE
Figure 3 4
LINE TO GROUND VOLTAGE FOR SINGLE CONDUCTOR (THREE PHASE)
3.3.41 ANNEX A, Methods of Measurement of Radio Influence Voltage (RN) of High Voltage
Apparatus
3.3.42 IEC 61284 Overhead Lines-Requirements and tests for fittings, Section 15 Corona and radio
interference wltage (RIV) tests
RIV measurements may be omitted if the test set-up a l l m completeUsual obsenration and all sources of
corona ha= been identified.
3.4 CANTILEVERSTRENGTHOFBUSSUPPORTS
The cantilewr strmgth shall be determinedby apmng a load t r a n m e lo the c o r n o r lo~gihrdnalaxis.
The bus supportshal k bolted iu a flat suribce, using the hardware recommended by the manufactu~r.
3.5 TORQUE STRPlGTH TEST OF BOLTED-TYPE CONNECTORS
The conducto~s)shall be assembled in the con- and the bolts tightened unibrmly and alternately in
11.3 FCm (100 Ib-in.) increments until 50% m r the nominal toque a u e is achie& (see 4.6).
Section 4
DESIGN REQUIREMENTS
BOLT HOLES FOR TERMINAL CONNECTORS WTH SINGLE TANGS OR MULTIPLE FLAT
BAR TANGS
4.3.1 The dimensions and the arrangement of bolt holes in the tangs of power connectors used in
North America shall be as shown in Annex C, Figures C-I to C6. Figures C-7 to C-9 show the typical
spacing for multiple flat bar tangs.
4.32 Metric terminal pad spacing and sizes used in some countries other than the U.S. are gien for
information in Annex D.
Figure 4-1
U-BOLT TYPE CONNECTOR
Figure 4-2
SHACKLE TYPE CONNECTOR
a. Terminal lugs shal h m a minimm of four bolts or the equivalent for a single conductor.
b. Stud connectors shal ha\^ a minimum of four bolts or the equimlerrt for the stud portion.
Ta ble 4-2
CONNECTOR CLAMPING BOLTS
U.S. STANDARD CONDUCTORS AND HARDWARE
Table 4 4
CONNECTOR CLAMPING BOLTS
IS0 STANDARD CONDUCTORS AND HARDWARE
Table 4 4
NOMINAL TORQUE VALUES
NOTES
LA = LubriFated-Aluminum
SB = Slllcon bronze or steel
See 4.5 for amngement and Ares of boltsfor termlnal connectors.
' For e r e n c e onlv
4.4.3 ExamplesIIIustratin
4.4.&1 Example1
A straight coupler connectw or a Sodegree (1-57 radian) elbow connector is used to connect a conducfw
of 1W in. copper pipe to another conductor of 1% in. copper pipe. After locating the proper line for the t%
in. copper pipe in the first column of the table, the total number of bolts required can be determined from
the following information giwn for the connectors.
AXB=C
4x2= 8
Where:
A = W in. diameter bolts per condu-r
B = Number of conductors
C = Number of 'A in. diameter M t s per littin9
Table 4 6
EXAMPLE 1
3 I 2 I 6 I Minimum
Bolt Size is 1/2 in.
44.12 Example 2
A single size T cannector is used to connect a 3-inch Schedub 40 aluminum main tu a 397.5 kcmil ASCR
(201 mm2)tap (outside diameter = 0.743 in., 18.87 mm).
After locating the propr line fpr the 3inch pipe in the first column of the table, it can be seen that the
connectors require bur 518 in. diameter bolts per conductor (see columns 13 and 14 of Table 4-2).
After locatitg the proper line for the0.743inh oukide dimeter ACSR tap inthe ttird column ofthe table, it
can be seen that the connectors requirefour % inch diamter bolk per conductor (see columns 13 and 14
of Table 4-2).
In this case and inacclordancewith 4.4.3.1, the rnanufiictu~rhas the choice of using either four X-inch
diameter bolts per conductor or bur e inch diameter M s per conductor.
