ELECTRICAL Construction Drawings
ELECTRICAL Construction Drawings
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 01
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 38
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F
1
16 12 11 6 1 b 21 16 12 11 6 1
i h a c a
1 5 9
2
b
1 E 1
PGEN
P1J E d
c c P1J GEN d d d 2
GEN
a c d
Sab SE b c d
Sc Sc Scd
E E Sa S
SE SE
d c E E c E c E c
a Sbcd
h S S b
1 1 SE Scd
3
3
Scd Scd Scd
P1G a P1H a SE
S
a
b b b
Sab Sab Scd 1 1 1
S SE Sa
Sab S P2E P2D S P2C S P2B S
P1G P1H a c d 1
Shi a a a Sab a
c b 1 b b b P2B
P1F E 1
SKWMC1 b P1F
c Sab Sab Sab S P2A
a
4
4
P2E P2D P2C P2A
E S3W S3W
b P1E UP 3
1 UP
P1E P1K DN
b a b a
d c a 2 1 8 c 1 6 11
Sab
i SE Sab P1K S 3w
E Scd
Scd S SE a
Sbc P2F P2G P2H Sab
1 P1K Sab Sab
1 S
Sde 4 P1K Sab 22
S3W 17 12
5
5
b 1
S
E b b b P2H 1
E 1 b P1D b 1 a a P2J
P2J
P1C b a
P1D P1C 1 1 S
S S a
d c a P2F P2G Sab
a c d Sc P2I
SE Sab Sab SE
S Scd S
Scd S
SE Sc Sc SE c
E E SE Sc S 1 b
E Sc
6
6
SE Sde P2I
c E
h c c d c
c d
S S E
Scd Scd
SE Sab Sab SE
d c a a c d Sd Sd Sd Sd
1 1 c
P1B
P1A
P1A P1B E d d d e
E b b d
7
7
d d d d d
S S S S
b Sd Sd Sd Sd Sd
c c c c c
c c c c
i c
E E E E E
SE SE
8
8
SE Sc Sc SE Sc Sc SE Sc
c
1 1 1 1 1
b S P2O P2N S P2M S P2L S P2M S
c
b b a a a a a
Sabc Sabc Sabc Sabc b b b b b
PS3
PS2
1 1 1 1
PS1 PS1 PS2 PS3 PS4 PS4
Sc Sab Sab Sab Sab Sab
9
9
a a a a Sabd P2O P2N P2M P2L P2K
SI SI SI SI S3W d
a b a
Sx e e S3W 3W
d d d
S3W 1 21
1
UP
6 16 5
14
MAIN
KWHRM DN
10
10
12 12 9
11 CENTER
3W
LEGEND 400 AT MCCB
EXHAUST FAN
A GROUND FLOOR LIGHTING AND SWITCH LAYOUT
SI SIGNAGE
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 02
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 39
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F
1
b 18 14 10 a
a
1 5 9
2
E d
d d d 3
GEN
b c d
c E E c E c E c
Sbcd
b Scd
SE
3
3
Scd Scd Scd
S SE
a
b
1 1 1
Sa
S P3E P3D S P3C S P3B S
a a a 1 a
Sab
b b b P3B
1
Sab Sab Sab S P3A
a
4
4
P3E P3D P3C P3A
S3W
4 UP
P1K DN 4 DN
a b a
1 6 11 P1K 6 11
3w c 3w
5
1
S Sabc
b b b P3H P3J
1
a a P3J a
b a
S 1 1 S S
P3F P3G a
Sab
Sc P3I
S
SE Sc Sc SE c
E E SE Sc S 1 b
E Sc
6
6
SE Sde P3I
c E
c c d c
E
Sd Sd Sd Sd
c
d d d e d
7
7
d d d d d
Sd Sd Sd Sd Sd
c c c c c
E E E E E
SE SE
8
8
SE Sc Sc SE Sc Sc SE Sc
c
1 1 1 1 1 b
S P3O P3N S P3M S P3L S P3M S
a a a a a
b b b b b
9
Sabd P3O P3N P3M P3L P3K
S3W a a d
b
3W
18
1
14
5
10 DN
10
10
9
3W
LEGEND
1 x 18 WATTS LED TUBE LAMP
A THIRD FLOOR LIGHTING AND SWITCH LAYOUT B DECK FLOOR LIGHTING AND SWITCH LAYOUT
6" dia DOWNLIGHT 12W / 18W LED
WALL LAMP
EXHAUST FAN
SI SIGNAGE
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 03
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 40
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F
1
1 HP
16 12 11 6 1 21 16 12 11 6 1
PUMP
1 5 9
2
P1J
4 4 2
P1J 4 4 4 4 4 4
P1G P1H P1J P2E P2D P2C P2B P2B
3
WP WP P1J
H WP
3
3
