ELECTRICAL Construction Drawings

sample of working drawings

Uploaded by

mateo bondoc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
275 views14 pages

ELECTRICAL Construction Drawings

sample of working drawings

Uploaded by

mateo bondoc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

125 AT 3P

MCCB GENERAL NOTES AND SPECIFICATIONS


3Ø NEMA 4X 1. THE ELECTRICAL WORK HEREIN SHALL BE DONE IN ACCORDANCE WITH THESE PLANS AND
SPECIFICATIONS APPLICABLE PROVISIONS OFF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL
70 AT 3P CODE. RULES AND REGULATIONS OF THE LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS
MCCB OF THE LOCAL POWER COMPANY.
3Ø 2. POWER SERVICE SHALL BE THREE PHASE THREE WIRE WITH GROUND 230 V 60 hz AC.
3. THE ELECTRICAL INSTALLATION SHALL BE DONE IN (a) POLYVINYL CONDUIT SCHEDULE 40. THE
MINIMUM SIZE OF WHICH IS 15 mm Ø ELECTRICAL TRADE SIZE FOR EMBEDDED PIPES. (b) EMT PIPES
FUTURE PUMP FOR EXPOSED TYPE OF WIRING (c) IMC PIPES FOR SUBFEEDER AND MAIN FEEDER.
LOAD OF 10 HP 4. NO CONDUIT PIPE SHALL BE USED IN ANY SYSTEM SMALLER THAN THE ELECTRICAL TRADE SIZE
2 - 30.0 mm² THHN SPECIFIED IN THE PLANS NOR SHALL MORE THAN FOUR 90 DEGREES BENDS IN ANY ON RUN, AND
TELCO
1 - 8.0 mm² (G) SINGLE PHASE WHERE NECESSARY, PULL BOXES SHALL BE PROVIDED AS DIRECTED.
TOWER
1 - 35 mmØ PVC 5. NO WIRE SHALL BE PULLED INTO ANY CONDUIT UNTIL THE CIRCUIT SYSTEM IS COMPLETE IN ALL
DETAILS.
6. THE ENDS OF ALL CONDUITS SHALL BE TIGHTLY PLUGGED TO EXCLUDE PLASTIC, DUST AND
MOISTURE WHILE INSTALLATION IS IN THE PROCESS.
DP3 100 AT 2P MCCB 100 AT 2P MCCB 100 AT 2P MCCB 7. ALL PIPES AND FITTINGS ON EXPOSED WORK SHALL BE SECURED BY MEANS OF METAL CLIPS
3 - 38 mm² THHN 3Ø WHICH SHALL BE HELD IN PLACE BY MEANS OF MACHINE SCREWS. WHEN RUNNING OVER CONCRETE
SINGLE PHASE SINGLE PHASE SINGLE PHASE
1 - 14 mm² (G) SURFACES, THE SCREW SHALL BE HELD IN PLACE BY EXPANSION SLEEVES. ALL PIPES ON EXPOSED
1 - 41 mmØ PVC WORK SHALL RUN AT RIGHT ANGLES TO AND PARALLEL WITH THE SURROUNDING WALLS AND SHALL
CONFORM TO THE FORM OF THE CEILING. NO DIAGONAL RUNS SHALL BE ALLOWED AT ALL ENDS AND
OFFSETS SHALL BE AVOIDED AS POSSIBLE. WHERE NECESSARY, CONDULET FITTINGS SHALL BE
USED. PIPING, IN ALL CASES SHALL BE RUN PERFECTLY STRAIGHT AND TRUE, SATISFACTORY TO THE
M M M M M M M M M M M M M M M TO 15 - 12W OWNER AND THE ENGINEERS.
LED LAMP 8. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE THHN UNLESS
OTHERWISE INDICATED IN PLANS WHEREIN THE MINIMUM SIZE SHALL BE 3.5 mm². PHELPS DODGE IN
BRAND.
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 9. ALL WIRES SHALL BE COPPER, SOFT-DRAWN AND ANNEALED, SHALL BE 98% CONDUCTIVITY
SHALL BE SMOOTH AND TRUE OF A CYLINDRICAL FORM, AND SHALL BE WITHIN 1% OF THE ACTUAL
2 - 8.0 mm² THHN SIZE CALLED FOR.
1 - 5.5 mm² (G) 10. ALL WIRES AND CABLES SHALL COMPLY WITH THE REQUIREMENTS OF THE UNDERWRITER'S
3 - 8.0 mm² THHN 1 - 27 mmØ PVC LABORATORIES, THE A.S.T.M., AND THE I.P.C.E.A. AS THEY APPLY TO THE PARTICULAR.
1 - 5.5 mm² (G) 11. COLOR CODING SHALL BE OBSERVED AS RED, BLACK, BLUE FOR PHASE ABC AND GREEN FOR
1 - 27 mmØ PVC GROUNDING.
P3K P3L P3M P3N P3O P3F P3G P3H P3I P3J P3A P3B P3C P3D P3E 12. ALL DISTRIBUTION AND SMALL PANEL BOARDS SHALL BE SCHNEIDER IN BRAND MANUFACTURED
IN ACCORDANCE WITH THE PHILIPPINES STANDARD AMPERE FRAME REQUIREMENTS.
13. STANDARD PANELS AND CABINETS AS FAR AS POSSIBLE, SHALL BE USED AND ASSEMBLED ON
2 - 30.0 mm² THHN JOB. ALL PANELS SHALL BE OF DEAD FRONT CONSTRUCTION FURNISHED WITH TRIMS FOR FLUSH OR
1 - 8.0 mm² (G) SURFACE MOUNTING AS REQUIRED. CABINETS SHALL BE OF CODE GAUGE STEEL WITH GUTTERS AT
1 - 35 mmØ PVC LEAST 100 mm AND WIDER IF NECESSARY. THE TRIM FOR ALL PANELS SHALL BE FINISHED IN GRAY
DP2 ENAMEL OVER A RUST INHIBITOR.
100 AT 2P MCCB 100 AT 2P MCCB 100 AT 2P MCCB
3 - 38 mm² THHN 3Ø 14. ALL PANELS SHALL BE MARKED USING PLASTIC TAG AND SECURELY ATTACHED WITH
SINGLE PHASE SINGLE PHASE SINGLE PHASE DESIGNATION NUMBER ETCHED ON THESE TAGS.
1 - 14 mm² (G)
15. B.I. BOX PLANT STEEL FRONT COMPLETE WITH PIANO HINGED DOOR, POLISHED METAL CATCH
1 - 41 mmØ PVC
AND LOCK MANUFACTURES STANDARD FINISH. MAIN BUS BARS SHALL BE FULLY RATED AND BUS BAR
TO BUS BAR JOINTS.
16. BREAKER MINIMUM INTERRUPTING CAPACITIES BASED ON NEMA AND UL PROCEDURES, 240
M M M M M M M M M M M M M M M TO 15 - 12W VPOLT BREAKERS, 10,000 AMPS BY SYMMETRICAL AMPERES AT 240 VOLTS.