44.13 Example3
A copper stud connector hAng a Ic inch - 12 thead is came- to a copper cable wnging in size from
400 to 800 kcml(203 to 405 mm2). This connector is considered a range taking connector. U s i q the
fourth column for the stud and the second colunn for the copper cable, it can be seen that the connectors
requite the following bolts:
a. Four ci-inch diameter bolts per conductor for the 1c-inch stud, range-taking column.
b. Four 2-inch diameter bolts per conductor for the cable (based on largest bolts required for
the range, cowrs both 310 AWG thru 500 and 550 thru 300 kcmil cable).
In this caseand inaccordance with 4.4.3.1, the manufacturer has the choice of using either four d-inch
diameter bolts per conductor or four % in. diameter bolts per conductor
47 TERMINAL CONNECTORS
On Oket Pad connedors there shall be a mininum dearance of3.18 mm (c inch) M w m any part of the
clamp or hardware and the contact surface of the pad. (See Figures C11 AND C12)
The size of flat (plain) washers shall hin accordance with Table G4.
Section 5
RECOMMENDATION FOR MAKING CONNECTIONS
The conmcbr and conductor surfaces should be ugorously cleaned with a wire brush or emery cloth. A
shiny, brigti surhoe is needed. A contad compound shorld be appCed imnediatelyfpllowing the cleaning
of the sumce.
Some connectors am plated with other metals. The surfaces of these connectolg should not be abraded
since this may remow a portion of the plating. They may be cleaned with a compatible solwnt, if
necessary.
Since it is the aluminum (anode) that corrodes in a cow-al~minum eledmlytic cell, aluminum cable and
tubing should not be used with unplatedcopper alloy connecbors. The m e ,h o w ~ r(copper
, wnbdor
and aluminum connector) is functionally acceptable p d d e d the aluminum connector is "massiw" in
comparisonto the copper cmducbr (i.e., the aluninum connector shall be s i d to handle the hll current
ratitw of the c o . , ~ conductorl.
m
In the case of an underhunrcopper switch pad, it is recommended that a copper bar extension Rrst be
W e d dlrectlyto the pad. This can be foilowed by direclly bokiog a massie aluminum connector property
Arebrushed and an appropriatejoint compound applied to the upper sudace of the bar extension. This
installation procedure m i d 8 the positioning of the aluminum terminal beneath the copper switch pad.
Another comnon aluminumbcopper oonnecb is an aluminum con&ctor janed b a copper sW. Such a
connectim can be madesalisfactuiiy by dire* joiring a massk aluminun connector, wire-brushed and
an appropriate joint compound applied to the copper stud.
53 SILVER-PLATEDALUMINUMCONNECTORS
Sikr-plated aluminum conmcbrs should not be used on unplated alunSnum bus.
54 WEDED CONNECTIONS
It is recommended that a wlder qualified for the material perfnrm the wlding. Prior to wlding, i t is
recommended that a test w l d be made on a typical aluminum casting (see 2.10).
hardwarn is not recomnended in a copper comectin under corrosiw condtions due to the &ct of copper
salts on the underside of the connection.
Section 6
MARKING REQUIREMENTS
The following minimum amount of information shall be gien on all electric power connectors:
a. Manufacturer's designation.
b. Nominalsizeorrangeofsizesoftheconducbrswithwhichtheconnectorisirrtendedto
be used.
6.2 MARKING OF C O N N m R S I E S
The size of an elechic p m connector shall be marked in t e r n of the size, or other sizes of conductors
that the connectoraccommodates. The size ofconductors shall be gien in the following units:
6.2.1 For WIm and Cable Conductom
6.2.1.1 American Wire Gauge ( A m or thousands of circular mils (kunil) . Reference is also made to
the equiwlent metric (rnm2) sizes for AWG or kcmil series conductors.
