Saudi Electricity Company
Distribution Services Sector
SPECIFICATIONS FOR NON-EXTENSIBLE Issue Date: 03/2022 Page: 20 of 25
SF6 INSULATED RING MAIN UNIT, 36 KV 32-SDMS-07 REV.01
10. Technical data schedule
NON-EXTENSIBLE RING MAIN UNIT, SF6, 36 kV
(Sheet 1 of 3)
SEC Inquiry No. ___________________________ Item No…………………
SEC Specified Vendor
No. Description
Values Values
5.0 DESIGN AND CONSTRUCTION REQUIREMENTS
GENERAL
1. RMU Type Outdoor & Indoor
2. RMU Configuration 3-Way / 4-Way
5.1
3. Tee-off Circuit Breaker
4. Terminal Fastener for Ring Switch M16
5. Terminal Fastener for Tee-off M16
RING SWITCH (LBS)
1. Service Voltage 33 KV
2. Maximum Operating Voltage 36 KV
3. Rated Frequency 60 Hz
4. Rated Current 400 A
5. Short Circuit Withstand Current,
25 KA
1 sec
5.2
6. Rated Making Current (peak) 65 KA
7. Rated Making Current of Earthing
65 KA
Switch (peak)
8. Impulse Withstand Voltage 200 KV
9. Power Frequency Withstand
80 KV rms
Voltage, 1 min. (Ref. 01-SDMS-01)
9. Internal Arc Fault Withstand Current
25 KA
for 1 sec
20
Saudi Electricity Company
Distribution Services Sector
SPECIFICATIONS FOR NON-EXTENSIBLE Issue Date: 03/2022 Page: 21 of 25
SF6 INSULATED RING MAIN UNIT, 36 KV 32-SDMS-07 REV.01
NON-EXTENSIBLE RING MAIN UNIT, SF6, 36 kV
(Sheet 2 of 3)
SEC Inquiry No. ___________________________ Item No………………………
Vendor
No. Description SEC Specified Values
Values
CIRCUIT BREAKER
1. Service Voltage 33 KV
2. Maximum Operating Voltage 36 KV
3. Rated Frequency 60 Hz
4. Rated Current 100 A
5. Rated Short Circuit Level, 1 sec 25 KA
6. Rated Making Current 65 KA
5.3.1
7. Re-striking Voltage Ratio 1.4
8. Duty Cycle O-t1-CO-t2-CO
9. Making Time ms
10. Opening Time ms
11. Arc Duration ms
12. Total Breaking Time ms
13. Operating Mechanism Spring charged
TERMINATIONS/CABLE BOX
Cable Box Size (w x h x depth) mm
5.8 Vertical Distance Between Terminal Bushings to Top of Clamp
Ring Switch mm
T-Off mm
ENCLOSURE
Overall Dimensions (W x D x H) mm
5.9
Degree of Protection As per 01-SDMS-01
Finish Color RAL 7035
21