Battery Calculation

The document outlines battery calculations for the Transformer & Switch Gear Room at Universiti Malaya, detailing current requirements during normal and alarm operations. It specifies the total current consumption and battery capacity needed to ensure proper functioning under various operational scenarios. Additionally, it includes safety factors and operational duration requirements for different types of operations.

Uploaded by

Ramlan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views1 page

Battery Calculation

The document outlines battery calculations for the Transformer & Switch Gear Room at Universiti Malaya, detailing current requirements during normal and alarm operations. It specifies the total current consumption and battery capacity needed to ensure proper functioning under various operational scenarios. Additionally, it includes safety factors and operational duration requirements for different types of operations.

Uploaded by

Ramlan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Title Universiti Malaya,Jalan LembahPantai, KL

Room Name Transformer & Switch Gear Room


Vendor MNB Engineering Sdn Bhd

BATTERY CALCULATION FOR 2-10NE FIREPROC8>


FIRE EXTINGUISHING PANEL

(A) Normal Operation

1 Controller Current = 0.135 A

2 Auxiliary Output Current - 0.100 A


a) Smoke Detector- 4 nos x 0.00045 A 0.0018 A
b) Heat Detector -~)~pro@
4 nos x 0.00040 A 0.0016 A
4 nos x 0.0005 A 0.002 A
* Total Normal StandbY~~~r::!:en~ 0.2404 A x 24 hrs*** 5.77 AH
(B) Alarm Operation

1 -Controller Current 0.135 A


2 Auxiliary Output Current 0.100 A

3 ..Q!!!putDevice Current 1.<XX>


A
.Total Alarm Current 1.235 A x 0.083hr- 0.102 AH
Total AH used 5.872 AH
SafetyFactor 1.2
Total PowerRe~ 7.05 AH
Total Battery Pack AH Avaftabte (12 AH)

Note:

.Total normal standbycurrent shall not exceed 1.000amp.


..Total alarm current shall not exceed4.135 amps.
...Minimum battery capacity must exceed (by more than 10%)normal operation power followed by alarm
operation power for these duration: -

OperationType Normal Oooration Alarm OperatIon


Local & Sprinklers Supervisory 90 hours 5 minutes
Auxiliary or Remote Station 60 hours 5 minutes
Local Operation Only 24 hours 5 minutes