6 . 2 . Metric or mm2size
6.2.2 ForTubing
6.2.21 Nominal Pipe Size
extra heay (EHPS or SCH 80) sizes, except for expansion or internal connectors. The connector
marked NPS or IPS indicatesthat it is designed to accommodate both SPS (SCH 40) and EHPS (SCH
80). Special marking is required if the connector is limited to SPS (SCH 40) or EHPS (SCH 80) only
Annex A
METHODS OF MEASUREMENT OF RADIO INFLUENCE VOLTAGE (RN)
OF HIGH WLTffiE APPARATUS
TABLE OF CONTENTS
FOREWORD .......................................................................................................... 23
Scope................................................................................................................. 2 4
Sectlon 1 REFERPlCED STANDARDS AND DEFIMllONS .................................................... 2 5
Sectlon 2 GENBAL TEST CONUllONS ................................................................................. 27
SecUon3 IABURATORYANDFACTORYRRITESTS+I.OlS TO 30MEGAHERTZ..................... 31
Section4 FlELDMEASURUllENTSOFW.015TO30 ......................................................... 34
Sectlon 5 HIGH-VDLTEETESTURCUT 001rRONENTS ....................................................... 35
FOREWORD
This standard slpemedes and is an extensiw d s i o n of NEMA Stmdards Publication No. 107-
1- (R 1971,1976, 1981), M 3 f h o d s o f ~ u # m e n tOfRadio Influence Volfage (Rw obH@bW&p
Appa~us.
Users of this NEMA Standards P & l M i n are adusedthat radio influencew l t q e (RRI)
measurements are not meant to be similar to corona measurementsewn though the saurce phenomena
may be the same.
In the preparation of this Standards Publidon, input of users and other int- parties has
been sought and d u a t e d . Inquiries, m e r t s , and prop- or recomnded d s i o n s should be
submitted to the concerned N E W subdiusion by conlactingthe:
This standard c m r s the methods of measurementof radio irrfluenoeunltage inthe frequency rage
of 0.015 to 30 megahertzthat may be associatedwith high-mltw power apparatus used on transmission
and distribution systems at line wltages of 0.6 kibwlts and a b m .
The decisionas bwhether this standard applim b a spedfic test sample may be &mined from
the specifidions w standardswhich apply to the equipmert in question.
The radio influenceWage which is of prindpal comm in ttis standard is t M wltage appeariy at
the terminals of test samples, or on conducbrs of p w r systems, which M s the coordination w n
powr and communicatim drab. bpEable Iowlewl radii irfluenoew l t q e measuredon the termimls of
powr equipment may not alTect the coordination behrreen powr systems and comnunicatim arc~ik,but,
may be of concern inthe Ibof the equipments internal insublion.
Because ofthe lsrge atage range and, consequently, the large chatqe in dimensions of high
M a g e test eqlipment, it is not feasibleto define a sinde stamlard highwltagetest drwit The general fprm
of the test arcuit is defined, and nominal limits are placed on conponerrts of the amit In order that unifprm
and significant radio irAuencew l t q e measurnmenis may be made, it is neoessary t k t ihe test drwib be
accurately calbrakd as desuibed in this standard By mars oft hi dibtabin, the effedsof circlit dements
and stmy circ* consbnts ofthe t ~cimit t a~ t a k n into eonsider;rtion.
Sectlon 1
REFERENCED STANDARDS AND DEFINITIONS
1.1 REFERENCED STANDARDS
ANSlC63.4-1981 AmricanNationalStandard,Methodof~asravementofEmi~sbnsfmm
Low V o h EAecthI
~ andEie&mk Equipment in the Raw of 10kM fu 1
Gm
1I Radio Noiise
Radio naise hAng a spectnrm which is broad comparedwith the nominal bandwidth of the radio-
noise meter.
NEMA Standard 527-1987.
The wltage that appears on the conductors of electric equipmerrt or cirwits, as measuredwith a
standard radianoise meter used as a 2-terminal wltmetw in accordance with the methods desui bed
herein.
NEMA Standard 527-1987.
The ratio of the wltage at the terminals of the radio-noisemeter (Ed to the signal generator
wttage (Ed. Thus, EJE, = P.