LED LAMP 17. ALL SERVICE ENTRANCE EQUIPMENT PANELBOARDS AND ALL NON-CONCURRENT CARRYING
METAL PARTS SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE PHILIPPINE ELECTRICAL
CODE.
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 18. GROUND TEST - THE ENTIRE INSTALLATION SHALL BE FREE FROM IMPROPER GROUND AND
FROM SHORT CIRCUITS. TEST SHALL BE MADE IN THE PRESENCE OF A REPRESENTATIVE OF THE
2 - 8.0 mm² THHN ENGINEERS. EACH INDIVIDUAL POWER FEEDER SHALL BE TESTED WITH THE POWER EQUIPMENT
1 - 5.5 mm² (G) CONNECTED FOR PROPER AND INTENDED OPERATIONS. IN NO CASE SHALL THE INSULATION
1 - 27 mmØ PVC RESISTANCE BE LESS THAN THE ALLOWED BY THE REGULATIONS. FAILURES SHALL BE CORRECTED IN
A MANNER SATISFACTORY TO THE ENGINEERS.
3 - 250 mm² THHN 19. NON CURRENT CARRYING METALLIC PARTS ASSOCIATED WITH THE ELECTRICAL EQUIPMENT
P2K P2L P2M P2N P2O P2F P2G P2H P2I P2J P2A P2B P2C P2D P2E SHALL HAVE A MAXIMUM RESISTANCE TO SOLID EARTH GROUND NOT EXCEEDING THE FOLLOWING
1 - 30 mm² (G)
1 - 100 mmØ RSC VALUES:
SERVICE ENTRANCE
GROUNDING LOOP SWITCHING.........................2 OHMS
THREE PHASE 230V-AC
GROUND IN HANDHOLES...................................10 OHMS
GROUNDING OTHER METAL
ENCLOSURES OF ELECTRICAL
400 AT 3P MCCB AND ELECTRICITY OPERATED EQUIPMENT.....1 OHMS
100 AT 3P MCCB 3 PHASE BUS BAR 20. ALL OUTLETS SHALL BE PROVIDED WITH SUITABLE FITTINGS. THIS SHALL BE A BOX OR OTHER
NEMA 4X
DEVICES ESPECIALLY DESIGNED TO RECEIVE THE TYPE OF DEVICE TO BE MOUNTED THEREON.
BUS BAR 21. THIS CONTRACTOR SHALL CONSULT WITH THE OWNER AND THE ENGINEERS AS TO THE NATURE
NEMA 3R GUTTER 3Ø OF THE VARIOUS FITTINGS TO BE USED BEFORE INSTALLING HIS OUTLET FITTINGS, AND SHALL
AB BC CA AB BC CA AB BC CA
3 - 30.0 mm² THHN CONFORM STRICTLY IN THE USE OF FITTINGS, TO THE DEVICE TO BE MOUNTED TO THEM. SO THAT
PS1 PS2 PS3 PS4 1 - 8.0 mm² (G) M M M M M M M M M THE WORK, WHEN COMPLETED, WILL BE A FINISHED DESIGN.
AB BC CA AB 3Ø 3Ø 3Ø 3Ø 3Ø TO 15 - 12W
1Ø 1Ø 1Ø 1Ø 1 - 41 mmØ PVC LED LAMP 22. JUNCTION AND PULL BOXES, OF CODE GAUGE STEEL, SHALL BE PROVIDED AS INDICATED OR AS
MAIN
KWHRMETER REQUIRED FOR FACILITATING THE PULLING OF WIRES AND CABLES. PULL BOXES IN FINISHED PLACES
M M M M M M M M M PAD SHALL BE LOCATED AND INSTALLED WITH THE PERMISSION OF AND TO THE SATISFACTION OF THE
CENTER 1Ø 1Ø 1Ø 1Ø 3Ø 3Ø 3Ø 3Ø 3Ø 50 50 50 50 50 50 50 50 50 2 - 3.5 mm² THHN
ENGINEERS.
2P 2P 2P 2P 3P 3P 3P 3P 3P 1 - 2.0 mm² (G)
NEMA 3R 23. PERFORMANCES - IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO
1 - 16 mmØ PVC TEST ALL SYSTEMS OF THE ENTIRE ELECTRICAL INSTALLATION FOR PROPER OPERATIONAL
BREAKER 50 50 50 50 125 125 125 125
GUTTER CONDITIONS. WHERE SEQUENCE OPERATION IS REQUIRED, THE ELECTRICAL CONTRACTOR SHALL
2 - 8.0 mm² THHN TEST THE PROPER SEQUENCE AND HE SHALL LEAVE THE ENTIRE ELECTRICAL INSTALLATION IN
1 - 5.5 mm² (G) SATISFACTORY WORKING CONDITION. ALL CABLE TERMINATION SHALL BE TESTED MECHANICALLY
1 - 27 mmØ PVC WITH A TORQUE TESTER.
24. ALL WIRE GUTTERS SHALL BE OF CODE OF GAUGE #16 MINIMUM POWDER COATED.
P1K 25. ALL LIGHTING FIXTURES WILL BE OF FLUORESCENT LED EXCEPT OTHERWISE AS SHOWN IN
P1A P1B P1C P1D P1E P1F P1G P1H P1J 3Ø PLANS, WITH THE APPROVAL OF THE OWNER AND WITH ICC MARKS.
PGEN 26. ANY DISCREPANCY IN LOCATION AND RATING OF ELECTRICAL EQUIPMENT SHALL BE VERIFIED
WITH THE OWNER AND CHANGES SHALL BE MADE ACCORDINGLY.
THREE PHASE 27. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND MUST BE THE APPROVES TYPE FOR
2 - 8.0 mm² THHN 3 - 8.0 mm² THHN THE LOCATION AND PURPOSE INTENDED.
TS SIGNAGE 28. MOUNTING HEIGHT SHALL BE AS FOLLOWS:
1 - 5.5 mm² (G) 1 - 5.5 mm² (G) 2 - 5.5 mm² THHN (a). LIGHT SWITCH (PANASONIC).......................1.40m above finished floor line
1 - 27 mmØ PVC 1 - 27 mmØ PVC 1 - 5.5 mm² (G) (b). CONVENIENCE OUTLET (PANASONIC)........0.30m above finished floor line
G 1 - 21 mmØ PVC (c). PANELBOARD (SCHNEIDER).........................1.40m above finished floor line
30 mm² (d). SPECIAL PURPOSE OUTLET (PANASONIC)......at convenient height near equipment
BCW 5KW 1Ø 230V 29. LIGHT SWITCHES SHALL BE RATED 5.00 AMPERES AND MOUNTED AT 1.40m ABOVE FINISHED
GEN SET FLOOR LINE, IT SHALL BE BTICINO BRAND.
1" x 10 ft 30. CONVENIENCE OUTLETS SHALL BE OF UNIVERSAL TYPE WITH 3 PRONG, 15.00 AMPERES BTICINO
GROUND ELECTRODE BRAND.
31. FIRE ALARM SYSTEM SHALL BE CLASS B SUPERVISED WITH 14-ZONE FIRE ALARM CONTROL

POWER RISER DIAGRAM PANEL EDWARDS IN BRAND.


