PRODUCT SELECTION D ATA
EXTRA SLIM
Extra slim
(129 mm depth 370mm height)
Easy installation
Elegant design and reduced
dimensions
Low energy consumption
Low noise level
42SI
Cooling capacity : 0.55 kW to 2.9 kW
Heating capacity : 0.57 kW to 2.5 kW
The 42SI is an hydronic slim wall fan coil available in 4 models (with or without cabinet
- standart or low height) and 5 sizes
The slim cabinet version can be installed in any ambient thanks to its elegant design
and reduced dimensions (depth is only 129 mm).
All the models perform very low electric consumption and extremely quite sound levels
according to the request of today’s new projects.
The range consists of the following versions:
SIC - standard version with cabinet
SIR - compact version with cabinet
SIN - standard version without cabinet
SIL - compact version without cabinet
CARRIER participates in the ECP programme for FC/FCP
Check ongoing validity of certificate:
www.eurovent-certification.com
Original document
RANGE
The 42SI range includes 4 models and 5 sizes .
It covers a range of cooling capacity from 0.55 kW to 2.9 kW at Eurovent conditions
The 42SI is available in :
- 2 pipe system heating or cooling
- 4 pipes system heating/cooling
CODIFICATION
Casing- Size& Modification
Range Coil Type Control Body Valve Electrical heater Actuators
motor type index
4 2 S I C 2 9 F - - - A
1 2 3 4 5 6 7 8 9 10 11 12 13
Digit 12
' - = without
A = ON/OFF 230V ACTUATOR
Digit 11
- = without
Digit 10
‘ - = without
G = 2 WAYS VALVE GROUP
H = 3 WAYS VALVE GROUP
Digit 9
- = without
A = With Electronic control & user interface built-in
B = With Electronic control & command built-in with Wifi
C= With Electronic control (witout wall user interface)
Digit 8
F = 2 pipes Left
G = 2 pipes Right
C = 4 pipes Left
D = 4 pipes Right
Digit 5 - 6 - 7
C 2 9 Size 2 _ Standard Height with cabinet_ EC motor
C 4 9 Size 4 _ Standard Height with cabinet_ EC motor
C 6 9 Size 6 _ Standard Height with cabinet_ EC motor
C 8 9 Size 8 _ Standard Height with cabinet_ EC motor
C 9 9 Size 9_ Standard Height with cabinet_ EC motor
R 2 9 Size 2 _ Low Height (370 mm) with cabinet EC motor
R 4 9 Size 4 _ Low Height (370 mm) with cabinet_ EC motor
R 6 9 Size 6 _ Low Height (370 mm) with cabinet_ EC motor
R 8 9 Size 8 _ Low Height (370 mm) with cabinet_ EC motor
R 9 9 Size 9_ Low Height (370 mm) with cabinet_ EC motor
N 2 9 Size 2 _ Standard Height without cabinet_ EC motor
N 4 9 Size 4 _ Standard Height without cabinet_ EC motor
N 6 9 Size 6 _ Standard Height without cabinet_ EC motor
N 8 9 Size 8 _ Standard Height without cabinet_ EC motor
N 9 9 Size 9_ Standard Height without cabinet_ EC motor
L 2 9 Size 2 _ Low Height without cabinet_ EC motor
L 4 9 Size 4 _ Low Height without cabinet_ EC motor
L 6 9 Size 6 _ Low Height without cabinet_ EC motor
L 8 9 Size 8 _ Low Height without cabinet_ EC motor
L 9 9 Size 9_ Low Height without cabinet_ EC motor
2
TECHNICAL DESCRIPTION
Frame
Made with high-resistance electrolytically zinc-coatted metal.
Casing (for 42SIC & 42SIR version)
Air intake grid made with electrolytically zinc-coated sheet metal painted with oven-dried epoxy powders, with quick-release
device to clean the filters.
