PSP&C Chapter Five
PSP&C Chapter Five
CHAPTER FIVE
2
February 18, 2025
Active and Reactive Power control
• The objective of the control strategy is to generate and deliver power in an
interconnected system:-
– Economically
– Reliably
– By maintaining voltage and frequency in permissible limits (stability).
• Real and reactive powers are controlled separately.
– Active power control is closely related to frequency control .
– Reactive power control is closely related to voltage control.
• The load frequency control (LFC) loop controls the real power and frequency.
• The automatic voltage regulator (AVR) loop regulates the reactive power and
voltage magnitude.
3
Basic Generator Control loops Schematic diagram of LFC
and AVR of a synchronous Generator
4
Control Area
All generators in an knit electric area constitute a coherent group so
that all the generators speed up and slow down together maintaining
their relative power angles. Such an area is called control area.
5
LFC
• In a power system the load demand is continuously changing.
• In accordance with it the power input has also to vary.
• If the input - output balance is not maintained a change in
frequency will occur.
• The change in frequency is sensed when the rotor angle is changed.
• The error signals are transformed in to real power command signal,
which is sent to prime mover to call for an increment in the torque.
• The prime mover then brings change in the generator output by an
amount which will change the values of with in the specified
tolerance.
6
Necessity of Maintaining Frequency Constant
The blades of the water turbine is designed to operate at a particular
speed and the frequency variations will cause change in the speed.
This will lead to excessive vibration and cause damage to the turbine
blades
Most of the AC motors require constant frequency supply in order to
maintain constant speed.
In industry, frequency affects the continuous operation of the process.
To maintain a synchronous operation of various units in the power
system.
Frequency is also responsible in affecting amount of power
transmitted through interconnected lines.
For synchronization purpose, this helps to have stable system. 7
Automatic Generation Control (AGC)
• Automatic Generation Control (AGC) is the name given to a
control system having three major objectives:
9
10
Cont.…
11
Load Model
12
Generator and load block diagram
13
Prime Mover Model
14
Speed Governing system
15
Speed Governing system
• Fly-ball speed governor: It is a purely mechanical, speed-sensitive
device coupled directly to and builds directly on the prime movers
to adjust the control valve opening via linkage mechanism.
• It senses a speed deviation or a power change command and
converts it into appropriate valve action.
• Hence, this is treated as the heart of the system, which controls
the change in speed(frequency).
• As the speed increases, the fly balls move outwards and the point
B on linkage mechanism moves upwards.
• The reverse will happen if the speed decreases.
16
Speed Governing system
Hydraulic amplifier: It is nothing but a single-state hydraulic
servomotor interposed between the governor and valve.
• Its downward movement opens the upper pilot valve so that more
steam is admitted to the turbine under steady conditions.
18
Speed Governing system
ABC is a rigid link pivoted at point B and CDE is another rigid
pivoted link at point D.
20
Cont..
21
Cont..
• By combining the above block diagrams, the complete
block diagram of the LFC of an isolated power station
is shown below:
22
Cont..
• The closed-loop transfer function relating the load change
Δ𝑃𝐿(i/p) to frequency deviation ΔΩ(o/p) is:
23
Example
24
25
26
27
AGC in a Single area system
• With the LFC loop, a change in the system load will result in
steady-state frequency deviation, depending on the governor speed
regulation.
29
Cont..
• The closed-loop transfer function of the above control system with
an input −Δ𝑃𝐿 and o/p ΔΩ becomes:
30
AGC in the multi area system
• The AGC of a multi area system can be realized by studying the
AGC for a two–area system.
• Consider two areas represented by an equivalent generating unit
interconnected by a lossless tie line with reactance 𝑋𝑡𝑖𝑒.
• Each area is represented by a voltage source behind an equivalent
reactance.
• The real power transferred over the tie line is given by:
31
Cont.
• For a small deviation in the tie-line flow Δ𝑃12:
32
Cont.
• A block diagram representation for the two-area system with LFC
containing the primary control loop is shown below.
33
AVR
• It is known that Voltage (V) of a power supply system must be maintained
at a constant value.
• The real need of the AVR is to deal with the voltage dip following the
sudden connection of extra load and to restore the rated Voltage without
undue overshooting and regeneration(i.e. voltage hunting).
34
Reasons To Keep The Voltage At Constant Level
In induction motor loads, variations in the voltage will affect and
change the torque.
The picture of the television set will start rolling due to the
voltage being below a specified level.
35
Introduction To Excitation System
• The basic function of an excitation system is to provide necessary
direct current to the field winding of the synchronous generator.
• The excitation system must be able to automatically adjust the
field current to maintain the required terminal voltage.
• The DC field current is obtained from a separate source called an
exciter.
36
Introduction To Exciter
• It is necessary to provide constancy of the alternator terminal
voltage during normal small and slow changes in the load.
37
Main Components
• In older power plants, the exciter consisted of a DC generator
driven by the main shaft.
38
Cont.
The AVR senses output voltage and alter the field current to
maintain the output voltage at set value.
Excitation voltage can be set by the hand trimmer.
The VOLTAGE SENSING unit transforms down, and rectifies
voltage.
This signal is compared with the set value at the COMPARATOR .
The 'error' signal from the Comparator is used to control the
excitation current through ERROR AMP. and CONTROLLER.
39
Modelling of AVR
Four basic parts of AVR
Exciter Modelling
Sensor modelling
40
Cont..
• The transfer equation that relates the generator terminal voltage Vt(s)
to the reference voltage Vref(s) is :
• The amplifier comes first in the AVR system to amplify the error
signal.
• Then the error signals alter the exciter and consequently the generator.
• The sensor sense the voltage output and send it to the transducer and
the transducer send in the signal after comparing it to the amplifier.
41
Summery
• The main problems of control in the large power system are:
Active Power.
Reactive Power.
42
• High load (Air conditions, machines) High pressure on
System is unstable.
43
Example2. A 100 MVA synchronous generator operates on full load at
frequency of 50Hz. The load is suddenly reduced to 50 MW. Due to time lag
in governor system, the steam valve begins to close after 0.4 seconds.
Determine the change in frequency that occurs in this time.
• Solution
• Assume, Pf=1,
• Active power=100MVA*1=100MW
44
• And
1
• 𝐾𝐸 = ∗ 𝑚𝑣 2
2
45
• Case II (at sudden reduced load=50MW)
• Due to the time delay of governor, we are getting some energy still.
• Excess power four 0.4sec =50MW
• Excess energy =50MW*0.4sec=0.2 ∗ 105 𝑘𝑤𝑠𝑒𝑐
• This excess energy is in the form of KE
• Then total KE=5.2 ∗ 105 𝑘𝑤𝑠𝑒𝑐
• 𝑓𝑛𝑒𝑤 2 = 2600
• 𝑓𝑛𝑒𝑤 = 50.99 𝐻𝑧
46
Thank YOU!
18-Feb-25 47