2 3 2 3
H WP
P1G P1H 3 WP WP WP WP
P1G P1H
P1F WP H
1 HP
H H 4 P2B
PUMP P1G P1H 3
2 P1F 2 3 2
3 2 2 3 2 3 P2B P2A
SUBKWHRM (3Ø) P1F P2B P2A
P2E P2E P2D P2D P2C P2C
x
CENTER 1 P1F H H H
SUBKWMC 2C
100 AT 2P H
125 AT 3P
4
4
H P2E P2D P2C P2A
P1E
2 9 7
10
4 P1E P1K P1K
1 8 P1K 1 6 11
P1E WP
3 6
P1K 5
P1E P2F P2G P2H
P1K
WP H P1K H H
1 4 22 17 12
5
5
3 2 2 3 WP 100 AT 2P
P2F P2F P2G P2G 2 H
P1D P1C SUBKWMC 2B P2J 2
2 2 P2H P2J 3
4 P1D P1C 4 3 P2J
P1D P1C WP WP P2H P2I
H
3 3 WP
H
P1D P1C 3 2 WP
WP H H WP
P2I P2I
6
6
WP H H WP
3 3 4 4 4 4 4
P2F P2G P2H P2I P2J
P1A P1B
4 4
P1A 2 2 P1B
P1A P1B
P1B
P1A
SUBKWHRM
CENTER 2A
7
7
100 AT 2P MCCB
DP2 (3Ø)
4 4 4 4 4
3 3 P2F P2N P2M P2L P2K
PS1 PS4
8
8
3 3
PS2 PS3
WP WP WP WP WP
2 2
PS1 2 2 PS4
3 2 2 3 2 3 2 3 2 3
PS2 PS3
PS3
PS2
P2F P2F P2N P2N P2M P2M P2L P2L P2K P2K
PS1 PS4 H H H H H
9
9
P2O P2N P2M P2L P2K
1 21
1
LEGEND
6 16 5
DUPLEX CONVENIENCE OUTLET MAIN
14
KWHRM
WATER HEATER OUTLET
10
10
12 12 9
H
11 CENTER
WP
WEATHER PROOF OUTLET
400 AT MCCB
EMERGENCY LIGHT 3 4x NEMA BOX
PAD
EXIT LIGHT TS NEMA 4X 3 PHASE, 230v
B SECOND FLOOR POWER AND CONVENIENCE OUTLETS LAYOUT
x
SERVICE
SIGNAGE
1 HP WATER PUMP ENTRANCE
ELECTRICAL PANELBOARD
ACU
GROUND
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 04
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 41
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F
1
1 HP
PUMP 18 14 10
1 5 9
2
4 4 4 4 4
P3E P3D P3C P3B P3B
3
3
WP WP WP WP
WP H
P3B
2 3 2 3
3 2 2 3 2 3 P3B P3A
P3B P3A
P3E P3E P3D P3D P3C P3C
H H H
SUBKWMC 3C
100 AT 2P H
4
4
P3E P3D P3C P3A
8 6
P1K P1K
1 6 11 6 11
5
3 2 2 3 WP 100 AT 2P
P3F P3F P3G P3G 2 H
SUBKWMC 3B P3J 2
P3H 3
P3J
3 P3J
WP WP P3H P3I
H
WP
H
3 2 WP
P3I P3I
6
6
4 4 4 4 4
P3F P3G P3H P3I P3J
SUBKWHRM
CENTER 3A
7
7
100 AT 2P MCCB
DP3
4 4 4 4 4
P3F P3N P3M P3L P3K 125 AT 3P MCCB
NEMA 4x
8
8
TO MAIN
WP WP WP WP WP
KWHRM
CENTER
@ GROUND
3 2 2 3 2 3 2 3 2 3 FLOOR
P3F P3F P3N P3N P3M P3M P3L P3L P3K P3K
H H H H H
9
9
P3O P3N P3M P3L P3K
18
1
LEGEND 14
5
10
9
H
WATER HEATER OUTLET
WP
WEATHER PROOF OUTLET
EMERGENCY LIGHT
EXIT LIGHT A THIRD FLOOR POWER AND CONVENIENCE OUTLETS LAYOUT B DECK FLOOR POWER AND CONVENIENCE OUTLETS LAYOUT
x
1 HP WATER PUMP
ELECTRICAL PANELBOARD
CIRCUIT HOMERUN
CIRCUIT BREAKER
ACU
GROUND
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 05
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 42
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
SCHEDULE AND COMPUTATIONS OF LOAD
PANEL BOARD PSI / PS2 / PS3 / PS4 - 60 AF SINGLE PHASE 230V KVAT = 3.503 PANEL BOARD PGEN - 50 AF SINGLE PHASE 230V KVAT = 0.478
MAIN BREAKER 50 AT 2P CB LOCATION Rentable Stalls Grd Flr MAIN BREAKER 32 AT 2P CB LOCATION GROUND FLOOR
MAIN FEEDER 8.00 mm² THHN 24m / 20m / 14m / 8m 2.3 Ω / km FROM KWHRmeter Center KVAM = 2.208 MAIN FEEDER 5.5 mm² THHN 5m 3.6 Ω / km FROM GEN SET KVAM = 0
