Kidde KC2-OSH-CD Two-Wire Conventional Optical Smoke and Heat Combination Detector K-70-370

The KC2-OSH-CD is a two-wire conventional smoke and heat combination detector that features photoelectric smoke detection and dual heat detection capabilities. It is designed for commercial and industrial environments, offering advanced alarm verification to reduce false alarms, and is compatible with various Kidde Fire Systems control units. The detector includes self-diagnostic capabilities, a low-profile design, and is listed by multiple safety standards organizations.

Uploaded by

Jun Antonio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
160 views2 pages

Kidde KC2-OSH-CD Two-Wire Conventional Optical Smoke and Heat Combination Detector K-70-370

The KC2-OSH-CD is a two-wire conventional smoke and heat combination detector that features photoelectric smoke detection and dual heat detection capabilities. It is designed for commercial and industrial environments, offering advanced alarm verification to reduce false alarms, and is compatible with various Kidde Fire Systems control units. The detector includes self-diagnostic capabilities, a low-profile design, and is listed by multiple safety standards organizations.

Uploaded by

Jun Antonio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

KC2-OSH-CD Two-Wire

Conventional Smoke and Heat


Combination Detector
Effective: October 2022
K-70-370
STANDARD FEATURES
• Photoelectric Smoke Detection and Dual Rate-of- • Self-diagnostic capability continually monitors
Rise and Fixed-Temperature Heat Detection In One operation
Two-Wire Conventional Detector • Remote LED indicator available
• Multi-criteria optical smoke sensing technology • Low-profile design blends into the ceiling
• ™
Compatible with Kidde Fire Systems AEGIS 2.0 • FM Approved
and AEGIS™-XLT Conventional Control Units • cULus Listed
• Advanced alarm verification feature reduces • California State Fire Marshal Listed
chance of nuisance alarms

DESCRIPTION INSTALLATION
The KC2 Optical Smoke and Heat KC2 Standard and Relay bases mount to:
Combination Detector is a conven- • North American single-gang box
tional low-profile, self-diagnostic, • Octagon box 3-1/2 in. (89 mm) by 1-1/2 in. (38 mm) deep
two-wire photoelectric smoke detec- • Octagon box 4 in. (102 mm) by 1-1/2 in. (38 mm) deep
tor combined with a rate-of-rise and • European single-gang box 75 mm with 60.3 mm fixing centers
fixed-temperature heat sensor. The • BESA box with 60.3 mm fixing centers
advanced photoelectric sensing • Square box 4 in. (102 mm) by 1-1/2 in. (38 mm) deep
chamber detects smoke from a fire (KC2-SB4 or KC2-RB4 base required)
versus nuisance smoke from non-
fire sources. The rate-of-rise heat Pin 2: Positive IN / Positive OUT
sensor quickly detects a fast, flam- To Remote LED+ Pin 4: Negative IN
ing fire. The fixed-temperature heat Pin 7: Negative OUT
To Remote LED-
sensor detects fire when the air temperature near the detector
exceeds the alarm point of 135 °F (nominal). Advanced smoke 5 6 5 6
detection combined with heat detection makes the KC2-OSH-CD 4 7 4 7
detector suitable not only for commercial and industrial environ-
3 1 3 1
ments, but also life safety protection. 2 2

COMPATIBLE BASES
CLASS B WIRING
The KC2-OSH-CD detector head attaches easily to either a KC2-SB
EOL RESISTOR
Standard or KC2-RB Relay Base. Detector bases have wiring 1- 2- 2+ 1+ 5.1K, 0.5 W
terminals that are accessible from the “room-side” after mounting the P/N 06-220184-001
base to the electrical box.
• Model KC2-SB/-SB4 Standard Base: Connects the detector to TB1, TB2, TB3
circuit. (AEGIS panel terminals)
• Model KC2-RB/-RB4 Relay Base: Connects the detector to circuit
Pin 2: Positive IN / Positive OUT
and provides optional Relay functionality to the KC2 series detec- To Remote LED+ Pin 4: Negative IN
tor. (The base’s relay contacts automatically change state when To Remote LED-
Pin 7: Negative OUT
detector goes into Alarm.)