Reversible air outlet grid made with aluminium painted with oven-dried epoxy powders (metallic siver paint). Its generous size
enhances its high mechanical strength
For 42SIC 2 pipes :
Lateral made in plastic (RAL9003)
Front panel made with electrolytically zinc-coated sheet metal painted with oven-dried epoxy powders
For 42SIC 4 pipes & 42SIR (low height) :
Sides and front panel made with electrolytically zinc-coated sheet metal painted with oven-dried epoxy powders (RAL 9003)
Air Filter
Polypropylene filter, washable or regenerable.
Fan Motor
Tangential fan made from synthetic material with staggered fins mounted on EPDM anti-vibration supports. Statically and
dynamically balanced rotor, assembled directly on the motor’s shaft.
Sigle phase electric motor fitted on anti-vibration EPDM supports.
Heat exchange coil
It is made with copper pipes and aluminium fins with high efficency coils . 3/4 Eurokonus threaded fittings compliant with the
requirements of the new EU Standards.
Condensate drip Tray
Made in ABS the outside diameter of the condensate discharge pipe is 14mm.
Options fitted in factory
• 2 ways valve
• 3 ways valve
• ON/OFF 230V actuator
• electronic control with user interface built-in
Accessoiries available in kit
• Kit 2 ways valve
• Kit 3 ways valve
• Back panel RAL9010 for cabinet version (42SIC or 42SIR)
• White color feet for covering floor pipes
• White color support feet
• In-wall box for vertical concealed version (42SIN or 42SIL)
• Front panel RAL90032 ‘equipped with return grill and supply adjustable blade for vertical concealed version (42SIN or 42SIL)
• LCD TOUCH electronic wall mounted control panel with or without WIFI module color black or white
3
DIMENSION, WEIGHT
With cabinet version : 42SIC 2 PIPES - 42SIC 4 PIPES - Without cabinet version : 42SIN 2-PIPE - 42SIN 4-PIPE
42SIR 2 PIPES - 42SIL 2 PIPE
A D
A D
B B
42SIC 2 PIPES
DIMENSIONS 42SIC29F/G 42SIC49F/G 42SIC69F/G 42SIC89F/G 42SIC99F/G
A mm 735 935 1135 1335 1535
B mm 579 579 579 579 579
D mm 129 129 129 129 129
WEIGHT
Net weight kg 17 20 23 26 29
42SIC 4 PIPES
DIMENSIONS 42SIC29C/D 42SIC49C/D 42SIC69C/D 42SIC89C/D 42SIC99C/D
A mm 737 937 1137 1337 1537
B mm 639 639 639 639 639
D mm 131 131 131 131 131
WEIGHT
Net weight kg 18 21 25 28 32
42SIR 2 PIPES
DIMENSIONS 42SIR29F/G 42SIR49F/G 42SIR69F/G 42SIR89F/G 42SIR99F/G
A mm 735 935 1135 1335 1535
B mm 379 379 379 379 379
D mm 129 129 129 129 129
WEIGHT
Net weight kg 12 14 16 19 23
42SIN 2-PIPES
DIMENSIONS 42SIN29F/G 42SIN49F/G 42SIN69F/G 42SIN89F/G 42SIN99F/G
A mm 525 725 925 1125 1325
B mm 576 576 576 576 576
D mm 126 126 126 126 126
WEIGHT
Net weight kg 9 12 15 18 21
4
DIMENSION, WEIGHT
42SIN 4-PIPE
DIMENSIONS 42SIN29C/D 42SIN49C/D 42SIN69C/D 42SIN89C/D 42SIN99C/D
A mm 479 679 879 1079 1279
B mm 639 639 639 639 639
D mm 126 126 126 126 126
WEIGHT
Net weight kg 10 13 17 20 24
42SIL 2 PIPES
DIMENSIONS 42SIL29C/D 42SIL49C/D 42SIL69C/D 42SIL89C/D 42SIL99C/D
A mm 525 725 925 1125 1325
B mm 376 376 376 376 376
D mm 126 126 126 126 126
Weight
Net Weight kg 7 8 9 10 12
POSITIONING
DISTANCES 29 49 69 89 99
A mm 140 140 140 140 140
B mm 80 80 80 80 80
C mm 20 20 20 20 20
D mm 20 20 20 20 20
E mm 400 400 400 400 400
