SFA-RM36.
F
SF6 GAS INSULATED MODULAR RMU
TRANSFORMER PROTECTION FEEDER WITH SWITCH-FUSE COMBINATION
Technical Drawings
All pictures below are only for information. Please contact SFA Electric for technical drawings of Specific Projects.
Front View Front View with Dimensions Single Line Diagram
Side View Base Detail
CLASSIFICATION: INTERNAL
SFA-RM36.F Components
The components of RMU are listed below.
1 unit Of 36kv, 630A, 16ka Modular RM36.F Gas Tank
1 unit Of RM-36.F Frame And Enclosure
1 unit Of Switch – Fuse Combination Mechanism
1 unit Of Fuse Trip Mechanisim
3 units Of Fuse Holder and Cover
6 units Of Connex Bushings
3 units Of B-Interface, Sliding Type Plug-in Bushings
Coil Voltage : 48 VDC
Earth Fault Indicator
Excluded : X Included : Brand :
Motor :
Excluded : Included : X Voltage : 48VDC
Cable Connector :
Excluded : Included : x Brand: Cellpack Brand
Fuse :
Excluded: Included : x Rating : Interteknik – 20 A
CLASSIFICATION: INTERNAL
Technical Characretistics
General Characteristics
Rated Voltage kV 36
Rated Lightning Impulse Withstand Voltage kV-
peak
Phase To Earth, Between The Phases 170
Across The Isolating Distance 195
Rated Power Frequency Withstand Voltage kV
Phase To Earth, Between The Phases 70
Across The Isolating Distance 80
Rated Normal Current (Main busbar) A 630
Rated Frequency Hz 50
Number Of Phase 3
Rated Short-Circuit Withstand Current kA 16
Rated Peak Withstand Current kA-p 40
Duration Of Short-Circuit s 1
IP Class
Switching Compartment IP 67
Cable Compartment IP 2X
HV Fuse Link Compartment
Operating Mechanism IP 3X
Compartment IP 2X
Loss of Service Continuity LSC 2A
Switchgear Classification PM
Internal Arc Classification (IAC) A (FLR)
Rated Filling Level For Insulation bar 1.10 (abs.)
Minimum Functional Level For Insulation bar 1.05 (abs.)
Ambient Temperature °C -5 < T < 40
Altitude m <2000
Overall Dimensions (Height X Width X Depth) mm 1800x500x935
Weight kg
CLASSIFICATION: INTERNAL
Switching Device
Type of switch General,
three
positioned
(open-close-
earth) switch-
disconnector
Type number SFA-RM-
630A-16kA
LBS
Electrical endurance class E3
Mechanical endurance class M1 (1000
times)
Rated normal current A 200
Rated frequency Hz 50/60
Number of phase 3
Rated short-circuit withstand current kA 16
Rated peak withstand current kA-p 40
Duration of short-circuit s 1
Short – circuit making current (peak) kA-p 50
TD load1, TD load2 (mainly active load) A 630
TD loop (closed-loop distribution) A 630
TD cc1 and TDcc2 (cable-charging A 20
TD lc (line-charging) A 2
TD Itr (transfer current) A 470
TD ef1 (earth fault) 60
TD ef2 (cable and line earth fault) 35
TD ma (line) kA-p 40
TD ma (earthing) kA-p 40
Earthing Switch At Upstream
Type number SFA-RM-
16kA ES
Rated short-circuit withstand current kA 16
Rated peak withstand current kA-p 40
Duration of short-circuit s 1
Short –circuit making current kA-p 40
Electrical endurance class E2 (5 times
making)
CLASSIFICATION: INTERNAL
Earthing Switch At Downstream
Type number FT-Y-001
Rated short-circuit withstand current kA 1 kA-
1second
Short–circuit making current kA-p 2.5 kA
Electrical endurance class E2 (5 times
making)
Operating Mechanism
Type number SFA-RM-
16kA ES
Rated short-circuit withstand current kA 16
Rated peak withstand current kA 40
Duration of short-circuit s 1
Short – circuit making current kA 40
Electrical endurance class E2 (5 times
making)
Related Standards
IEC 62271 – 102 Alternating Current Disconnectors and Earthing Switches
IEC 62271 – 103 Switches for Rated Voltages between 1kV and 52kV
IEC 62271 – 105 Alternating Current Switch-Fuse Combinations
IEC 62271 – 200 AC Metal Enclosed Switchgear and Controlgear
IEC 62271 – 206 VPIS systems for Rated Voltages Between 1kV and 52kV
IEC 62271 – 1 HV Switchgear and Controlgear : Common Spesifications
IEC 61243 – 5 Voltage Detecting Systems