TRIM SKIRT
5 6 5 6
A trim skirt is supplied with the KC2-SB4 and KC2-RB4 bases to help 4 4
7 7
hide mounting tabs. The GSA-TS trim skirt may optionally be ordered
3 1 3 1
for KC2-RB or KC2-SB bases if desired. 2 2

STATUS LED
KC2-OSH-CD detectors use an LED to indicate the detector’s condi- CLASS A WIRING
tion. A flashing green LED every 30 seconds indicates Normal con-
1- 2- 2+ 1+
dition. A Trouble condition is indicated by a flashing green LED every
5 seconds. A steady red LED indicates an Alarm condition. An
optional Remote LED Indicator is available for convenient viewing. EOL RESISTOR
TB1, TB2, TB3 5.1K, 0.5 W
(AEGIS panel terminals) P/N 06-220184-001
TECHNICAL SPECIFICATIONS

Electrical/Environmental Physical
Operating Voltage 6.5 to 33 VDC Color White head and base

88 µA at 18 VDC Detector Head 4.375 in. D x 2.25 in. H


Standby Current
145 µA at 33 VDC Dimensions (11.10 cm x 5.70 cm)

up to 60 mA maximum, 4.4 in. D x 0.75 in. H


Alarm Current Base Dimensions
if not limited by control unit (11.18 cm x 1.90 cm)

Remote LED 0.225 mA average Total Height


2.625 in. (6.67 cm) H
Output Current (50 msec ON, 1 sec OFF) (head and base)

Reset Voltage 2.5 V, maximum


ORDERING INFORMATION
Reset Time 1 second, minimum
KC2-OSH-CD Optical Smoke and Heat Combination
10 to 35 Hz, Detector, head only, two-wire
Vibration Level
with an amplitude of 0.01 in.
KC2-SB Standard Base for KC2 Series Detectors
Photoelectric 0.5 to 4.36 %/ft. obscuration with output for Remote LED, 4 in. diameter
Sensitivity (1.63 to 13.62 %/m)
KC2-SB4 Standard Base for KC2 Series Detectors
Air velocity 0 to 4000 ft/min (0 to 20.32 m/s) with output for Remote LED, 4 in. diameter
Rate-of-rise 15 °F/min (8 °C/min) (with tabs for 4-in. square box; includes
trim skirt)
Fixed Temperature 135 °F (57.2 °C)
KC2-RB Relay Base for KC2 Series Detectors, 4 in.
Actual Alarm Point 129 to 141 °F (53.9 to 60.6 °C) diameter

Environmental KC2-RB4 Relay Base for KC2 Series Detectors, 4 in.


Automatic
Compensation diameter (with tabs for 4-in. square box;
includes trim skirt)
Response Time Index
(evaluated by FM Quick GSA-TS Optional Trim Skirt for KC2 Series Bases
Approvals)
GSA-LED Optional Remote LED Alarm Indicator (for
Operating use with KC2-SB and KC2-SB4 Standard
32°F to 100°F (0°C to 38°C) Bases Only)
Temperature Range

Relative Humidity SIGA-RTA Optional Removal Tool (attaches to


0 to 93% noncondensing standard telescoping pole)
Range

Storage Temperature -4 to 140 °F (-20 to 60 °C) SM200-12PKG Canned smoke for functional testing of
smoke detectors
Normal = Green every 30 seconds
LED Indicator Alarm = Steady Red
Trouble = Green every 5 seconds
NOTE: Refer to Kidde Fire Systems Datasheet Number
UL Two-Wire Detector K-70-300 for smoke detector compatibility.
S10AR2
Compatibility Identifier

KC2-SB, KC2-SB4, KC2-RB,


Compatible Bases
KC2-RB4

Wall Mounting:
12 in. (305 mm) maximum
Distance from Ceiling
Kidde is a registered trademark of Kidde-Fenwal, Inc. or its parents, subsidiaries or affiliates.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. believes this data to be accurate, but it is published and presented
without any guarantee or warranty whatsoever. KIDDE-FENWAL, INC. assumes no responsibility for the product's suitability for a particular
application. The fire suppression system design, installation, maintenance, service and troubleshooting must be performed by trained, authorized
Kidde Fire Systems distributors for the product to work correctly. If you need more information on this product, or if you have a particular problem or
question, contact: KIDDE-FENWAL, INC., Ashland, MA 01721 USA, Telephone: (508) 881-2000.
Kidde Fire Systems
400 Main Street
K-70-370 Rev AB Ashland, MA 01721 USA
Ph: 508.881.2000
© 2022 Carrier
www.kiddefiresystems.com

You might also like