32. ALL ELECTRICAL WORKS INSIDE THE PUMPS ROOM SHALL BE SUITABLE FOR CLASS 1 DIVISION 2
HAZARDOUS LOCATIONS. CONDUITS LEAVING / ENTERING THE AREAS SHALL BE PROVIDED WITH
SEALANT FITTINGS.
33. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE IMMEDIATE SUPERVISION OF A DULY
LICENSED PROFESSIONAL ELECTRICAL ENGINEER.

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 01
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 38
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F

1
16 12 11 6 1 b 21 16 12 11 6 1

i h a c a
1 5 9

2
b
1 E 1

PGEN
P1J E d
c c P1J GEN d d d 2
GEN
a c d
Sab SE b c d
Sc Sc Scd
E E Sa S
SE SE
d c E E c E c E c
a Sbcd
h S S b
1 1 SE Scd
3

3
Scd Scd Scd
P1G a P1H a SE
S
a
b b b
Sab Sab Scd 1 1 1
S SE Sa
Sab S P2E P2D S P2C S P2B S
P1G P1H a c d 1
Shi a a a Sab a
c b 1 b b b P2B
P1F E 1
SKWMC1 b P1F
c Sab Sab Sab S P2A
a
4

4
P2E P2D P2C P2A
E S3W S3W
b P1E UP 3
1 UP
P1E P1K DN
b a b a
d c a 2 1 8 c 1 6 11
Sab
i SE Sab P1K S 3w
E Scd
Scd S SE a
Sbc P2F P2G P2H Sab
1 P1K Sab Sab
1 S
Sde 4 P1K Sab 22
S3W 17 12
5

5
b 1
S
E b b b P2H 1
E 1 b P1D b 1 a a P2J
P2J
P1C b a
P1D P1C 1 1 S
S S a
d c a P2F P2G Sab
a c d Sc P2I
SE Sab Sab SE
S Scd S
Scd S
SE Sc Sc SE c
E E SE Sc S 1 b
E Sc
6

6
SE Sde P2I
c E
h c c d c
c d
S S E
Scd Scd
SE Sab Sab SE
d c a a c d Sd Sd Sd Sd
1 1 c

P1B
P1A

P1A P1B E d d d e
E b b d
7

7
d d d d d
S S S S

b Sd Sd Sd Sd Sd
c c c c c
c c c c
i c
E E E E E
SE SE
8

8
SE Sc Sc SE Sc Sc SE Sc
c

1 1 1 1 1
b S P2O P2N S P2M S P2L S P2M S
c
b b a a a a a
Sabc Sabc Sabc Sabc b b b b b
PS3
PS2

1 1 1 1
PS1 PS1 PS2 PS3 PS4 PS4
Sc Sab Sab Sab Sab Sab
9

9
a a a a Sabd P2O P2N P2M P2L P2K
SI SI SI SI S3W d
a b a
Sx e e S3W 3W
d d d
S3W 1 21
1

UP
6 16 5

14
MAIN
KWHRM DN
10

10
12 12 9
11 CENTER

3W
LEGEND 400 AT MCCB

1 x 18 WATTS LED TUBE LAMP 3Ø, 230v


6" dia DOWNLIGHT 12W / 18W LED
SERVICE
ENTRANCE
B SECOND FLOOR LIGHTING AND SWITCH LAYOUT
12W SQUARE P.L (EMERGENCY)
X X
WALL LAMP

EXHAUST FAN
A GROUND FLOOR LIGHTING AND SWITCH LAYOUT
SI SIGNAGE

Sa ONE GANG SWITCH

Sab TWO GANG SWITCH

Sabc THREE GANG SWITCH

S3w THREE WAY SWITCH

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 02
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 39
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F

1
b 18 14 10 a
a
1 5 9

2
E d
d d d 3
GEN
b c d

c E E c E c E c
Sbcd
b Scd
SE
3

3
Scd Scd Scd
S SE
a
b
1 1 1
Sa
S P3E P3D S P3C S P3B S
a a a 1 a
Sab
b b b P3B
1
Sab Sab Sab S P3A
a
4

4
P3E P3D P3C P3A
S3W
4 UP
P1K DN 4 DN
a b a
1 6 11 P1K 6 11

3w c 3w

P3F P3G P3H Sab


Sab Sab
Sab 22
S3W 17 12 22S3W 17 12
5

5
1
S Sabc
b b b P3H P3J
1
a a P3J a
b a
S 1 1 S S
P3F P3G a
Sab
Sc P3I
S
SE Sc Sc SE c
E E SE Sc S 1 b
E Sc
6

6
SE Sde P3I
c E
c c d c
E

Sd Sd Sd Sd
c
d d d e d
7

7
d d d d d

Sd Sd Sd Sd Sd
c c c c c

E E E E E
SE SE
8

8
SE Sc Sc SE Sc Sc SE Sc
c

1 1 1 1 1 b
S P3O P3N S P3M S P3L S P3M S
a a a a a
b b b b b

Sc Sab Sab Sab Sab Sab


9

9
Sabd P3O P3N P3M P3L P3K
S3W a a d
b
3W
18
1

14
5

10 DN
10

10
9

3W
LEGEND
1 x 18 WATTS LED TUBE LAMP
A THIRD FLOOR LIGHTING AND SWITCH LAYOUT B DECK FLOOR LIGHTING AND SWITCH LAYOUT
6" dia DOWNLIGHT 12W / 18W LED

12W SQUARE P.L (EMERGENCY)

WALL LAMP

EXHAUST FAN

SI SIGNAGE

Sa ONE GANG SWITCH

Sab TWO GANG SWITCH

Sabc THREE GANG SWITCH

S3w THREE WAY SWITCH

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 03
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 40
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F

1
1 HP
16 12 11 6 1 21 16 12 11 6 1
PUMP

1 5 9

2
P1J
4 4 2
P1J 4 4 4 4 4 4
P1G P1H P1J P2E P2D P2C P2B P2B
3
WP WP P1J
H WP
3

3
2 3 2 3
H WP
P1G P1H 3 WP WP WP WP
P1G P1H
P1F WP H
1 HP
H H 4 P2B
PUMP P1G P1H 3
2 P1F 2 3 2
3 2 2 3 2 3 P2B P2A
SUBKWHRM (3Ø) P1F P2B P2A
P2E P2E P2D P2D P2C P2C

x
CENTER 1 P1F H H H
SUBKWMC 2C
100 AT 2P H
125 AT 3P
4

4
H P2E P2D P2C P2A
P1E
2 9 7
10
4 P1E P1K P1K
1 8 P1K 1 6 11
P1E WP

3 6
P1K 5
P1E P2F P2G P2H
P1K
WP H P1K H H
1 4 22 17 12
5

5
3 2 2 3 WP 100 AT 2P
P2F P2F P2G P2G 2 H
P1D P1C SUBKWMC 2B P2J 2
2 2 P2H P2J 3
4 P1D P1C 4 3 P2J
P1D P1C WP WP P2H P2I
H
3 3 WP
H
P1D P1C 3 2 WP

