TECHNICAL DATA SHEET
3.5 C X 400 Sq Mm A2XFY - STR/XLPE/HDPE-T/STRIP ARMD/PVC(ST2)
"GLOSTER", 1100Volts, Stranded Aluminium Conductor, XLPE Insulated, Wrapped Thermoplastic Tape
Inner Sheath, Galvanized Steel Strip Armoured & Overall PVC ST2 Sheathed Power Cable Conforming to
IS: 7098 (Part 1) - 1988 as amended up to date.
Sno Particulars Units Description
1.0 Manufacture & Country GLOSTER CABLES LIMITED ,
0 Type of Cable INDIA A2XFY
2.0 Applicable Standard IS: 7098 (PART-1) -1988
0 Rated Volt 1100 VOLTS
3.0 Voltage s Hz 50
0
Frequency % Voltage ±10, Frequency
4.0 ±5
Permissible Voltage/Frequency Nos
0
Variation Number of Cores 3.5
5.0
0
6.0
0
7.0
0
Conductor
8.1 Material H2/ H4 grade Aluminium conductor Class 2 to IS: 8130
0 - 2013
Nominal Cross Sectional Sqm
8.2 Area Shape of Conductor m 400/185
0 Stranded Compacted Sector shape
8.3
0
Insulation
9.1 Material XLPE to IS: 7098 (Part 1) - 1988
0 Nominal Thickness of mm 2.00/1.60
9.2 Insulation Tolerance on m The Smallest measured values of thickness of Insulation shall not fall below
0 Thickness the Nominal
m
9.3 value (ti) by more than 0.1mm+0.1mm(ti)
0 Minimum Volume Resistivity of Insulation at 27 ºC is 1x10^14 & at 90 ºC is
Specific Insulation Ohm-
Resistance Core Cm 1x10^12 Red,Yellow,Blue & Black
9.4
0 Identification
9.5
0
Inner Sheath
10.1 Material Thermoplastic
0 Minimum Thickness of Inner Sheath mm Tape 0.70
10.2
0
Armouring
11.1 Materia Single Layer Galvanized Steel Strip to IS: 3975 - 1999
0 l
11.20 Nominal Dimensions of Strip mm 4.00X0.80 ±
Outer Sheath 10%
12.10 Material
PVC Type ST-2 to IS 5831-
1984
12.2 Minimum Thickness of Outer Sheath mm 2.52
0
12.30 Colour of Outer Sheath BLACK
12.4 Approximate Overall Diameter mm 61.00 ± 3 mm
0
Electrical Parameters
13.10 Max DC Resistance at Ohm/ 0.0778/0.164
20°C
Km 0.1020/0.211
13.20 Max. AC resistance at
Ohm-
90°C
Km
13.30 Approx. Reactance @ 50Hz For XLPE Insula Ohm/km 0.07
13.40 Approx. Capacitance For XLPE µF/Km 0.67
Insulation olts/Km/Am 0.22
13.50 Approx. Estimated Voltage Drops p
in XLPE Cables Aluminium
Conductor
420
Continuous Current rating of the Cable under Sta Amp 356
14.10 In Ground at 30°C
s
14.20 In Duct at 30°C
Amp
s
14.3 In Air at Amps 526
0 40°C
15.00 Maximum Permissible Short Circuit Cu rrent
15.10 Duration KA 37.6
Maximum Conductor Temperature 0
Sec
16.10 Continuous Operation ONE
°C
90
16.2 Short Circuit Operation °C 250
0
17.00 Drum Length with Tolerance
mt 500/1000 ±5% (5% of ordered quantity shall be in NSL with min length of
18.00 Recommended Minimum Bending
r 100 mtr) 12 X Overall diameter of the cable
Radius
Recommended Maximum Pulling Force, When m
m
19.1 Pulled by Pulling Eye N/ 30
0 mm2
19.2 Pulled by Stocking N P=9X
0 D²
0
20.10
20.20
20.30
20.40
20.50
Additional Features
Sequential Marking Shall be provided on outer sheath of cable at every 1 mtr interval
Embossing on Outer Sheath GLOSTER HEAVY DUTY 1100 V 400.00 Sqmm XLPE ELECTRIC CABLE ST2 IS : 7098 PART-I : ISI CM/L-6353669/ISI CM/L-4410645