NEMA Standard 527-1987.
Tests that can be made in a factory or outdmr area, using a calibrated high-wltagetest circuit,
with the test sanple enerFjzed at its rated test mltage so thd oped- conditions are simulated.
NEMA Standard 527-1987.
Tests which can be made (usually in an outdoor area) on energized w r sysbrn equipmnt or
lines, using a high-wltage coupling capadtor and the c h i b y descrbed herein.
NEMA Standsrd 527-1987.
'J
Tests that aE
enclosure, using a callaraw high-wltage test circuit and a filtered p h r supply, withihe test sample
energized so that
NEMA Standard 5-27-1 987.
1
1
lewl. Test samples shall be pemitw to indude any power system equipment, such as insubto
bushings, t ransformet's, w i t w e a r , conductors, and so forth.
4
The equipment (unit, component assembly or system) which is to be tested to determine the R
Section 2
GENERAL TEST CONDITIONS
TEST AREA
For labomtoy, M o y , or Ield tests,the test area shdl be of a slitable size to maintain adequate ckmnces
so that the electtic Ield arocnd the test sample is not distorted. See F i i 2-1.
NEMASQnctard527-1987.
HIGH-VOLTAGE BUS
TO HIGH-VOLTAGE
TEST TRANSFORMER
t
RADIO FREQUENCY
CHORE
I I
I
t
HIGH-VOLTAGE
CWPUNG CAPACITOR
GROUND PLANE
Figure 21
Setup of High-VoHage RW Test Cimit
It is desirable that the ambient W led at each measlrement frequency be measued fb tehence
puposes at the requred test mttage vAth the test sample d i s m e d . Where an allcwakle RNlimit is specikd in the
a p p l i i speckahon or standad, it is usually desirable that the ambient W le\el be at least 6 decibels belw (one
the specrCed limit.
A u h k e d Ergiwng hbmakn6n-1987.
2.1.4 Ternpedure
TESTSAMPLE S m P
Condttlonina of
-
b t sa
canbeobGn*~1ontkspecinenpiwto~rgmeas~.
1
2.2.3
1 1
Test Srr mple GroudRg
When it is desied to identify the character of the RW, measuremen9should be monitored using
either a headset, IwcCspakr, or asdlloscope. Precalrtions should be herken to dermine whether these
M c e s a w t the radiorwrise meter i n d i d o m during measurements.
Authorized Engimriw lrrfprmationW-1W
R a d i o interference studies ha^ indicated that ~frad~oinfluence wltages are generaled by power
system apparatus, readings can be obtained at 1 megakrk, t k appoximate midpoint of the AM broadcast
band. Because of ths, radio influence t s t s at the singk frequency of 1 megaherlz can be considered to
produce representalk test results. and tests on high-voltage powr system a ~ a r a t u smay tp carried out at
this single frequency. . -
- -
Table 24
MEGAHERTZ
Other hquencies which ate not listed for measurement in Table 2-1 can be scmned whle
monitoring wilh a headset or spedrer. ifany indicated peab occur during scanning, m u r e m r t s should
be taken at each tequemy where such a peak ocwrs. If an unwanted radiosignal is encornered at any of
the listedfrequencies, another frequency on either side of the signal shodd be substitued.
ALlthorhed h&matiar M-IW
Section 3
LABORATORY AND FACTORY RIV TESTS-0.015 TO 30 MEGAHERTZ
For laboratory and factory RIV tests, the circuit shown in Figure 3-1 shall be used. Because of
the wide frequency range to be cowed by this test circuit and the wriable attenuation factors which
will occur due to stray circuit constants (see C, and CS,stray capacitances, and the series
inductance, LJ, the circuit shall be calibrated for each frequency at which R N measurements are
made. Below 1.0 megahertz where the reactance of the high-wltage coupling capacitor, C, is
generally high, a wriable inductor (circuit element L,) which is capable of producing series resonance
in the high-wltage measuring circuit at the test frequency shall be introduced.