WP H H WP
P2I P2I
6

6
WP H H WP
3 3 4 4 4 4 4
P2F P2G P2H P2I P2J
P1A P1B
4 4
P1A 2 2 P1B
P1A P1B

P1B
P1A

SUBKWHRM
CENTER 2A
7

7
100 AT 2P MCCB
DP2 (3Ø)

4 4 4 4 4
3 3 P2F P2N P2M P2L P2K
PS1 PS4
8

8
3 3
PS2 PS3
WP WP WP WP WP

2 2
PS1 2 2 PS4
3 2 2 3 2 3 2 3 2 3
PS2 PS3
PS3
PS2

P2F P2F P2N P2N P2M P2M P2L P2L P2K P2K
PS1 PS4 H H H H H
9

9
P2O P2N P2M P2L P2K

1 21
1

LEGEND
6 16 5
DUPLEX CONVENIENCE OUTLET MAIN
14
KWHRM
WATER HEATER OUTLET
10

10
12 12 9
H
11 CENTER
WP
WEATHER PROOF OUTLET
400 AT MCCB
EMERGENCY LIGHT 3 4x NEMA BOX
PAD
EXIT LIGHT TS NEMA 4X 3 PHASE, 230v
B SECOND FLOOR POWER AND CONVENIENCE OUTLETS LAYOUT
x

SERVICE
SIGNAGE
1 HP WATER PUMP ENTRANCE

ELECTRICAL PANELBOARD

CIRCUIT HOMERUN A GROUND FLOOR POWER AND CONVENIENCE OUTLETS LAYOUT


CIRCUIT BREAKER

ACU

SERVICE ENTRANCE, 3 PAHSE

GROUND

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 04
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 41
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F

1
1 HP
PUMP 18 14 10

1 5 9

2
4 4 4 4 4
P3E P3D P3C P3B P3B
3

3
WP WP WP WP
WP H
P3B
2 3 2 3
3 2 2 3 2 3 P3B P3A
P3B P3A
P3E P3E P3D P3D P3C P3C
H H H
SUBKWMC 3C
100 AT 2P H
4

4
P3E P3D P3C P3A

8 6
P1K P1K
1 6 11 6 11

P3F P3G P3H


H H
22 17 12 22 17 12
5

5
3 2 2 3 WP 100 AT 2P
P3F P3F P3G P3G 2 H
SUBKWMC 3B P3J 2
P3H 3
P3J
3 P3J
WP WP P3H P3I
H
WP
H
3 2 WP
P3I P3I
6

6
4 4 4 4 4
P3F P3G P3H P3I P3J

SUBKWHRM
CENTER 3A
7

7
100 AT 2P MCCB
DP3

4 4 4 4 4
P3F P3N P3M P3L P3K 125 AT 3P MCCB
NEMA 4x
8

8
TO MAIN
WP WP WP WP WP
KWHRM
CENTER
@ GROUND
3 2 2 3 2 3 2 3 2 3 FLOOR
P3F P3F P3N P3N P3M P3M P3L P3L P3K P3K
H H H H H
9

9
P3O P3N P3M P3L P3K

18
1

LEGEND 14
5

DUPLEX CONVENIENCE OUTLET


10
10

10
9
H
WATER HEATER OUTLET

WP
WEATHER PROOF OUTLET

EMERGENCY LIGHT

EXIT LIGHT A THIRD FLOOR POWER AND CONVENIENCE OUTLETS LAYOUT B DECK FLOOR POWER AND CONVENIENCE OUTLETS LAYOUT
x

1 HP WATER PUMP

ELECTRICAL PANELBOARD

CIRCUIT HOMERUN

CIRCUIT BREAKER

ACU

SERVICE ENTRANCE, 3 PAHSE

GROUND

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 05
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 42
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
SCHEDULE AND COMPUTATIONS OF LOAD
PANEL BOARD PSI / PS2 / PS3 / PS4 - 60 AF SINGLE PHASE 230V KVAT = 3.503 PANEL BOARD PGEN - 50 AF SINGLE PHASE 230V KVAT = 0.478
MAIN BREAKER 50 AT 2P CB LOCATION Rentable Stalls Grd Flr MAIN BREAKER 32 AT 2P CB LOCATION GROUND FLOOR
MAIN FEEDER 8.00 mm² THHN 24m / 20m / 14m / 8m 2.3 Ω / km FROM KWHRmeter Center KVAM = 2.208 MAIN FEEDER 5.5 mm² THHN 5m 3.6 Ω / km FROM GEN SET KVAM = 0
MINI THHN WIRE - mm² CONDUIT MINI THHN WIRE - mm² CONDUIT
CIRCUIT NO. OF VOLT CIRCUIT NO. OF VOLT
DESCRIPTION VOLTS AMPS BOLT POLES KAIC DESCRIPTION VOLTS AMPS BOLT POLES KAIC
NO. OUTLETS AMPS ON L 1L2 - THHN GRD PVCmmØ NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ
1 18W LED LAMP (+) SIGNAGE 3+1 354 230 1.54 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 1 12W LED SQUARE PINLIGHT 10 120 230 0.52 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 4 576 230 2.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 2 12W LED SQUARE PINLIGHT 15 180 230 0.78 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
3 2.0 HP ACU 1 2760 230 12 32 AT 2 10 2 -------- 5.5 1 -------- 5.5 1-------- 21 3 12W LED SQUARE PINLIGHT 15 180 230 0.78 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
4 SPACE 230 2 4 SPACE 230 2

