Room Name Transformer & Switch Gear Room
Vendor MNB Engineering Sdn Bhd
BATTERY CALCULATION FOR 2-10NE FIREPROC8>
FIRE EXTINGUISHING PANEL
(A) Normal Operation
1 Controller Current = 0.135 A
2 Auxiliary Output Current - 0.100 A
a) Smoke Detector- 4 nos x 0.00045 A 0.0018 A
b) Heat Detector -~)~pro@
4 nos x 0.00040 A 0.0016 A
4 nos x 0.0005 A 0.002 A
* Total Normal StandbY~~~r::!:en~ 0.2404 A x 24 hrs*** 5.77 AH
(B) Alarm Operation
1 -Controller Current 0.135 A
2 Auxiliary Output Current 0.100 A
3 ..Q!!!putDevice Current 1.<XX>
A
.Total Alarm Current 1.235 A x 0.083hr- 0.102 AH
Total AH used 5.872 AH
SafetyFactor 1.2
Total PowerRe~ 7.05 AH
Total Battery Pack AH Avaftabte (12 AH)
Note:
.Total normal standbycurrent shall not exceed 1.000amp.
..Total alarm current shall not exceed4.135 amps.
...Minimum battery capacity must exceed (by more than 10%)normal operation power followed by alarm
operation power for these duration: -
OperationType Normal Oooration Alarm OperatIon
Local & Sprinklers Supervisory 90 hours 5 minutes
Auxiliary or Remote Station 60 hours 5 minutes
Local Operation Only 24 hours 5 minutes
Lali