NEMA Standard 5-27-1987
See Paragraph(s)
Figure 3-1
Circuit for the Measurement of Radio-Influence Voltage of
High-Voltage Apparatus, 0.015 to 30 Megahertz
The Figure 3-1 circuit shall be calibrated by applying at points " a " and "b,"with the test
specimen not connected; the unmodulated sine waw output of a signal generator tuned to the desired
test frequency. The output of this signal generator shall be set to a lewl at least ten times the ambient
noise lewl which is measured by the radio-noise meter when tuned to the output of the signal
generator. If tests are to be made at or aboe 1.0 megahertz, switch S1shall be closed. For tests
below 1.0 megahertz, switch S1shall be open and mriable inductance Ll, mried until a maximum
signal is obtained on the radio-noise meter. The inductance of L, shall be held constant while the
wltages E, (signal generator wltage at point ab) and E, (wltage at the radio-noise meter terminals,
point cd) are measured.
NEMA Standard 5-27-1987
The Figure 3-2 circuit shall be calibrated by applying at points "a" and "b," with point "a" not
connected to the power conductor "PC," the unmodulated sine waw output of a signal generator
tuned to the desired test frequency. The signal generator output and other calibration provisions shall
be the same as outlined in 3.2.1.
NEMA Standard 5-27-1987
Figure 3-2
Circuit for the Measurement of Radio-Influence
Voltage from an Energized Power System
Both calibratiq wltages (E* and Edshall be measured by the same instrument so that
emr is minimized. The coaxial cable, CA, of the length to be used fpr RRI measurements shall be in
the circuit when the test circuit calibration is made.
NEMA Standard 527-1987
The circuit RRI factor (P) should be held a b m 0.25 at midband at approximately 1
megahertz. The circuit RRI Factor (P) fPr other test frequencies betwen 0.03 and 5 megahertz
should preferably be held greater than 0.2.
Authorized Engineering lnfprmation 5-27-1987
3.2.6 RIV F eC m
Since this factor (P) will wry with frequency, a curue of the RRI hctor can beobtained fnr the
test circuit. The calibration c u m so obtained may not be wlid if the circuit components or the circuit
corrfiguration is changed.
- .
Authorized Engineering lnfprmation 5-27-1987
' M n E R REAMNG
0
t-ni er
leaulnas shallbebade in the manner described in 2.3. lT- leading'so obtained shall then be
Section 4
FIELD MEASUREMENTS OF RIV 0.015 TO 30
For the measurements of RRIfrom the conductors and apparatus of an energized m r system,
the measuring circuit shown in Figure 3-2 may be used. Extrem care s h d d be taken to i n s m that the
application of this rneasurirlg circut to the p w r system does not irterfere with the normal operatian of the
circuit and that proper grounding of the lowwttage mwuring amit is carried out so that the equipmert
and the operators are not endangered.
Authorized Engineering Information5-27-1987
Sectlon 5
HIGH-VOLTME TEST-CIRCUIT COMPONENTS
GENERAL
The fnllowing components refier to items which are associated with the highwltage RRI test
circuits indicated schematically in Figum 3-1, 32, and S3,and illustrated in Figure 2-1.
Authorized Engineering Information 5-27-1987
R 1 = 50 O h Interne1M* lnpedance
R3 = 100 Ohm No~Ind&a Resrstor
L3 = 60 Hz Drain Coil (Impadance at Test Frequency
greeter than 1500 Ohm)
CA = 50 O h Cabla lmpadancs
Fy)ure3- 50 Ohm Coax Cable, 50 Ohm Impedance RIV Meter
Figure 3 3
Circuit Diagramsfor Use of 50, 75, and 185-Ohm
Coaxial Cable in Conjunction with Figure 3-1 and 3-2
The p o w r supply for the high-wltage test circuit shall ha= a kVA rating which is suAicient to
supply a 60+lertz sine waw vnltage of acceptable commercial standard as defined in ANSI C50.10.