MINI THHN WIRE - mm² CONDUIT MINI THHN WIRE - mm² CONDUIT
CIRCUIT NO. OF VOLT CIRCUIT NO. OF VOLT
DESCRIPTION VOLTS AMPS BOLT POLES KAIC DESCRIPTION VOLTS AMPS BOLT POLES KAIC
NO. OUTLETS AMPS ON L 1L2 - THHN GRD PVCmmØ NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ
1 18W LED LAMP (+) SIGNAGE 3+1 354 230 1.54 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 1 12W LED SQUARE PINLIGHT 10 120 230 0.52 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 4 576 230 2.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 2 12W LED SQUARE PINLIGHT 15 180 230 0.78 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
3 2.0 HP ACU 1 2760 230 12 32 AT 2 10 2 -------- 5.5 1 -------- 5.5 1-------- 21 3 12W LED SQUARE PINLIGHT 15 180 230 0.78 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
4 SPACE 230 2 4 SPACE 230 2
IPS1 = IPS2 = IPS3 = IPS4 = [ 16.04 + 0.25 (12) ] 0.8 D.F. 2 - 8.0 mm² THHN
IPGEN = 2.08 @ 100% D.F. 2 - 5.5 mm² THHN
= 15.23 AMPS 1 - 5.5 mm² (G)
=2.08 AMPS 1 - 5.5 mm² (G)
USE 50 AT 2P CB 1 - 27 mmØ PVC
USE 32 AT 2P CB 1 - 21 mmØ PVC
PANEL BOARD P1A P1F, P2A P2O, P3A P3O USE 5KW SINGLE PHASE 230V
KVAT = 3.038 GAS ENGINE SMALL GENERATOR
MAIN BREAKER 50 AT 2P CB LOCATION Rentable Stalls GF/SF/TF
MAIN FEEDER 8.00 mm² THHN 2.3 Ω / km FROM Submeter Center KVAM = 1.472
CIRCUIT NO. OF VOLT MINI THHN WIRE - mm² CONDUIT FOR SUBKWHRMETER CENTER 1
DESCRIPTION VOLTS AMPS BOLT POLES KAIC AMPS ISMI = √3 (40.94) ( 0.8 D.F )
NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ LOAD AB BC CA
1 12W LED LAMP (+) 18W LED TUBE (+) EX. FAN 4+1+1 136 230 0.59 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 = 56.73 AMPS
P1A 13.27
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 4 576 230 2.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 USE 100 AT 3P MCCB
P1B 13.27 3 - 30.0 mm² THHN
3 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
P1C 13.27 1 - 8.0 mm² (G)
4 1.0 HP ACU 1 1840 230 8 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
P1D 13.27 1 - 4.1 mmØ PVC
5 SPACE 230 2 L = 20 ƻ = 0.66 Ω / KM
P1E 13.27
I = [ 14.59 + 0.25 (8) ] 0.8 D.F. 2 - 8.0 mm² THHN P1F 13.27
= 13.27 AMPS 1 - 5.5 mm² (G) P1G 13.22 KVAT = √3 56.73 (230) = 22.6
USE 50 AT 2P CB 1 - 27 mmØ PVC P1H 13.22 1000
PANEL BOARD P1G / PIH - 60 AF SINGLE PHASE 230V 60HZ P1J 14.4
KVAT = 3.04
MAIN BREAKER 50 AT 2P CB LOCATION UNITS G & H @ GF FOR MOTOR LOADS:
KVAM = 1.472 TOTAL 39.76 39.76 40.94 KVAM = 9 (8) (230) (0.8 D.F.) = 13.25
MAIN FEEDER 8.00 mm² THHN 5m / 4m 2.3 Ω / km FROM SubKWHRmeter Center 1
MINI 1000
CIRCUIT NO. OF VOLT THHN WIRE - mm² CONDUIT
DESCRIPTION VOLTS AMPS BOLT POLES KAIC
NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ
1 12W LED LAMP (+) 18W LED TUBE (+) EX. FAN 3+1+1 124 230 0.54 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 SUBKWHRM CENTER DISTANCE FROM MAIN METER CENTER FOR ALL SUBKWHRMETER CENTERS
