SLDdraft - Not Final - Commented - v1.1
SLDdraft - Not Final - Commented - v1.1
161 0.11 0.11 0.11 0.11 kV 161 0.11 0.11 0.11 0.11 kV 161 0.11 0.11 0.11 0.11 kV
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
W1: CL. 3P, 30VA W1: CL. 3P, 30VA W1: CL. 3P, 30VA
W2 : CL. 0.5, 30VA W2 : CL. 0.5, 30VA W2 : CL. 0.5, 30VA
W3 : CL. 0.2, 30VA W3 : CL. 0.2, 30VA W3 : CL. 0.2, 30VA
W4 : CL. 3P, 30VA W4 : CL. 3P, 30VA W4 : CL. 3P, 30VA
Energy Meters
Main + Check
HSES HSES HSES
(Not supply by
M M M
ABB)
see Export line 1
DS DS DS
see Export line 1
M M M
ES BBP + 50BF + internal Check Zone ES ES
161kV Bay Control Unit 161kV Bay Control Unit 161kV Bay Control Unit
CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA
25 A V P Q F 25 A V P Q F 25 A V P Q F
CL. 0.2, 30VA PQM CL. 0.2, 30VA PQM CL. 0.2, 30VA PQM
MAIN-1 (Export Cable) MAIN-1 (Export Cable) MAIN-1 (Export Cable)
DFR
Energy Meters (Main + Check) Not 21 27 49L 21 27 49L 21 27 49L P1 P1 P1 P1
supply by ABB CL. PX CL. PX CL. PX
50N 50 51 51N 50N 50 51 51N 50N 50 51 51N
FROM FROM FROM
59 67N 87L REMOTE 59 67N 87L REMOTE 59 67N 87L REMOTE
CL. PX STATION CL. PX STATION CL. PX STATION
P2 P2 P2
MAIN-2 (Export Cable) MAIN-2 (Export Cable) MAIN-2 (Export Cable) P2 P2 P2 P2
21 27 49L 21 27 49L 21 27 49L
CB CB CB
2000A 50N 50 51 51N 2000A 50N 50 51 51N 2000A 50N 50 51 51N
M FROM M FROM M FROM
50kA 50kA 50kA
59 67N 87L REMOTE 59 67N 87L REMOTE 59 67N 87L REMOTE
STATION 161 0.11 0.11 0.11 kV STATION 161 0.11 0.11 0.11 kV STATION 161 0.11 0.11 0.11 kV
BBP BBP
M 3 3 3 3 M 3 3 3 3 M RHS BusTie Voltage 3 3 3 3 BBP
W1: CL. 3P, 30VA 27, 59, 59Vo W1: CL. 3P, 30VA 27, 59, 59Vo W1: CL. 3P, 30VA
ES ES ES 27, 59, 59Vo
W2: CL. 0.5, 30VA W2: CL. 0.5, 30VA W2: CL. 0.5, 30VA
W3: CL. 3P, 30VA W3: CL. 3P, 30VA W3: CL. 3P, 30VA
W3 to connect to DFR DFR DFR
DFR ? M M M
M M M
Mid TieBus Voltage
DS HSES DS HSES DS HSES
GIS 161kV, 2000A, 3-PH, 60Hz, 25kA / 1s LHS BusTie BCU GIS 161kV, 2000A, 3-PH, 60Hz, 25kA / 1s GIS 161kV, 2000A, 3-PH, 60Hz, 25kA / 1s
M M M M
M M
DS DS DS DS
DS DS
see BusTie 1
M M M M comments M M see Tx2 comments
Main 1 Tx Protection
ES ES ES ES ES ES
87T, 24, 50, 51/67 or 21, 50N, BBP + 50BF +
51N/67N or 21N, 27, 59. internal Check
Zone
CB CB CB CB
2000A 2000A 2000A 2000A
50kA 50kA BCPU (Backup) 50kA BCPU (Backup) 50kA
M M M M
Transformer Protection 25 50 51 50N 51N 25 50 51 50N 51N Transformer Protection
P1 Panel P1 Panel
2000 / 1 / 1 / 1 / 1 / 1 A P1 A V P Q Hz This should be backup P1 A V P Q Hz 2000 / 1 / 1 / 1 / 1 / 1 A
remove this CT
CL. 5P20, 30VA 2000/1/1/1 A protection as BBP is Main 2000/1/1/1 A CL. 5P20, 30VA
MAIN-2 (TRANSFORMER) CL. 5P20, 30VA CL. 5P20, 30VA MAIN-2 (TRANSFORMER)
protection for Busbar,
Feeder Prot. (Main) Feeder Prot. (Main)
50, 51, 50N, 51N
CL. PX 24 50BF 50 50N CL. PX 24 50BF 50 50N
Change to Winding No. 3 50 51 50N 51N 50 51 50N 51N
50G 50G CL. 5P20, 30VA series with DFR CL. 5P20, 30VA series with DFR 50G 50G
51 51N 51 51N
CL. 0.5, 30VA HV MV CL. 0.5, 30VA HV MV
This should be backup protection as
Change to Winding No. 2 87N 87N BBP BBP + 50BF + internal Check BBP 87N 87N
87T BBP is Main protection for Busbar, 87T
5P20, 30VA for Backup OCEF HV MV HV MV
CL. PX
CL. PX 87B Zone 50, 51, 50N, 51N CL. PX 87B
CL. PX
BBP P2 P2 BBP
CL. PX 87B 161kV Bay Control Unit CL. PX 87B 161kV Bay Control Unit