NEMA Standard 527-1987
The p o w r line filter, when employed, shall not distort the supply wltage. It shall suppress
any RRI which may be on the p m r mains so that the conditions giwn in 2.1.1 will be met.
NEMA Standard 527-1987
A wriable and undistorted -age shall be supplied to the prirnay of the tighwltage k t
transformer.
NEMA Standard 5-n-1987
HIGH-VOLTAGETESTTRANSWRMER (T)
The high--age test transformer should be h e of RW within the mltage range at which
tests aw to k-made
r -
ation 5-27-1987
5.6 RADIO-FREQUENCY C H O E (L
1'
MA radio-frequency choke dih an impedance less than '1W0 dhms at ihe&asu&ma$t
frequency shall be installed at or near the top of the high~wltage8c~upllng capa&ar*=s elmwit
shall limit the loss of conducted radiefrequency energy forthe t ~ t - ~ m p T e m d s hbefree
# of@v-
within the wltage range nf the test cimue.
I, m I NEMA,&andard
57 HIGH-VOLTAE COUPLING CAPACTTOR (C)
The highdage coupling capacitor of the required wltage rating shall befree of RW within
the wltage range of the test circuit.
NEMA Standard 527-1987
A coupling capacitor of small capacitance will d m a minimum cumnt, but at the Iowr test
frequencies it will appear as an excessiwiy high reactiw element and produce a Iw RRI factor (P)
as described in Section 3. It is wcommended that the capacitance be not less than 0.001 microfarad.
The capacitance CPom the bottom end of the coupling capacitor to ground should be kept small so
that this capacitance will not appreciably reduce the impedance of 150 ohms obtained from the
metering system (Figum 3-3).
Authorized Engineering Information5-27-1987
S W W SHORTlNGSWrrCH (53
A series shorting switch shall be applied across wriable inductor L1, when is used, to short
out the inductor during RRI t a t s at 1.0 megahertz and a b m .
NEMA Standard 5-27-1987
A corona-free bus shall be connected from the high-wltage coupling capacitor to the test
sample. This bus shall be supported by a minimum number of RN-free insulators to minimize stray
capacitance (C2)to ground and shall be as short as possible to minimize series inductance (LJ.
NEMA Standard 5-27-1987
CONDUCTOR DIAM€IER
T h e smooth conductor diameter for a corona-free bus for mltages up to 400 @b\rol&may be
obtained by alloLling at least 0.01 inch of bus diameter per kilowlt of test wltage. A b v 400 kilomlts
bundled conductors may be preferred to sin& conductors. C
50-, 79, and 1 8 5 4 m coaxialcab& cm be used p d d i n g the proper cable terminations at the
sending and receicig ends are utilbed. See Fiure 3 3 a d fpr the proper nodndmliw resistus or 185150-
ohm matching impedanceandlor atknuabr spedfidms. The cmial cable desigmm may be either R G
8, RG-11, or RG114
Authorized k g i n e e r i ~
lnfnrmation 527-1987
Because of cable atteruation,it is m m n d e d that the cable length be kept as short as possble
in order to meet the circuit RRI factor (P) tecommndations.
Authorized Engineering Information 527-1987
A WHz drain coil with an impedance of not less than 1500 ohms at the measuremntkquency,
shall be in-stalled in the metering c i c ~ iacross
t gap (GI.For safiety masons, this unitshall be substantial in
size, and all eledhd connediom shall be made mechanicaly and elecbicaly secm.
NEMA Standard 5-27-1987
Annex B
(IN FORMATIONAL)
CONDUCTOR CURRENT RATINGS
The %Hz c u m ratings of copper conductors haung a conductiuty of 98 percent lACS (International
Annealed Copper Standard) and copper tubing condudors sM I be in accordance with Tables B-1 and B-2.
Table 5 1
CURRENT (A) FOR BARE COPPER CABLE CONDUCTORS'
NOTES
1. Table B-1 calculated according to ANSIIIEEE Std 738-2006.
2. The mlnlmundldance b-n condudomahall be 457 mm (1 8 In .), unlsm the proxlmlty eRed should be takn Into
conaderation.