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 4 576 230 2.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 SUBKWHRM CENTER 2A 20 m @ 2ND FLR AND 3RD FLR
3 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.48 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 SUBKWHRM CENTER 2B 35 m
4 1.0 HP ACU 1 1840 230 8.0 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 SUBKWHRM CENTER 2C 40 m
ISMI = 5 (13.27) ( 0.8) KVAT = 53.08 (230) = 12.21
5 SPACE 230 2 SUBKWHRM CENTER 3A 25 m = 53.08 AMPS 1000
SUBKWHRM CENTER 3B 40 m USE 100 AT 2P MCCB
IPIG = IPIH = [ 14.52 + 0.25 (8) ] 0.8 D.F. 2 - 8.0 mm² THHN 2 - 30.0 mm² THHN FOR MOTOR LOADS:
SUBKWHRM CENTER 3C 45 m
=13.22 AMPS 1 - 5.5 mm² (G) 1 - 8.0 mm² (G)
USE 50 AT 2P CB 1 - 27 mmØ PVC 1 - 3.5 mmØ PVC KVAM = 5 (8) (230) 0.8 D.F. = 7.36
PANEL BOARD P1J - 60 AF SINGLE PHASE 230V 60HZ ƻ = 0.66 Ω / KM 1000
KVAT = 3.312
MAIN BREAKER 50 AT 2P CB LOCATION OWNER'S UNIT @ GF
MAIN FEEDER 8.00 mm² THHN 10m 2.3 Ω / km FROM SubKWHRmeter Center 1 KVAM = 1.472
MINI THHN WIRE - mm² CONDUIT
CIRCUIT NO. OF VOLT PANEL BOARD DP2 / DP3 - 150 AF 3PL
DESCRIPTION VOLTS AMPS BOLT POLES KAIC KVAT = 31.073
NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ MAIN BREAKER 125 AT 3P MCCB LOCATION 2ND FLR / 3RD FLR
1 12W LED LAMP (+) 18W LED TUBE (+) EX. FAN 6+1+1 160 230 0.7 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 MAIN FEEDER 38 mm² THHN 25 / 30 m 0.55 Ω / km FROM MAIN METER CENTER KVAM = 18.77
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 6 864 230 3.8 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 CIRCUIT NO. OF VOLT AMPERES THHN WIRE - mm² CONDUIT
DESCRIPTION VOLTS MCCB POLES KAIC
3 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 NO. OUTLETS AMPS 3Ø AB BC CA AT L1L2 GRD PVCmmØ
4 1.0 HP ACU 1 1840 230 8 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 1 SUBKWHRMETER CENTER 2A / 3A - 12208 230 53.08 100 2 25 2 -------- 30 1 -------- 8.0 1-------- 35
5 SPACE 230 2 2 SUBKWHRMETER CENTER 2B / 3B - 12208 230 53.08 100 2 25 2 -------- 30 1 -------- 8.0 1-------- 35
3 SUBKWHRMETER CENTER 2C / 3C - 12208 230 53.08 100 2 25 2 -------- 30 1 -------- 8.0 1-------- 35
IPIJ = [ 16 + 0.25 (8) ] 0.8 D.F. 2 - 8.0 mm² THHN
= 14.4 AMPS 1 - 5.5 mm² (G) 4 SPACE 230 2
USE 50 AT 2P CB 1 - 27 mmØ PVC TOTAL 36,624 230 - 53.08 53.08 53.08
PANEL BOARD P1K - 60 AF 3 PHASE 230V 60HZ KVAT = 5.386 IDP2 = 36624 (0.85) 3 - 38 mm² THHN
MAIN BREAKER 50 AT 3P CB LOCATION UTILITY GF √3 230 1 - 14 mm² (G)
MAIN FEEDER 8.00 mm² THHN 18m 2.3 Ω / km FROM KVAM = 1.472 = 78 AMPS 1 - 41 mmØ PVC
AMPERES MINI CONDUIT USE 125 AT 3P MCCB
CIRCUIT NO. OF VOLT THHN WIRE - mm²
DESCRIPTION VOLTS BOLT POLES KAIC
NO. OUTLETS AMPS 3Ø AB BC CA ON L1L2 GRD PVCmmØ
1 12W LED LAMP (+) EXHAUST FAN 11 + 1 202 230 0.88 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
