Test Report
Gypsum Test
Customer Name : Perlcon Premix Pvt Ltd. Branch Code : 01
Office Address : 302 Akshay, 53, Shirmali Society Navrangpura, Ahmedabad- Material Code : OT
382009 Sample Ref No. : 60364
Site Name : Perlcon Premix Pvt Ltd., Ahmedabad Record No. : 3303/1-1
Description : Perlcon Gypsum Plaster Bill No : 201920PUN5010
Supplier Name : --- Date of Mat. Recd : 20-Nov-2019
Contact Details : Mr. Sunil Chaursiya & Pravin Rathod - 9850372039 (Route : R1 Date of Testing : 05-Dec-2019
)
Date of Issue : 06-Dec-2019
OBSERVATIONS & CALCULATIONS :
Sr no. Test Unit Test Result
1 Normal Consistency % 48.7
2 Setting Time Minutes 41.0
3 Flexural Strength (1 Day) Kg/cm² 32.0
4 Compressive Strength (1 Day) N/mm² 3.0
5 Compressive Strength (7 Day) N/mm² 7.85
6 Loose Bulk Density Kg/m³ 656
Requirement as per IS 2547(Part-1) - 1976, RA-2002, Amend No.2 'Specification For Gypsum Building Plaster.'
Sr no. Test Unit Plaster of paris Anhydrous Keene's Plaster
Type A (short Type B (Long Gypsum plaster
time setting) time setting)
1 Normal Consistency % - - - -
2 Setting Time Minutes - - - -
3 a) Plaster sand mixture Minutes 45-120 120-900 - -
4 b) Neat Plaster Minutes 10-30 60-180 20-360 20-360
5 Flexural Strength (Min) kg/cm² 5 4* - -
6 Residue on 150um sieve % 5.0 5.0* (1.0)+ 2.0 2.0
(Max)
Requirement as per IS 2547(Part-2) - 1976, RA-2002, 'Specification For Gypsum Building Plaster.'
Sr no. Test Unit Undercoat Plaster(Type A) Final Coat
Browning Metal Lathing Bonding Plaster Plaster(Type B)
Plaster Plaster Finish Plaster
1 Compressive N/mm² 0.93 1.0 1.0 -
Strength(Min.)
2 Loose Bulk Density(Max.) Kg/m³ 640 770 770 -
Regd. Office: 1160/5,Gharpure Colony, Shivaji Nagar,Pune 411005. Maharashtra,India. CIN: U28939PN1999PTC014212. Toll-Free No : 18001206465
References :
1) IS 2547(Part -1 & 2) - 1976,RA-2002 - Specification For Gypsum Building Plasters(Part-I Excluding Premixed Lightweight
Plasters).
2) IS 2542(Part 1/Sec 1 to 12) - 1978,RA-2002 - Methods of test for Gypsum Plaster, Concrete & Products.
Remarks :
1) * Applicable to undercoat plasters only.
2) + Applicable to final coat plasters.
Notes :
1) The test reports and results relate to the particular specimen/sample(s) of the material as delivered/received and tested in the laboratory.
2) Any test report shall not be reproduced except in full,without the written permission from Durocrete.
3) Any alteration/change in the originally printed and issued report, would render this report as INVALID.
This report can be authenticated on our website www.durocrete.com
Authorized Signatory
Irsha Kangude
(Senior Engineer )
Checked by : Dileep Kumar Singh
--End of Report--