I'
#
I
1
- 1 I
I1
81.1.2 Outdoor ratings ate gien for a wind elocity of 0.8 meters per second (2 R per second), an
ambient air temperature of 4oaC,a conductor tempemhe of 70'C (30nCrise), and emissiuty, e, equal to
0.35. Sun efkct was not taken into consideration because of the wide wriation depending upon the
location. The designer should recalculate these wlues to take sun effect into consideration once the
installation location is determined.
B.1.1.3 If higher current ratings are desired, connector test currents per 3.1.1 should be adjusted
accordingly.
Table 6 4
CURRENT (A) FOR BARE ALUMINUM CABLE CONDUCTORS'
NOTES
1. Table 8-3 calculated according to ANSlllEEE Std 738-2006.
2. Cumnt Ratlngsam based upon 57431% mndudlvlty IACS Cable.
3. The mlnlmum dldance b e w e n condudors ahall be 457 mm (18 In), unles the pmldmlty effect Is takn Into
conslderatlon.
Table B4
CURRENT (A) FOR BARE ALUMINUM PIPE CONDUCTOM'
1.
2.
d.
Thewrrentratings1nthistabIeaebased;u
m EMAStd8-16-195l,Re~.7-d3j&~
Current Ratlngsare based upon 53% condu' M f y ACS. Pipe orTubing available in Dth6k
table. See B.&Z below.
~ f i #mi
6 nlm urh &libti&'beWR~7&HuHdrs'a l l ,Msislm (Wqh'j, M e s s th'e.pr&h~lfy ahould b&t'&WlWd
arnddentim.
82.1.2 Outdoor ratings are giwn fnr a wind #locity of 0.6 meters per second (2 It per second), an
ambient air temperature of 40mC,a conductor temperaim of 70'C @UmC rise), and emissiuty, e, equal to
0.35. Sun e k c t was not taken into consideration because of the wide wriation depending upon the
location. The designer shwld recalculate these wlues to take sun effect into consideration once the
installation location is determined.
82.1.3 if higher current ratings are desired, connector test cumnts per 3.1.1 should be adjusted
accordingly.
IWWW = ~ , ~ ( ~ o n d ~ # : toifvnew
i i y aiiofl. 53)"
I(Nw --Current Rating of New Alloy
,I 4 u m n t Rating of 53% alloy h m the table a b m
Annex C
(NORMATIVE)
North American Dimensional Standards
SHAPE
HOLE DIAMETER =
D +.062 f.032
1 - (1.6 f.8)
WHERE D STUD
DIAMETER
-
1-----1
Figure C-I - C-2
Fiqure
l HOLE NAL PAD HOLE lNEM
/
Figure C 3 Figure C 4
4HOLE NEMA PAD 4-HOLE WIDE NEMA PAD
(2 X 2 BOLT HOLE PATIERN) (2 X 2 BOLT HOLE PATIERN)
Figure C-8
TYPICAL SPACING FOR
MULTlPLE FLAT BAR TANGS
NOTES-
All dimensionsin inchesand (mm).
Fortongue dimensionsand drilling,see FiguresC-2 through G6.
1 F,","
in. in.
O.D.
rnrn in.
3 in. (76.2rnrn)
rnrn
5 and 7 in. (127.0 and 177.8 mrn)
in. rnrn
112 .840 21.00 *
1-314 1/16 *
44.4 1.6 *
2-118 1/16 *
54.0 1.6
314 1.050 26.25 2&1116 50.8 & 1.6 2-114 k 1/16 57.2 & 1.6
1 1.315 32.88 *
2 1/16 *
50.8 1.6 *
2-114 1/16 *
57.2 1.6
1-114 1.660 41.50 *
2-114 1/16 *
57.2 1.6 *
2-318 1/16 60.3k 1.6
Figure C-10
BUS SUPPORT CLAMP
Table C-2
HEIGHT OF OFFSET PAD TERMINAL CONNECTORS FOR TUBULAR BUS
(See Figures C-11 and C-I 2)
Pipe Size Height f % in. (f13 mm)
Trade 0.D.