IPS1 = IPS2 = IPS3 = IPS4 = [ 16.04 + 0.25 (12) ] 0.8 D.F. 2 - 8.0 mm² THHN
IPGEN = 2.08 @ 100% D.F. 2 - 5.5 mm² THHN
= 15.23 AMPS 1 - 5.5 mm² (G)
=2.08 AMPS 1 - 5.5 mm² (G)
USE 50 AT 2P CB 1 - 27 mmØ PVC
USE 32 AT 2P CB 1 - 21 mmØ PVC
PANEL BOARD P1A P1F, P2A P2O, P3A P3O USE 5KW SINGLE PHASE 230V
KVAT = 3.038 GAS ENGINE SMALL GENERATOR
MAIN BREAKER 50 AT 2P CB LOCATION Rentable Stalls GF/SF/TF
MAIN FEEDER 8.00 mm² THHN 2.3 Ω / km FROM Submeter Center KVAM = 1.472
CIRCUIT NO. OF VOLT MINI THHN WIRE - mm² CONDUIT FOR SUBKWHRMETER CENTER 1
DESCRIPTION VOLTS AMPS BOLT POLES KAIC AMPS ISMI = √3 (40.94) ( 0.8 D.F )
NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ LOAD AB BC CA
1 12W LED LAMP (+) 18W LED TUBE (+) EX. FAN 4+1+1 136 230 0.59 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 = 56.73 AMPS
P1A 13.27
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 4 576 230 2.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 USE 100 AT 3P MCCB
P1B 13.27 3 - 30.0 mm² THHN
3 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
P1C 13.27 1 - 8.0 mm² (G)
4 1.0 HP ACU 1 1840 230 8 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
P1D 13.27 1 - 4.1 mmØ PVC
5 SPACE 230 2 L = 20 ƻ = 0.66 Ω / KM
P1E 13.27
I = [ 14.59 + 0.25 (8) ] 0.8 D.F. 2 - 8.0 mm² THHN P1F 13.27
= 13.27 AMPS 1 - 5.5 mm² (G) P1G 13.22 KVAT = √3 56.73 (230) = 22.6
USE 50 AT 2P CB 1 - 27 mmØ PVC P1H 13.22 1000
PANEL BOARD P1G / PIH - 60 AF SINGLE PHASE 230V 60HZ P1J 14.4
KVAT = 3.04
MAIN BREAKER 50 AT 2P CB LOCATION UNITS G & H @ GF FOR MOTOR LOADS:
KVAM = 1.472 TOTAL 39.76 39.76 40.94 KVAM = 9 (8) (230) (0.8 D.F.) = 13.25
MAIN FEEDER 8.00 mm² THHN 5m / 4m 2.3 Ω / km FROM SubKWHRmeter Center 1
MINI 1000
CIRCUIT NO. OF VOLT THHN WIRE - mm² CONDUIT
DESCRIPTION VOLTS AMPS BOLT POLES KAIC
NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ
1 12W LED LAMP (+) 18W LED TUBE (+) EX. FAN 3+1+1 124 230 0.54 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 SUBKWHRM CENTER DISTANCE FROM MAIN METER CENTER FOR ALL SUBKWHRMETER CENTERS
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 4 576 230 2.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 SUBKWHRM CENTER 2A 20 m @ 2ND FLR AND 3RD FLR
3 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.48 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 SUBKWHRM CENTER 2B 35 m
4 1.0 HP ACU 1 1840 230 8.0 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 SUBKWHRM CENTER 2C 40 m
ISMI = 5 (13.27) ( 0.8) KVAT = 53.08 (230) = 12.21
5 SPACE 230 2 SUBKWHRM CENTER 3A 25 m = 53.08 AMPS 1000
SUBKWHRM CENTER 3B 40 m USE 100 AT 2P MCCB
IPIG = IPIH = [ 14.52 + 0.25 (8) ] 0.8 D.F. 2 - 8.0 mm² THHN 2 - 30.0 mm² THHN FOR MOTOR LOADS:
SUBKWHRM CENTER 3C 45 m
=13.22 AMPS 1 - 5.5 mm² (G) 1 - 8.0 mm² (G)
USE 50 AT 2P CB 1 - 27 mmØ PVC 1 - 3.5 mmØ PVC KVAM = 5 (8) (230) 0.8 D.F. = 7.36
PANEL BOARD P1J - 60 AF SINGLE PHASE 230V 60HZ ƻ = 0.66 Ω / KM 1000
KVAT = 3.312
MAIN BREAKER 50 AT 2P CB LOCATION OWNER'S UNIT @ GF
MAIN FEEDER 8.00 mm² THHN 10m 2.3 Ω / km FROM SubKWHRmeter Center 1 KVAM = 1.472
MINI THHN WIRE - mm² CONDUIT
CIRCUIT NO. OF VOLT PANEL BOARD DP2 / DP3 - 150 AF 3PL
DESCRIPTION VOLTS AMPS BOLT POLES KAIC KVAT = 31.073
NO. OUTLETS AMPS ON L1L2 - THHN GRD PVCmmØ MAIN BREAKER 125 AT 3P MCCB LOCATION 2ND FLR / 3RD FLR
1 12W LED LAMP (+) 18W LED TUBE (+) EX. FAN 6+1+1 160 230 0.7 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16 MAIN FEEDER 38 mm² THHN 25 / 30 m 0.55 Ω / km FROM MAIN METER CENTER KVAM = 18.77
2 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 6 864 230 3.8 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 CIRCUIT NO. OF VOLT AMPERES THHN WIRE - mm² CONDUIT
DESCRIPTION VOLTS MCCB POLES KAIC
3 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 NO. OUTLETS AMPS 3Ø AB BC CA AT L1L2 GRD PVCmmØ
4 1.0 HP ACU 1 1840 230 8 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16 1 SUBKWHRMETER CENTER 2A / 3A - 12208 230 53.08 100 2 25 2 -------- 30 1 -------- 8.0 1-------- 35
5 SPACE 230 2 2 SUBKWHRMETER CENTER 2B / 3B - 12208 230 53.08 100 2 25 2 -------- 30 1 -------- 8.0 1-------- 35
3 SUBKWHRMETER CENTER 2C / 3C - 12208 230 53.08 100 2 25 2 -------- 30 1 -------- 8.0 1-------- 35
IPIJ = [ 16 + 0.25 (8) ] 0.8 D.F. 2 - 8.0 mm² THHN
= 14.4 AMPS 1 - 5.5 mm² (G) 4 SPACE 230 2
USE 50 AT 2P CB 1 - 27 mmØ PVC TOTAL 36,624 230 - 53.08 53.08 53.08

PANEL BOARD P1K - 60 AF 3 PHASE 230V 60HZ KVAT = 5.386 IDP2 = 36624 (0.85) 3 - 38 mm² THHN
MAIN BREAKER 50 AT 3P CB LOCATION UTILITY GF √3 230 1 - 14 mm² (G)
MAIN FEEDER 8.00 mm² THHN 18m 2.3 Ω / km FROM KVAM = 1.472 = 78 AMPS 1 - 41 mmØ PVC
AMPERES MINI CONDUIT USE 125 AT 3P MCCB
CIRCUIT NO. OF VOLT THHN WIRE - mm²
DESCRIPTION VOLTS BOLT POLES KAIC
NO. OUTLETS AMPS 3Ø AB BC CA ON L1L2 GRD PVCmmØ
1 12W LED LAMP (+) EXHAUST FAN 11 + 1 202 230 0.88 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
2 12W LED LAMP (+) 18W LED WALL LAMP 18 + 2 240 230 1.04 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
3 12W LED LAMP 18 216 230 0.94 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
4 -do- 20 240 230 2.0 16 AT 2 10 2 -------- 3.5 1 -------- 2.0 1-------- 16
5 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 5 720 230 3.13 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
6 -do- 6 864 230 3.75 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
7 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 7 1008 230 4.4 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
8 DUPLEX CONVENIENCE OUTLETS @ 0.8 d.f. 7 1008 230 4.4 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
9 1 KW SMALL WATER HEATER @ 0.8 d.f. 1 800 230 3.5 20 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
10 1.0 HP ACU 1 1840 230 8.0 25 AT 2 10 2 -------- 3.5 1 -------- 3.5 1-------- 16
11 SPACE 230 2
12 SPACE 230 2
TOTAL 7138 230 - 10.72 10.38 10.94

