Exhaust Fan GREENHECK Data Sheet
Exhaust Fan GREENHECK Data Sheet
Model: RBUMO-3L60-100
Propeller Upblast Belt Drive Motor Out-of-
Airstream
Dimensional
Quantity 1
75.00
Weight w/o Acc's (lb) 1,055
Weight w/ Acc's (lb) 1,061
Max T Motor Frame Size 256
23.00
Roof Opening (in.) 68 x 68
2.25
72.00 SQ
90.25
Performance
Requested Volume (CFM) 47,086
Actual Volume (CFM) 47,086
Total External SP (in. wg) 0.25
Fan RPM 483
Operating Power (hp) 8.18
Elevation (ft) 6,558
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.059
Drive Loss (%) 3.6
Tip Speed (ft/min) 7,582
Static Eff. (%) 23
Motor
Motor Mounted Yes
Size (hp) 10
Voltage/Cycle/Phase 460/60/3
Enclosure ODP
Motor RPM 1725
Efficiency Rating NEMA Premium
Windings 1
NEC FLA* (Amps) 14
Notes:
All dimensions shown are in units of in.
*NEC FLA, MCA and MOP are for reference only – based on
tables 430.248 or 430.25 of National Electric Code 2020. Actual
motor FLA may vary, for sizing thermal overload, consult factory.
MCA and MOP values shown only account for the motor, not
accessories (damper actuator, field supplied VFD, etc).
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not licensed
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 102 98 92 90 86 90 77 72 94 83 42
AMCA
AMCA Licensed for Sound and Air Performance and FEI ratings. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA certified ratings seal applies
to sound and air performance and FEI ratings only. FEI calculation is based on default motor calculation in accordance
with ANSI/AMCA Standard 208. Performance certified is for installation type A: Free inlet, Free outlet. Power rating
(BHP/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances
(accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field
calculated per AMCA Standard 301. The A-Weighted sound ratings shown have been calculated per AMCA
International Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. dBA levels
are not licensed by AMCA International. The AMCA Certified Ratings Seal applies to LwiA and inlet sone ratings only.