P2 25 A V P Q F P2 25 A V P Q F
Voltage Transformer
3R X 1C X 800 SQ.MM, AL, CABLE 3R X 1C X 800 SQ.MM, AL, CABLE
W1: CL. 0.5, 30VA
W2: CL. 3P, 30VA
W3: CL. 3P, 30VA
49 80 63 26 49 80 63 26
P2 P2
P1 P1
2500/1/1/1/1 A 2500/1/1/1/1 A
CL. 0.5, 30VA BCPU (Backup) CL. 0.5, 30VA BCPU (Backup)
CL. PX CL. PX
P2 P2
ES ES ES ES ES ES ES ES ES ES ES
DS DS DS DS DS DS DS DS see WTG DS DS DS
Feeder Protection Panel see Feeder
AuxTx1 Protection Panel
Feeder Protection Panel Feeder Protection Panel
Typical
M M M M M M M M M M M Typical
BCPU (Backup) BCPU (Backup) BBP + 50BF + internal BCPU (Backup) BCPU (Backup)
BCPU (Backup)
CB CB CB CB CB CB CB CB CB
1250A 50 50N 51 51N 1250A 25 27 59 67 67N 1250A 1250A Check Zone 1250A 1250A 25 27 59 67 67N 1250A 1250A 1250A 50 50N 51 51N
25 50 51 50N 51N P2
40kA 40kA 40kA 40kA 40kA 40kA 40kA 40kA 40kA
M A V P Q Hz M A V P Q Hz M M M 2500/1/1/1 A M A V P Q Hz M M M A V P Q Hz
21, 21N, 46, A V P Q Hz
CL. 5P20, 30VA
P1 P1 67, 67N, 27,
P1 59 P1 P1 P1 P1 P1 P1
Feeder Prot. (Main) Feeder Prot. (Main)
1200/1/1/1/1 A 1200/1/1/1/1 A Feeder Prot. (Main) 1200/1/1/1/1 A 1200/1/1/1/1 A 1200/1/1/1/1 A Feeder Prot. (Main) 1200/1/1/1/1 A Feeder Prot. (Main) 1200/1/1/1/1 A 1200/1/1/1/1 A 1200/1/1/1/1 A
CL. 5P20, 30VA 50G 50G CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA 50G 50G
CT consider to remove if Main Feeder HV MV 21 27 46 49L 21 27 46 49L HV MV
50 51 50N 51N CL. 5P20, 30VA
OCEF relay with backup 64SBEF relay CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA CL. 5P20, 30VA
59 59N 67 67N 59 59N 67 67N
is acceptable by client 50 50N 51 51N 50 50N 51 51N
CL. 0.5, 30VA CL. 0.5, 30VA CL. 0.5, 30VA CL. 0.5, 30VA CL. 0.5, 30VA CL. 0.5, 30VA CL. 0.5, 30VA CL. 0.5, 30VA CL. 0.5, 30VA
Backup OCEF Prot, BBP
BBP BBP
CL. PX
CL. PX CL. PX BBP 50, 51, 50N, 51N CL. PX CL. PX CL. PX 87B CL. PX BBP CL. PX CL. PX CL. PX
87B 87B
P2 P2 P2 P2 P2 P1 P2 P2 P2 P2
87B 87B
M M M M M M M M M
Feeder Prot,
DS DS DS DS DS DS DS DS DS
50, 51, 50N, 51N, 64SBEF
ES ES ES ES ES ES ES ES ES
M M M M M M M M M
Missing CB
BBP + 50BF + internal Check Zone
HSES HSES LINE VT HSES LINE VT HSES LINE VT HSES LINE VT HSES LINE VT HSES LINE VT HSES LINE VT HSES
VT specification ?
From Bus PT From Bus PT
W1: CL 3P, 50VA
W2: CL 0.5, 50VA
W3: CL 3P, 50VA
3R X 1C X 800 SQ.MM, Al, 3R X 1C X 800 SQ.MM, Al, 3R X 1C X 800 SQ.MM, Al, 3R X 1C X 800 SQ.MM, Al, 3R X 1C X 800 SQ.MM, Al, 3R X 1C X 800 SQ.MM, Al, 3R X 1C X 800 SQ.MM, Al,
SUBMARINE CABLE, SUBMARINE CABLE, SUBMARINE CABLE, SUBMARINE CABLE, SUBMARINE CABLE, SUBMARINE CABLE, SUBMARINE CABLE,
XXXX MTRS. XXXX MTRS. XXXX MTRS. XXXX MTRS. XXXX MTRS. XXXX MTRS. XXXX MTRS.
STRING 6 - 4 WTGs STRING 7 - 4 WTGs STRING 2 - 4 WTGs STRING 1 - 4 WTGs STRING 3 - 4 WTGs STRING 4 - 5 WTGs STRING 5 - 5 WTGs
100 / 1 / 1 A 100 / 1 / 1 A
(TYPICAL) (TYPICAL) (TYPICAL) (TYPICAL) (TYPICAL) (TYPICAL) (TYPICAL)
CL. 5P20 CL. 5P20
CL. 5P20 synchrocheck scheme , or just put ansi code 25 at BCU will be CL. 5P20
understood ? Because 161kV is not showing this detail.
Normally this is not shown in SLD
CL. 5P20 CL. 5P20
P2 P2
49 80 63 26 49 80 63 26
EARTHING AUX. TRAFO. EARTHING AUX. TRAFO.
P1 66kV / 400V, 630 KVA (ONAN), ZNyn11(d) P1 66kV / 400V, 630 KVA (ONAN), ZNyn11(d)
Uk 5%, Uk0 0.65% Uk 5%, Uk0 0.65%
CL. 5P20 P1 CL. 5P20 P1
CL. 5P20 CL. 5P20