IPIK = 7138 + 0.25 (1840) 0.8 D.F. 3 - 8.0 mm² THHN FOR 10HP PUMP I = 28 AMPS
√3 230 1 - 5.5 mm² (G) USE 70 AT 3P MCCB
= 15.26 AMPS 1 - 27 mmØ PVC 3 - 8.0 mm² THHN L = 20m
USE 50 AT 3P CB 1 - 5.5 mm² (G) ƻ = 2.3 Ω / km
1 - 27 mmØ PVC
FOR ADMIN PANEL PAD
IT [ 28 + 13.52 + 0.25 (28) ] 0.8 D.F. 3 - 14.0 mm² THHN
=38.82 AMPS 1 - 5.5 mm² (G)
USE 60 AT 3P MCCB 1 - 27 mmØ PVC
L = 5m ƻ = 1.48 Ω / km

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 06
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 43
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
1. LOAD ANALYSIS EQUIVALENT REACTANCE DIAGRAM

BALANCING OF LOADS @ MAIN METER CENTER


AMPERES
LOAD 1.5 x 10-4 p.u.
3Ø AB BC CA IT = [ 301.05 + √3 (30.46) ] 0.9 D.F. KVAT = √3 (318) (230) = 127 KVA
SUBKWHRM CENTER 1 56.73 = 318 AMPS 1000
DP 2 78 USE 400 AT 3P MCCB 0.04 p.u.
DP 3 78 3 - 250 mm² THHN USE 3-50 KVA SINGLE PHASE DISTRIBUTION
1 - 30 mm² (G) TRANSFORMER IN 3 PHASE BANK
PAD 38.32 0.00261 p.u.
1 - 100 mmØ RSC ≈ 150 KVA
PS1 15.23 L=5 ƻ = 0.184 Ω / KM
PS2 15.23 X F
PS3 15.23
PS4 15.23
FUTURE TELCO TOWER 50
TOTAL 301.05 30.46 15.23 15.23 0.021 0.03743 0.00975 p.u. 0.0117 p.u. Xth

0.313 0.2609 0.18261 0.1043 0.04679


2. VOLTAGE DROP CALCULATIONS
0.00187 0.014 0.0187 0.00187 0.014 0.0187
16.984 16.984 16.984 16.984 0.1174 0.13 2.83
VD = C L i ƻ VOLTS % VD = VD 100%
1000 230 5.0951 5.0951 5.0951 5.0951 5.0951 5.0951
OPEN OPEN 3.362
LOAD C i (h) ℓ (m) ƻ Ω / km VD % VD REMARKS
PS1 2 15.23 24 2.3 1.68 0.86 PASSED
PS2 2 15.23 20 2.3 1.4 0.73 PASSED
PS3 2 15.23 14 2.3 0.98 0.55 PASSED
PS4 2 15.23 8 2.3 0.56 0.37 PASSED
PAD 1 38.82 5 1.48 0.56 0.37 PASSED
SUBKWHRM CENTER 1 1 56.73 20 0.66 0.75 0.45 PASSED
SUBKWHRM CENTER 2A 2 53.08 2 0.66 0.14 0.65 PASSED
SUBKWHRM CENTER 2B 2 53.08 15 0.66 1.05 1.05 PASSED USE PER UNIT CALCULATIONS XF = 0.0074 x 150 = 0.021 XPAD= 3.513 p.u. FOR DP3:
XF = 0.0165 x 37.5 = 0.0117 p.u.
SUBKWHRM CENTER 2C 2 53.08 20 0.66 1.4 1.2 PASSED 0.0529 1000 0.0529 1000
DP2 1 78 25 0.55 1.07 0.59 PASSED XS = 150 = 1.5 x 10-4 p.u.
FOR TELCO TOWER: FOR SUBMC3A:
SUBKWHRM CENTER 3A 2 53.08 2 0.66 0.14 0.65 PASSED 1,000,000
Xwi = 0.0165 x 150 = 0.04679 p.u. XL= ꝏ (OPEN) Xwi = 0.00187 XL = 5.0951 XSMC3A = 5.097 p.u
SUBKWHRM CENTER 3B 2 53.08 15 0.66 1.05 1.05 PASSED
Xt = 0.04 p.u.
SUBKWHRM CENTER 3C 2 53.08 20 0.66 1.4 1.2 PASSED 0.0529 1000 FOR SUBMC3B:
XMF = 0.0092 x 150 = 0.00261
DP3 1 78 30 0.55 1.29 0.69 PASSED Xwi = 0.0104 XL = 5.0951 XSMC3B= 5.1091 p.u
0.0529 1000
FUTURE TELCO TOWER 1 (50) 30 0.55 0.83 0.49 PASSED XI = 0.0428 p.u.
FOR SKWHM - 1 FOR SUBMC3C:
MAIN 1 318 5 0.184 0.29 0.13 PASSED Xwi = 0.0132 x 150 = 0.03743 XL= 37.5 = 2.83 Xwi = 0.0187 XL = 5.0951 XSMC3C= 5.11381 p.u
FOR PS1:
X = 2.8676 p.u. 1 = 0.1962 + 0.0384 + 0.1955
Xwi = 0.1104 x 150 = 0.313 XL= 37.5 = 16.984
0.0529 1000 13.25 XL
XPS1 = 17.3 p.u.
XL= 2.325 p.u.
0.0529 1000 2.208
FOR DP2: XDP3= 2.337 p.u.
1 = 0.0578 + 0.058 + 0.0582 + 0.0585 + 0.2846 + 0.3487 + 0.4283 + 0.4279
FOR PS2:
SIMPLIFIED EQUIVALENT REACTANCE DIAGRAM Xwi = 0.092 x 150 = 0.2609 XL= 16.984
XF = 0.01375 x 37.5 = 0.00975 p.u. XLT
0.0529 1000 XLT = 0.5807 p.u.
XPS2 = 17.24 p.u.
0.0529 1000
FOR SUBMC2A:
Xwi = 0.00264 x 37.5 = 0.00187
FOR PS3:
0.0529 1000
Xwi = 0.0644 x 150 = 0.18261 XL= 16.984
XL= 37.5 = 5.0951
XPS3 = 17.167 p.u.
7.36
0.0529 1000
XSMC2A = 5.097 p.u.
0.0428 0.5807 Xth
FOR SUBMC2B:
FOR PS4:
Xwi = 0.0198 x 37.5 = 0.014
Xwi = 0.0368 x 150 = 0.1043 XL= 16.984
0.0529 1000
XPS4 = 17.0883 p.u.
XL= 5.0951
0.0529 1000
XSMC2B= 5.1091 p.u
Xth= 0.0428 (0.5807) = 0.0249 = 0.03986 FOR P1K:
FOR SUBMC2C:
0.0428 + 0.5807 0.6235 Xwi = 0.0414 x 150 = 0.1174 XL= 37.5 = ꝏ
Xwi = 0.0264 x 37.5 = 0.0187
XP1K IS OPEN
0.0529 1000
ISC= 150,000 = 9446 AMPS 0.0529 1000 0
XL= 5.0951
√3 230 (0.03986) XSMC2C= 5.11381 p.u
XPUMP = 0.046 x 150 = 0.13 XL= 37.5 = 3.362
1 = 0.1962 + 0.0384 + 0.1955
USE 400 AT 3P MCCB 25 KAIC XP = 3.492
XL
0.0529 1000 11.154
XL= 2.325 p.u.
XDP2= 2.33475 p.u.
FOR PAD:

