بسم هللا الرحمن الرحيم
What is the Classic
Control?
Eng./Mohamed Fathy
00201147207593
Mohamed Fathy
Mohamed Fathy 1
Topic
History of Automation.
What is the Classic control?
Classic control components.
Classic control applications.
Advantages of classic control
Why we replaced it with PLC?
Mohamed Fathy 2
Mohamed Fathy
NO AUTOMATION
Mohamed Fathy 3
Mohamed Fathy
Automation
Remotely Industrial operation to get economic production with specific standards
Saving time ,money and eliminate human errors.
Mohamed Fathy 4
Mohamed Fathy
Classic Control
Relay logic control
Is a control system used remotely control the process to obtain final
product with an economic and standard specification .
Invented with electromagnetic relays and contactors
Mohamed Fathy 5
Automated Control system
Contactor
PUMP
Mohamed Fathy 6
Mohamed Fathy
Push button
NO
NC
proximity switch
•Principle of Operation:
•Proximity Switch consists a sensor circuit and a driver
circuit.
•The sensor circuit purpose is used to detect any near
by objects.
•The sensor circuit sends an output High signal to the
transistor based driver circuit when any object found
near to the sensor circuit.
Relay
Relay “Josef Henry 1835”
• An electromagnetic device used for remote or automatic control.
• Is the link between low power digital electronic and High power devices.
Mohamed Fathy 9
Mohamed Fathy
Relay construction
•A relay is an electrically operated switch used for a single or multiple control
signals.
• Coil
• Movable armature
• Set of input terminals.
Mohamed Fathy 10
Mohamed Fathy
Relay types
Contactor
A contactor is an electrically-controlled switch used for switching
an electrical power circuit
Contactor current should be more than load current to achieve long
life time and not much more for the economic side
Link between low level power (coil) and High level power
(Motor power)
A contactor has three components:
Iron core
Main point
Helping point
Mohamed Fathy 12
Contactor
Input point : (1 -3 -5) , (L1- L2- L3 ) , (R-T- S)
Output point : (2-4-6) , (T1-T2-T3) , (U -V -W)
Helping point: low voltage points for control
circuit can be increased by external pieces
Relay Contactor
electrically-controlled switch
Coil + NO +NC
Has Main points and auxiliary points
1 phase not recommended to use 3 phase high current (3 Phase)
Has no ARC shutdown has ARC shutdown
Main contacts are the same auxiliary Main contacts not the same auxiliary
Need abase with the same number of legs Can increase auxiliary points
Thermal over load
Protect motor from high current as the thermal over loading or over heating of the
motor may lead to insulation failure and damage of winding.
Do not protect circuit from short circuit current
Between Contactor and motor
Thermal over load
(U - V - W) ) 5- 3 - 1( to contactor directly
(T1 T2 T3 ) ( 2-4-6) TO power circuit (Motor)
Auxiliary points
(95-96 NC) alarm lamp or sound
(97-98 NO) helping points to control circuit
Test button (test auxiliary points)
Pointer to select Current cut off Range according to motor range.
Reset button (M manually –A automatically)
Stop button ( Disconnect the Main points (Open ))
Circuit breaker(CBs)
Protection from short circuit ,over load current , earth leakage
MCB (Miniature circuit breaker)
MCCB (Molded Case Circuit Breaker”)
MCB (Miniature circuit breaker)
Rated current (amp): selected according to load current
MCB (“Miniature Circuit Breaker) its rated current up to 100A
6A 10A 16A 20A 25A 32A 40A
Short circuit current “interrupt rating” (KA) : max current can
withstand on short circuit (Short Circuit Capacity) for a few seconds
interrupt rating is up to 1800 amps
3KA 6KA 10KA 80KA 100KA
MCB
1- C60H
C60 : Product Model Number
H : Type Breaking Capacity ,
2 -C Tripping Curve Type
63 :Max .Current Rating
In: Rated Current of C.B (AMP) depend On KVA Of load
Standard values:6A , 10A , 16A , 20A , 25A , 32A , 40A , 50A , 63A
4 - 415 V ͠ : Rated operational Voltage (Ue)
5-Breaking Capacity Icu OR Icn (KA) 10000
6- Energy degree-3
MCCB (Molded Case Circuit Breaker”)
Rated current :
selected according to load current up to 2500 A
Interrupt rating
Short circuit current “interrupt rating” (KA) : max current can
withstand on short circuit (Short Circuit Capacity) for a few seconds
10KA-200KA
Timers
1- ON DELAY
2- OFF DELAY
3-ON/OFF DELAY
Classic control Industrial process Design
The prepose (Function)of the industrial process (control tank level).
Power circuit (load motor and protection devices)
and Control circuit (coils –operating devices)
design and Simulation
Design (Autocade)
Simulation (Automation studio or EKTS).
Select components.
Implement the circuit .
Mohamed Fathy 22
Mohamed Fathy
1 Start / 1 stop
2 start /1 stop
1start /2 off
M1 (ANY TIME ) M2 (ONLY WITH M1)
M1 (ANY TIME ) M2( WITH M1) (M3 WITH M2)
L1 when (on) -L2 (off) - L3 ( OL operate)
Motor operate at two directions
Motor operate on two direction by limit
switches and stop by off push button
M1 (operate any time ) M2 (operate after M1 by certain time)
Classic Control Panel
Mohamed Fathy 33
Mohamed Fathy
Classic Control system example
Contactor
PUMP
Mohamed Fathy 34
Mohamed Fathy
Classic control Applications
Mohamed Fathy 35
Mohamed Fathy
Relay Logic Control with large industries
Mohamed Fathy 36
Mohamed Fathy
Classic Control Disadvantages
Use Limit Input Outputs.
Complex to implement.
Troubleshooting and maintenance is difficult.
Reconfiguration is difficult.
huge space required.
Wiring complexity.
More maintenance
Mohamed Fathy 37
Mohamed Fathy
Wish you Have some useful information
Mohamed Fathy