Site Test Checklist
Field Result / Value Notes
Output voltage limits are accounted Yes No N/A
for in line with IEC 61851, and error
shutdown is triggered in time as stated
in IEC 61851
Verify that vehicle connector latching Yes No N/A
functions properly
All system components and structures Yes No N/A
have been selected and erected to
withstand the expected external
influences such as wind, sandstorm,
temperature and corrosion
Earth fault, short circuit and Yes No N/A
Overcurrent integrity is verified
according to IEC 61851
User initiated shutdown verified Yes No N/A
Overloading of parallel conductors – Yes No N/A
checked by system design layout
Sleep mode of EV charging pole Yes No N/A
verified according to IEC 61851
Protection against electric shock Yes No N/A
checked in line with IEC 62477-1 and
IEC 62368-1
There is no cascading of two or more Yes No N/A
supply leads
There is no supply of electricity to any Yes No N/A
systems and/or devices other than an
electric vehicle from a charging station
If located in non-domestic premises, Yes No N/A
the charging station is supplied from a
circuit protected by residual current
device (RCD) providing personal
protection.
Site Test Checklist
Verify the RCD type and RCD rating for Yes No N/A
all RCD’s
If located in domestic premises, the Yes No N/A
charging station is supplied by a
dedicated circuit.
Periodic assessment program present Yes No N/A
Record of periodic assessment register Yes No N/A
present
Charging poles comply with UL 2251 Yes No N/A
DC charging poles comply with UL Yes No N/A
2202
EV Charging system components Yes No N/A
comply with IP54 of IEC 60529
Critical EV Charging system compliant Yes No N/A
with IEC 61439-7
Critical EV Charging system compliant Yes No N/A
with external mechanical impact of
IK07 in accordance with IEC 62262
Current protective devices not Yes No N/A
supplied by the charging pole
manufacturer is compatible with the
conductor size
Earth continuity monitoring verified Yes No N/A
Voltage and Frequency marked on the Yes No N/A
charging pole and connector is
compatible with the power supply it is
connected to
The mounting height of EV charging Yes No N/A
pole for Mode 3 or Mode 4 charging
system should be at least 800 mm
above the finished ground or floor
level
Site Test Checklist
Software boot-up and robustness Yes No N/A
verified
Communication interface verified Yes No N/A
between the EV and the
charger/station
Components and equipment installed Yes No
internally or externally do not obstruct
in any way the existing means of
egress
Result Accepted Not Accepted
…………………………………………….
Site Test Checklist
Labelling and identification
Field Result / Value Notes
All circuits, protective devices, Yes No
switches and terminals suitably
labelled to the requirements of IEC
60364
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating
manufacturer's name, initials,
trademark or distinctive marking
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating type
designation or identification number
or any other means of identification,
making it possible to obtain relevant
information
Site Test Checklist
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating,
“Indoor Use Only", or the equivalent, if
intended for indoor use only
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating type
of current
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating
frequency and number of phases in
case of alternating current
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating
rated voltage (input and output if
different)
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating
rated current (input and output if
different) and the ambient
temperature used to determine
the rated current
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating
degree of protection
Site Test Checklist
EV charging pole has a label marked in Yes No N/A
a durable manner and located in a
visible and legible manner stating all
necessary information relating to the
special declared classifications,
characteristics
and diversity factor(s)
Cable assemblies for Mode 1 Case B or Yes No N/A
Mode 3 Case B shall be marked in a
durable manner with manufacturer's
name or trademark
Cable assemblies for Mode 1 Case B or Yes No N/A
Mode 3 Case B shall be marked in a
durable manner with type designation
or identification number or any other
means of identification, making it
possible to obtain relevant information
Cable assemblies for Mode 1 Case B or Yes No N/A
Mode 3 Case B shall be marked with
rated voltage, current, number of
phases and degree of protection
Emergency contact numbers are Yes No
labeled in durable manner and located
in a visible and legible marking
Durability of marking and signs Yes No N/A
checked in accordance with IEC 61851-
1 section 16.5
Result Accepted Not Accepted