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 07
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 44
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
BARE COPPER
BARE COPPER WIRE
A B C D E F WIRE

GROUND ROD

1 "NC" "NC" "NC" TYPE "TA" CONN.

"VS" "VS"
16 12 11 6
"VS"
1 TYPE "NC" CONN.
TYPE "VS" CONN.
2

"NC"
"NC"

"VS" "VS" B GROUND CONNECTION DETAILS


3

500

420
4

12mmØ LIFT BAR


1 8

"NC"
"NC" SOLDERLESS
3/0 SOFT DRAWN
1 4 CONNECTOR
5

"VS" "VS" BARE COOPER

500
250
GRAVEL LAYER
SAND LAYER
6

100 mm² BARE COPPER


WIRE (TYPICAL)
20mmØ x 3000mm 50±
LONG GROUND ROD
GROUND WELL "GW"
7

"NC"
C GROUND PIT DETAIL
"VS"

20 mm²Ø x 3000 LONG


GROUND ROD (TYPICAL)
8

0.200

0.175
0.200
10mmØ HOLE (TYP.)
"VS" "VS" "VS" "VS" TO STEEL STRUCTURE COUNTER SUNK FOR
OF THE BUILDING 5mmØ FLAT HEAD SCREW
9

6mm THK. SHEET METAL


"NC" "NC" "NC" "NC" 6mm THK. SCREWED ONTO WELL COVER
1
FLANGE FLR LVL

0.200
A
5mmØ ANCHOR ROD
6

14
10

12
11
TO OTHER GROUND ROD TO OTHER GROUND ROD

100mm BARE COPPER 20mm Ø x 300mm


0.025 0.150 0.025
GROUND WIRE (TYPICAL) COPPER-WELD GROUND ROD
(TYPICAL)

A STRUCTURE GROUNDING SYSTEM @ GROUND FLOOR


D GROUND ROD WELL DETAIL

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 08
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 45
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
LIGHTNING ARRESTER
(SEE DETAILS)

A B C D E F
COMMUNICATION TOWER

TOP OF ROOF BEAM


1

@ + 14.16 mts
2

DECK FINISHED FLOOR LINE


@ + 11.46 mts
3

THIRD FINISHED FLOOR LINE DOWN CONDUCTOR


@ + 8.01 mts
4

SECOND FINISHED FLOOR LINE


@ + 4.56 mts

LIGHTNING STRIKE COUNTER


5

INSPECTION JOINT
PROTECTION SHEALTH
GROUND FINISHED FLOOR LINE
@ + 0.40 mts
ASSUMED ROAD LEVEL @ GUTTER @ + 00.0
@ + 00.0 mts
6

@ - 1.10

RISER DOWN
B LIGHTING ARRESTER LOCATION (FRONT ELEVATION)
7

DOWN
HELITA PULSAR 60
CONDUCTOR
AIR TERMINAL
EXTENSION MAST
STAINLESS STEEL
8

BOLTS & NUTS 250mm² SOFT DRAWN 3000

40mm
BARE COPPER

BARE COPPER WIRE


LIGHTING ARRESTER DOWN CONDUCTOR
AIR TERMINAL GROUND PIT

170mm
9

(SEE DETAIL)

G.I. MAST (SCHED. 40)

60
00
3/0mm Ø x 3m
COPPER GROUND ROD

80mm
10

D GROUND CONNECTION DETAILS E LIGHTNING STROKE COUNTER DETAIL


A LIGHTING ARRESTER LOCATION C AIR TERMINAL DETAIL
NOTES:

1. ALL CONDITIONS AND DIMENSIONS SHOWN ARE PRIMARILY, PENDING ACTUAL SITE
VERIFICATION BY CONTRACTOR.

2. THE LOCATION OF ALL UTILITY LINES, STRUCTURES AND EQUIPMENT SHOWN ARE
PRELIMINARY; SEE RESPECTIVE ENGINEERING DESIGN DRAWINGS & SPECIFICATIONS.

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM / PF 09
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 46
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F

1
4 8
16 12 11 6 1 21 16 12 11 6 1

5
1 5 9

2
3

3
3
4

4
7
1 8 1 6 11

MONITOR /
1 4 CONTROL 22 17 12
5

5
6

6
7

7
8

8
2
9

9
6
1 21
1

6 16 5

14

B SECOND FLOOR ANCILLARY LAYOUT


10

10
12 12 9
11

LEGEND
CCTV CAMERA
MONITOR / CONTROL
1

A GROUND FLOOR ANCILLARY LAYOUT

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM 10
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 47
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
A B C D E F A B C D E F

1
11
18 14 10

1 5 9
2

2
3

3
4

4
10 12
1 6 11 6 11

22 17 12 22 17 12
5

5
6

6
7

7
8

8
9

9
9
18
1

14
5

10
A THIRD FLOOR ANCILLARY LAYOUT B DECK FLOOR ANCILLARY LAYOUT
10

10
9

LEGEND
CCTV CAMERA
MONITOR / CONTROL

PROFESSIONAL ELECTRICAL ENGINEER IMPORTANT : PROJECT TITLE OWNER: JEA SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract
DESIGNED
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
DRAWN KAM 11
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 48
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of
SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED JEA 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE
FIRE DETECTION AND ALARM
SYSTEM GENERAL NOTES
1. ALL WIRING AND CONDUIT SIZES AND QUANTITIES
SHALL BE IN ACCORDANCE WITH THE FIRE ALARM SYSTEM
@ DECK FLOOR @ THIRD FLOOR MANUFACTURER'S RECOMMENDATIONS, NFPA 70 AND
NFPA 72. COORDINATE ALL WORK WITH THE SPRINKLER,
ZONE 3 SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD EOLR
MECHANICAL, AND ELEVATOR CONTRACTORS.

