0% found this document useful (0 votes)
56 views7 pages

Schneider Electric - Harmony-Control - RM17UB310

The document provides a detailed product data sheet for the RM17UB310 voltage control relay, including specifications such as voltage range, relay type, and switching capacity. It highlights features like adjustable time delay, monitoring parameters for overvoltage and undervoltage, and various certifications. The product is available in stock for a list price of 189.00 USD and includes information on environmental compliance and warranty details.

Uploaded by

matt5464
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views7 pages

Schneider Electric - Harmony-Control - RM17UB310

The document provides a detailed product data sheet for the RM17UB310 voltage control relay, including specifications such as voltage range, relay type, and switching capacity. It highlights features like adjustable time delay, monitoring parameters for overvoltage and undervoltage, and various certifications. The product is available in stock for a list price of 189.00 USD and includes information on environmental compliance and warranty details.

Uploaded by

matt5464
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Product data sheet

Specifications

voltage control relay, Harmony


Control Relays, 5A, 1CO,
208...480V AC
RM17UB310

Product availability: Stock - Normally stocked in distribution


facility

Price*: 189.00 USD

Main
Range of Product Harmony Control Relays

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Relay Type Voltage control relay

Product or Component Type 3-phase control relay

Product Specific Application For 3-phase supply

Relay name RM17UB3

Relay monitored parameters Overvoltage and undervoltage between phases

time delay Adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault

Switching capacity in VA 1250 VA

Measurement range 220...480 V AC

Contacts type and composition 1 C/O

Complementary
Reset time 1500 ms time delay

Maximum switching voltage 250 V AC/DC

Minimum switching current 10 mA 5 V DC

Maximum switching current 5 A AC/DC

Supply voltage limits 183…528 V AC

Power consumption in VA 0…22 VA 400 V AC 50 Hz

Control circuit frequency 50...60 Hz +/- 10 %

Voltage detection threshold 183 V

Output contacts 1 C/O

Nominal output current 5A

Hysteresis 2%

Measurement accuracy +/- 10 % of the full scale value

delay at power up 650 ms

Maximum measuring cycle 150 ms measurement cycle as true rms value

Threshold adjustment voltage 2...20 % of Un selected


-2...-17 % in the range 220 V AC
+2...+10 % in the range 480 V AC
-2...-12 % in the range 208 V AC

Repeat accuracy +/- 0.5 % input and measurement circuit


+/- 1 % time delay

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Sep 1, 2024 1
Measurement error < 1 % over the whole range with voltage variation
0.05 %/°C with temperature variation

Response time < 200 ms (in the event of a fault)

Quality labels CE

Insulation resistance > 500 MOhm 500 V DC IEC 60255-5


> 500 MOhm 500 V DC IEC 60664-1

Operating position Any position without derating

Local signalling for power ON LED (green)


for relay ON LED (yellow)

Overvoltage category III IEC 60664-1

[Ui] rated insulation voltage 400 V IEC 60664-1

Connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end

Tightening torque 5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1

Housing material Self-extinguishing plastic

Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability 100000 cycles

Mechanical durability 30000000 cycles

Operating rate <= 360 operations/hour full load

Utilisation category AC-12 IEC 60947-5-1


AC-13 IEC 60947-5-1
AC-14 IEC 60947-5-1
AC-15 IEC 60947-5-1
DC-12 IEC 60947-5-1
DC-13 IEC 60947-5-1
DC-14 IEC 60947-5-1

[Un] rated nominal voltage , self-powered

Safety reliability data B10d = 470000


MTTFd = 502.2 years

Control Type Without test button

Width 0.7 in (17.5 mm)

Net Weight 0.18 lb(US) (0.08 kg)

Environment
Electromagnetic compatibility Emission standard for industrial environments conforming to IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments
conforming to IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Ambient air temperature for -4.0000000000…122.0000000000 °F (-20…50 °C)


operation
Vibration resistance 0.35 mm 5…57.6 Hz)IEC 60068-2-6
1 gn 57.6…150 Hz)IEC 60255-21-1

Shock resistance 5 gn IEC 60068-2-27

Standards IEC 60255-1

Product Certifications GOST


UL
GL
C-tick
CSA

Ambient Air Temperature for -40.0000000000…158.0000000000 °F (-40…70 °C)


Storage

2 Sep 1, 2024
Relative humidity 95 % 131.0000000000 °F (55 °C) IEC 60068-2-30

IP degree of protection IP20 IEC 60529 terminals)


IP30 IEC 60529 casing)

Pollution degree 3 IEC 60664-1

Directives 89/336/EEC - electromagnetic compatibility


73/23/EEC - low voltage directive

Dielectric test voltage 2 kV AC 50 Hz, 1 min

Non-dissipating shock wave 4 kV

Ordering and shipping details


Category US10CP222380

Discount Schedule 0CP2

GTIN 3389119405133

Returnability Yes

Country of origin ID

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 0.945 in (2.400 cm)

Package 1 Width 3.071 in (7.800 cm)

Package 1 Length 3.898 in (9.900 cm)

Package 1 Weight 3.069 oz (87.000 g)

Unit Type of Package 2 S02

Number of Units in Package 2 48

Package 2 Height 5.906 in (15.000 cm)

Package 2 Width 11.811 in (30.000 cm)

Package 2 Length 15.748 in (40.000 cm)

Package 2 Weight 10.307 lb(US) (4.675 kg)

Contractual warranty
Warranty 18 months

Sep 1, 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead
compounds, which is known to the State of California to cause cancer and birth
defects or other reproductive harm. For more information go to
www.P65Warnings.ca.gov

4 Sep 1, 2024
Product data sheet RM17UB310

Dimensions Drawings

3-Phase Voltage Control Relays

Dimensions and Mounting

Sep 1, 2024 5
Product data sheet RM17UB310

Connections and Schema

3-Phase Voltage Control Relays

Wiring Diagram

6 Sep 1, 2024
Product data sheet RM17UB310

Technical Description

Function Diagrams

Phase Failure Detection (U measured < 0.7 x nominal supply voltage)

Control of Overvoltage and Undervoltage

Legend
Un Nominal supply voltage
R Output relay
Tt Overvoltage and undervoltage threshold delay (adjustable on front panel from 0.3 to 30 s)
H Hysteresis
U> Overvoltage threshold
U< Undervoltage threshold
L1, L2, L3 Phases of the supply voltage monitored
11-12, 11-14 R1 output relay connections
Relay status: black color = energized.