Bolted Connectors Welded Connectors
Size
in. in. mm in. mm in. mm
1I2 .840 21.OO 1-318 35 15116 24
314 1.050 26.25 1-318 35 1 25
1 1.315 32.88 1-318 35 1-118 29
1-114 1.660 41.50 1-112 38 1-114 32
1-112 1.900 47.50 1-518 41 1-112 38
2 2.375 59.38 1-314 44 1-314 44
2-112 2.875 71.88 2-118 54 2 54
3 3.500 87.50 2-318 60 2-318 60
3-112 4.000 100.00 2-518 67 2-518 67
4 4.500 112.50 3-118 79 2-718 73
5 5.563 125.03 3-314 95 3-318 86
6 6.625 165.63 4-318
-
-
111 4 102
.115
-(3.21-
MIN
Figure C-12
WELDED OFFSET PAD TERMINAL CONNECTOR
Table C 4
STANDARD THREADS FOR STUD TERMINAL CONNECTORS
Table C 4 1
F U T WASHEWBOLT WMBlNATIQ
W h e r Blze A
inside,mmefer- O-Ie Dlamewr
M5lm Ma%
- Max-
-
In. mm In. mm In. mm
lw qQA3 TI4 6 I . 71a 222
-y14.2r
@I6
11116 117.41 1-112 38.1
ANNEX D
(INFORMATIONAL)
BOLT HOLE SPACINGS AND PAD DIMENSIONS FOR OTHER COUNTRIES
Figure D-I
E2
BOLT HOLE PAITERN FOR TERMINAL CONNECTORS
C
-As? D
Tab,. M f
t
l y
mm mm mm mm mm
40 82 45 16 48
Figure D-2
2 X 2 BOLT HOLE PAlTERN FOR TERMINAL CONNECTORS
Table D-2
COUNTRY C D (min) E F K N
mm mm mm mm mm mm
France 76 80 45 45 16 16
Germany 100 100 50 50 14 25
Sweden 76 76 40 40 14 18
Figure D 3
2 X 4 BOLT HOLE PAlTERN FOR TERMINAL CONNECTORS
Table D 3
mm rnm - _,
mm - ,/mm- rnm
Figure D 4
3 X 3 BOLT HOLE PAlTERN FOR TERMINAL CONNECTORS
Table D 4
COUNTRY C D (min) E F K N
mm mm mm mm mm mm
France 125 125 45 45 16 16
Sweden 120 120 40 40 14 20
ANNEX E
(INFORMATIONAL)
COMMON TYPES OF SUBSTATION CONNECTORS
angle connector: A connector that joins two conductors end to end at a specified angle.
combined "t" and straight connector ("t" coupler): A combined "T' and
straight connectorjoins two main conductors end toend and also joins a
--:::-I
+- =+---
- - --~= - ---
- ----
connector: A device that joins two or more conductors for the purpose of providing a contitwous electrical
path.
shrink-fit-type connector: A connector in which the contact between the conductor and the connector is
made by a shrink fit.
soldered-type connector: A connector in which the contact betweenthe conductor and the connector is
made by a soldered joint.
split-sleeve connector: A connector that is of split-skew form and is tinned for soldering.
tang: That portion of a connector which is used to fasten a connector to a terminal pad.
terminal connector: A comector that joins a conductor to a lead, termind pad (solid or laminated block),
or round terminal stud of electrical apparatus.
threaded-type connector: A connector in which the contact between thecondctor and the connector is
made by pressure exerted on a threaded part.
twisted sleeve connector: A pardlelcomectw in which the contact between the conductors is obtained
by forming a spiral twist in the connector and conductors after they are assembled.
"Y' connector: A connector that joins two branch conductors to the main
conductor at an angle. The three conductors are in the same plane.