2. FIRE ALARM RISER DIAGRAM IS DIAGRAMMATIC. RUNS


FA - 3A FA - 3B OF CONDUIT AND MANNER OF CONNECTION SHALL BE
DETERMINED BY THE FIRE ALARM / ELECTRICAL
MPS MPS CONTRACTOR AND IN ACCORDANCE WITH THE FIRE ALARM
ZONE 2 @ SECOND FLOOR SYSTEM MANUFACTURER'S RECOMMENDATIONS, NFPA 70,
NFPA 72, AND THE CONTRACT SPECIFICATIONS.
SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD EOLR
3. ALL FIRE ALARM WIRING SHALL BE INSTALLED 3/4"
FA - 2A FA - 2B CONDUIT (MINIMUM).

4. SEE FLOOR PLAN DRAWINGS FOR THE FIRE ALARM


MPS MPS SYSTEM INITIATING AND NOTIFICATION APPLIANCE DEVICE
ZONE 1 @ SECOND FLOOR LOCATIONS AND QUANTITIES.

SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD SD EOLR
QTY SYMBOL DETAIL
FA - 1A FA - 1B
54 SD PHOTOELECTRIC SMOKE DETECTOR
6 MPS MANUAL STATION
MPS MPS
6 HORN STROBE

FACP 1 set FACP 4 ZONES FACP, W/ BACK UP BATTERY

@ GROUND 4 END OF LINE RESISTOR


FLOOR - 2.0 mm² THHN IN PVC PIPE

4 ZONES WITH
A FDAS RISER DIAGRAM NOTE:
BACK - UP BATTERY
1. FOR FIRE DETECTION AND ALARM SYSTEM, THE SIZE
AND TYPE OF WIRE AND AS FOLLOWS:

A. INITIATING DEVICE LINE - USE 2.00mm² THHN


B. NOTIFICATION DEVICE LINE, USE 2.00mm² THHN
C. POWER SUPPLY LINE, USE 2 - 3.5mm² THHN

HORN / STOBE
UNIT
?" { EMT CONDUIT
SURFACE
STANDARD OR 4" x 4" UTILITY BOX
DEEP 4" (DEEP TYPE)
OCTAGON OR ?" { EMT CONDUIT
SQUARE WIRING
BOX

CEILING SLAB OR ƒ" { EMT CONDUIT


GYPBD.
MANUAL PULL
MOUNTING BASE CONCEALED STATION
STANDARD OR
DEEP 4"
OCTAGON OR 2" x 4" UTILITY BOX
CEILING SLAB OR SQUARE WIRING (DEEP TYPE)
BOX NEW FACP
GYPBD.

2.20
MOUNTING BASE

1.80 m (MAX)

1.80 m (MAX)
DRY WALL
1.22

MULTI - SENSOR SMOKE


DETECTOR MOUNTING DETAIL DRY WALL

HALLWAY
FIN. FLR. LINE FINISHED FLOOR LINE

FRONT VIEW SIDE VIEW

IMPORTANT : PROFESSIONAL ELECTRONICS


PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE OWNER: DESIGNED CM SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract COMMUNICATION ENGINEER
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
CZANDER C. MANALO DRAWN KAM 12
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 49
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of PRC NO. 01075 TIN 230 - 722 - 622 SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED CM 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in PTR NO. 1952978
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE NO. 04 JAN' 24 DATE
A B C D E F A B C D E F

1
16 12 11 6 1 21 16 12 11 6 1

1 5 9

2
SD
SD SD SD SD

SD SD SD SD
3

3
SD

MPS
SD
FA - 2B
4

4
FA - 1B MPS
SD
1 8 SD 1 to FACP
6 11
SD SD
ZONE 2
4 ZONES ZONE 1 SD
1FACP
4 to FACP
22 17 12
5

5
SD SD

SD SD SD
6

6
SD SD

SD

SD SD
7

7
EOLR SD SD SD SD SD
8

8
SD
EOLR SD SD to FACP SD SD

FA - 1A
MPS

to FACP
9

9
MPS
FA - 2A
1 21
1

6 16 5

14
10

10
12 12 9
11

B SECOND FLOOR FIRE DETECTION AND ALARM SYSTEM

A GROUND FLOOR FIRE DETECTION AND ALARM SYSTEM

IMPORTANT : PROFESSIONAL ELECTRONICS


PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE OWNER: DESIGNED CM SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract COMMUNICATION ENGINEER
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
CZANDER C. MANALO DRAWN KAM 13
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 50
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of PRC NO. 01075 TIN 230 - 722 - 622 SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED CM 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in PTR NO. 1952978
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE NO. 04 JAN' 24 DATE
A B C D E F A B C D E F

1
18 14 10

1 5 9

2
SD

SD SD SD SD
3

3
ZONE 3

FA - 3B
4

4
MPS

SD 1 to FACP
6 11 6 11
SD SD DN

to FACP DN
22 17 12 22 17 12
5

5
SD SD SD
6

6
SD

SD
7

7
EOLR SD SD SD SD SD
8

8
to FACP
9

9
MPS
FA - 3A
18
1

14
5

10
10

10
9

A THIRD FLOOR FIRE DETECTION AND ALARM SYSTEM A DECK FLOOR FIRE DETECTION AND ALARM SYSTEM

IMPORTANT : PROFESSIONAL ELECTRONICS


PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE OWNER: DESIGNED CM SHEET CONTENTS SHEET NO.
Drawings and specifications and other contract COMMUNICATION ENGINEER
MVBondoc Architects JOVEN E. ANGELES
documents duly signed, stamped or sealed, as
instruments of service, are the intellectual property and
CZANDER C. MANALO DRAWN KAM 14
16 Edna Street, Globe: 0917-130-8571
documents of the ARCHITECT, whether the object for
which they are made is executed or not. It shall be
THREE STOREY MIXED-USE BUILDING 51
PRC NO. 2756 TIN 120 - 051 - 097 - 002 unlawful for any person to duplicate or to make copies of PRC NO. 01075 TIN 230 - 722 - 622 SPS. REYNALDO & SUSANA COLINDRES AS SHOWN
San Sebastian, Smart: 0920-901-4138 said documents for use in the repetition of and for the CHECKED CM 14
Tarlac City, 2300 PLDT: 045-923-9591 PTR NO. 1951639 other projects or buildings, whether executed partly or in PTR NO. 1952978
[email protected] [email protected] whole, without the written consent of architect or author of ALONG LUMBANG ST., AMPARO SUBD., CALOOCAN CITY METRO MANILA JUNE 2024 ELECTRICAL
DATE NO. 02 JAN' 24 said documents. DATE NO. 04 JAN' 24 DATE