Technical Datasheet
ENER-G 125 (Low NOx) Natural Gas CHP Unit
Energy Balance and Load Data at Power Factor 1 Units 100% 75%*** 50%***
Electrical Output (+/-3%) kW 124 93 62
Electrical Efficiency (Net) (+/-5%) % 34.3% 32.5% 29.6%
Heat Output (+/-10%) kW 200 166 126
Thermal Efficiency (Net) (+/-8%) % 55.4% 58.0% 60.3%
Fuel Input (Net / Gross)* (+/-5%) kW 361 / 399 286 / 316 209 / 231
Total Efficiency (Net) (+/-8%) % 89.7% 90.5% 89.9%
Heat Output from Jacket Water (+/-8%) kW 131 111 88
Heat Output from Exhaust Gas @ Outlet Temp. (+/-8%) kW 69 55 38
Aftercooler Heat Output (+/-8%) kW N/A N/A N/A
Radiated Heat Output (+/-8%) kW 14 11 7
3
Combustion Air Flow (30 °C, 100 kPa, 30% RH)** (+/-5%) m /h 380 308 226
Fuel Mass Flow (ρ = 0.75kg/Nm³) (+/-5%) kg/h 27.1 21.5 15.7
Fuel Volume Flow (LHV = 10kWh/Nm³) (+/-5%) Nm3/h 36.1 28.6 20.9
Exhaust Mass Flow (Wet) (+/-5%) kg/h 475 385 281
3
Exhaust Volume Flow @ Outlet Temp. (+/-5%) m /h 529 429 313
*Natural gas Net and Gross fuel input figures are based on 36MJ/Nm3 and 39.8MJ/Nm3 respectively. The Gross figure is used when establishing UK fuel costs. Net figures are provided for ease of performance comparison with
other technologies. Fuel must comply with engine manufacturer's fuel quality guide, supplied seperately.
**Engine technical data is based on Standard Conditions according to DIN ISO 3046-1 but engine de-rate applies when Combustion Air Temperature is >25°C.
*** If operating at part load for long periods of time, the unit should be run at full load for at least 5 hours in a given 24 hour period.
Engine Details Generator Details
Manufacturer … … … … … … … … … … … … … … .… ENER-G Manufacturer … … … … … … … … … … … … …. … … Stamford
Model … … … … … … … … … … … … … … … … … EGE-06L Model ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
. ... UCI274H-311
Fuel Type ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .... ... ... ... ... ... ... ...Natural Gas Type ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ....... ... Synchronous
Min. Methane Number ... ... ... ... ... ... ... ... ... .... ... ... ... ... ... ... ... ... ... ... ... 70 ... ... Rating ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
kVA ... ... 200
Cylinders ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
. ... ... ... 6 Voltage ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...V... ... 400
Aspiration ... ... ... ... ... ... ... ... ... ... ... ... ... ... .... ... Natural Phase ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...Ph... 3
Speed ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...rpm
... ... ... ... ... ... ... ... 1500 Frequency ... ... ... ... ... ... ... ... ... ... ... ... ... ... Hz... ... … 50
Aftercooler ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . ... ... ... ... ... ... No Protection Class ... ... ... ... ... ... ... ... ... ... ... ... . ... IP23
Rated Power Factor ... ... ... ... ... ... ... ... ... ...PF ... ... ... ... ... ... ... … 0.8
Hot Water Details Xd Dir. Axis Synchronous ... ... ... ... ... ... ... .... ... ... ... ... 1.91
Max. Water In/Out Temp. ... ... ... ... ... ... ... ... ... °C.. 80/90°C X'd Dir. Axis Transient ... ... ... ... ... ... ... ... .... ... ... 0.16
Max. Water Flow Rate* ... ... ... ... ... ... ... ... ... ..l/s 4.92 X"d Dir. Axis Sub-Transient ... ... ... ... ... ... .... ... ... 0.11
Max. Glycol Content ... ... ... ... ... ... ... … … … …%… … … … 30 T" Sub-Transient Time Const. ... ... ... ... ... .... ... 0.012
Connection Size ... ... ... ... ... ... ... ... ... ... mm 50 T'do O.C Field Time Const. ... ... ... ... ... ... ... .... 1.1
Flange Type ... ... ... ... ... ... ... ... ... ... ... ... ... ... .... .. PN16 CHP Protection Device … … … … … … … … … A/Ph …………… 225
Pressure Loss** … … … … … … … … … … … … … k…Pa 20.9 Indicative Client Protection Device … … … …A/Ph … … … … … 250 … …(Adjustable)
………
Max. Test Pressure ... ... ... ... ... ... ... ... ... ... ... ... Bar 9.75 Current Per Phase @ 0.8PF ... ... ... ... ... ... ...A... ... ... ... ... ... ... ... ... 220...