F mm 2500 2500 2500 2500 2500
5
THERMAL PERFORMANCES
2 PIPES
42SIC29F/G 42SIR29F/G 42SIC49F/G 42SIR49F/G 42SIC69F/G
PERFORMANCE 42SIN29F/G 42SIL29F/G 42SIN49F/G 42SIL49F/G 42SIN69F/G
Total cooling capacity a kW 0,91 0,51 2,12 1,21 2,81
Sensible cooling capacity a kW 0,73 0,43 1,72 1,01 2,11
Water flow rate a L/h 157 88 365 208 483
Water pressure drop a kPa 12,1 4,1 8,2 11,2 17,1
Heating capacity b kW 1,02 0,61 2,21 1,51 3,02
Water flow rate b L/h 175 105 380 260 519
Water pressure loss b kPa 9,1 5,2 9,2 16,1 19,1
HYDRAULIC FEATURES
Coil water content L 0,47 0,28 0,8 0,5 1,13
Maximum operating pressure bar 10 10 10 10 10
Hydraulic connections EK 3/4
AERAULIC DATA
Maximum airflow d m3/h 146 113 294 228 438
Airflow at medium speed (AUTO
m3/h 90 63 210 155 318
mode)"
Airflow at minimum ventilation speed m3/h 49 35 118 84 180
Maximum static pressure available Pa 10 10 10 10 13
ELECTRICAL DATA
Power supply voltage V/ph/Hz 230/1/50
Maximum electrical power consumption W 11 11 19 19 20
Maximum current input A 0,11 0,11 0,16 0,16 0,18
Abs. Electrical power at minimum speed W 5 3 4 4 6
SOUND LEVEL
Sound Power at maximum speed db(A) 51 51 53 53 54
Sound pressure at maximum airflow e db(A) 41 39 42 40 44
Sound pressure at average airflow e db(A) 33 33 34 33 34
Sound pressure at minimum airflow e db(A) 24 24 25 25 26
(a) Inlet water temperature 7°C, outlet water temperature 12°C, ambient air temperature 27°C dry bulb and 19°C wet bulb (UNI EN 1397).
(b) Inlet water temperature 45°C, outlet water temperature 40°C, air temperature 20°C (UNI EN 1397 standard).
(c) Inlet water temperature 65°C, outlet water temperature 55°C, ambient air temperature 20°.
(d) Airflow measured with clean filters.
(e) Sound pressure measuredat a distance of 1 metre according to ISO7779
6
THERMAL PERFORMANCES
2 PIPES
42SIR69F/G 42SIC89F/G 42SIR89F/G 42SIC99F/G 42SIR99F/G
PERFORMANCE 42SIL69F/G 42SIN89F/G 42SIL89F/G 42SIN99F/G 42SIL99F/G
Total cooling capacity a kW 1,62 3,30 2,12 3,71 2,60
Sensible cooling capacity a kW 1,44 2,71 1,99 2,90 2,34
Water flow rate a L/h 279 568 365 638 447
Water pressure drop a kPa 5,1 18,0 5,3 21,2 7,2
Heating capacity b kW 2,03 3,81 2,62 4,32 3,11
Water flow rate b L/h 349 655 451 743 535
Water pressure loss b kPa 7,3 21,2 8,1 23,3 10,2
HYDRAULIC FEATURES
Coil water content L 0,61 1,46 0,77 1,8 0,9
Maximum operating pressure bar 10 10 10 10 10
Hydraulic connections EK 3/4
AERAULIC DATA
Maximum airflow d m3/h 331 567 440 663 489
Airflow at medium speed
m3/h 229 410 283 479 344
(AUTO mode)
Airflow at minimum ventilation speed m3/h 124 247 138 262 167
Maximum static pressure available Pa 10 13 10 13 10
ELECTRICAL DATA
Power supply voltage V/ph/Hz 230/1/50
Maximum electrical power consumption W 20 29 29 33 33
Maximum current input A 0,18 0,26 0,26 0,28 0,28
Abs. Electrical power at minimum speed W 4 5 4 5 5
SOUND LEVEL
Sound Power at maximum speed dB(A) 54 55 55 57 57
Sound pressure at maximum airflow e dB(A) 41 46 42 47 43
Sound pressure at average airflow e dB(A) 34 35 34 38 36
Sound pressure at minimum airflow e dB(A) 25 26 26 28 27
(a) Inlet water temperature 7°C, outlet water temperature 12°C, ambient air temperature 27°C dry bulb and 19°C wet bulb (UNI EN 1397).