2 12W LED LAMP (+) 18W LED WALL LAMP 18 + 2 240 230 1.04 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
3 12W LED LAMP 18 216 230 0.94 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
4 -do- 20 240 230 2.0 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
5 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 5 720 230 3.13 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
6 -do- 6 864 230 3.75 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
7 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 7 1008 230 4.4 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
8 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 7 1008 230 4.4 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
9 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
10 1.0 HP ACU 1 1840 230 8.0 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
11 SPACE 230 2
12 SPACE 230 2
TOTAL 7138 230 - 10.72 10.38 10.94
IPIK = 7138 + 0.25 (1840) 0.8 D.F. 3 - 8.0 mm² THHN FOR 10HP PUMP I = 28 AMPS
√3 230 1 - 5.5 mm² (G) USE 70 AT 3P MCCB
= 15.26 AMPS 1 - 27 mmØ PVC 3 - 8.0 mm² THHN L = 20m
USE 50 AT 3P CB 1 - 5.5 mm² (G) ƻ = 2.3 Ω / km
1 - 27 mmØ PVC
FOR ADMIN PANEL PAD
IT [ 28 + 13.52 + 0.25 (28) ] 0.8 D.F. 3 - 14.0 mm² THHN
=38.82 AMPS 1 - 5.5 mm² (G)
USE 60 AT 3P MCCB 1 - 27 mmØ PVC
L = 5m ƻ = 1.48 Ω / km
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 06
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 43
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
1. LOAD ANALYSIS EQUIVALENT REACTANCE DIAGRAM
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 07
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 44
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
BARE COPPER
BARE COPPER WIRE
A B C D E F WIRE
GROUND ROD
"VS" "VS"
16 12 11 6
"VS"
1 TYPE "NC" CONN.
TYPE "VS" CONN.
2
"NC"
"NC"
500
420
4
"NC"
"NC" SOLDERLESS
3/0 SOFT DRAWN
1 4 CONNECTOR
5
500
250
GRAVEL LAYER
SAND LAYER
6
"NC"
C GROUND PIT DETAIL
"VS"
0.200
0.175
0.200
10mmØ HOLE (TYP.)
"VS" "VS" "VS" "VS" TO STEEL STRUCTURE COUNTER SUNK FOR
OF THE BUILDING 5mmØ FLAT HEAD SCREW
9
0.200
A
5mmØ ANCHOR ROD
6
14
10
12
11
TO OTHER GROUND ROD TO OTHER GROUND ROD
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 08
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 45
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
LIGHTNING ARRESTER
(SEE DETAILS)
A B C D E F
COMMUNICATION TOWER
@ + 14.16 mts
2
INSPECTION JOINT
PROTECTION SHEALTH
GROUND FINISHED FLOOR LINE
@ + 0.40 mts
ASSUMED ROAD LEVEL @ GUTTER @ + 00.0
@ + 00.0 mts
6
@ - 1.10
RISER DOWN
B LIGHTING ARRESTER LOCATION (FRONT ELEVATION)
7
DOWN
HELITA PULSAR 60
CONDUCTOR
AIR TERMINAL
EXTENSION MAST
STAINLESS STEEL
8
40mm
BARE COPPER
170mm
9
(SEE DETAIL)
60
00
3/0mm Ø x 3m
COPPER GROUND ROD
80mm
10
1. ALL CONDITIONS AND DIMENSIONS SHOWN ARE PRIMARILY, PENDING ACTUAL SITE
VERIFICATION BY CONTRACTOR.