* Assuming Cp = 4.2 kJ/kg·K and ρ = 968.55 kg/m³ Current Per Phase @ 0.95PF ... ... ... ... ... ... A ... ... ... ... ... ... ... ... ...188
... ...
** Pressure loss figures stated are at max. water flow rate. Internal unit only. Efficiency @ 0.8PF... ... ... ... ... ... ... ... ... ... ...%... ... ... ... ... 93.8%
Efficiency @ 0.95PF... ... ... ... ... ... ... ... ... ... % ... ... ... ... ... ... 95.0%
2
Exhaust Details Indicative Main Cable Size ᵃ † … … … … … … mm … … … … … … … … TBC
2
Connection Size ... ... ... ... ... ... ... ... ... ... mm 125 Indicative Earth Cable Size ᵇ † … … … … … …mm … … … … … … … … TBC
Flange Type ... ... ... ... ... ... ... ... ... ... … … … … . PN16 ᵃ 4-Core XLPE/SWA/PVC to BS5467, Max 50 meters.
Outlet Temp***. ... ... ... ... ... ... ... ... ... … … … … °C… … … … 120 ᵇ 1-Core 6491B to BS7211, Max 50 meters.
Allowable Backpressure ... ... ... … … … … … … …Pa 2870 † Sizes and lengths based on IET 17TH Edition BS7671, Installation method 31.
Allowable Backpressure with Catalyst... ... ... …Pa ……………… 1150
*** For engines with exhaust bypass, please request exhaust bypass temp. from ECPL. Fuel Details
Connection Size ... ... ... ... ... ... ... ... ... ... mm 40
Ventilation Details Flange Type … … … … … … … … … … … … … . PN16
Connection Size ... ... ... ... ... ... ... ... ... ... ... ... ...mm
... ... 500 Min/Max. Supply Pressure … … … … mbar 20/55
Ventilation Rate**** ... ... ... ... ... ... ... ... ... ... ... m3.../s... . 1.49
Max. Air Inlet Temp. ... ... ... ... ... ... ... ... ... ... ...°C... .. 30 Emissions @ 5% O2
Max. Air Outlet Temp. … … … … … … … … … … … °C… … … 45 NOx ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . mg/Nm3 3676
Enclosure Pressure Drop … … … … … … … … … … Pa… … … … 108 CO ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. mg/Nm3 2163
**** Vent rate is stated at max. air outlet temp, 100kPa NOx ... ... ... (With
... ... ...Catalyst)
... ... ... ....................................…...…...…... ...3... ... ... ... ... …
mg/Nm <50……
3
CO ... ... ... ...(With
... ... ...
Catalyst)
... ... ... ... ... ... ... ... ... ...mg/Nm ... ... ... ... ...
…… ... ... ...<150
... ... ... ... ... ... … …
Weight Details
Enclosure (Dry) ... ... STD/PREM. ... … … … … … … See Sales Drawing
Container (Dry) ... ... STD/PREM. ... … … … … … … See Sales Drawing
Noise Data
Enclosure SPL @ 1m ... ... ... ... ...
SN/LN
... ... …
... …
... …
...dB(A)
…... ... ... ... ... ...70/64.99
... ... ... ... ... … …
Container SPL @ 1m … … … … … SN/LN
……… … … …dB(A) … 75/65
NB: Output figures are based on operation at DIN ISO 3046-1 conditions with the exception of exhaust output, which is quoted to 120°C/180°C for Natural Gas/Biogas respectively, figures are stated from manufacturer's declared performance figures subject to the manufacturer's tolerances and subject
to change without notice. Values for de-rated units are estimates only. Energy balance data assumes perfect combustion. All information detailed is for guidance only and is subject to change without notice due to our commitment to continuous improvement - all values should be confirmed with
Centrica Business Solutions on a project specific basis.
Datasheet Issue Date 30/05/2018 T: +44 161 745 7450 Edison House
Datasheet Revision A F: +44 161 745 7457 2 Daniel Adamson Road, Salford
Sheet 1 of 1 www.centricabusinesssolutions.com Manchester, M50 1DT, UK