(b) Inlet water temperature 45°C, outlet water temperature 40°C, air temperature 20°C (UNI EN 1397 standard).
(c) Inlet water temperature 65°C, outlet water temperature 55°C, ambient air temperature 20°.
(d) Airflow measured with clean filters.
(e) Sound pressure measuredat a distance of 1 metre according to ISO7779
7
THERMAL PERFORMANCES
4 PIPES
42SIC29C/D 42SIC49C/D 42SIC69C/D 42SIC89C/D 42SIC99C/D
PERFORMANCE 42SIN29C/D 42SIN49C/D 42SIN69C/D 42SIN89C/D 42SIN99C/D
Total cooling capacity a kW 0,71 1,42 2,01 2,43 2,92
Sensible cooling capacity a kW 0,55 1,11 1,50 1,92 2,26
Water flow rate a L/h 122 244 346 418 502
Water pressure drop a kPa 8,1 6,2 13,1 10,3 8,1
Heating capacity b kW 0,51 1,10 1,52 2,21 2,50
Water flow rate b L/h 88 189 261 380 430
Water pressure loss b kPa 3,0 5,1 7,2 5,2 6,1
HYDRAULIC FEATURES
Cooling Coil water content L 0,47 0,80 1,13 1,46 1,80
Heating Coil water content L 0,16 0,30 0,38 0,49 0,60
Maximum operating pressure bar 10 10 10 10 10
Hydraulic connections EK 3/4
AERAULIC DATA
Maximum airflow d m3/h 132 260 370 476 542
Airflow at medium speed
m3/h 91 207 291 367 416
(AUTO mode)
Airflow at minimum ventilation speed m3/h 46 124 194 302 364
Maximum static pressure available Pa 8 8 11 11 11
ELECTRICAL DATA
Power supply voltage V/ph/Hz 230/1/50
Maximum electrical power consumption W 11 19 20 29 33
Maximum current input A 0,11 0,16 0,18 0,26 0,28
Abs. Electrical power at minimum speed W 4 4 4 4 5
SOUND LEVEL
Sound Power at maximum speed dB(A) 51 53 54 55 57
Sound pressure at maximum airflow e dB(A) 41 42 44 46 47
Sound pressure at average airflow e dB(A) 33 34 34 35 37
Sound pressure at minimum airflow e dB(A) 24 25 25 26 27
(a) Inlet water temperature 7°C, outlet water temperature 12°C, ambient air temperature 27°C dry bulb and 19°C wet bulb (UNI EN 1397).
(b) Inlet water temperature 45°C, outlet water temperature 40°C, air temperature 20°C (UNI EN 1397 standard).
(c) Inlet water temperature 65°C, outlet water temperature 55°C, ambient air temperature 20°.
(d) Airflow measured with clean filters.
(e) Sound pressure measuredat a distance of 1 metre according to ISO7779