2. THE LOCATION OF ALL UTILITY LINES, STRUCTURES AND EQUIPMENT SHOWN ARE
PRELIMINARY; SEE RESPECTIVE ENGINEERING DESIGN DRAWINGS & SPECIFICATIONS.
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 09
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 46
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F
1
4 8
16 12 11 6 1 21 16 12 11 6 1
5
1 5 9
2
3
3
3
4
4
7
1 8 1 6 11
MONITOR /
1 4 CONTROL 22 17 12
5
5
6
6
7
7
8
8
2
9
9
6
1 21
1
6 16 5
14
10
12 12 9
11
LEGEND
CCTV CAMERA
MONITOR / CONTROL
1
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM 10
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 47
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F
1
11
18 14 10
1 5 9
2
2
3
3
4
4
10 12
1 6 11 6 11
22 17 12 22 17 12
5
5
6
6
7
7
8
8
9
9
9
18
1
14
5
10
A THIRD FLOOR ANCILLARY LAYOUT B DECK FLOOR ANCILLARY LAYOUT
10
10
9
LEGEND
CCTV CAMERA
MONITOR / CONTROL
PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM 11
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 48
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
FIRE DETECTION AND ALARM
SYSTEM GENERAL NOTES
1. ALL WIRING AND CONDUIT SIZES AND QUANTITIES
SHALL BE IN ACCORDANCE WITH THE FIRE ALARM SYSTEM
@ DECK FLOOR @ THIRD FLOOR MANUFACTURER'S RECOMMENDATIONS, NFPA 70 AND
NFPA 72. COORDINATE ALL WORK WITH THE SPRINKLER,
ZONE 3 SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD EOLR
MECHANICAL, AND ELEVATOR CONTRACTORS.
SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD EOLR
QTY SYMBOL DETAIL
FA - 1A FA - 1B
54 SD PHOTOELECTRIC SMOKE DETECTOR
6 MPS MANUAL STATION
MPS MPS
6 HORN STROBE
4 ZONES WITH
A FDAS RISER DIAGRAM NOTE:
BACK - UP BATTERY
1. FOR FIRE DETECTION AND ALARM SYSTEM, THE SIZE
AND TYPE OF WIRE AND AS FOLLOWS:
HORN / STOBE
UNIT
?" { EMT CONDUIT
SURFACE
STANDARD OR 4" x 4" UTILITY BOX
DEEP 4" (DEEP TYPE)
OCTAGON OR ?" { EMT CONDUIT
SQUARE WIRING
BOX
2.20
MOUNTING BASE
1.80 m (MAX)
1.80 m (MAX)
DRY WALL
1.22
HALLWAY
FIN. FLR. LINE FINISHED FLOOR LINE
1
16 12 11 6 1 21 16 12 11 6 1
1 5 9
2
SD
SD SD SD SD
SD SD SD SD
3
3
SD
MPS
SD
FA - 2B
4
4
FA - 1B MPS
SD
1 8 SD 1 to FACP
6 11
SD SD
ZONE 2
4 ZONES ZONE 1 SD
1FACP
4 to FACP
22 17 12
5
5
SD SD
SD SD SD
6
6
SD SD
SD
SD SD
7
7
EOLR SD SD SD SD SD
8
8
SD
EOLR SD SD to FACP SD SD
FA - 1A
MPS
to FACP
9
9
MPS
FA - 2A
1 21
1
6 16 5
14
10
10
12 12 9
11
1
18 14 10
1 5 9
2
SD
SD SD SD SD
3
3
ZONE 3
FA - 3B
4
4
MPS
SD 1 to FACP
6 11 6 11
SD SD DN
to FACP DN
22 17 12 22 17 12
5
5
SD SD SD
6
6
SD
SD
7
7
EOLR SD SD SD SD SD
8
8
to FACP
9
9
MPS
FA - 3A
18
1
14
5
10
10
10
9
A THIRD FLOOR FIRE DETECTION AND ALARM SYSTEM A DECK FLOOR FIRE DETECTION AND ALARM SYSTEM